KNX Database

AKI-0816.03 Switch Actuator 8-fold, 8SU, 16/20A AKI-0816.03

MDT technologies GmbH · Order number AKI-0816.03 · Actuators › Switch Actuators, standard and industrial version

Industrial version 230VAC, 16/20A, 200µF C-Load

Download .knxprod Switching, Staircase 8f 2.1 · 153 KB

Product

ManufacturerMDT technologies GmbH
Product nameAKI-0816.03 Switch Actuator 8-fold, 8SU, 16/20A
Order numberAKI-0816.03
HardwareSchaltaktoren 8-fach
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)142.3
RegistrationCertified · 2016-03-09
Languagesde-DE, en-US
Catalog entryM-0083_H-24-2_HP-0015-21-78B4_CI-AKI.2D0816.2E03-1
Fingerprint78B4
SHA-25694195abbb59760f2276c8ae293773cce438094441843b5135e085fa429e47715
First seen2026-11-25
Markets69 markets

Application program: Switching, Staircase 8f 2.1

Application number$0015
Version2.1
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters916
Group objects210
Group objects (210)
NoNameFunctionSizeDPTFlags
0Channel ASwitch On/Off1 Bit1.1 switchCW
1Channel AStaircase light1 Bit1.1 switchCW
1Channel AService required1 Bit1.5 alarmCRT
1Channel ASwitch pulse1 Bit1.1 switchCW
2Channel AResponse operating hours2 Bytes7.7 time (h)CRT
2Channel ATime to next service2 Bytes7.7 time (h)CRT
2Channel AStaircase light with time1 Byte5.5 ratio (0..255)CW
2Channel AResponse operating hours4 Bytes13.100 time lag (s)CRT
2Channel ATime to next service4 Bytes13.100 time lag (s)CRT
3Channel APrewarning1 Bit1.1 switchCT
3Channel AReset operation hours1 Bit1.1 switchCW
3Channel AReset sevice1 Bit1.1 switchCW
4Channel ALock1 Bit1.3 enableCW
5Channel AForced control2 Bit2.1 switch controlCW
5Channel APriority1 Bit1.1 switchCW
6Channel AScene1 Byte17.1 scene numberCW
7Channel AState1 Bit1.11 stateCRT
8Channel AInverted state1 Bit1.11 stateCRT
9Channel ALogic 11 Bit1.2 booleanCW
10Channel ALogic 21 Bit1.2 booleanCW
11Channel AThreshold switch1 Byte5.5 ratio (0..255)CW
11Channel AThreshold switch2 Bytes7.1 pulsesCW
11Channel AThreshold switch2 Bytes9.1 temperature (°C)CW
11Channel AThreshold switch1 Byte5.1 percentage (0..100%)CW
11Channel AThreshold switch2 Bytes9.4 lux (Lux)CW
12Channel BSwitch On/Off1 Bit1.1 switchCW
13Channel BService required1 Bit1.5 alarmCRT
13Channel BStaircase light1 Bit1.1 switchCW
13Channel BSwitch pulse1 Bit1.1 switchCW
14Channel BResponse operating hours4 Bytes13.100 time lag (s)CRT
14Channel BResponse operating hours2 Bytes7.7 time (h)CRT
14Channel BTime to next service4 Bytes13.100 time lag (s)CRT
14Channel BTime to next service2 Bytes7.7 time (h)CRT
14Channel BStaircase light with time1 Byte5.5 ratio (0..255)CW
15Channel BReset operation hours1 Bit1.1 switchCW
15Channel BReset sevice1 Bit1.1 switchCW
15Channel BPrewarning1 Bit1.1 switchCT
16Channel BLock1 Bit1.3 enableCW
17Channel BForced control2 Bit2.1 switch controlCW
17Channel BPriority1 Bit1.1 switchCW
18Channel BScene1 Byte17.1 scene numberCW
19Channel BState1 Bit1.11 stateCRT
20Channel BInverted state1 Bit1.11 stateCRT
21Channel BLogic 11 Bit1.2 booleanCW
22Channel BLogic 21 Bit1.2 booleanCW
23Channel BThreshold switch1 Byte5.1 percentage (0..100%)CW
23Channel BThreshold switch1 Byte5.5 ratio (0..255)CW
23Channel BThreshold switch2 Bytes7.1 pulsesCW
23Channel BThreshold switch2 Bytes9.1 temperature (°C)CW
23Channel BThreshold switch2 Bytes9.4 lux (Lux)CW
24Channel CSwitch On/Off1 Bit1.1 switchCW
25Channel CService required1 Bit1.5 alarmCRT
25Channel CStaircase light1 Bit1.1 switchCW
25Channel CSwitch pulse1 Bit1.1 switchCW
26Channel CResponse operating hours4 Bytes13.100 time lag (s)CRT
26Channel CResponse operating hours2 Bytes7.7 time (h)CRT
26Channel CTime to next service4 Bytes13.100 time lag (s)CRT
26Channel CTime to next service2 Bytes7.7 time (h)CRT
26Channel CStaircase light with time1 Byte5.5 ratio (0..255)CW
27Channel CReset operation hours1 Bit1.1 switchCW
27Channel CReset sevice1 Bit1.1 switchCW
27Channel CPrewarning1 Bit1.1 switchCT
28Channel CLock1 Bit1.3 enableCW
29Channel CForced control2 Bit2.1 switch controlCW
29Channel CPriority1 Bit1.1 switchCW
30Channel CScene1 Byte17.1 scene numberCW
31Channel CState1 Bit1.11 stateCRT
32Channel CInverted state1 Bit1.11 stateCRT
33Channel CLogic 11 Bit1.2 booleanCW
34Channel CLogic 21 Bit1.2 booleanCW
35Channel CThreshold switch1 Byte5.1 percentage (0..100%)CW
35Channel CThreshold switch1 Byte5.5 ratio (0..255)CW
35Channel CThreshold switch2 Bytes7.1 pulsesCW
35Channel CThreshold switch2 Bytes9.1 temperature (°C)CW
35Channel CThreshold switch2 Bytes9.4 lux (Lux)CW
36Channel DSwitch On/Off1 Bit1.1 switchCW
37Channel DService required1 Bit1.5 alarmCRT
37Channel DStaircase light1 Bit1.1 switchCW
37Channel DSwitch pulse1 Bit1.1 switchCW
38Channel DResponse operating hours4 Bytes13.100 time lag (s)CRT
38Channel DResponse operating hours2 Bytes7.7 time (h)CRT
38Channel DTime to next service4 Bytes13.100 time lag (s)CRT
38Channel DTime to next service2 Bytes7.7 time (h)CRT
38Channel DStaircase light with time1 Byte5.5 ratio (0..255)CW
39Channel DReset operation hours1 Bit1.1 switchCW
39Channel DReset sevice1 Bit1.1 switchCW
39Channel DPrewarning1 Bit1.1 switchCT
40Channel DLock1 Bit1.3 enableCW
41Channel DForced control2 Bit2.1 switch controlCW
41Channel DPriority1 Bit1.1 switchCW
42Channel DScene1 Byte17.1 scene numberCW
43Channel DState1 Bit1.11 stateCRT
44Channel Dinverted state1 Bit1.11 stateCRT
45Channel DLogic 11 Bit1.2 booleanCW
46Channel DLogic 21 Bit1.2 booleanCW
47Channel DThreshold switch1 Byte5.1 percentage (0..100%)CW
47Channel DThreshold switch1 Byte5.5 ratio (0..255)CW
47Channel DThreshold switch2 Bytes7.1 pulsesCW
47Channel DThreshold switch2 Bytes9.1 temperature (°C)CW
47Channel DThreshold switch2 Bytes9.4 lux (Lux)CW
48Channel ESwitch On/Off1 Bit1.1 switchCW
49Channel EService required1 Bit1.5 alarmCRT
49Channel EStaircase light1 Bit1.1 switchCW
49Channel ESwitch pulse1 Bit1.1 switchCW
50Channel EResponse operating hours4 Bytes13.100 time lag (s)CRT
50Channel EResponse operating hours2 Bytes7.7 time (h)CRT
50Channel ETime to next service4 Bytes13.100 time lag (s)CRT
50Channel ETime to next service2 Bytes7.7 time (h)CRT
50Channel EStaircase light with time1 Byte5.5 ratio (0..255)CW
51Channel EReset operation hours1 Bit1.1 switchCW
51Channel EReset sevice1 Bit1.1 switchCW
51Channel EPrewarning1 Bit1.1 switchCT
52Channel ELock1 Bit1.3 enableCW
53Channel EForced control2 Bit2.1 switch controlCW
53Channel EPriority1 Bit1.1 switchCW
54Channel EScene1 Byte17.1 scene numberCW
55Channel EState1 Bit1.11 stateCRT
56Channel Einverted state1 Bit1.11 stateCRT
57Channel ELogic 11 Bit1.2 booleanCW
58Channel ELogic 21 Bit1.2 booleanCW
59Channel EThreshold switch1 Byte5.1 percentage (0..100%)CW
59Channel EThreshold switch1 Byte5.5 ratio (0..255)CW
59Channel EThreshold switch2 Bytes7.1 pulsesCW
59Channel EThreshold switch2 Bytes9.1 temperature (°C)CW
59Channel EThreshold switch2 Bytes9.4 lux (Lux)CW
60Channel FSwitch On/Off1 Bit1.1 switchCW
61Channel FService required1 Bit1.5 alarmCRT
61Channel FStaircase light1 Bit1.1 switchCW
61Channel FSwitch pulse1 Bit1.1 switchCW
62Channel FResponse operating hours4 Bytes13.100 time lag (s)CRT
62Channel FResponse operating hours2 Bytes7.7 time (h)CRT
62Channel FTime to next service4 Bytes13.100 time lag (s)CRT
62Channel FTime to next service2 Bytes7.7 time (h)CRT
62Channel FStaircase light with time1 Byte5.5 ratio (0..255)CW
63Channel FReset operation hours1 Bit1.1 switchCW
63Channel FReset sevice1 Bit1.1 switchCW
63Channel FPrewarning1 Bit1.1 switchCT
64Channel FLock1 Bit1.3 enableCW
65Channel FForced control2 Bit2.1 switch controlCW
65Channel FPriority1 Bit1.1 switchCW
66Channel FScene1 Byte17.1 scene numberCW
67Channel FState1 Bit1.11 stateCRT
68Channel Finverted state1 Bit1.11 stateCRT
69Channel FLogic 11 Bit1.2 booleanCW
70Channel FLogic 21 Bit1.2 booleanCW
71Channel FThreshold switch1 Byte5.1 percentage (0..100%)CW
71Channel FThreshold switch1 Byte5.5 ratio (0..255)CW
71Channel FThreshold switch2 Bytes7.1 pulsesCW
71Channel FThreshold switch2 Bytes9.1 temperature (°C)CW
71Channel FThreshold switch2 Bytes9.4 lux (Lux)CW
72Channel GSwitch On/Off1 Bit1.1 switchCW
73Channel GService required1 Bit1.5 alarmCRT
73Channel GStaircase light1 Bit1.1 switchCW
73Channel GSwitch pulse1 Bit1.1 switchCW
74Channel GResponse operating hours4 Bytes13.100 time lag (s)CRT
74Channel GResponse operating hours2 Bytes7.7 time (h)CRT
74Channel GTime to next service4 Bytes13.100 time lag (s)CRT
74Channel GTime to next service2 Bytes7.7 time (h)CRT
74Channel GStaircase light with time1 Byte5.5 ratio (0..255)CW
75Channel GReset operation hours1 Bit1.1 switchCW
75Channel GReset sevice1 Bit1.1 switchCW
75Channel GPrewarning1 Bit1.1 switchCT
76Channel GLock1 Bit1.3 enableCW
77Channel GForced control2 Bit2.1 switch controlCW
77Channel GPriority1 Bit1.1 switchCW
78Channel GScene1 Byte17.1 scene numberCW
79Channel GState1 Bit1.11 stateCRT
80Channel Ginverted state1 Bit1.11 stateCRT
81Channel GLogic 11 Bit1.2 booleanCW
82Channel GLogic 21 Bit1.2 booleanCW
83Channel GThreshold switch1 Byte5.1 percentage (0..100%)CW
83Channel GThreshold switch1 Byte5.5 ratio (0..255)CW
83Channel GThreshold switch2 Bytes7.1 pulsesCW
83Channel GThreshold switch2 Bytes9.1 temperature (°C)CW
83Channel GThreshold switch2 Bytes9.4 lux (Lux)CW
84Channel HSwitch On/Off1 Bit1.1 switchCW
85Channel HService required1 Bit1.5 alarmCRT
85Channel HStaircase light1 Bit1.1 switchCW
85Channel HSwitch pulse1 Bit1.1 switchCW
86Channel HResponse operating hours4 Bytes13.100 time lag (s)CRT
86Channel HResponse operating hours2 Bytes7.7 time (h)CRT
86Channel HTime to next service4 Bytes13.100 time lag (s)CRT
86Channel HTime to next service2 Bytes7.7 time (h)CRT
86Channel HStaircase light with time1 Byte5.5 ratio (0..255)CW
87Channel HReset operation hours1 Bit1.1 switchCW
87Channel HReset sevice1 Bit1.1 switchCW
87Channel HPrewarning1 Bit1.1 switchCT
88Channel HLock1 Bit1.3 enableCW
89Channel HForced control2 Bit2.1 switch controlCW
89Channel HPriority1 Bit1.1 switchCW
90Channel HScene1 Byte17.1 scene numberCW
91Channel HState1 Bit1.11 stateCRT
92Channel Hinverted state1 Bit1.11 stateCRT
93Channel HLogic 11 Bit1.2 booleanCW
94Channel HLogic 21 Bit1.2 booleanCW
95Channel HThreshold switch1 Byte5.1 percentage (0..100%)CW
95Channel HThreshold switch1 Byte5.5 ratio (0..255)CW
95Channel HThreshold switch2 Bytes7.1 pulsesCW
95Channel HThreshold switch2 Bytes9.1 temperature (°C)CW
95Channel HThreshold switch2 Bytes9.4 lux (Lux)CW
96Central functionSwitch On/Off1 Bit1.1 switchCW
97Central functionLock hand control1 Bit1.3 enableCW
98Central functionOperating1 Bit1.11 stateCRT
99CO_dummy01 Bit
100CO_dummy11 Bit
101CO_dummy21 Bit
102CO_dummy31 Bit
103CO_dummy41 Bit
104CO_dummy51 Bit
105CO_dummy61 Bit
Parameters (100)
ParameterTypeDefault
Startup timeoutlist1 s
Modelistnormally open
Prewarninglistnot active
Manual switching offlistactive
On delayunsignedInt 0…300000
Off delayunsignedInt 0…300000
Send state cyclic (0 = not active)unsignedInt 0…300000
Central functionlistnot active
Inverte Lock objectlistno invert
Send statelistat change
Release time for forced control ( 0 = not active)unsignedInt 0…6000
Behavior at bus power uplistno change
Delay time for status after bus power uplist1 s
Logic functionlistwith Switch object and one Logic object
Behavior at bus power uplistState before bus power down
Logic operationslistOR
Channel Alistswitching
Sceneslistnot active
Learn scenelistnot active
Behavior of scenelistOn
Eco mode, switch LED's off afterlistnot active
Send "Operation" cyclic (0 = not active)unsignedInt 0…300000
Extend time staircase lightlistrestart time
Release time for priority (0 = not active)unsignedInt 0…6000
Priority / Forced controllistnot active
Additional inverted statelistnot active
Invert inputslistno invert
Invert outputlistno invert
Set objects value after bus power uplistnot active
Value for switch objectlistno set
Set object of Logic 1listno set
Set object of Logic 2listno set
Threshold switchlistnot active
Operation hours counterlistnot active
Scene Alistnot active
Scene numberlist1
Scene Blistnot active
Scene numberlist2
Scene Clistnot active
Scene numberlist3
Scene Dlistnot active
Scene numberlist4
Scene Elistnot active
Scene numberlist5
Scene Flistnot active
Scene numberlist6
Scene Glistnot active
Scene numberlist7
Scene Hlistnot active
Scene numberlist8
Lower threshold <list0%
Lower threshold <unsignedInt 0…655000
Lower threshold <float -100…20010
Value settinglist1Byte percent value (0-100%)
Lower threshold <unsignedInt 0…2550
Lower threshold <float 0…100000100
Upper threshold >list90%
Upper threshold >unsignedInt 0…2550
Upper threshold >unsignedInt 0…655000
Upper threshold >float -100…20030
Upper threshold >float 0…10000060000
Behavior of Channel at lower deviationlistnot active
Behavior of Channel at exceedancelistnot active
Set valuelist50%
Set valueunsignedInt 1…25510
Set valueunsignedInt 1…65500100
Set valuefloat -100…20020
Set valuefloat 0…100000400
Initialise with an object for threshold switch after bus power uplistnot active
Type of operation hours counterlistoperation hours counter
Send status of operation hours every … (0 = not active)unsignedInt 0…100000
Send status of Service hours every … (0 = not active)unsignedInt 0…100000
Send service status at intervalsunsignedInt 0…600000
Send operation hours cycliclistnot active
Time factor for object "Staircase light with time"list1 s
Switch objectlistnot active
Repeat impuls signal oncelistnot active
Behavior at unlockinglistno change
Behavior at unlockinglistOff
Behavior after forced controllistno change
Behavior after forced controllistOff
Behavior after deactivation of prioritylistno change
Behavior after deactivation of prioritylistOff
Manual controllistactive
Time of staircase lightunsignedInt 1…300001
Impuls timelist500 ms
Prewarning timeunsignedInt 0…300000
Select data typelist4Byte value in s (DPT 13.100)
Channel Blistswitching
Channel Clistswitching
Channel Dlistswitching
Channel Elistswitching
Channel Flistswitching
Channel Glistswitching
Channel Hlistswitching
Bahavior at lockinglistno change
Prewarning durationunsignedInt 0…300001
Time to the next imulslist0,5 s
Logic functionlistnot active
Behavior at bus power downlistno change

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Switching, Staircase 8f 2.1 latest$001578B42026-11-25153 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH AKI-0816.03 Switch Actuator 8-fold, 8SU, 16/20A (AKI-0816.03), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from MDT technologies GmbH