AKH-0400.02 Heating Actuator 4-fold, 2SU MDRC, 24/230 VAC AKH-0400.02
MDT technologies GmbH · Order number AKH-0400.02 · Actuators › Heating actuators
Control valves, Control, 24/230VAC
Download .knxprod Heating actuator 4-fold 2.4 · 125 KB
Product
| Manufacturer | MDT technologies GmbH |
|---|---|
| Product name | AKH-0400.02 Heating Actuator 4-fold, 2SU MDRC, 24/230 VAC |
| Order number | AKH-0400.02 |
| Product text | AKH-0400.02 Heating actuator 4-fold, 2SU,24/230VAC |
| Hardware | Heizungsaktor 4-fach |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | Yes |
| Width (mm) | 36.3 |
| Registration | Certified · 2016-02-24 |
| Languages | de-DE, en-US |
| Catalog entry | M-0083_H-61-1_HP-003B-24-C073_CI-AKH.2D0400.2E02-1 |
| Fingerprint | C073 |
| SHA-256 | 0d828434d047f590c08ec66256086eb60799e63e1d6ca951be6fc23cdb779a94 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Heating actuator 4-fold 2.4
| Application number | $003B |
|---|---|
| Version | 2.4 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 460 |
| Group objects | 143 |
Group objects (143)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | A: {{203:Channel A}} | Control value | 1 Bit | 1.1 switch | CWTU |
| 0 | A: {{203:Channel A}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 0 | A: {{203:Channel A}} | Temperature value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 1 | A: {{203:Channel A}} | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 2 | A: {{203:Channel A}} | Block | 1 Bit | 1.3 enable | CW |
| 3 | A: {{203:Channel A}} | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 3 | A: {{203:Channel A}} | State control value | 1 Bit | 1.1 switch | CRT |
| 4 | A: {{203:Channel A}} | Comfort extension | 1 Bit | 1.1 switch | CW |
| 4 | A: {{203:Channel A}} | Presence | 1 Bit | 1.1 switch | CW |
| 5 | A: {{203:Channel A}} | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 5 | A: {{203:Channel A}} | Forced position | 1 Bit | 1.3 enable | CW |
| 6 | A: {{203:Channel A}} | PWM cooling for 4 pipe system | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 7 | A: {{203:Channel A}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 7 | A: {{203:Channel A}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CWT |
| 8 | A: {{203:Channel A}} | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 8 | A: {{203:Channel A}} | Setpoint value offset | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 9 | A: {{203:Channel A}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 10 | A: {{203:Channel A}} | Mode selection | 1 Byte | 20.102 HVAC mode | CRWT |
| 10 | A: {{203:Channel A}} | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 11 | A: {{203:Channel A}} | DPT_HVAC Status | 1 Byte | CRT | |
| 11 | A: {{203:Channel A}} | DPT_HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 12 | A: {{203:Channel A}} | DPT_RHCC Status | 2 Bytes | 22.101 RHCC status | CRT |
| 13 | A: {{203:Channel A}} | Mode comfort | 1 Bit | 1.1 switch | CW |
| 14 | A: {{203:Channel A}} | Mode night | 1 Bit | 1.1 switch | CW |
| 15 | A: {{203:Channel A}} | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 15 | A: {{203:Channel A}} | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 15 | A: {{203:Channel A}} | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 16 | A: {{203:Channel A}} | Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 17 | A: {{203:Channel A}} | Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 18 | A: {{203:Channel A}} | Setpoint value offset(1=+/0=-) | 1 Bit | 1.7 step | CW |
| 19 | A: {{203:Channel A}} | Diagnosis text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 20 | B: {{204:Channel B}} | Control value | 1 Bit | 1.1 switch | CWTU |
| 20 | B: {{204:Channel B}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 20 | B: {{204:Channel B}} | Temperature value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 21 | B: {{204:Channel B}} | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 22 | B: {{204:Channel B}} | Block | 1 Bit | 1.3 enable | CW |
| 23 | B: {{204:Channel B}} | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 23 | B: {{204:Channel B}} | State control value | 1 Bit | 1.1 switch | CRT |
| 24 | B: {{204:Channel B}} | Switch presence | 1 Bit | 1.1 switch | CW |
| 24 | B: {{204:Channel B}} | Comfort extension | 1 Bit | 1.1 switch | CW |
| 25 | B: {{204:Channel B}} | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 25 | B: {{204:Channel B}} | Forced position | 1 Bit | 1.3 enable | CW |
| 26 | B: {{204:Channel B}} | PWM output cooling for 4 Pipe | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 27 | B: {{204:Channel B}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 27 | B: {{204:Channel B}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CWT |
| 28 | B: {{204:Channel B}} | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 28 | B: {{204:Channel B}} | Setpoint value offset | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 29 | B: {{204:Channel B}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 30 | B: {{204:Channel B}} | Mode selection | 1 Byte | 20.102 HVAC mode | CRWT |
| 30 | B: {{204:Channel B}} | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 31 | B: {{204:Channel B}} | DPT_HVAC Status | 1 Byte | CRT | |
| 31 | B: {{204:Channel B}} | DPT_HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 32 | B: {{204:Channel B}} | DPT_RHCC Status | 2 Bytes | 22.101 RHCC status | CRT |
| 33 | B: {{204:Channel B}} | Mode comfort | 1 Bit | 1.1 switch | CW |
| 34 | B: {{204:Channel B}} | Mode night | 1 Bit | 1.1 switch | CW |
| 35 | B: {{204:Channel B}} | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 35 | B: {{204:Channel B}} | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 35 | B: {{204:Channel B}} | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 36 | B: {{204:Channel B}} | Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 37 | B: {{204:Channel B}} | Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 38 | B: {{204:Channel B}} | Setpoint value offset(1=+/0=-) | 1 Bit | 1.7 step | CW |
| 39 | B: {{204:Channel B}} | Diagnosis text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 40 | C: {{206:Channel C}} | Control value | 1 Bit | 1.1 switch | CWTU |
| 40 | C: {{206:Channel C}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 40 | C: {{206:Channel C}} | Temperature value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 41 | C: {{206:Channel C}} | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 42 | C: {{206:Channel C}} | Block | 1 Bit | 1.3 enable | CW |
| 43 | C: {{206:Channel C}} | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 43 | C: {{206:Channel C}} | State control value | 1 Bit | 1.1 switch | CRT |
| 44 | C: {{206:Channel C}} | Switch presence | 1 Bit | 1.1 switch | CW |
| 44 | C: {{206:Channel C}} | Comfort extension | 1 Bit | 1.1 switch | CW |
| 45 | C: {{206:Channel C}} | Dew point alarm | 1 Bit | 1.4 ramp | CW |
| 45 | C: {{206:Channel C}} | Forced position | 1 Bit | 1.3 enable | CW |
| 45 | C: {{206:Channel C}} | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 46 | C: {{206:Channel C}} | PWM output cooling for 4 Pipe | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 47 | C: {{206:Channel C}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 47 | C: {{206:Channel C}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CWT |
| 48 | C: {{206:Channel C}} | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 48 | C: {{206:Channel C}} | Setpoint value offset | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 49 | C: {{206:Channel C}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 50 | C: {{206:Channel C}} | Mode selection | 1 Byte | 20.102 HVAC mode | CRWT |
| 50 | C: {{206:Channel C}} | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 51 | C: {{206:Channel C}} | DPT_HVAC Status | 1 Byte | CRT | |
| 51 | C: {{206:Channel C}} | DPT_HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 52 | C: {{206:Channel C}} | DPT_RHCC Status | 2 Bytes | 22.101 RHCC status | CRT |
| 53 | C: {{206:Channel C}} | Mode comfort | 1 Bit | 1.1 switch | CW |
| 54 | C: {{206:Channel C}} | Mode night | 1 Bit | 1.1 switch | CW |
| 55 | C: {{206:Channel C}} | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 55 | C: {{206:Channel C}} | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 55 | C: {{206:Channel C}} | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 56 | C: {{206:Channel C}} | Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 57 | C: {{206:Channel C}} | Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 58 | C: {{206:Channel C}} | Setpoint value offset(1=+/0=-) | 1 Bit | 1.7 step | CW |
| 59 | C: {{206:Channel C}} | Diagnosis text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 60 | D: {{207:Channel D}} | Control value | 1 Bit | 1.1 switch | CWTU |
| 60 | D: {{207:Channel D}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 60 | D: {{207:Channel D}} | Temperature value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 61 | D: {{207:Channel D}} | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 62 | D: {{207:Channel D}} | Block | 1 Bit | 1.3 enable | CW |
| 63 | D: {{207:Channel D}} | State control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 63 | D: {{207:Channel D}} | State control value | 1 Bit | 1.1 switch | CRT |
| 64 | D: {{207:Channel D}} | Switch presence | 1 Bit | 1.1 switch | CW |
| 64 | D: {{207:Channel D}} | Comfort extension | 1 Bit | 1.1 switch | CW |
| 65 | D: {{207:Channel D}} | Dew point alarm | 1 Bit | 1.5 alarm | CW |
| 65 | D: {{207:Channel D}} | Forced position | 1 Bit | 1.3 enable | CW |
| 66 | D: {{207:Channel D}} | PWM output cooling for 4 Pipe | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 67 | D: {{207:Channel D}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CW |
| 67 | D: {{207:Channel D}} | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CWT |
| 68 | D: {{207:Channel D}} | Setpoint value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 68 | D: {{207:Channel D}} | Setpoint value offset | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 69 | D: {{207:Channel D}} | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 70 | D: {{207:Channel D}} | Mode selection | 1 Byte | 20.102 HVAC mode | CRWT |
| 70 | D: {{207:Channel D}} | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 71 | D: {{207:Channel D}} | DPT_HVAC Status | 1 Byte | CRT | |
| 71 | D: {{207:Channel D}} | DPT_HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 72 | D: {{207:Channel D}} | DPT_RHCC Status | 2 Bytes | 22.101 RHCC status | CRT |
| 73 | D: {{207:Channel D}} | Mode comfort | 1 Bit | 1.1 switch | CW |
| 74 | D: {{207:Channel D}} | Mode night | 1 Bit | 1.1 switch | CW |
| 75 | D: {{207:Channel D}} | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 75 | D: {{207:Channel D}} | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 75 | D: {{207:Channel D}} | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 76 | D: {{207:Channel D}} | Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 77 | D: {{207:Channel D}} | Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 78 | D: {{207:Channel D}} | Setpoint value offset(1=+/0=-) | 1 Bit | 1.7 step | CW |
| 79 | D: {{207:Channel D}} | Diagnosis text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 80 | Summer / Winter | Switchover | 1 Bit | 1.1 switch | CWTU |
| 81 | Heating / Cooling | Switchover | 1 Bit | 1.100 heating/cooling | CWTU |
| 81 | Heating / Cooling | Status | 1 Bit | 1.100 heating/cooling | CRT |
| 82 | Heating/Cooling requirement | 0 if all valves closed, else 1 | 1 Bit | 1.2 boolean | CRT |
| 82 | Heating/Cooling requirement | 0 if control values = 0%, else 1 | 1 Bit | 1.2 boolean | CRT |
| 82 | Heating requirement | 0 if all valves closed, else 1 | 1 Bit | 1.2 boolean | CRT |
| 82 | Heating requirement | 0 if control values = 0%, else 1 | 1 Bit | 1.2 boolean | CRT |
| 82 | Cooling requirement | 0 if all valves closed, else 1 | 1 Bit | 1.2 boolean | CRT |
| 82 | Cooling requirement | 0 if control values = 0%, else 1 | 1 Bit | 1.2 boolean | CRT |
| 83 | Cooling requirement | 0 if all valves closed, else 1 | 1 Bit | 1.2 boolean | CRT |
| 83 | Cooling requirement | 0 if control values = 0%, else 1 | 1 Bit | 1.2 boolean | CRT |
| 84 | Fault | At power failure/short circuit | 1 Bit | 1.5 alarm | CRT |
| 84 | Fault | At short circuit | 1 Bit | 1.5 alarm | CRT |
| 85 | Max. control value | Output | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 86 | Max. control value | Input | 1 Byte | 5.1 percentage (0..100%) | CW |
| 87 | Scene | Activate | 1 Byte | 17.1 scene number | CW |
| 88 | Central function | Operating | 1 Bit | 1.11 state | CRT |
| 89 | Dummy | 1 Bit |
Parameters (110)
| Parameter | Type | Default |
|---|---|---|
| Additional sensor for flow temperature | list | inactive |
| Emergency mode | list | active |
| Startup delaytime | unsignedInt 2…240 | 2 |
| Thermal driving | list | 230V |
| Object for requirement Heating/Cooling | list | not active |
| Switching for heating/cooling | list | not active |
| Protection of forse fit (all 6 days for 5 min valve open/close) | list | not active |
| Object max. control value | list | not active |
| Regard channel in Heating / Cooling requirement and max. control value | list | Yes |
| Mode | list | Chanel not active |
| Basic comfort setpoint | list | 21,0 °C |
| Send state control value | list | not active |
| Standby reduction | list | 2,0 K |
| Night reduction | list | 3,0 K |
| Dead zone between Heating and Cooling | list | 2,0 K |
| Standby increase | list | 3,0 K |
| Night increase | list | 2,0 K |
| Max setpoint offset | list | 3,0 K |
| Max setpoint offset vaild for | list | Comfort |
| Reset setpoint offset after change of mode | list | No |
| Operating mode after bus power reset | list | Comfort |
| Heating / Cooling mode | list | Heating |
| Valve type | list | not energized closed |
| Proportional range | list | 3 K |
| Reset time | list | 120 min |
| PWM cycle time | list | 10 min |
| Control value for emergency mode winter | list | 50% |
| Control value for emergency mode summer | list | 0% |
| System | list | 2 Pipe system |
| Frost alarm if value less | list | 8 °C |
| Heat alarm if value greater | list | 35 °C |
| Send setpoint change | list | No |
| Priority | list | Frost/Comfort/Night/Standby |
| Maximum limit of control value at heating | list | 100% |
| Maximum limit of control value at cooling | list | 100% |
| Flow temperature maximum limit at heating | list | 38 °C |
| Flow temperature minimum limit at cooling | list | 18 °C |
| Control value for forced position winter | list | 50% |
| Behavior after bus power reset | list | Winter mode |
| Heating control values set to 0% at summer mode | list | No |
| Polarity for object "Summer/Winter" | list | Summer = 1 / Winter = 0 |
| Control value for forced position summer | list | 0% |
| Minimum limit of control value at cooling | list | 0% |
| Minimum limit of control value at heating | list | 0% |
| Block object | list | inactive |
| Heating system | list | Warm water heating (4K / 120 min) |
| Cooling system | list | Warm water heating (4K / 120 min) |
| Heating / Cooling system | list | Warm water heating (4K / 120 min) |
| Request control value/temperature value after bus power reset | list | inactive |
| Setpoint value offset over 1Byte/2Byte object | list | not active |
| Step width | list | 0,5 K |
| Send status on object "Mode selection" (HVAC Mode) | list | No |
| Language for diagnosis text | list | German |
| Enable objects for | list | 2 pipe system (Heating or Cooling) |
| Minimum limit of flow temperature | list | inactive |
| Setpoint frost mode | list | 7 °C |
| Referent channel for automatic switch Heating/Cooling (2 pipe system) | list | Channel A |
| Minimum temperature flow | list | 20 °C |
| Enabled for Comfort | list | active |
| Enabled for Standby | list | inactive |
| Enabled for Night | list | inactive |
| Enabled for Frost | list | inactive |
| Send diagnosis text | list | not active |
| Step width | list | 1 K |
| Send cyclic setpoint comfort | list | 5 min |
| Send cyclic current setpoint | list | not active |
| Cycle time | list | 5 min |
| Send cyclic Mode selection | list | not active |
| Send cyclic HVAC-Status | list | not active |
| Object "HVAC Status" as | list | HVAC-Status |
| Controll value at lower deviation of minimum limit | list | 0% = 0% otherwise use minimum limit |
| Controll value Heating at lower deviation of minimum limit | list | 0% = 0% otherwise use minimum limit |
| Scene number | list | 1 |
| Scene A | list | inactive |
| Mode | list | no change |
| Basis comfort setpoint | list | no change |
| Change for Channel A | list | inactive |
| Change for Channel B | list | inactive |
| Change for Channel C | list | inactive |
| Change for Channel D | list | inactive |
| Mode Heating/Cooling | list | no change |
| Mode Summer/Winter | list | no change |
| Scene B | list | inactive |
| Scene C | list | inactive |
| Scene D | list | inactive |
| Scene E | list | inactive |
| Scene F | list | inactive |
| Scene G | list | inactive |
| Scene H | list | inactive |
| Scene I | list | inactive |
| Scene J | list | inactive |
| Scene K | list | inactive |
| Scene L | list | inactive |
| Scene M | list | inactive |
| Scene N | list | inactive |
| Scene O | list | inactive |
| Scene P | list | inactive |
| Presence / Comfort extention at night | list | not active |
| Comfrot extention time | list | 30 min |
| Enabled for Comfort | list | inactive |
| Send "Operation" cyclic | list | not active |
| Requirement according to | list | valve status |
| Setpoint value offset over 1Bit object | list | inactive |
| Forced position / dew point alarm | list | not active |
| Forced position | list | not active |
| Emergency mode at failure of control value after | list | 30 min |
| Emergency mode at failure of temperature value after | list | 30 min |
| Recover modes and setpoints after bus power reset | list | inactive |
| Setting mode | list | Heating |
| Objects description | text |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Heating actuator 4-fold 2.4 latest | $003B | C073 | 2026-11-25 | 125 KB | Download |
About this file
This is the official ETS product database for the MDT technologies GmbH AKH-0400.02 Heating Actuator 4-fold, 2SU MDRC, 24/230 VAC (AKH-0400.02), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from MDT technologies GmbH
- Analog I/O 2fold, flush mounted AIO-0210V.01
- Analog I/O 4fold, MDRC AIO-0410V.01
- AKD-0103.01 Dimming actuator 1-f, 4TE, 230VAC,600W AKD-0103.01
- AKD-0201.01 Dimming actuator 2-f, 4TE, 230VAC,250W AKD-0201.01
- AKD-0201.02 Dimming Actuator 2-fold AKD-0201.02
- AKD-0203.01 Dimming actuator 2-f, 8TE, 230VAC,600W AKD-0203.01
- AKD-0224V.02 LED Controler 2 Ch AKD-0224V.02
- AKD-0230CC.02 LED Controller CC/CV 30 W / 230 V 2-channel AKD-0230CC.02
- AKD-0260CC.02 LED Controller CC/CV 60 W / 230 V 2-channel AKD-0260CC.02
- AKD-0324V.02 LED Controler 3 Ch/RGB AKD-0324V.02
- AKD-0401.01 Dimming actuator 4-f, 8TE, 230VAC,250W AKD-0401.01
- AKD-0401.02 Dimming Actuator 4-fold AKD-0401.02