AKH-0400.02 Heating Actuator 4-fold, 2SU MDRC, 24/230 VAC AKH-0400.02

MDT technologies GmbH · Order number AKH-0400.02 · Actuators › Heating actuators

Control valves, Control, 24/230VAC

Download .knxprod Heating actuator 4-fold 2.4 · 125 KB

Product

ManufacturerMDT technologies GmbH
Product nameAKH-0400.02 Heating Actuator 4-fold, 2SU MDRC, 24/230 VAC
Order numberAKH-0400.02
Product textAKH-0400.02 Heating actuator 4-fold, 2SU,24/230VAC
HardwareHeizungsaktor 4-fach
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)36.3
RegistrationCertified · 2016-02-24
Languagesde-DE, en-US
Catalog entryM-0083_H-61-1_HP-003B-24-C073_CI-AKH.2D0400.2E02-1
FingerprintC073
SHA-2560d828434d047f590c08ec66256086eb60799e63e1d6ca951be6fc23cdb779a94
First seen2026-11-25
Markets69 markets

Application program: Heating actuator 4-fold 2.4

Application number$003B
Version2.4
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters460
Group objects143
Group objects (143)
NoNameFunctionSizeDPTFlags
0A: {{203:Channel A}}Control value1 Bit1.1 switchCWTU
0A: {{203:Channel A}}Control value1 Byte5.1 percentage (0..100%)CWTU
0A: {{203:Channel A}}Temperature value2 Bytes9.1 temperature (°C)CWTU
1A: {{203:Channel A}}Flow temperature2 Bytes9.1 temperature (°C)CW
2A: {{203:Channel A}}Block1 Bit1.3 enableCW
3A: {{203:Channel A}}State control value1 Byte5.1 percentage (0..100%)CRT
3A: {{203:Channel A}}State control value1 Bit1.1 switchCRT
4A: {{203:Channel A}}Comfort extension1 Bit1.1 switchCW
4A: {{203:Channel A}}Presence1 Bit1.1 switchCW
5A: {{203:Channel A}}Dew point alarm1 Bit1.5 alarmCW
5A: {{203:Channel A}}Forced position1 Bit1.3 enableCW
6A: {{203:Channel A}}PWM cooling for 4 pipe system1 Byte5.1 percentage (0..100%)CRT
7A: {{203:Channel A}}Setpoint comfort2 Bytes9.1 temperature (°C)CW
7A: {{203:Channel A}}Setpoint comfort2 Bytes9.1 temperature (°C)CWT
8A: {{203:Channel A}}Setpoint value offset2 Bytes9.2 temperature difference (K)CW
8A: {{203:Channel A}}Setpoint value offset1 Byte6.10 counter pulses (-128..127)CW
9A: {{203:Channel A}}Current setpoint2 Bytes9.1 temperature (°C)CRT
10A: {{203:Channel A}}Mode selection1 Byte20.102 HVAC modeCRWT
10A: {{203:Channel A}}Mode selection1 Byte20.102 HVAC modeCW
11A: {{203:Channel A}}DPT_HVAC Status1 ByteCRT
11A: {{203:Channel A}}DPT_HVAC Mode1 Byte20.102 HVAC modeCRT
12A: {{203:Channel A}}DPT_RHCC Status 2 Bytes22.101 RHCC statusCRT
13A: {{203:Channel A}}Mode comfort1 Bit1.1 switchCW
14A: {{203:Channel A}}Mode night1 Bit1.1 switchCW
15A: {{203:Channel A}}Mode heat protection1 Bit1.1 switchCW
15A: {{203:Channel A}}Mode frost/heat protection1 Bit1.1 switchCW
15A: {{203:Channel A}}Mode frost protection1 Bit1.1 switchCW
16A: {{203:Channel A}}Frost alarm1 Bit1.5 alarmCRT
17A: {{203:Channel A}}Heat alarm1 Bit1.5 alarmCRT
18A: {{203:Channel A}}Setpoint value offset(1=+/0=-)1 Bit1.7 stepCW
19A: {{203:Channel A}}Diagnosis text14 Bytes16.0 Character String (ASCII)CRT
20B: {{204:Channel B}}Control value1 Bit1.1 switchCWTU
20B: {{204:Channel B}}Control value1 Byte5.1 percentage (0..100%)CWTU
20B: {{204:Channel B}}Temperature value2 Bytes9.1 temperature (°C)CWTU
21B: {{204:Channel B}}Flow temperature2 Bytes9.1 temperature (°C)CW
22B: {{204:Channel B}}Block1 Bit1.3 enableCW
23B: {{204:Channel B}}State control value1 Byte5.1 percentage (0..100%)CRT
23B: {{204:Channel B}}State control value1 Bit1.1 switchCRT
24B: {{204:Channel B}}Switch presence1 Bit1.1 switchCW
24B: {{204:Channel B}}Comfort extension1 Bit1.1 switchCW
25B: {{204:Channel B}}Dew point alarm1 Bit1.5 alarmCW
25B: {{204:Channel B}}Forced position1 Bit1.3 enableCW
26B: {{204:Channel B}}PWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
27B: {{204:Channel B}}Setpoint comfort2 Bytes9.1 temperature (°C)CW
27B: {{204:Channel B}}Setpoint comfort2 Bytes9.1 temperature (°C)CWT
28B: {{204:Channel B}}Setpoint value offset2 Bytes9.2 temperature difference (K)CW
28B: {{204:Channel B}}Setpoint value offset1 Byte6.10 counter pulses (-128..127)CW
29B: {{204:Channel B}}Current setpoint2 Bytes9.1 temperature (°C)CRT
30B: {{204:Channel B}}Mode selection1 Byte20.102 HVAC modeCRWT
30B: {{204:Channel B}}Mode selection1 Byte20.102 HVAC modeCW
31B: {{204:Channel B}}DPT_HVAC Status1 ByteCRT
31B: {{204:Channel B}}DPT_HVAC Mode1 Byte20.102 HVAC modeCRT
32B: {{204:Channel B}}DPT_RHCC Status 2 Bytes22.101 RHCC statusCRT
33B: {{204:Channel B}}Mode comfort1 Bit1.1 switchCW
34B: {{204:Channel B}}Mode night1 Bit1.1 switchCW
35B: {{204:Channel B}}Mode heat protection1 Bit1.1 switchCW
35B: {{204:Channel B}}Mode frost/heat protection1 Bit1.1 switchCW
35B: {{204:Channel B}}Mode frost protection1 Bit1.1 switchCW
36B: {{204:Channel B}}Frost alarm1 Bit1.5 alarmCRT
37B: {{204:Channel B}}Heat alarm1 Bit1.5 alarmCRT
38B: {{204:Channel B}}Setpoint value offset(1=+/0=-)1 Bit1.7 stepCW
39B: {{204:Channel B}}Diagnosis text14 Bytes16.0 Character String (ASCII)CRT
40C: {{206:Channel C}}Control value1 Bit1.1 switchCWTU
40C: {{206:Channel C}}Control value1 Byte5.1 percentage (0..100%)CWTU
40C: {{206:Channel C}}Temperature value2 Bytes9.1 temperature (°C)CWTU
41C: {{206:Channel C}}Flow temperature2 Bytes9.1 temperature (°C)CW
42C: {{206:Channel C}}Block1 Bit1.3 enableCW
43C: {{206:Channel C}}State control value1 Byte5.1 percentage (0..100%)CRT
43C: {{206:Channel C}}State control value1 Bit1.1 switchCRT
44C: {{206:Channel C}}Switch presence1 Bit1.1 switchCW
44C: {{206:Channel C}}Comfort extension1 Bit1.1 switchCW
45C: {{206:Channel C}}Dew point alarm1 Bit1.4 rampCW
45C: {{206:Channel C}}Forced position1 Bit1.3 enableCW
45C: {{206:Channel C}}Dew point alarm1 Bit1.5 alarmCW
46C: {{206:Channel C}}PWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
47C: {{206:Channel C}}Setpoint comfort2 Bytes9.1 temperature (°C)CW
47C: {{206:Channel C}}Setpoint comfort2 Bytes9.1 temperature (°C)CWT
48C: {{206:Channel C}}Setpoint value offset2 Bytes9.2 temperature difference (K)CW
48C: {{206:Channel C}}Setpoint value offset1 Byte6.10 counter pulses (-128..127)CW
49C: {{206:Channel C}}Current setpoint2 Bytes9.1 temperature (°C)CRT
50C: {{206:Channel C}}Mode selection1 Byte20.102 HVAC modeCRWT
50C: {{206:Channel C}}Mode selection1 Byte20.102 HVAC modeCW
51C: {{206:Channel C}}DPT_HVAC Status1 ByteCRT
51C: {{206:Channel C}}DPT_HVAC Mode1 Byte20.102 HVAC modeCRT
52C: {{206:Channel C}}DPT_RHCC Status 2 Bytes22.101 RHCC statusCRT
53C: {{206:Channel C}}Mode comfort1 Bit1.1 switchCW
54C: {{206:Channel C}}Mode night1 Bit1.1 switchCW
55C: {{206:Channel C}}Mode heat protection1 Bit1.1 switchCW
55C: {{206:Channel C}}Mode frost/heat protection1 Bit1.1 switchCW
55C: {{206:Channel C}}Mode frost protection1 Bit1.1 switchCW
56C: {{206:Channel C}}Frost alarm1 Bit1.5 alarmCRT
57C: {{206:Channel C}}Heat alarm1 Bit1.5 alarmCRT
58C: {{206:Channel C}}Setpoint value offset(1=+/0=-)1 Bit1.7 stepCW
59C: {{206:Channel C}}Diagnosis text14 Bytes16.0 Character String (ASCII)CRT
60D: {{207:Channel D}}Control value1 Bit1.1 switchCWTU
60D: {{207:Channel D}}Control value1 Byte5.1 percentage (0..100%)CWTU
60D: {{207:Channel D}}Temperature value2 Bytes9.1 temperature (°C)CWTU
61D: {{207:Channel D}}Flow temperature2 Bytes9.1 temperature (°C)CW
62D: {{207:Channel D}}Block1 Bit1.3 enableCW
63D: {{207:Channel D}}State control value1 Byte5.1 percentage (0..100%)CRT
63D: {{207:Channel D}}State control value1 Bit1.1 switchCRT
64D: {{207:Channel D}}Switch presence1 Bit1.1 switchCW
64D: {{207:Channel D}}Comfort extension1 Bit1.1 switchCW
65D: {{207:Channel D}}Dew point alarm1 Bit1.5 alarmCW
65D: {{207:Channel D}}Forced position1 Bit1.3 enableCW
66D: {{207:Channel D}}PWM output cooling for 4 Pipe1 Byte5.1 percentage (0..100%)CRT
67D: {{207:Channel D}}Setpoint comfort2 Bytes9.1 temperature (°C)CW
67D: {{207:Channel D}}Setpoint comfort2 Bytes9.1 temperature (°C)CWT
68D: {{207:Channel D}}Setpoint value offset2 Bytes9.2 temperature difference (K)CW
68D: {{207:Channel D}}Setpoint value offset1 Byte6.10 counter pulses (-128..127)CW
69D: {{207:Channel D}}Current setpoint2 Bytes9.1 temperature (°C)CRT
70D: {{207:Channel D}}Mode selection1 Byte20.102 HVAC modeCRWT
70D: {{207:Channel D}}Mode selection1 Byte20.102 HVAC modeCW
71D: {{207:Channel D}}DPT_HVAC Status1 ByteCRT
71D: {{207:Channel D}}DPT_HVAC Mode1 Byte20.102 HVAC modeCRT
72D: {{207:Channel D}}DPT_RHCC Status 2 Bytes22.101 RHCC statusCRT
73D: {{207:Channel D}}Mode comfort1 Bit1.1 switchCW
74D: {{207:Channel D}}Mode night1 Bit1.1 switchCW
75D: {{207:Channel D}}Mode heat protection1 Bit1.1 switchCW
75D: {{207:Channel D}}Mode frost/heat protection1 Bit1.1 switchCW
75D: {{207:Channel D}}Mode frost protection1 Bit1.1 switchCW
76D: {{207:Channel D}}Frost alarm1 Bit1.5 alarmCRT
77D: {{207:Channel D}}Heat alarm1 Bit1.5 alarmCRT
78D: {{207:Channel D}}Setpoint value offset(1=+/0=-)1 Bit1.7 stepCW
79D: {{207:Channel D}}Diagnosis text14 Bytes16.0 Character String (ASCII)CRT
80Summer / WinterSwitchover1 Bit1.1 switchCWTU
81Heating / CoolingSwitchover1 Bit1.100 heating/coolingCWTU
81Heating / CoolingStatus1 Bit1.100 heating/coolingCRT
82Heating/Cooling requirement0 if all valves closed, else 11 Bit1.2 booleanCRT
82Heating/Cooling requirement0 if control values = 0%, else 11 Bit1.2 booleanCRT
82Heating requirement0 if all valves closed, else 11 Bit1.2 booleanCRT
82Heating requirement0 if control values = 0%, else 11 Bit1.2 booleanCRT
82Cooling requirement0 if all valves closed, else 11 Bit1.2 booleanCRT
82Cooling requirement0 if control values = 0%, else 11 Bit1.2 booleanCRT
83Cooling requirement0 if all valves closed, else 11 Bit1.2 booleanCRT
83Cooling requirement0 if control values = 0%, else 11 Bit1.2 booleanCRT
84FaultAt power failure/short circuit1 Bit1.5 alarmCRT
84FaultAt short circuit1 Bit1.5 alarmCRT
85Max. control valueOutput1 Byte5.1 percentage (0..100%)CRT
86Max. control valueInput1 Byte5.1 percentage (0..100%)CW
87SceneActivate1 Byte17.1 scene numberCW
88Central functionOperating1 Bit1.11 stateCRT
89Dummy1 Bit
Parameters (110)
ParameterTypeDefault
Additional sensor for flow temperaturelistinactive
Emergency modelistactive
Startup delaytimeunsignedInt 2…2402
Thermal drivinglist230V
Object for requirement Heating/Coolinglistnot active
Switching for heating/coolinglistnot active
Protection of forse fit (all 6 days for 5 min valve open/close)listnot active
Object max. control valuelistnot active
Regard channel in Heating / Cooling requirement and max. control valuelistYes
ModelistChanel not active
Basic comfort setpointlist21,0 °C
Send state control valuelistnot active
Standby reductionlist2,0 K
Night reductionlist3,0 K
Dead zone between Heating and Coolinglist2,0 K
Standby increaselist3,0 K
Night increaselist2,0 K
Max setpoint offsetlist3,0 K
Max setpoint offset vaild forlistComfort
Reset setpoint offset after change of modelistNo
Operating mode after bus power resetlistComfort
Heating / Cooling modelistHeating
Valve typelistnot energized closed
Proportional rangelist3 K
Reset timelist120 min
PWM cycle timelist10 min
Control value for emergency mode winterlist50%
Control value for emergency mode summerlist0%
Systemlist2 Pipe system
Frost alarm if value lesslist8 °C
Heat alarm if value greaterlist35 °C
Send setpoint changelistNo
PrioritylistFrost/Comfort/Night/Standby
Maximum limit of control value at heatinglist100%
Maximum limit of control value at coolinglist100%
Flow temperature maximum limit at heatinglist38 °C
Flow temperature minimum limit at coolinglist18 °C
Control value for forced position winterlist50%
Behavior after bus power resetlistWinter mode
Heating control values set to 0% at summer modelistNo
Polarity for object "Summer/Winter"listSummer = 1 / Winter = 0
Control value for forced position summerlist0%
Minimum limit of control value at coolinglist0%
Minimum limit of control value at heatinglist0%
Block objectlistinactive
Heating systemlistWarm water heating (4K / 120 min)
Cooling systemlistWarm water heating (4K / 120 min)
Heating / Cooling systemlistWarm water heating (4K / 120 min)
Request control value/temperature value after bus power resetlistinactive
Setpoint value offset over 1Byte/2Byte objectlistnot active
Step widthlist0,5 K
Send status on object "Mode selection" (HVAC Mode)listNo
Language for diagnosis textlistGerman
Enable objects forlist2 pipe system (Heating or Cooling)
Minimum limit of flow temperaturelistinactive
Setpoint frost modelist7 °C
Referent channel for automatic switch Heating/Cooling (2 pipe system)listChannel A
Minimum temperature flowlist20 °C
Enabled for Comfortlistactive
Enabled for Standbylistinactive
Enabled for Nightlistinactive
Enabled for Frostlistinactive
Send diagnosis textlistnot active
Step widthlist1 K
Send cyclic setpoint comfortlist5 min
Send cyclic current setpointlistnot active
Cycle timelist5 min
Send cyclic Mode selectionlistnot active
Send cyclic HVAC-Statuslistnot active
Object "HVAC Status" aslistHVAC-Status
Controll value at lower deviation of minimum limitlist0% = 0% otherwise use minimum limit
Controll value Heating at lower deviation of minimum limitlist0% = 0% otherwise use minimum limit
Scene numberlist1
Scene Alistinactive
Modelistno change
Basis comfort setpointlistno change
Change for Channel Alistinactive
Change for Channel Blistinactive
Change for Channel Clistinactive
Change for Channel Dlistinactive
Mode Heating/Coolinglistno change
Mode Summer/Winterlistno change
Scene Blistinactive
Scene Clistinactive
Scene Dlistinactive
Scene Elistinactive
Scene Flistinactive
Scene Glistinactive
Scene Hlistinactive
Scene Ilistinactive
Scene Jlistinactive
Scene Klistinactive
Scene Llistinactive
Scene Mlistinactive
Scene Nlistinactive
Scene Olistinactive
Scene Plistinactive
Presence / Comfort extention at nightlistnot active
Comfrot extention timelist30 min
Enabled for Comfortlistinactive
Send "Operation" cycliclistnot active
Requirement according tolistvalve status
Setpoint value offset over 1Bit objectlistinactive
Forced position / dew point alarmlistnot active
Forced positionlistnot active
Emergency mode at failure of control value afterlist30 min
Emergency mode at failure of temperature value afterlist30 min
Recover modes and setpoints after bus power resetlistinactive
Setting modelistHeating
Objects descriptiontext

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Heating actuator 4-fold 2.4 latest$003BC0732026-11-25125 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH AKH-0400.02 Heating Actuator 4-fold, 2SU MDRC, 24/230 VAC (AKH-0400.02), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.