KNX Database
MDT technologies GmbH AKS-01UP.03 AKS-01UP.03 Switch Actuator 1-fold, flush mounted, 16A

AKS-01UP.03 Switch Actuator 1-fold, flush mounted, 16A AKS-01UP.03

MDT technologies GmbH · Order number AKS-01UP.03 · Actuators › Switch Actuators, standard and industrial version

Standard version 230VAC, 16A, 140µF C-Load

Download .knxprod Switching, Staircase 1-fold UP, flush mounted 3.2 · 164 KB

Product

ManufacturerMDT technologies GmbH
Product nameAKS-01UP.03 Switch Actuator 1-fold, flush mounted, 16A
Order numberAKS-01UP.03
HardwareSchaltaktor 1-fach UP
MediumTwisted Pair
Bus current (mA)5
Rail mountedNo
RegistrationCertified · 2022-06-03
Languagesde-DE, en-US, es-ES, fr-FR
Catalog entryM-0083_H-369-1_HP-00A9-32-63C9_CI-AKS.2D01UP.2E03-1
Fingerprint63C9
SHA-25635586435ec81bfd377ffa3bcd358bbe3787293047fb21720844e7d8ffbb0144f
First seen2026-11-25
Markets69 markets

Application program: Switching, Staircase 1-fold UP, flush mounted 3.2

Application number$00A9
Version3.2
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version5.0
Parameters296
Group objects36
Group objects (36)
NoNameFunctionSizeDPTFlags
0Channel A: {{0}}Switch On/Off1 Bit1.1 switchCW
1Channel A: {{0}}Staircase light1 Bit1.1 switchCW
1Channel A: {{0}}Service required1 Bit1.5 alarmCRT
1Channel A: {{0}}Switch pulse1 Bit1.1 switchCW
2Channel A: {{0}}Response operating hours2 Bytes7.7 time (h)CRT
2Channel A: {{0}}Time to next service2 Bytes7.7 time (h)CRT
2Channel A: {{0}}Staircase light with time1 Byte5.5 ratio (0..255)CW
2Channel A: {{0}}Response operating hours4 Bytes13.100 time lag (s)CRT
2Channel A: {{0}}Time to next service4 Bytes13.100 time lag (s)CRT
3Channel A: {{0}}Prewarning1 Bit1.1 switchCT
3Channel A: {{0}}Reset operation hours1 Bit1.1 switchCW
3Channel A: {{0}}Reset sevice1 Bit1.1 switchCW
4Channel A: {{0}}Lock1 Bit1.3 enableCW
5Channel A: {{0}}Forced control2 Bit2.1 switch controlCW
5Channel A: {{0}}Priority1 Bit1.1 switchCW
6Channel A: {{0}}Scene1 Byte17.1 scene numberCW
6Channel A: {{0}}Scene1 Byte18.1 scene controlCW
7Channel A: {{0}}State1 Bit1.11 stateCRT
8Channel A: {{0}}Inverted state1 Bit1.11 stateCRT
9Channel A: {{0}}Logic 11 Bit1.2 booleanCW
10Channel A: {{0}}Logic 21 Bit1.2 booleanCW
11Channel A: {{0}}Threshold switch1 Byte5.5 ratio (0..255)CW
11Channel A: {{0}}Threshold switch2 Bytes7.1 pulsesCW
11Channel A: {{0}}Threshold switch2 Bytes9.1 temperature (°C)CW
11Channel A: {{0}}Threshold switch1 Byte5.1 percentage (0..100%)CW
11Channel A: {{0}}Threshold switch2 Bytes9.4 lux (Lux)CW
12Central functionSwitch On/Off1 Bit1.1 switchCW
13Dummy1 BitCR
14Central functionOperating1 Bit1.11 stateCRT
15Dummy1 Bit
16Dummy1 Bit
17Dummy1 Bit
18Dummy1 Bit
19Dummy1 Bit
20Dummy1 Bit
21Dummy1 Bit
Parameters (93)
ParameterTypeDefault
Startup timeoutlist1 s
Modelistnormally open
Prewarninglistnot active
Manual switching offlistactive
On delayunsignedInt 0…300000
Off delayunsignedInt 0…300000
Send state cyclic (0 = not active)unsignedInt 0…300000
Central functionlistnot active
Inverte Lock objectlistno invert
Send statelistat change
Release time for forced control ( 0 = not active)unsignedInt 0…6000
Behavior at bus power uplistno change
Delay time for status after bus power uplist1 s
Logic functionlistwith Switch object and one Logic object
Behavior at bus power uplistState before bus power down
Logic operationslistOR
Channel Alistswitching
Sceneslistnot active
Learn scenelistnot active
Behavior of scenelistOn
Send "Operation" cyclic (0 = not active)unsignedInt 0…300000
Extend time staircase lightlistrestart time
Release time for priority (0 = not active)unsignedInt 0…6000
Priority / Forced controllistnot active
Additional inverted statelistnot active
Invert inputslistno invert
Invert outputlistno invert
Set objects value after bus power uplistnot active
Value for switch objectlistno set
Set object of Logic 1listno set
Set object of Logic 2listno set
Threshold switchlistnot active
Operation hours counterlistnot active
Scene Alistnot active
Scene numberlist1
Scene Blistnot active
Scene numberlist2
Scene Clistnot active
Scene numberlist3
Scene Dlistnot active
Scene numberlist4
Scene Elistnot active
Scene numberlist5
Scene Flistnot active
Scene numberlist6
Scene Glistnot active
Scene numberlist7
Scene Hlistnot active
Scene numberlist8
Lower threshold <list0%
Lower threshold <unsignedInt 0…655000
Lower threshold <float -100…20010
Value settinglist1Byte percent value (0-100%)
Lower threshold <unsignedInt 0…2550
Lower threshold <float 0…100000100
Upper threshold >list90%
Upper threshold >unsignedInt 0…2550
Upper threshold >unsignedInt 0…655000
Upper threshold >float -100…20030
Upper threshold >float 0…10000060000
Behavior of Channel at lower deviationlistnot active
Behavior of Channel at exceedancelistnot active
Set valuelist50%
Set valueunsignedInt 1…25510
Set valueunsignedInt 1…65500100
Set valuefloat -100…20020
Set valuefloat 0…100000400
Initialise with an object for threshold switch after bus power uplistnot active
Type of operation hours counterlistoperation hours counter
Send status of operation hours every … (0 = not active)unsignedInt 0…100000
Send status of Service hours every … (0 = not active)unsignedInt 0…100000
Send service status at intervalsunsignedInt 0…600000
Send operation hours cycliclistnot active
Time factor for object "Staircase light with time"list1 s
Switch objectlistnot active
Repeat impuls signal oncelistnot active
Behavior at unlockinglistno change
Behavior at unlockinglistOff
Behavior after forced controllistno change
Behavior after forced controllistOff
Behavior after deactivation of prioritylistno change
Behavior after deactivation of prioritylistOff
Time of staircase lightunsignedInt 1…300001
Impuls timelist500 ms
Prewarning timeunsignedInt 0…300000
Select data typelist4Byte value in s (DPT 13.100)
Bahavior at lockinglistno change
Prewarning durationunsignedInt 0…300001
Time to the next imulslist0,5 s
Logic functionlistnot active
Behavior at bus power downlistno change
Description of channel/objectstext
Additional texttext

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Switching, Staircase 1-fold UP, flush mounted 3.2 latest$00A963C92026-11-25164 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH AKS-01UP.03 Switch Actuator 1-fold, flush mounted, 16A (AKS-01UP.03), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from MDT technologies GmbH

All MDT technologies GmbH products