| 0 | A: {{682:Channel A}} | Control value | 1 Bit | 1.1 switch | CWTU |
| 0 | A: {{682:Channel A}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 0 | A: {{682:Channel A}} | Temperature value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 1 | A: {{682:Channel A}} | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 2 | A: {{682:Channel A}} | Block | 1 Bit | 1.3 enable | CW |
| 3 | A: {{682:Channel A}} | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 3 | A: {{682:Channel A}} | State control value | 1 Bit | 1.1 switch | CRT |
| 4 | A: {{682:Channel A}} | Comfort extension | 1 Bit | 1.1 switch | CW |
| 4 | A: {{682:Channel A}} | Presecnce | 1 Bit | 1.1 switch | CW |
| 5 | A: {{682:Channel A}} | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 5 | A: {{682:Channel A}} | Forced position | 1 Bit | 1.3 enable | CW |
| 6 | A: {{682:Channel A}} | PWM cooling for 4 pipe system | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 7 | A: {{682:Channel A}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 7 | A: {{682:Channel A}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CWT |
| 8 | A: {{682:Channel A}} | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 8 | A: {{682:Channel A}} | Setpoint value offset | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 9 | A: {{682:Channel A}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 10 | A: {{682:Channel A}} | Mode selection | 1 Byte | 20.102 HVAC mode | CRWT |
| 10 | A: {{682:Channel A}} | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 11 | A: {{682:Channel A}} | DPT_HVAC Status | 1 Byte | | CRT |
| 11 | A: {{682:Channel A}} | DPT_HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 12 | A: {{682:Channel A}} | DPT_RHCC Status | 2 Bytes | 22.101 RHCC status | CRT |
| 13 | A: {{682:Channel A}} | Mode comfort | 1 Bit | 1.1 switch | CW |
| 14 | A: {{682:Channel A}} | Mode night | 1 Bit | 1.1 switch | CW |
| 15 | A: {{682:Channel A}} | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 15 | A: {{682:Channel A}} | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 15 | A: {{682:Channel A}} | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 16 | A: {{682:Channel A}} | Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 17 | A: {{682:Channel A}} | Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 18 | A: {{682:Channel A}} | Setpoint value offset(1=+/0=-) | 1 Bit | 1.7 step | CW |
| 19 | A: {{682:Channel A}} | Diagnosis text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 20 | B: {{683:Channel B}} | Control value | 1 Bit | 1.1 switch | CWTU |
| 20 | B: {{683:Channel B}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 20 | B: {{683:Channel B}} | Temperature value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 21 | B: {{683:Channel B}} | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 22 | B: {{683:Channel B}} | Block | 1 Bit | 1.3 enable | CW |
| 23 | B: {{683:Channel B}} | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 23 | B: {{683:Channel B}} | State control value | 1 Bit | 1.1 switch | CRT |
| 24 | B: {{683:Channel B}} | Switch presence | 1 Bit | 1.1 switch | CW |
| 24 | B: {{683:Channel B}} | Comfort extension | 1 Bit | 1.1 switch | CW |
| 25 | B: {{683:Channel B}} | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 25 | B: {{683:Channel B}} | Forced position | 1 Bit | 1.3 enable | CW |
| 26 | B: {{683:Channel B}} | PWM output cooling for 4 Pipe | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 27 | B: {{683:Channel B}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 27 | B: {{683:Channel B}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CWT |
| 28 | B: {{683:Channel B}} | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 28 | B: {{683:Channel B}} | Setpoint value offset | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 29 | B: {{683:Channel B}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 30 | B: {{683:Channel B}} | Mode selection | 1 Byte | 20.102 HVAC mode | CRWT |
| 30 | B: {{683:Channel B}} | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 31 | B: {{683:Channel B}} | DPT_HVAC Status | 1 Byte | | CRT |
| 31 | B: {{683:Channel B}} | DPT_HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 32 | B: {{683:Channel B}} | DPT_RHCC Status | 2 Bytes | 22.101 RHCC status | CRT |
| 33 | B: {{683:Channel B}} | Mode comfort | 1 Bit | 1.1 switch | CW |
| 34 | B: {{683:Channel B}} | Mode night | 1 Bit | 1.1 switch | CW |
| 35 | B: {{683:Channel B}} | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 35 | B: {{683:Channel B}} | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 35 | B: {{683:Channel B}} | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 36 | B: {{683:Channel B}} | Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 37 | B: {{683:Channel B}} | Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 38 | B: {{683:Channel B}} | Setpoint value offset(1=+/0=-) | 1 Bit | 1.7 step | CW |
| 39 | B: {{683:Channel B}} | Diagnosis text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 40 | C: {{694:Channel C}} | Control value | 1 Bit | 1.1 switch | CWTU |
| 40 | C: {{694:Channel C}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 40 | C: {{694:Channel C}} | Temperature value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 41 | C: {{694:Channel C}} | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 42 | C: {{694:Channel C}} | Block | 1 Bit | 1.3 enable | CW |
| 43 | C: {{694:Channel C}} | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 43 | C: {{694:Channel C}} | State control value | 1 Bit | 1.1 switch | CRT |
| 44 | C: {{694:Channel C}} | Switch presence | 1 Bit | 1.1 switch | CW |
| 44 | C: {{694:Channel C}} | Comfort extension | 1 Bit | 1.1 switch | CW |
| 45 | C: {{694:Channel C}} | Dew point alarm | 1 Bit | 1.4 ramp | CW |
| 45 | C: {{694:Channel C}} | Forced position | 1 Bit | 1.3 enable | CW |
| 45 | C: {{694:Channel C}} | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 46 | C: {{694:Channel C}} | PWM output cooling for 4 Pipe | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 47 | C: {{694:Channel C}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 47 | C: {{694:Channel C}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CWT |
| 48 | C: {{694:Channel C}} | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 48 | C: {{694:Channel C}} | Setpoint value offset | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 49 | C: {{694:Channel C}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 50 | C: {{694:Channel C}} | Mode selection | 1 Byte | 20.102 HVAC mode | CRWT |
| 50 | C: {{694:Channel C}} | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 51 | C: {{694:Channel C}} | DPT_HVAC Status | 1 Byte | | CRT |
| 51 | C: {{694:Channel C}} | DPT_HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 52 | C: {{694:Channel C}} | DPT_RHCC Status | 2 Bytes | 22.101 RHCC status | CRT |
| 53 | C: {{694:Channel C}} | Mode comfort | 1 Bit | 1.1 switch | CW |
| 54 | C: {{694:Channel C}} | Mode night | 1 Bit | 1.1 switch | CW |
| 55 | C: {{694:Channel C}} | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 55 | C: {{694:Channel C}} | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 55 | C: {{694:Channel C}} | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 56 | C: {{694:Channel C}} | Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 57 | C: {{694:Channel C}} | Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 58 | C: {{694:Channel C}} | Setpoint value offset(1=+/0=-) | 1 Bit | 1.7 step | CW |
| 59 | C: {{694:Channel C}} | Diagnosis text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 60 | D: {{695:Channel D}} | Control value | 1 Bit | 1.1 switch | CWTU |
| 60 | D: {{695:Channel D}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 60 | D: {{695:Channel D}} | Temperature value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 61 | D: {{695:Channel D}} | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 62 | D: {{695:Channel D}} | Block | 1 Bit | 1.3 enable | CW |
| 63 | D: {{695:Channel D}} | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 63 | D: {{695:Channel D}} | State control value | 1 Bit | 1.1 switch | CRT |
| 64 | D: {{695:Channel D}} | Switch presence | 1 Bit | 1.1 switch | CW |
| 64 | D: {{695:Channel D}} | Comfort extension | 1 Bit | 1.1 switch | CW |
| 65 | D: {{695:Channel D}} | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 65 | D: {{695:Channel D}} | Forced position | 1 Bit | 1.3 enable | CW |
| 66 | D: {{695:Channel D}} | PWM output cooling for 4 Pipe | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 67 | D: {{695:Channel D}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 67 | D: {{695:Channel D}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CWT |
| 68 | D: {{695:Channel D}} | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 68 | D: {{695:Channel D}} | Setpoint value offset | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 69 | D: {{695:Channel D}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 70 | D: {{695:Channel D}} | Mode selection | 1 Byte | 20.102 HVAC mode | CRWT |
| 70 | D: {{695:Channel D}} | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 71 | D: {{695:Channel D}} | DPT_HVAC Status | 1 Byte | | CRT |
| 71 | D: {{695:Channel D}} | DPT_HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 72 | D: {{695:Channel D}} | DPT_RHCC Status | 2 Bytes | 22.101 RHCC status | CRT |
| 73 | D: {{695:Channel D}} | Mode comfort | 1 Bit | 1.1 switch | CW |
| 74 | D: {{695:Channel D}} | Mode night | 1 Bit | 1.1 switch | CW |
| 75 | D: {{695:Channel D}} | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 75 | D: {{695:Channel D}} | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 75 | D: {{695:Channel D}} | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 76 | D: {{695:Channel D}} | Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 77 | D: {{695:Channel D}} | Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 78 | D: {{695:Channel D}} | Setpoint value offset(1=+/0=-) | 1 Bit | 1.7 step | CW |
| 79 | D: {{695:Channel D}} | Diagnosis text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 80 | E: {{987:Channel E}} | Control value | 1 Bit | 1.1 switch | CWTU |
| 80 | E: {{987:Channel E}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 80 | E: {{987:Channel E}} | Temperature value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 81 | E: {{987:Channel E}} | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 82 | E: {{987:Channel E}} | Block | 1 Bit | 1.3 enable | CW |
| 83 | E: {{987:Channel E}} | State control value | 1 Bit | 1.1 switch | CRT |
| 83 | E: {{987:Channel E}} | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | E: {{987:Channel E}} | Switch presence | 1 Bit | 1.1 switch | CW |
| 84 | E: {{987:Channel E}} | Comfort extension | 1 Bit | 1.1 switch | CW |
| 85 | E: {{987:Channel E}} | Forced position | 1 Bit | 1.3 enable | CW |
| 85 | E: {{987:Channel E}} | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 86 | E: {{987:Channel E}} | PWM output cooling for 4 Pipe | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 87 | E: {{987:Channel E}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 87 | E: {{987:Channel E}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CWT |
| 88 | E: {{987:Channel E}} | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 88 | E: {{987:Channel E}} | Setpoint value offset | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 89 | E: {{987:Channel E}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 90 | E: {{987:Channel E}} | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 90 | E: {{987:Channel E}} | Mode selection | 1 Byte | 20.102 HVAC mode | CRWT |
| 91 | E: {{987:Channel E}} | DPT_HVAC Status | 1 Byte | | CRT |
| 91 | E: {{987:Channel E}} | DPT_HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 92 | E: {{987:Channel E}} | DPT_RHCC Status | 2 Bytes | 22.101 RHCC status | CRT |
| 93 | E: {{987:Channel E}} | Mode comfort | 1 Bit | 1.1 switch | CW |
| 94 | E: {{987:Channel E}} | Mode night | 1 Bit | 1.1 switch | CW |
| 95 | E: {{987:Channel E}} | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 95 | E: {{987:Channel E}} | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 95 | E: {{987:Channel E}} | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 96 | E: {{987:Channel E}} | Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 97 | E: {{987:Channel E}} | Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 98 | E: {{987:Channel E}} | Setpoint value offset(1=+/0=-) | 1 Bit | 1.7 step | CW |
| 99 | E: {{987:Channel E}} | Diagnosis text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 100 | F: {{988:Channel F}} | Control value | 1 Bit | 1.1 switch | CWTU |
| 100 | F: {{988:Channel F}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 100 | F: {{988:Channel F}} | Temperature value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 101 | F: {{988:Channel F}} | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 102 | F: {{988:Channel F}} | Block | 1 Bit | 1.3 enable | CW |
| 103 | F: {{988:Channel F}} | State control value | 1 Bit | 1.1 switch | CRT |
| 103 | F: {{988:Channel F}} | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 104 | F: {{988:Channel F}} | Switch presence | 1 Bit | 1.1 switch | CW |
| 104 | F: {{988:Channel F}} | Comfort extension | 1 Bit | 1.1 switch | CW |
| 105 | F: {{988:Channel F}} | Forced position | 1 Bit | 1.3 enable | CW |
| 105 | F: {{988:Channel F}} | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 106 | F: {{988:Channel F}} | PWM output cooling for 4 Pipe | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 107 | F: {{988:Channel F}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 107 | F: {{988:Channel F}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CWT |
| 108 | F: {{988:Channel F}} | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 108 | F: {{988:Channel F}} | Setpoint value offset | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 109 | F: {{988:Channel F}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 110 | F: {{988:Channel F}} | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 110 | F: {{988:Channel F}} | Mode selection | 1 Byte | 20.102 HVAC mode | CRWT |
| 111 | F: {{988:Channel F}} | DPT_HVAC Status | 1 Byte | | CRT |
| 111 | F: {{988:Channel F}} | DPT_HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 112 | F: {{988:Channel F}} | DPT_RHCC Status | 2 Bytes | 22.101 RHCC status | CRT |
| 113 | F: {{988:Channel F}} | Mode comfort | 1 Bit | 1.1 switch | CW |
| 114 | F: {{988:Channel F}} | Mode night | 1 Bit | 1.1 switch | CW |
| 115 | F: {{988:Channel F}} | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 115 | F: {{988:Channel F}} | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 115 | F: {{988:Channel F}} | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 116 | F: {{988:Channel F}} | Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 117 | F: {{988:Channel F}} | Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 118 | F: {{988:Channel F}} | Setpoint value offset(1=+/0=-) | 1 Bit | 1.7 step | CW |
| 119 | F: {{988:Channel F}} | Diagnosis text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 120 | G: {{991:Channel G}} | Control value | 1 Bit | 1.1 switch | CWTU |
| 120 | G: {{991:Channel G}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 120 | G: {{991:Channel G}} | Temperature value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 121 | G: {{991:Channel G}} | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 122 | G: {{991:Channel G}} | Block | 1 Bit | 1.3 enable | CW |
| 123 | G: {{991:Channel G}} | State control value | 1 Bit | 1.1 switch | CRT |
| 123 | G: {{991:Channel G}} | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 124 | G: {{991:Channel G}} | Switch presence | 1 Bit | 1.1 switch | CW |
| 124 | G: {{991:Channel G}} | Comfort extension | 1 Bit | 1.1 switch | CW |
| 125 | G: {{991:Channel G}} | Forced position | 1 Bit | 1.3 enable | CW |
| 125 | G: {{991:Channel G}} | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 126 | G: {{991:Channel G}} | PWM output cooling for 4 Pipe | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 127 | G: {{991:Channel G}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 127 | G: {{991:Channel G}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CWT |
| 128 | G: {{991:Channel G}} | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 128 | G: {{991:Channel G}} | Setpoint value offset | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 129 | G: {{991:Channel G}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 130 | G: {{991:Channel G}} | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 130 | G: {{991:Channel G}} | Mode selection | 1 Byte | 20.102 HVAC mode | CRWT |
| 131 | G: {{991:Channel G}} | DPT_HVAC Status | 1 Byte | | CRT |
| 131 | G: {{991:Channel G}} | DPT_HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 132 | G: {{991:Channel G}} | DPT_RHCC Status | 2 Bytes | 22.101 RHCC status | CRT |
| 133 | G: {{991:Channel G}} | Mode comfort | 1 Bit | 1.1 switch | CW |
| 134 | G: {{991:Channel G}} | Mode night | 1 Bit | 1.1 switch | CW |
| 135 | G: {{991:Channel G}} | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 135 | G: {{991:Channel G}} | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 135 | G: {{991:Channel G}} | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 136 | G: {{991:Channel G}} | Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 137 | G: {{991:Channel G}} | Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 138 | G: {{991:Channel G}} | Setpoint value offset(1=+/0=-) | 1 Bit | 1.7 step | CW |
| 139 | G: {{991:Channel G}} | Diagnosis text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 140 | H: {{992:Channel H}} | Control value | 1 Bit | 1.1 switch | CWTU |
| 140 | H: {{992:Channel H}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 140 | H: {{992:Channel H}} | Temperature value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 141 | H: {{992:Channel H}} | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 142 | H: {{992:Channel H}} | Block | 1 Bit | 1.3 enable | CW |
| 143 | H: {{992:Channel H}} | State control value | 1 Bit | 1.1 switch | CRT |
| 143 | H: {{992:Channel H}} | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 144 | H: {{992:Channel H}} | Switch presence | 1 Bit | 1.1 switch | CW |
| 144 | H: {{992:Channel H}} | Comfort extension | 1 Bit | 1.1 switch | CW |
| 145 | H: {{992:Channel H}} | Forced position | 1 Bit | 1.3 enable | CW |
| 145 | H: {{992:Channel H}} | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 146 | H: {{992:Channel H}} | PWM output cooling for 4 Pipe | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 147 | H: {{992:Channel H}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 147 | H: {{992:Channel H}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CWT |
| 148 | H: {{992:Channel H}} | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 148 | H: {{992:Channel H}} | Setpoint value offset | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 149 | H: {{992:Channel H}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 150 | H: {{992:Channel H}} | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 150 | H: {{992:Channel H}} | Mode selection | 1 Byte | 20.102 HVAC mode | CRWT |
| 151 | H: {{992:Channel H}} | DPT_HVAC Status | 1 Byte | | CRT |
| 151 | H: {{992:Channel H}} | DPT_HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 152 | H: {{992:Channel H}} | DPT_RHCC Status | 2 Bytes | 22.101 RHCC status | CRT |
| 153 | H: {{992:Channel H}} | Mode comfort | 1 Bit | 1.1 switch | CW |
| 154 | H: {{992:Channel H}} | Mode night | 1 Bit | 1.1 switch | CW |
| 155 | H: {{992:Channel H}} | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 155 | H: {{992:Channel H}} | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 155 | H: {{992:Channel H}} | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 156 | H: {{992:Channel H}} | Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 157 | H: {{992:Channel H}} | Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 158 | H: {{992:Channel H}} | Setpoint value offset(1=+/0=-) | 1 Bit | 1.7 step | CW |
| 159 | H: {{992:Channel H}} | Diagnosis text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 160 | Summer / Winter | Switchover | 1 Bit | 1.1 switch | CWTU |
| 161 | Heating / Cooling | Switchover | 1 Bit | 1.100 heating/cooling | CWTU |
| 161 | Heating / Cooling | Status | 1 Bit | 1.100 heating/cooling | CRT |
| 162 | Heating/Cooling requirement | 0 if all valves closed, else 1 | 1 Bit | 1.2 boolean | CRT |
| 162 | Heating/Cooling requirement | 0 if control values = 0%, else 1 | 1 Bit | 1.2 boolean | CRT |
| 162 | Heating requirement | 0 if all valves closed, else 1 | 1 Bit | 1.2 boolean | CRT |
| 162 | Heating requirement | 0 if control values = 0% else 1 | 1 Bit | 1.2 boolean | CRT |
| 162 | Heating requirement | 0 if control values = 0%, else 1 | 1 Bit | 1.2 boolean | CRT |
| 162 | Cooling requirement | 0 if all valves closed, else 1 | 1 Bit | 1.2 boolean | CRT |
| 162 | Cooling requirement | 0 if control values = 0%, else 1 | 1 Bit | 1.2 boolean | CRT |
| 163 | Cooling requirement | 0 if all valves closed, else 1 | 1 Bit | 1.2 boolean | CRT |
| 163 | Cooling requirement | 0 if control values = 0%, else 1 | 1 Bit | 1.2 boolean | CRT |
| 164 | Fault | At power failure/short circuit | 1 Bit | 1.5 alarm | CRT |
| 164 | Fault | At short circuit | 1 Bit | 1.5 alarm | CRT |
| 165 | Max. control value | Output | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 166 | Max. control value | Input | 1 Byte | 5.1 percentage (0..100%) | CW |
| 167 | Scene | Activate | 1 Byte | 17.1 scene number | CW |
| 168 | Central function | Operating | 1 Bit | 1.11 state | CRT |
| 169 | Dummy | | 1 Bit | | |