MDT technologies GmbH AKK-03UP.03 AKK-03UP.03 Switch Actuator 3fold, FanCoil

AKK-03UP.03 Switch Actuator 3fold, FanCoil AKK-03UP.03

MDT technologies GmbH · Order number AKK-03UP.03 · Actuators › Switch Actuators with current measurment

Compact version 230VAC, 10A ohmic load

Download .knxprod Switch, Staircase 3fold, FanCoil 2.0 · 125 KB

Product

ManufacturerMDT technologies GmbH
Product nameAKK-03UP.03 Switch Actuator 3fold, FanCoil
Order numberAKK-03UP.03
HardwareSchaltaktor 3fach, FainCoil
MediumTwisted Pair
Bus current (mA)18
Rail mountedNo
RegistrationRegistered · 2017-02-23
Languagesde-DE, en-US, es-ES, fr-FR
Catalog entryM-0083_H-3.2E28-2_HP-001A-20-A2C5_CI-AKK.2D03UP.2E03-2
FingerprintA2C5
SHA-256a45eec094464767387666c0c67116dcd2d8aa1d802abbaafeabe22bb8a76e37e
First seen2026-11-25
Markets69 markets

Application program: Switch, Staircase 3fold, FanCoil 2.0

Application number$001A
Version2.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters312
Group objects91
Group objects (91)
NoNameFunctionSizeDPTFlags
0Additional fanEnable additional fan1 Bit1.1 switchCW
0Channel ASwitch On/Off1 Bit1.1 switchCW
1Switching Auto/Manual1=Automatic / 0 = Manual1 Bit1.1 switchCRWTU
1Channel AStaircase lighting1 Bit1.1 switchCW
1Channel ASwitch pulse1 Bit1.1 switchCW
2Channel APrewarning1 Bit1.1 switchCT
2Automatic modeControl value heating1 Byte5.1 percentage (0..100%)CW
3Automatic modeControl value cooling1 Byte5.1 percentage (0..100%)CW
3Channel ALock1 Bit1.3 enableCW
4Automatic modeControl value failure1 Bit1.1 switchCRT
4Channel AScene1 Byte17.1 scene numberCW
5Automatic modeHeating/cooling switch over1 Bit1.100 heating/coolingCRWTU
5Automatic modeHeating/cooling toggle1 Bit1.100 heating/coolingCRWTU
5Automatic modeHeating/cooling switch over1 Bit1.100 heating/coolingCRT
5Channel AState1 Bit1.11 stateCRT
6Automatic modeSwitch heating valve1 Bit1.1 switchCRT
6Automatic modeSwitch heating/cooling valve1 Bit1.1 switchCRT
6Channel AInverted state1 Bit1.11 stateCRT
7Automatic modeSwitch cooling valve1 Bit1.1 switchCRT
7Channel ALogic 11 Bit1.2 booleanCW
8Automatic modeManual set point offset (1=+/0=-)1 Bit1.7 stepCW
8Channel ALogic 21 Bit1.2 booleanCW
9Direct modeStep 01 Bit1.1 switchCW
9Direct modeBit 01 Bit1.1 switchCW
9Direct modeUp/Down1 Bit1.7 stepCW
9Direct mode1Byte value1 Byte5.5 ratio (0..255)CW
10Direct modeStep 11 Bit1.1 switchCW
10Direct modeBit 11 Bit1.1 switchCW
11Direct modeStep 21 Bit1.1 switchCW
11Channel BSwitch On/Off1 Bit1.1 switchCW
12Direct modeStep 31 Bit1.1 switchCW
12Channel BStaircase lighting1 Bit1.1 switchCW
12Channel BSwitch pulse1 Bit1.1 switchCW
13Channel BPrewarning1 Bit1.1 switchCT
14External heating requestStatus input (Cascading)1 Bit1.1 switchCW
14Channel BLock1 Bit1.3 enableCW
15External heating requestStatus output1 Bit1.1 switchCRT
15Channel BScene1 Byte17.1 scene numberCW
16External cooling requestStatus input (Cascading)1 Bit1.1 switchCW
16Channel BState1 Bit1.11 stateCRT
17External cooling requestStatus output1 Bit1.11 stateCRT
17Channel BInverted state1 Bit1.11 stateCRT
18Maximum control value for heatingStatus input (Cascading)1 Byte5.1 percentage (0..100%)CW
18Channel BLogic 11 Bit1.2 booleanCW
19Maximum control value for heatingStatus output1 Byte5.1 percentage (0..100%)CRT
19Channel BLogic 21 Bit1.2 booleanCW
20Maximum control value for coolingStatus input (Cascading)1 Byte5.1 percentage (0..100%)CW
21Maximum control value for coolingStatus output1 Byte5.1 percentage (0..100%)CRT
22Maximum fan level heatingStatus input (Cascading)1 Byte5.5 ratio (0..255)CW
22Channel CSwitch On/Off1 Bit1.1 switchCW
22Maximum fan level heatingStatus level 11 Bit1.11 stateCRT
23Maximum fan level heatingStatus output1 Byte5.5 ratio (0..255)CRT
23Channel CStaircase lighting1 Bit1.1 switchCW
23Channel CSwitch pulse1 Bit1.1 switchCW
23Maximum fan level heatingStatus level 21 Bit1.11 stateCRT
24Channel CPrewarning1 Bit1.1 switchCT
24Maximum fan level heatingStatus level 31 Bit1.11 stateCRT
25Channel CLock1 Bit1.3 enableCW
26Maximum fan level coolingStatus input (Cascading)1 Byte5.5 ratio (0..255)CW
26Channel CScene1 Byte17.1 scene numberCW
26Maximum fan level coolingStatus level 11 Bit1.11 stateCRT
27Maximum fan level coolingStatus output1 Byte5.5 ratio (0..255)CRT
27Channel CState1 Bit1.11 stateCRT
27Maximum fan level coolingStatus level 21 Bit1.11 stateCRT
28Maximum fan level coolingStatus level 31 Bit1.11 stateCRT
28Channel CInverted state1 Bit1.11 stateCRT
29Channel CLogic 11 Bit1.2 booleanCW
30Lock object 1Lock1 Bit1.3 enableCW
30Channel CLogic 21 Bit1.2 booleanCW
31Lock object 2Lock1 Bit1.3 enableCW
32Dummy1 Bit
33Dummy1 Bit
34Dummy1 Bit
35Dummy1 Bit
36Dummy1 Bit
37Dummy1 Bit
38Dummy1 Bit
39Dummy1 Bit
40Dummy1 Bit
41Dummy1 Bit
42Dummy1 Bit
43Dummy1 Bit
44Automatic modeTemperature value2 Bytes9.1 temperature (°C)CW
45Automatic modeSetpoint temperature2 Bytes9.1 temperature (°C)CW
46Automatic modeSetpoint offset2 Bytes9.2 temperature difference (K)CW
47Automatic modeCurrent setpoint temperature2 Bytes9.1 temperature (°C)CRT
48Central functionSwitch On/Off1 Bit1.1 switchCW
49Dummy1 Bit
50OperatingSend Status1 Bit1.1 switchCRT
51Day/NightSwitching1 Bit1.1 switchCW
51Day/NightSwitching1 Bit1.1 switchCRWTU
Parameters (125)
ParameterTypeDefault
Startup timeoutunsignedInt 0…1205
Cyclic telegram "Operating"listnot used
Day/Night objectlistno use
Polarity of Day/Night objectlistDay = 1 / Night = 0
ModelistFanCoil
Betriebsart Lüfterlisttoggle switch
Type of FanCoil systemlist2-Rohr, heating and cooling
Send cyclic Switch heating valveunsignedInt 0…36000
Send cyclicunsignedInt 0…36000
Delay between step switchingunsignedInt 50…5000200
Type of step switchinglistswitch successive
Minimum holding time of each stepunsignedInt 0…10005
Maximum step at nightlistStep 3
Switch-on behaviorlistdirect start
Minimum holding time of start-up levelunsignedInt 0…10000
Off delay of the fanunsignedInt 0…10000
Sommer/Winter ObjektlistSummer = 1 / Winter = 0
Block object 1listnot active
Action at activation of blocking 1listswitch to step 2
Action at deactivation of blocking 1listrestore previous step (memory function)
Block object 2listnot active
Action at activation of blocking 2listswitch to step 2
Action at deactivation of blocking 2listrestore previous step (memory function)
Additional Fanlistnot active
Automatic modelistactive
Deirect modelistnot active
Status objectlistactive
Cyclic time for additional fanunsignedInt 0…15000
Duration for additional fanunsignedInt 0…10000
Step additional fanlistStep 2
Manual additional fanlistactive
Duration for manual additional fanunsignedInt 0…180020
Step manual additional fanlistStep 3
Automatic modelistcontrol value
Release time to automatic modeunsignedInt 0…14400
Dead time at switching Heating/CoolingunsignedInt 0…100060
Monitoring time of control valueunsignedInt 0…3600
Ventilating fan step with control value failurelistStep 1
Threshold for fan step 1list5%
Threshold for fan step 2list50%
Threshold for fan step 3list80%
Threshold for fan step 1list0,5 K
Threshold for fan step 2list1,5 K
Threshold for fan step 3list3,0 K
Hysteresislist0,2 K
Hysteresislist2%
Umschalten zwischen Heizen und Kühlenlistmanually over object, 1 control value
Switch over between heating and coolinglistautomatically by control value
Setpoint temperaturelist21 °C
Setpoint offset over 2Byte objectlistnot active
Maximum setpoint offsetlist1,0 K
Setpoint offset over 1Bit objectlistnot active
Step rangelist0,5 K
Switch over between heating and coolinglistover temperature and over object
Dead zone between Heating and Coolinglist2,0 K
Setting of the input mode for direct operationliststep switch
Step for statuslistuse actual step
Status fan at heating modelistactive
Send conditionlistat changes
Time for cyclic sendingunsignedInt 0…3600300
Status fan at heating mode active cascadablelistnot active
Status maximum control valuelistnot active
Send conditionlistat changes (<2%)
Status of maximum control value cascadable at heating modelistnot active
Status maximum fanlistnot active
Status of maximum fan step cascadable at heating modelistnot active
Status fan at cooling modelistactive
Status fan at cooling mode active cascadablelistnot active
Status of maximum control valuelistnot active
Status of maximum control value cascadable at cooling modelistnot active
Status of maximum fan steplistnot active
Status of maximum fan step cascadable at cooling modelistnot active
Channel Alistswitching
Logic functionlistnot active
Sceneslistnot active
Modelistnormally open
On delayunsignedInt 0…300000
Off delayunsignedInt 0…300000
Central functionlistnot active
Send statelistat change
Send state cyclic (0 = not active)unsignedInt 0…300000
Additional inverted statelistnot active
Bahavior at lockinglistno change
Behavior at unlockinglistno change
Behavior at bus power uplistno change
Behavior at bus power downlistno change
Prewarning timeunsignedInt 0…300000
Inverte Lock objectlistnot inverted
Manual switching offlistactive
Extend time staircase lightlistrestart time
Delay time for status after bus power uplist1 s
Logic operationslistOR
Logic functionlistwith one object
Invert inputslistno invert
Invert outputlistnot inverted
Learn scenelistdisabled
Scene Alistnot active
Scene numberlist1
Behavior of scenelistON
Scene Blistnot active
Scene numberlist2
Scene Clistnot active
Scene numberlist3
Scene Dlistnot active
Scene numberlist4
Scene Elistnot active
Scene numberlist5
Scene Flistnot active
Scene numberlist6
Scene Glistnot active
Scene numberlist7
Scene Hlistnot active
Scene numberlist8
Switch objectlistnot active
Time of staircase lightunsignedInt 1…300001
Prewarninglistnot active
Prewarning durationunsignedInt 0…300001
Behavior at unlockinglistOff
Behavior at bus power uplistState before bus power down
Priority / Forced controllistnot active
Impuls timelist500 ms
Repeat impuls signal oncelistnot active
Time to the next imulslist0,5 s
Channel Blistswitching
Channel Clistswitching

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Switch, Staircase 3fold, FanCoil 2.0 latest$001AA2C52026-11-25125 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH AKK-03UP.03 Switch Actuator 3fold, FanCoil (AKK-03UP.03), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from MDT technologies GmbH

All MDT technologies GmbH products