AKH-0800.02 Heating Actuator 8-fold, 4SU MDRC, 24/230 VAC AKH-0800.02

MDT technologies GmbH · Order number AKH-0800.02 · Actuators › Heating actuators

Control valves, Control, 24/230VAC

Download .knxprod Heating actuator 8-fold 2.4 · 162 KB

Product

ManufacturerMDT technologies GmbH
Product nameAKH-0800.02 Heating Actuator 8-fold, 4SU MDRC, 24/230 VAC
Order numberAKH-0800.02
Product textAKH-0800.02 Heating actuator 8-fold, 4SU,24/230VAC
HardwareHeizungsaktor 8-fach
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)71.3
RegistrationCertified · 2016-02-24
Languagesde-DE, en-US
Catalog entryM-0083_H-60-1_HP-003A-24-6CD7_CI-AKH.2D0800.2E02-1
Fingerprint6CD7
SHA-25650aafeedc25db53ad997bb31141e8476d7cd32062781babacfdb792f1d9a5693
First seen2026-11-25
Markets69 markets

Application program: Heating actuator 8-fold 2.4

Application number$003A
Version2.4
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters788
Group objects268
Group objects (268)
NoNameFunctionSizeDPTFlags
0A: {{682:Channel A}}Control value1 Bit1.1 switchCWTU
0A: {{682:Channel A}}Control value1 Byte5.1 percentage (0..100%)CWTU
0A: {{682:Channel A}}Temperature value2 Bytes9.1 temperature (°C)CWTU
1A: {{682:Channel A}}Flow temperature2 Bytes9.1 temperature (°C)CW
2A: {{682:Channel A}}Block1 Bit1.3 enableCW
3A: {{682:Channel A}}State control value1 Byte5.1 percentage (0..100%)CRT
3A: {{682:Channel A}}State control value1 Bit1.1 switchCRT
4A: {{682:Channel A}}Comfort extension1 Bit1.1 switchCW
4A: {{682:Channel A}}Presecnce1 Bit1.1 switchCW
5A: {{682:Channel A}}Dew point alarm1 Bit1.5 alarmCW
5A: {{682:Channel A}}Forced position1 Bit1.3 enableCW
6A: {{682:Channel A}}PWM cooling for 4 pipe system1 Byte5.1 percentage (0..100%)CRT
7A: {{682:Channel A}}Setpoint comfort2 Bytes9.1 temperature (°C)CW
7A: {{682:Channel A}}Setpoint comfort2 Bytes9.1 temperature (°C)CWT
8A: {{682:Channel A}}Setpoint value offset2 Bytes9.2 temperature difference (K)CW
8A: {{682:Channel A}}Setpoint value offset1 Byte6.10 counter pulses (-128..127)CW
9A: {{682:Channel A}}Current setpoint2 Bytes9.1 temperature (°C)CRT
10A: {{682:Channel A}}Mode selection1 Byte20.102 HVAC modeCRWT
10A: {{682:Channel A}}Mode selection1 Byte20.102 HVAC modeCW
11A: {{682:Channel A}}DPT_HVAC Status1 ByteCRT
11A: {{682:Channel A}}DPT_HVAC Mode1 Byte20.102 HVAC modeCRT
12A: {{682:Channel A}}DPT_RHCC Status 2 Bytes22.101 RHCC statusCRT
13A: {{682:Channel A}}Mode comfort1 Bit1.1 switchCW
14A: {{682:Channel A}}Mode night1 Bit1.1 switchCW
15A: {{682:Channel A}}Mode heat protection1 Bit1.1 switchCW
15A: {{682:Channel A}}Mode frost/heat protection1 Bit1.1 switchCW
15A: {{682:Channel A}}Mode frost protection1 Bit1.1 switchCW
16A: {{682:Channel A}}Frost alarm1 Bit1.5 alarmCRT
17A: {{682:Channel A}}Heat alarm1 Bit1.5 alarmCRT
18A: {{682:Channel A}}Setpoint value offset(1=+/0=-)1 Bit1.7 stepCW
19A: {{682:Channel A}}Diagnosis text14 Bytes16.0 Character String (ASCII)CRT
20B: {{683:Channel B}}Control value1 Bit1.1 switchCWTU
20B: {{683:Channel B}}Control value1 Byte5.1 percentage (0..100%)CWTU
20B: {{683:Channel B}}Temperature value2 Bytes9.1 temperature (°C)CWTU
21B: {{683:Channel B}}Flow temperature2 Bytes9.1 temperature (°C)CW
22B: {{683:Channel B}}Block1 Bit1.3 enableCW
23B: {{683:Channel B}}State control value1 Byte5.1 percentage (0..100%)CRT
23B: {{683:Channel B}}State control value1 Bit1.1 switchCRT
24B: {{683:Channel B}}Switch presence1 Bit1.1 switchCW
24B: {{683:Channel B}}Comfort extension1 Bit1.1 switchCW
25B: {{683:Channel B}}Dew point alarm1 Bit1.5 alarmCW
25B: {{683:Channel B}}Forced position1 Bit1.3 enableCW
26B: {{683:Channel B}}PWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
27B: {{683:Channel B}}Setpoint comfort2 Bytes9.1 temperature (°C)CW
27B: {{683:Channel B}}Setpoint comfort2 Bytes9.1 temperature (°C)CWT
28B: {{683:Channel B}}Setpoint value offset2 Bytes9.2 temperature difference (K)CW
28B: {{683:Channel B}}Setpoint value offset1 Byte6.10 counter pulses (-128..127)CW
29B: {{683:Channel B}}Current setpoint2 Bytes9.1 temperature (°C)CRT
30B: {{683:Channel B}}Mode selection1 Byte20.102 HVAC modeCRWT
30B: {{683:Channel B}}Mode selection1 Byte20.102 HVAC modeCW
31B: {{683:Channel B}}DPT_HVAC Status1 ByteCRT
31B: {{683:Channel B}}DPT_HVAC Mode1 Byte20.102 HVAC modeCRT
32B: {{683:Channel B}}DPT_RHCC Status 2 Bytes22.101 RHCC statusCRT
33B: {{683:Channel B}}Mode comfort1 Bit1.1 switchCW
34B: {{683:Channel B}}Mode night1 Bit1.1 switchCW
35B: {{683:Channel B}}Mode heat protection1 Bit1.1 switchCW
35B: {{683:Channel B}}Mode frost/heat protection1 Bit1.1 switchCW
35B: {{683:Channel B}}Mode frost protection1 Bit1.1 switchCW
36B: {{683:Channel B}}Frost alarm1 Bit1.5 alarmCRT
37B: {{683:Channel B}}Heat alarm1 Bit1.5 alarmCRT
38B: {{683:Channel B}}Setpoint value offset(1=+/0=-)1 Bit1.7 stepCW
39B: {{683:Channel B}}Diagnosis text14 Bytes16.0 Character String (ASCII)CRT
40C: {{694:Channel C}}Control value1 Bit1.1 switchCWTU
40C: {{694:Channel C}}Control value1 Byte5.1 percentage (0..100%)CWTU
40C: {{694:Channel C}}Temperature value2 Bytes9.1 temperature (°C)CWTU
41C: {{694:Channel C}}Flow temperature2 Bytes9.1 temperature (°C)CW
42C: {{694:Channel C}}Block1 Bit1.3 enableCW
43C: {{694:Channel C}}State control value1 Byte5.1 percentage (0..100%)CRT
43C: {{694:Channel C}}State control value1 Bit1.1 switchCRT
44C: {{694:Channel C}}Switch presence1 Bit1.1 switchCW
44C: {{694:Channel C}}Comfort extension1 Bit1.1 switchCW
45C: {{694:Channel C}}Dew point alarm1 Bit1.4 rampCW
45C: {{694:Channel C}}Forced position1 Bit1.3 enableCW
45C: {{694:Channel C}}Dew point alarm1 Bit1.5 alarmCW
46C: {{694:Channel C}}PWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
47C: {{694:Channel C}}Setpoint comfort2 Bytes9.1 temperature (°C)CW
47C: {{694:Channel C}}Setpoint comfort2 Bytes9.1 temperature (°C)CWT
48C: {{694:Channel C}}Setpoint value offset2 Bytes9.2 temperature difference (K)CW
48C: {{694:Channel C}}Setpoint value offset1 Byte6.10 counter pulses (-128..127)CW
49C: {{694:Channel C}}Current setpoint2 Bytes9.1 temperature (°C)CRT
50C: {{694:Channel C}}Mode selection1 Byte20.102 HVAC modeCRWT
50C: {{694:Channel C}}Mode selection1 Byte20.102 HVAC modeCW
51C: {{694:Channel C}}DPT_HVAC Status1 ByteCRT
51C: {{694:Channel C}}DPT_HVAC Mode1 Byte20.102 HVAC modeCRT
52C: {{694:Channel C}}DPT_RHCC Status 2 Bytes22.101 RHCC statusCRT
53C: {{694:Channel C}}Mode comfort1 Bit1.1 switchCW
54C: {{694:Channel C}}Mode night1 Bit1.1 switchCW
55C: {{694:Channel C}}Mode heat protection1 Bit1.1 switchCW
55C: {{694:Channel C}}Mode frost/heat protection1 Bit1.1 switchCW
55C: {{694:Channel C}}Mode frost protection1 Bit1.1 switchCW
56C: {{694:Channel C}}Frost alarm1 Bit1.5 alarmCRT
57C: {{694:Channel C}}Heat alarm1 Bit1.5 alarmCRT
58C: {{694:Channel C}}Setpoint value offset(1=+/0=-)1 Bit1.7 stepCW
59C: {{694:Channel C}}Diagnosis text14 Bytes16.0 Character String (ASCII)CRT
60D: {{695:Channel D}}Control value1 Bit1.1 switchCWTU
60D: {{695:Channel D}}Control value1 Byte5.1 percentage (0..100%)CWTU
60D: {{695:Channel D}}Temperature value2 Bytes9.1 temperature (°C)CWTU
61D: {{695:Channel D}}Flow temperature2 Bytes9.1 temperature (°C)CW
62D: {{695:Channel D}}Block1 Bit1.3 enableCW
63D: {{695:Channel D}}State control value1 Byte5.1 percentage (0..100%)CRT
63D: {{695:Channel D}}State control value1 Bit1.1 switchCRT
64D: {{695:Channel D}}Switch presence1 Bit1.1 switchCW
64D: {{695:Channel D}}Comfort extension1 Bit1.1 switchCW
65D: {{695:Channel D}}Dew point alarm1 Bit1.5 alarmCW
65D: {{695:Channel D}}Forced position1 Bit1.3 enableCW
66D: {{695:Channel D}}PWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
67D: {{695:Channel D}}Setpoint comfort2 Bytes9.1 temperature (°C)CW
67D: {{695:Channel D}}Setpoint comfort2 Bytes9.1 temperature (°C)CWT
68D: {{695:Channel D}}Setpoint value offset2 Bytes9.2 temperature difference (K)CW
68D: {{695:Channel D}}Setpoint value offset1 Byte6.10 counter pulses (-128..127)CW
69D: {{695:Channel D}}Current setpoint2 Bytes9.1 temperature (°C)CRT
70D: {{695:Channel D}}Mode selection1 Byte20.102 HVAC modeCRWT
70D: {{695:Channel D}}Mode selection1 Byte20.102 HVAC modeCW
71D: {{695:Channel D}}DPT_HVAC Status1 ByteCRT
71D: {{695:Channel D}}DPT_HVAC Mode1 Byte20.102 HVAC modeCRT
72D: {{695:Channel D}}DPT_RHCC Status 2 Bytes22.101 RHCC statusCRT
73D: {{695:Channel D}}Mode comfort1 Bit1.1 switchCW
74D: {{695:Channel D}}Mode night1 Bit1.1 switchCW
75D: {{695:Channel D}}Mode heat protection1 Bit1.1 switchCW
75D: {{695:Channel D}}Mode frost/heat protection1 Bit1.1 switchCW
75D: {{695:Channel D}}Mode frost protection1 Bit1.1 switchCW
76D: {{695:Channel D}}Frost alarm1 Bit1.5 alarmCRT
77D: {{695:Channel D}}Heat alarm1 Bit1.5 alarmCRT
78D: {{695:Channel D}}Setpoint value offset(1=+/0=-)1 Bit1.7 stepCW
79D: {{695:Channel D}}Diagnosis text14 Bytes16.0 Character String (ASCII)CRT
80E: {{987:Channel E}}Control value1 Bit1.1 switchCWTU
80E: {{987:Channel E}}Control value1 Byte5.1 percentage (0..100%)CWTU
80E: {{987:Channel E}}Temperature value2 Bytes9.1 temperature (°C)CWTU
81E: {{987:Channel E}}Flow temperature2 Bytes9.1 temperature (°C)CW
82E: {{987:Channel E}}Block1 Bit1.3 enableCW
83E: {{987:Channel E}}State control value1 Bit1.1 switchCRT
83E: {{987:Channel E}}State control value1 Byte5.1 percentage (0..100%)CRT
84E: {{987:Channel E}}Switch presence1 Bit1.1 switchCW
84E: {{987:Channel E}}Comfort extension1 Bit1.1 switchCW
85E: {{987:Channel E}}Forced position1 Bit1.3 enableCW
85E: {{987:Channel E}}Dew point alarm1 Bit1.5 alarmCW
86E: {{987:Channel E}}PWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
87E: {{987:Channel E}}Setpoint comfort2 Bytes9.1 temperature (°C)CW
87E: {{987:Channel E}}Setpoint comfort2 Bytes9.1 temperature (°C)CWT
88E: {{987:Channel E}}Setpoint value offset2 Bytes9.2 temperature difference (K)CW
88E: {{987:Channel E}}Setpoint value offset1 Byte6.10 counter pulses (-128..127)CW
89E: {{987:Channel E}}Current setpoint2 Bytes9.1 temperature (°C)CRT
90E: {{987:Channel E}}Mode selection1 Byte20.102 HVAC modeCW
90E: {{987:Channel E}}Mode selection1 Byte20.102 HVAC modeCRWT
91E: {{987:Channel E}}DPT_HVAC Status1 ByteCRT
91E: {{987:Channel E}}DPT_HVAC Mode1 Byte20.102 HVAC modeCRT
92E: {{987:Channel E}}DPT_RHCC Status 2 Bytes22.101 RHCC statusCRT
93E: {{987:Channel E}}Mode comfort1 Bit1.1 switchCW
94E: {{987:Channel E}}Mode night1 Bit1.1 switchCW
95E: {{987:Channel E}}Mode frost protection1 Bit1.1 switchCW
95E: {{987:Channel E}}Mode heat protection1 Bit1.1 switchCW
95E: {{987:Channel E}}Mode frost/heat protection1 Bit1.1 switchCW
96E: {{987:Channel E}}Frost alarm1 Bit1.5 alarmCRT
97E: {{987:Channel E}}Heat alarm1 Bit1.5 alarmCRT
98E: {{987:Channel E}}Setpoint value offset(1=+/0=-)1 Bit1.7 stepCW
99E: {{987:Channel E}}Diagnosis text14 Bytes16.0 Character String (ASCII)CRT
100F: {{988:Channel F}}Control value1 Bit1.1 switchCWTU
100F: {{988:Channel F}}Control value1 Byte5.1 percentage (0..100%)CWTU
100F: {{988:Channel F}}Temperature value2 Bytes9.1 temperature (°C)CWTU
101F: {{988:Channel F}}Flow temperature2 Bytes9.1 temperature (°C)CW
102F: {{988:Channel F}}Block1 Bit1.3 enableCW
103F: {{988:Channel F}}State control value1 Bit1.1 switchCRT
103F: {{988:Channel F}}State control value1 Byte5.1 percentage (0..100%)CRT
104F: {{988:Channel F}}Switch presence1 Bit1.1 switchCW
104F: {{988:Channel F}}Comfort extension1 Bit1.1 switchCW
105F: {{988:Channel F}}Forced position1 Bit1.3 enableCW
105F: {{988:Channel F}}Dew point alarm1 Bit1.5 alarmCW
106F: {{988:Channel F}}PWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
107F: {{988:Channel F}}Setpoint comfort2 Bytes9.1 temperature (°C)CW
107F: {{988:Channel F}}Setpoint comfort2 Bytes9.1 temperature (°C)CWT
108F: {{988:Channel F}}Setpoint value offset2 Bytes9.2 temperature difference (K)CW
108F: {{988:Channel F}}Setpoint value offset1 Byte6.10 counter pulses (-128..127)CW
109F: {{988:Channel F}}Current setpoint2 Bytes9.1 temperature (°C)CRT
110F: {{988:Channel F}}Mode selection1 Byte20.102 HVAC modeCW
110F: {{988:Channel F}}Mode selection1 Byte20.102 HVAC modeCRWT
111F: {{988:Channel F}}DPT_HVAC Status1 ByteCRT
111F: {{988:Channel F}}DPT_HVAC Mode1 Byte20.102 HVAC modeCRT
112F: {{988:Channel F}}DPT_RHCC Status 2 Bytes22.101 RHCC statusCRT
113F: {{988:Channel F}}Mode comfort1 Bit1.1 switchCW
114F: {{988:Channel F}}Mode night1 Bit1.1 switchCW
115F: {{988:Channel F}}Mode frost protection1 Bit1.1 switchCW
115F: {{988:Channel F}}Mode heat protection1 Bit1.1 switchCW
115F: {{988:Channel F}}Mode frost/heat protection1 Bit1.1 switchCW
116F: {{988:Channel F}}Frost alarm1 Bit1.5 alarmCRT
117F: {{988:Channel F}}Heat alarm1 Bit1.5 alarmCRT
118F: {{988:Channel F}}Setpoint value offset(1=+/0=-)1 Bit1.7 stepCW
119F: {{988:Channel F}}Diagnosis text14 Bytes16.0 Character String (ASCII)CRT
120G: {{991:Channel G}}Control value1 Bit1.1 switchCWTU
120G: {{991:Channel G}}Control value1 Byte5.1 percentage (0..100%)CWTU
120G: {{991:Channel G}}Temperature value2 Bytes9.1 temperature (°C)CWTU
121G: {{991:Channel G}}Flow temperature2 Bytes9.1 temperature (°C)CW
122G: {{991:Channel G}}Block1 Bit1.3 enableCW
123G: {{991:Channel G}}State control value1 Bit1.1 switchCRT
123G: {{991:Channel G}}State control value1 Byte5.1 percentage (0..100%)CRT
124G: {{991:Channel G}}Switch presence1 Bit1.1 switchCW
124G: {{991:Channel G}}Comfort extension1 Bit1.1 switchCW
125G: {{991:Channel G}}Forced position1 Bit1.3 enableCW
125G: {{991:Channel G}}Dew point alarm1 Bit1.5 alarmCW
126G: {{991:Channel G}}PWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
127G: {{991:Channel G}}Setpoint comfort2 Bytes9.1 temperature (°C)CW
127G: {{991:Channel G}}Setpoint comfort2 Bytes9.1 temperature (°C)CWT
128G: {{991:Channel G}}Setpoint value offset2 Bytes9.2 temperature difference (K)CW
128G: {{991:Channel G}}Setpoint value offset1 Byte6.10 counter pulses (-128..127)CW
129G: {{991:Channel G}}Current setpoint2 Bytes9.1 temperature (°C)CRT
130G: {{991:Channel G}}Mode selection1 Byte20.102 HVAC modeCW
130G: {{991:Channel G}}Mode selection1 Byte20.102 HVAC modeCRWT
131G: {{991:Channel G}}DPT_HVAC Status1 ByteCRT
131G: {{991:Channel G}}DPT_HVAC Mode1 Byte20.102 HVAC modeCRT
132G: {{991:Channel G}}DPT_RHCC Status 2 Bytes22.101 RHCC statusCRT
133G: {{991:Channel G}}Mode comfort1 Bit1.1 switchCW
134G: {{991:Channel G}}Mode night1 Bit1.1 switchCW
135G: {{991:Channel G}}Mode frost protection1 Bit1.1 switchCW
135G: {{991:Channel G}}Mode heat protection1 Bit1.1 switchCW
135G: {{991:Channel G}}Mode frost/heat protection1 Bit1.1 switchCW
136G: {{991:Channel G}}Frost alarm1 Bit1.5 alarmCRT
137G: {{991:Channel G}}Heat alarm1 Bit1.5 alarmCRT
138G: {{991:Channel G}}Setpoint value offset(1=+/0=-)1 Bit1.7 stepCW
139G: {{991:Channel G}}Diagnosis text14 Bytes16.0 Character String (ASCII)CRT
140H: {{992:Channel H}}Control value1 Bit1.1 switchCWTU
140H: {{992:Channel H}}Control value1 Byte5.1 percentage (0..100%)CWTU
140H: {{992:Channel H}}Temperature value2 Bytes9.1 temperature (°C)CWTU
141H: {{992:Channel H}}Flow temperature2 Bytes9.1 temperature (°C)CW
142H: {{992:Channel H}}Block1 Bit1.3 enableCW
143H: {{992:Channel H}}State control value1 Bit1.1 switchCRT
143H: {{992:Channel H}}State control value1 Byte5.1 percentage (0..100%)CRT
144H: {{992:Channel H}}Switch presence1 Bit1.1 switchCW
144H: {{992:Channel H}}Comfort extension1 Bit1.1 switchCW
145H: {{992:Channel H}}Forced position1 Bit1.3 enableCW
145H: {{992:Channel H}}Dew point alarm1 Bit1.5 alarmCW
146H: {{992:Channel H}}PWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
147H: {{992:Channel H}}Setpoint comfort2 Bytes9.1 temperature (°C)CW
147H: {{992:Channel H}}Setpoint comfort2 Bytes9.1 temperature (°C)CWT
148H: {{992:Channel H}}Setpoint value offset2 Bytes9.2 temperature difference (K)CW
148H: {{992:Channel H}}Setpoint value offset1 Byte6.10 counter pulses (-128..127)CW
149H: {{992:Channel H}}Current setpoint2 Bytes9.1 temperature (°C)CRT
150H: {{992:Channel H}}Mode selection1 Byte20.102 HVAC modeCW
150H: {{992:Channel H}}Mode selection1 Byte20.102 HVAC modeCRWT
151H: {{992:Channel H}}DPT_HVAC Status1 ByteCRT
151H: {{992:Channel H}}DPT_HVAC Mode1 Byte20.102 HVAC modeCRT
152H: {{992:Channel H}}DPT_RHCC Status 2 Bytes22.101 RHCC statusCRT
153H: {{992:Channel H}}Mode comfort1 Bit1.1 switchCW
154H: {{992:Channel H}}Mode night1 Bit1.1 switchCW
155H: {{992:Channel H}}Mode frost protection1 Bit1.1 switchCW
155H: {{992:Channel H}}Mode heat protection1 Bit1.1 switchCW
155H: {{992:Channel H}}Mode frost/heat protection1 Bit1.1 switchCW
156H: {{992:Channel H}}Frost alarm1 Bit1.5 alarmCRT
157H: {{992:Channel H}}Heat alarm1 Bit1.5 alarmCRT
158H: {{992:Channel H}}Setpoint value offset(1=+/0=-)1 Bit1.7 stepCW
159H: {{992:Channel H}}Diagnosis text14 Bytes16.0 Character String (ASCII)CRT
160Summer / WinterSwitchover1 Bit1.1 switchCWTU
161Heating / CoolingSwitchover1 Bit1.100 heating/coolingCWTU
161Heating / CoolingStatus1 Bit1.100 heating/coolingCRT
162Heating/Cooling requirement0 if all valves closed, else 11 Bit1.2 booleanCRT
162Heating/Cooling requirement0 if control values = 0%, else 11 Bit1.2 booleanCRT
162Heating requirement0 if all valves closed, else 11 Bit1.2 booleanCRT
162Heating requirement0 if control values = 0% else 11 Bit1.2 booleanCRT
162Heating requirement0 if control values = 0%, else 11 Bit1.2 booleanCRT
162Cooling requirement0 if all valves closed, else 11 Bit1.2 booleanCRT
162Cooling requirement0 if control values = 0%, else 11 Bit1.2 booleanCRT
163Cooling requirement0 if all valves closed, else 11 Bit1.2 booleanCRT
163Cooling requirement0 if control values = 0%, else 11 Bit1.2 booleanCRT
164FaultAt power failure/short circuit1 Bit1.5 alarmCRT
164FaultAt short circuit1 Bit1.5 alarmCRT
165Max. control valueOutput1 Byte5.1 percentage (0..100%)CRT
166Max. control valueInput1 Byte5.1 percentage (0..100%)CW
167SceneActivate1 Byte17.1 scene numberCW
168Central functionOperating1 Bit1.11 stateCRT
169Dummy1 Bit
Parameters (121)
ParameterTypeDefault
Additional sensor for flow temperaturelistinactive
Emergency modelistactive
Startup delaytimeunsignedInt 2…2402
Thermal drivinglist230V
Object for requirement Heating/Coolinglistnot active
Switching for heating/coolinglistnot active
Protection of forse fit (all 6 days for 5 min valve open/close)listnot active
Object max. control valuelistnot active
Regard channel in Heating / Cooling requirement and max. control valuelistYes
ModelistChanel not active
Basic comfort setpointlist21,0 °C
Send state control valuelistnot active
Standby reductionlist2,0 K
Night reductionlist3,0 K
Dead zone between Heating and Coolinglist2,0 K
Standby increaselist3,0 K
Night increaselist2,0 K
Max setpoint offsetlist3,0 K
Max setpoint offset vaild forlistComfort
Reset setpoint offset after change of modelistNo
Operating mode after bus power resetlistComfort
Heating / Cooling modelistHeating
Valve typelistnot energized closed
Proportional rangelist3 K
Reset timelist120 min
PWM cycle timelist10 min
Control value for emergency mode winterlist50%
Control value for emergency mode summerlist0%
Systemlist2 Pipe system
Frost alarm if value lesslist8 °C
Heat alarm if value greaterlist35 °C
Send setpoint changelistNo
PrioritylistFrost/Comfort/Night/Standby
Maximum limit of control value at heatinglist100%
Maximum limit of control value at coolinglist100%
Flow temperature maximum limit at heatinglist38 °C
Flow temperature minimum limit at coolinglist18 °C
Control value for forced position winterlist50%
Behavior after bus power resetlistNo request values
Heating control values set to 0% at summer modelistNo
Polarity for object "Summer/Winter"listSummer = 1 / Winter = 0
Control value for forced position summerlist0%
Minimum limit of control value at coolinglist0%
Minimum limit of control value at heatinglist0%
Block objectlistinactive
Heating systemlistWarm water heating (4K / 120 min)
Cooling systemlistWarm water heating (4K / 120 min)
Heating / Cooling systemlistWarm water heating (4K / 120 min)
Request control value/temperature value after bus power resetlistinactive
Setpoint value offset over 1Byte/2Byte objectlistnot active
Step widthlist0,5 K
Send status on object 10 "Mode selection" (HVAC Mode)listNo
Send status on object 30 "Mode selection" (HVAC Mode)listNo
Send status on object 50 "Mode selection" (HVAC Mode)listNo
Send status on object 70 "Mode selection" (HVAC Mode)listNo
Language for diagnosis textlistGerman
Setting heating systemlist2 pipe system (Heating or Cooling)
Minimum limit of flow temperaturelistinactive
Setpoint frost modelist7 °C
Referent channel for automatic switch Heating/Cooling (2 pipe system)listChannel A
Minimum temperature flowlist20 °C
Enabled for Comfortlistactive
Enabled for Standbylistinactive
Enabled for Nightlistinactive
Enabled for Frostlistinactive
Send diagnosis textlistnot active
Step widthlist1 K
Send cyclic setpoint comfortlist5 min
Send cyclic current setpointlistnot active
Cycle timelist5 min
Send cyclic Mode selectionlistnot active
Send cyclic HVAC-Statuslistnot active
Object "HVAC Status" aslistHVAC-Status
Controll value at lower deviation of minimum limitlist0% = 0% otherwise use minimum limit
Controll value Heating at lower deviation of minimum limitlist0% = 0% otherwise use minimum limit
Scene numberlist1
Scene Alistinactive
Modelistno change
Basis comfort setpointlistno change
Change for Channel Alistinactive
Change for Channel Blistinactive
Change for Channel Clistinactive
Change for Channel Dlistinactive
Mode Heating/Coolinglistno change
Mode Summer/Winterlistno change
Scene Blistinactive
Scene Clistinactive
Scene Dlistinactive
Scene Elistinactive
Scene Flistinactive
Scene Glistinactive
Scene Hlistinactive
Scene Ilistinactive
Scene Jlistinactive
Scene Klistinactive
Scene Llistinactive
Scene Mlistinactive
Scene Nlistinactive
Scene Olistinactive
Scene Plistinactive
Presence / Comfort extention at nightlistnot active
Comfrot extention timelist30 min
Enabled for Comfortlistinactive
Send "Operation" cycliclistnot active
Requirement according tolistvalve status
Setpoint value offset over 1Bit objectlistinactive
Forced position / dew point alarmlistnot active
Forced positionlistnot active
Emergency mode at failure of control value afterlist30 min
Emergency mode at failure of temperature value afterlist30 min
Send status on object 90 "Mode selection" (HVAC Mode)listNo
Send status on object 110 "Mode selection" (HVAC Mode)listNo
Send status on object 130 "Mode selection" (HVAC Mode)listNo
Send status on object 150 "Mode selection" (HVAC Mode)listNo
Change for Channel Elistinactive
Change for Channel Flistinactive
Change for Channel Glistinactive
Change for Channel Hlistinactive
Recover modes and setpoints after bus power resetlistinactive
Setting modelistHeating
Objects descriptiontext

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Heating actuator 8-fold 2.4 latest$003A6CD72026-11-25162 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH AKH-0800.02 Heating Actuator 8-fold, 4SU MDRC, 24/230 VAC (AKH-0800.02), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from MDT technologies GmbH

All MDT technologies GmbH products