AKK-03UP.03 Switch Actuator 3fold, FanCoil AKK-03UP.03
MDT technologies GmbH · Order number AKK-03UP.03 · Actuators › Switch Actuators with current measurment
Compact version 230VAC, 10A ohmic load
Download .knxprod Switch, Staircase 3fold, FanCoil 2.0 · 125 KB
Product
| Manufacturer | MDT technologies GmbH |
|---|---|
| Product name | AKK-03UP.03 Switch Actuator 3fold, FanCoil |
| Order number | AKK-03UP.03 |
| Hardware | Schaltaktor 3fach, FainCoil |
| Medium | Twisted Pair |
| Bus current (mA) | 18 |
| Rail mounted | No |
| Registration | Registered · 2017-02-23 |
| Languages | de-DE, en-US, es-ES, fr-FR |
| Catalog entry | M-0083_H-3.2E28-2_HP-001A-20-A2C5_CI-AKK.2D03UP.2E03-2 |
| Fingerprint | A2C5 |
| SHA-256 | a45eec094464767387666c0c67116dcd2d8aa1d802abbaafeabe22bb8a76e37e |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Switch, Staircase 3fold, FanCoil 2.0
| Application number | $001A |
|---|---|
| Version | 2.0 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 312 |
| Group objects | 91 |
Group objects (91)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Additional fan | Enable additional fan | 1 Bit | 1.1 switch | CW |
| 0 | Channel A | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 1 | Switching Auto/Manual | 1=Automatic / 0 = Manual | 1 Bit | 1.1 switch | CRWTU |
| 1 | Channel A | Staircase lighting | 1 Bit | 1.1 switch | CW |
| 1 | Channel A | Switch pulse | 1 Bit | 1.1 switch | CW |
| 2 | Channel A | Prewarning | 1 Bit | 1.1 switch | CT |
| 2 | Automatic mode | Control value heating | 1 Byte | 5.1 percentage (0..100%) | CW |
| 3 | Automatic mode | Control value cooling | 1 Byte | 5.1 percentage (0..100%) | CW |
| 3 | Channel A | Lock | 1 Bit | 1.3 enable | CW |
| 4 | Automatic mode | Control value failure | 1 Bit | 1.1 switch | CRT |
| 4 | Channel A | Scene | 1 Byte | 17.1 scene number | CW |
| 5 | Automatic mode | Heating/cooling switch over | 1 Bit | 1.100 heating/cooling | CRWTU |
| 5 | Automatic mode | Heating/cooling toggle | 1 Bit | 1.100 heating/cooling | CRWTU |
| 5 | Automatic mode | Heating/cooling switch over | 1 Bit | 1.100 heating/cooling | CRT |
| 5 | Channel A | State | 1 Bit | 1.11 state | CRT |
| 6 | Automatic mode | Switch heating valve | 1 Bit | 1.1 switch | CRT |
| 6 | Automatic mode | Switch heating/cooling valve | 1 Bit | 1.1 switch | CRT |
| 6 | Channel A | Inverted state | 1 Bit | 1.11 state | CRT |
| 7 | Automatic mode | Switch cooling valve | 1 Bit | 1.1 switch | CRT |
| 7 | Channel A | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 8 | Automatic mode | Manual set point offset (1=+/0=-) | 1 Bit | 1.7 step | CW |
| 8 | Channel A | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 9 | Direct mode | Step 0 | 1 Bit | 1.1 switch | CW |
| 9 | Direct mode | Bit 0 | 1 Bit | 1.1 switch | CW |
| 9 | Direct mode | Up/Down | 1 Bit | 1.7 step | CW |
| 9 | Direct mode | 1Byte value | 1 Byte | 5.5 ratio (0..255) | CW |
| 10 | Direct mode | Step 1 | 1 Bit | 1.1 switch | CW |
| 10 | Direct mode | Bit 1 | 1 Bit | 1.1 switch | CW |
| 11 | Direct mode | Step 2 | 1 Bit | 1.1 switch | CW |
| 11 | Channel B | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 12 | Direct mode | Step 3 | 1 Bit | 1.1 switch | CW |
| 12 | Channel B | Staircase lighting | 1 Bit | 1.1 switch | CW |
| 12 | Channel B | Switch pulse | 1 Bit | 1.1 switch | CW |
| 13 | Channel B | Prewarning | 1 Bit | 1.1 switch | CT |
| 14 | External heating request | Status input (Cascading) | 1 Bit | 1.1 switch | CW |
| 14 | Channel B | Lock | 1 Bit | 1.3 enable | CW |
| 15 | External heating request | Status output | 1 Bit | 1.1 switch | CRT |
| 15 | Channel B | Scene | 1 Byte | 17.1 scene number | CW |
| 16 | External cooling request | Status input (Cascading) | 1 Bit | 1.1 switch | CW |
| 16 | Channel B | State | 1 Bit | 1.11 state | CRT |
| 17 | External cooling request | Status output | 1 Bit | 1.11 state | CRT |
| 17 | Channel B | Inverted state | 1 Bit | 1.11 state | CRT |
| 18 | Maximum control value for heating | Status input (Cascading) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 18 | Channel B | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 19 | Maximum control value for heating | Status output | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 19 | Channel B | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 20 | Maximum control value for cooling | Status input (Cascading) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 21 | Maximum control value for cooling | Status output | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 22 | Maximum fan level heating | Status input (Cascading) | 1 Byte | 5.5 ratio (0..255) | CW |
| 22 | Channel C | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 22 | Maximum fan level heating | Status level 1 | 1 Bit | 1.11 state | CRT |
| 23 | Maximum fan level heating | Status output | 1 Byte | 5.5 ratio (0..255) | CRT |
| 23 | Channel C | Staircase lighting | 1 Bit | 1.1 switch | CW |
| 23 | Channel C | Switch pulse | 1 Bit | 1.1 switch | CW |
| 23 | Maximum fan level heating | Status level 2 | 1 Bit | 1.11 state | CRT |
| 24 | Channel C | Prewarning | 1 Bit | 1.1 switch | CT |
| 24 | Maximum fan level heating | Status level 3 | 1 Bit | 1.11 state | CRT |
| 25 | Channel C | Lock | 1 Bit | 1.3 enable | CW |
| 26 | Maximum fan level cooling | Status input (Cascading) | 1 Byte | 5.5 ratio (0..255) | CW |
| 26 | Channel C | Scene | 1 Byte | 17.1 scene number | CW |
| 26 | Maximum fan level cooling | Status level 1 | 1 Bit | 1.11 state | CRT |
| 27 | Maximum fan level cooling | Status output | 1 Byte | 5.5 ratio (0..255) | CRT |
| 27 | Channel C | State | 1 Bit | 1.11 state | CRT |
| 27 | Maximum fan level cooling | Status level 2 | 1 Bit | 1.11 state | CRT |
| 28 | Maximum fan level cooling | Status level 3 | 1 Bit | 1.11 state | CRT |
| 28 | Channel C | Inverted state | 1 Bit | 1.11 state | CRT |
| 29 | Channel C | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 30 | Lock object 1 | Lock | 1 Bit | 1.3 enable | CW |
| 30 | Channel C | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 31 | Lock object 2 | Lock | 1 Bit | 1.3 enable | CW |
| 32 | Dummy | 1 Bit | |||
| 33 | Dummy | 1 Bit | |||
| 34 | Dummy | 1 Bit | |||
| 35 | Dummy | 1 Bit | |||
| 36 | Dummy | 1 Bit | |||
| 37 | Dummy | 1 Bit | |||
| 38 | Dummy | 1 Bit | |||
| 39 | Dummy | 1 Bit | |||
| 40 | Dummy | 1 Bit | |||
| 41 | Dummy | 1 Bit | |||
| 42 | Dummy | 1 Bit | |||
| 43 | Dummy | 1 Bit | |||
| 44 | Automatic mode | Temperature value | 2 Bytes | 9.1 temperature (°C) | CW |
| 45 | Automatic mode | Setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 46 | Automatic mode | Setpoint offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 47 | Automatic mode | Current setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 48 | Central function | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 49 | Dummy | 1 Bit | |||
| 50 | Operating | Send Status | 1 Bit | 1.1 switch | CRT |
| 51 | Day/Night | Switching | 1 Bit | 1.1 switch | CW |
| 51 | Day/Night | Switching | 1 Bit | 1.1 switch | CRWTU |
Parameters (125)
| Parameter | Type | Default |
|---|---|---|
| Startup timeout | unsignedInt 0…120 | 5 |
| Cyclic telegram "Operating" | list | not used |
| Day/Night object | list | no use |
| Polarity of Day/Night object | list | Day = 1 / Night = 0 |
| Mode | list | FanCoil |
| Betriebsart Lüfter | list | toggle switch |
| Type of FanCoil system | list | 2-Rohr, heating and cooling |
| Send cyclic Switch heating valve | unsignedInt 0…3600 | 0 |
| Send cyclic | unsignedInt 0…3600 | 0 |
| Delay between step switching | unsignedInt 50…5000 | 200 |
| Type of step switching | list | switch successive |
| Minimum holding time of each step | unsignedInt 0…1000 | 5 |
| Maximum step at night | list | Step 3 |
| Switch-on behavior | list | direct start |
| Minimum holding time of start-up level | unsignedInt 0…1000 | 0 |
| Off delay of the fan | unsignedInt 0…1000 | 0 |
| Sommer/Winter Objekt | list | Summer = 1 / Winter = 0 |
| Block object 1 | list | not active |
| Action at activation of blocking 1 | list | switch to step 2 |
| Action at deactivation of blocking 1 | list | restore previous step (memory function) |
| Block object 2 | list | not active |
| Action at activation of blocking 2 | list | switch to step 2 |
| Action at deactivation of blocking 2 | list | restore previous step (memory function) |
| Additional Fan | list | not active |
| Automatic mode | list | active |
| Deirect mode | list | not active |
| Status object | list | active |
| Cyclic time for additional fan | unsignedInt 0…1500 | 0 |
| Duration for additional fan | unsignedInt 0…1000 | 0 |
| Step additional fan | list | Step 2 |
| Manual additional fan | list | active |
| Duration for manual additional fan | unsignedInt 0…1800 | 20 |
| Step manual additional fan | list | Step 3 |
| Automatic mode | list | control value |
| Release time to automatic mode | unsignedInt 0…1440 | 0 |
| Dead time at switching Heating/Cooling | unsignedInt 0…1000 | 60 |
| Monitoring time of control value | unsignedInt 0…360 | 0 |
| Ventilating fan step with control value failure | list | Step 1 |
| Threshold for fan step 1 | list | 5% |
| Threshold for fan step 2 | list | 50% |
| Threshold for fan step 3 | list | 80% |
| Threshold for fan step 1 | list | 0,5 K |
| Threshold for fan step 2 | list | 1,5 K |
| Threshold for fan step 3 | list | 3,0 K |
| Hysteresis | list | 0,2 K |
| Hysteresis | list | 2% |
| Umschalten zwischen Heizen und Kühlen | list | manually over object, 1 control value |
| Switch over between heating and cooling | list | automatically by control value |
| Setpoint temperature | list | 21 °C |
| Setpoint offset over 2Byte object | list | not active |
| Maximum setpoint offset | list | 1,0 K |
| Setpoint offset over 1Bit object | list | not active |
| Step range | list | 0,5 K |
| Switch over between heating and cooling | list | over temperature and over object |
| Dead zone between Heating and Cooling | list | 2,0 K |
| Setting of the input mode for direct operation | list | step switch |
| Step for status | list | use actual step |
| Status fan at heating mode | list | active |
| Send condition | list | at changes |
| Time for cyclic sending | unsignedInt 0…3600 | 300 |
| Status fan at heating mode active cascadable | list | not active |
| Status maximum control value | list | not active |
| Send condition | list | at changes (<2%) |
| Status of maximum control value cascadable at heating mode | list | not active |
| Status maximum fan | list | not active |
| Status of maximum fan step cascadable at heating mode | list | not active |
| Status fan at cooling mode | list | active |
| Status fan at cooling mode active cascadable | list | not active |
| Status of maximum control value | list | not active |
| Status of maximum control value cascadable at cooling mode | list | not active |
| Status of maximum fan step | list | not active |
| Status of maximum fan step cascadable at cooling mode | list | not active |
| Channel A | list | switching |
| Logic function | list | not active |
| Scenes | list | not active |
| Mode | list | normally open |
| On delay | unsignedInt 0…30000 | 0 |
| Off delay | unsignedInt 0…30000 | 0 |
| Central function | list | not active |
| Send state | list | at change |
| Send state cyclic (0 = not active) | unsignedInt 0…30000 | 0 |
| Additional inverted state | list | not active |
| Bahavior at locking | list | no change |
| Behavior at unlocking | list | no change |
| Behavior at bus power up | list | no change |
| Behavior at bus power down | list | no change |
| Prewarning time | unsignedInt 0…30000 | 0 |
| Inverte Lock object | list | not inverted |
| Manual switching off | list | active |
| Extend time staircase light | list | restart time |
| Delay time for status after bus power up | list | 1 s |
| Logic operations | list | OR |
| Logic function | list | with one object |
| Invert inputs | list | no invert |
| Invert output | list | not inverted |
| Learn scene | list | disabled |
| Scene A | list | not active |
| Scene number | list | 1 |
| Behavior of scene | list | ON |
| Scene B | list | not active |
| Scene number | list | 2 |
| Scene C | list | not active |
| Scene number | list | 3 |
| Scene D | list | not active |
| Scene number | list | 4 |
| Scene E | list | not active |
| Scene number | list | 5 |
| Scene F | list | not active |
| Scene number | list | 6 |
| Scene G | list | not active |
| Scene number | list | 7 |
| Scene H | list | not active |
| Scene number | list | 8 |
| Switch object | list | not active |
| Time of staircase light | unsignedInt 1…30000 | 1 |
| Prewarning | list | not active |
| Prewarning duration | unsignedInt 0…30000 | 1 |
| Behavior at unlocking | list | Off |
| Behavior at bus power up | list | State before bus power down |
| Priority / Forced control | list | not active |
| Impuls time | list | 500 ms |
| Repeat impuls signal once | list | not active |
| Time to the next imuls | list | 0,5 s |
| Channel B | list | switching |
| Channel C | list | switching |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Switch, Staircase 3fold, FanCoil 2.0 latest | $001A | A2C5 | 2026-11-25 | 125 KB | Download |
About this file
This is the official ETS product database for the MDT technologies GmbH AKK-03UP.03 Switch Actuator 3fold, FanCoil (AKK-03UP.03), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from MDT technologies GmbH
- Analog I/O 2fold, flush mounted AIO-0210V.01
- Analog I/O 4fold, MDRC AIO-0410V.01
- AKD-0103.01 Dimming actuator 1-f, 4TE, 230VAC,600W AKD-0103.01
- AKD-0201.01 Dimming actuator 2-f, 4TE, 230VAC,250W AKD-0201.01
- AKD-0201.02 Dimming Actuator 2-fold AKD-0201.02
- AKD-0203.01 Dimming actuator 2-f, 8TE, 230VAC,600W AKD-0203.01
- AKD-0224V.02 LED Controler 2 Ch AKD-0224V.02
- AKD-0230CC.02 LED Controller CC/CV 30 W / 230 V 2-channel AKD-0230CC.02
- AKD-0260CC.02 LED Controller CC/CV 60 W / 230 V 2-channel AKD-0260CC.02
- AKD-0324V.02 LED Controler 3 Ch/RGB AKD-0324V.02
- AKD-0401.01 Dimming actuator 4-f, 8TE, 230VAC,250W AKD-0401.01
- AKD-0401.02 Dimming Actuator 4-fold AKD-0401.02