KNX Database
MDT technologies GmbH AKD-0201.02 AKD-0201.02 Dimming Actuator 2-fold

AKD-0201.02 Dimming Actuator 2-fold AKD-0201.02

MDT technologies GmbH · Order number AKD-0201.02 · Actuators › Dimming actuators

250W ohmic load with active power measurement

Download .knxprod Dimming 2-fold 2.3 · 244 KB

Product

ManufacturerMDT technologies GmbH
Product nameAKD-0201.02 Dimming Actuator 2-fold
Order numberAKD-0201.02
HardwareDimmaktor 2-fach
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)49
RegistrationCertified · 2019-04-15
Languagesde-DE, en-US, es-ES, fr-FR, it-IT
Catalog entryM-0083_H-252-1_HP-001C-23-8C75_CI-AKD.2D0201.2E02-1
Fingerprint8C75
SHA-2565207a5a3f0dee5c4f2214580d26ab0ee43a2e1e6d660475059ce348839a957d7
First seen2026-11-25
Markets69 markets

Application program: Dimming 2-fold 2.3

Application number$001C
Version2.3
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version5.0
Parameters442
Group objects142
Group objects (142)
NoNameFunctionSizeDPTFlags
0A: {{0:Channel A}}Switch1 Bit1.1 switchCW
0A+B: {{0:Channel A+B}}Switch1 Bit1.1 switchCW
1A: {{0:Channel A}}Staircase light1 Bit1.1 switchCW
1A+B: {{0:Channel A+B}}Staircase light1 Bit1.1 switchCW
2A: {{0:Channel A}}Staircase light with time1 Byte5.5 ratio (0..255)CW
2A+B: {{0:Channel A+B}}Staircase light with time1 Byte5.5 ratio (0..255)CW
2A: {{0:Channel A}}Staircase light with time2 Bytes7.5 time (s)CW
2A+B: {{0:Channel A+B}}Staircase light with time2 Bytes7.5 time (s)CW
3A: {{0:Channel A}}Prewarning1 Bit1.11 stateCT
3A+B: {{0:Channel A+B}}Prewarning1 Bit1.11 stateCT
4A: {{0:Channel A}}Dimming relative4 Bit3.7 dimming controlCW
4A+B: {{0:Channel A+B}}Dimming relative4 Bit3.7 dimming controlCW
4A: {{0:Channel A}}Dimming relative (Staircase light)4 Bit3.7 dimming controlCW
4A+B: {{0:Channel A+B}}Dimming relative (Staircase light)4 Bit3.7 dimming controlCW
5A: {{0:Channel A}}Dimming absolute1 Byte5.1 percentage (0..100%)CW
5A+B: {{0:Channel A+B}}Dimming absolute1 Byte5.1 percentage (0..100%)CW
5A: {{0:Channel A}}Dimming absolute (Staircase light)1 Byte5.1 percentage (0..100%)CW
5A+B: {{0:Channel A+B}}Dimming absolute (Staircase light)1 Byte5.1 percentage (0..100%)CW
6A: {{0:Channel A}}State On/Off1 Bit1.11 stateCRT
6A+B: {{0:Channel A+B}}State On/Off1 Bit1.11 stateCRT
7A: {{0:Channel A}}State of dimming value1 Byte5.1 percentage (0..100%)CRT
7A+B: {{0:Channel A+B}}State of dimming value1 Byte5.1 percentage (0..100%)CRT
8A: {{0:Channel A}}Block 11 Bit1.3 enableCW
8A: {{0:Channel A}}Block 12 Bit2.1 switch controlCW
8A: {{0:Channel A}}Block 11 Byte5.1 percentage (0..100%)CW
8A+B: {{0:Channel A+B}}Block 11 Bit1.3 enableCW
8A+B: {{0:Channel A+B}}Block 12 Bit2.1 switch controlCW
8A+B: {{0:Channel A+B}}Block 11 Byte5.1 percentage (0..100%)CW
8A: {{0:Channel A}}Block 1 inverted1 Bit1.3 enableCW
8A+B: {{0:Channel A+B}}Block 1 inverted1 Bit1.3 enableCW
9A: {{0:Channel A}}Block 21 Bit1.3 enableCW
9A: {{0:Channel A}}Block 22 Bit2.1 switch controlCW
9A: {{0:Channel A}}Block 21 Byte5.1 percentage (0..100%)CW
9A+B: {{0:Channel A+B}}Block 21 Bit1.3 enableCW
9A+B: {{0:Channel A+B}}Block 22 Bit2.1 switch controlCW
9A+B: {{0:Channel A+B}}Block 21 Byte5.1 percentage (0..100%)CW
9A: {{0:Channel A}}Block 2 inverted1 Bit1.3 enableCW
9A+B: {{0:Channel A+B}}Block 2 inverted1 Bit1.3 enableCW
10A: {{0:Channel A}}Block state1 Bit1.11 stateCRT
10A+B: {{0:Channel A+B}}Block state1 Bit1.11 stateCRT
11A: {{0:Channel A}}Scene1 Byte17.1 scene numberCW
11A: {{0:Channel A}}Scene1 Byte18.1 scene controlCW
11A+B: {{0:Channel A+B}}Scene1 Byte17.1 scene numberCW
11A+B: {{0:Channel A+B}}Scene1 Byte18.1 scene controlCW
12A: {{0:Channel A}}Bit Scene 11 Bit1.22 sceneCW
12A+B: {{0:Channel A+B}}Bit Scene 11 Bit1.22 sceneCW
13A: {{0:Channel A}}Bit Scene 21 Bit1.22 sceneCW
13A+B: {{0:Channel A+B}}Bit Scene 21 Bit1.22 sceneCW
14A: {{0:Channel A}}Bit Scene 31 Bit1.22 sceneCW
14A+B: {{0:Channel A+B}}Bit Scene 31 Bit1.22 sceneCW
15A: {{0:Channel A}}Bit Scene 41 Bit1.22 sceneCW
15A+B: {{0:Channel A+B}}Bit Scene 41 Bit1.22 sceneCW
16A: {{0:Channel A}}Time dependent dimming - Switching1 Bit1.1 switchCW
16A+B: {{0:Channel A+B}}Time dependent dimming - Switching1 Bit1.1 switchCW
17A: {{0:Channel A}}Time dependent dimming - Status1 Bit1.11 stateCRT
17A+B: {{0:Channel A+B}}Time dependent dimming - Status1 Bit1.11 stateCRT
18A: {{0:Channel A}}Switch-On value (0% = Parameter)1 Byte5.1 percentage (0..100%)CW
18A+B: {{0:Channel A+B}}Switch-On value (0% = Parameter)1 Byte5.1 percentage (0..100%)CW
19A: {{0:Dummy}}1 ByteCW
19A+B: {{0:Dummy}}1 ByteCW
20A: {{0:Channel A}}Active power4 Bytes14.56 power (W)CRT
20A: {{0:Channel A}}Active power2 Bytes9.24 power (kW)CRT
20A+B: {{0:Channel A+B}}Active power2 Bytes9.24 power (kW)CRT
20A+B: {{0:Channel A+B}}Active power4 Bytes14.56 power (W)CRT
21A: {{0:Channel A}}Active power meter4 Bytes13.10 active energy (Wh)CRT
21A: {{0:Channel A}}Active power meter4 Bytes13.13 active energy (kWh)CRT
21A+B: {{0:Channel A+B}}Active power meter4 Bytes13.10 active energy (Wh)CRT
21A+B: {{0:Channel A+B}}Active power meter4 Bytes13.13 active energy (kWh)CRT
22A: {{0:Channel A}}Reset active power meter1 Bit1.15 resetCW
22A+B: {{0:Channel A+B}}Reset active power meter1 Bit1.15 resetCW
23A: {{0:Channel A}}Overtemperature1 Bit1.5 alarmCRT
23A+B: {{0:Channel A+B}}Overtemperature1 Bit1.5 alarmCRT
24A: {{0:Channel A}}Overload / Short circuit1 Bit1.5 alarmCRT
24A+B: {{0:Channel A+B}}Overload / Short circuit1 Bit1.5 alarmCRT
25A: {{0:Channel A}}Power error1 Bit1.5 alarmCRT
25A+B: {{0:Channel A+B}}Power error1 Bit1.5 alarmCRT
26A: {{0:Channel A}}Load failure1 Bit1.5 alarmCRT
26A+B: {{0:Channel A+B}}Load failure1 Bit1.5 alarmCRT
27A: {{0:Channel A}}Start lamp test1 Bit1.10 start/stopCW
27A+B: {{0:Channel A+B}}Start lamp test1 Bit1.10 start/stopCW
28A: {{0:Channel A}}Diagnosis text14 Bytes16.1 Character String (ISO 8859-1)CRT
28A+B: {{0:Channel A+B}}Diagnosis text14 Bytes16.1 Character String (ISO 8859-1)CRT
29Dummy1 BitCW
30Dummy4 BytesCW
31Dummy4 BytesCW
32B: {{0:Channel B}}Switch1 Bit1.1 switchCW
33B: {{0:Channel B}}Staircase light1 Bit1.1 switchCW
34B: {{0:Channel B}}Staircase light with time1 Byte5.5 ratio (0..255)CW
34B: {{0:Channel B}}Staircase light with time2 Bytes7.5 time (s)CW
35B: {{0:Channel B}}Prewarning1 Bit1.11 stateCT
36B: {{0:Channel B}}Dimming relative4 Bit3.7 dimming controlCW
36B: {{0:Channel B}}Dimming relative (Staircase light)4 Bit3.7 dimming controlCW
37B: {{0:Channel B}}Dimming absolute1 Byte5.1 percentage (0..100%)CW
37B: {{0:Channel B}}Dimming absolute (Staircase light)1 Byte5.1 percentage (0..100%)CW
38B: {{0:Channel B}}State On/Off1 Bit1.11 stateCRT
39B: {{0:Channel B}}State of dimming value1 Byte5.1 percentage (0..100%)CRT
40B: {{0:Channel B}}Block 11 Bit1.3 enableCW
40B: {{0:Channel B}}Block 1 inverted1 Bit1.3 enableCW
40B: {{0:Channel B}}Block 12 Bit2.1 switch controlCW
40B: {{0:Channel B}}Block 11 Byte5.1 percentage (0..100%)CW
41B: {{0:Channel B}}Block 21 Bit1.3 enableCW
41B: {{0:Channel B}}Block 2 inverted1 Bit1.3 enableCW
41B: {{0:Channel B}}Block 22 Bit2.1 switch controlCW
41B: {{0:Channel B}}Block 21 Byte5.1 percentage (0..100%)CW
42B: {{0:Channel B}}Block state1 Bit1.11 stateCRT
43B: {{0:Channel B}}Scene1 Byte17.1 scene numberCW
43B: {{0:Channel B}}Scene1 Byte18.1 scene controlCW
44B: {{0:Channel B}}Bit Scene 11 Bit1.22 sceneCW
45B: {{0:Channel B}}Bit Scene 21 Bit1.22 sceneCW
46B: {{0:Channel B}}Bit Scene 31 Bit1.22 sceneCW
47B: {{0:Channel B}}Bit Scene 41 Bit1.22 sceneCW
48B: {{0:Channel B}}Time dependent dimming - Switching1 Bit1.1 switchCW
49B: {{0:Channel B}}Time dependent dimming - Status1 Bit1.11 stateCRT
50B: {{0:Channel B}}Switch-On value (0% = Parameter)1 Byte5.1 percentage (0..100%)CW
51B: {{0:Dummy}}1 ByteCW
52B: {{0:Channel B}}Active power4 Bytes14.56 power (W)CRT
52B: {{0:Channel B}}Active power2 Bytes9.24 power (kW)CRT
53B: {{0:Channel B}}Active power meter4 Bytes13.10 active energy (Wh)CRT
53B: {{0:Channel B}}Active power meter4 Bytes13.13 active energy (kWh)CRT
54B: {{0:Channel B}}Reset active power meter1 Bit1.15 resetCW
55B: {{0:Channel B}}Overtemperature1 Bit1.5 alarmCRT
56B: {{0:Channel B}}Overload / Short circuit1 Bit1.5 alarmCRT
57B: {{0:Channel B}}Power error1 Bit1.5 alarmCRT
58B: {{0:Channel B}}Load failure1 Bit1.5 alarmCRT
59B: {{0:Channel B}}Start lamp test1 Bit1.10 start/stopCW
60B: {{0:Channel B}}Diagnosis text14 Bytes16.1 Character String (ISO 8859-1)CRT
61Dummy1 BitCW
62Dummy4 BytesCW
63Dummy4 BytesCW
64CentralSwitch1 Bit1.1 switchCW
65CentralDimming relative4 Bit3.7 dimming controlCW
66CentralDimming absolute1 Byte5.1 percentage (0..100%)CW
67CentralScene1 Byte17.1 scene numberCW
68TimeReceive current value3 Bytes10.1 time of dayCWTU
69DateReceive current value3 Bytes11.1 dateCWTU
70Date/TimeReceive current values8 Bytes19.1 date timeCWTU
71OperationOutput1 Bit1.11 stateCRT
72Day/NightDay=1 / Night=01 Bit1.2 booleanCWTU
72Day/NightNight=1 / Day=01 Bit1.2 booleanCWTU
73Dummy1 Bit
74Dummy1 Bit
75Dummy1 Bit
Parameters (173)
ParameterTypeDefault
Channel Alistactive
Channel Blistactive
Staircase lightlistnot active
Scenelistnot active
Bit Sceneslistnot active
Prewarninglistnot active
Switching on delaylistno delay
Switching off delaylistno delay
Duration of staircase lightunsignedInt 0…1440090
Manual switching offlistnot active
Extend time for staircase lightlistrestart time
Dimming speed for relative dimmingunsignedInt 1…12015
Value of dimming downlist20%
Prewarning durationunsignedInt 0…1440010
Block object 1 -> Action at unlockinglistvalue before locking
Block object 1 -> Action at lockinglistbrightness value
Brightness valuelist100%
Scene number Alistnot active
Scene number Blistnot active
Scene number Clistnot active
Scene number Dlistnot active
Scene number Elistnot active
Scene number Flistnot active
Scene number Glistnot active
Scene number Hlistnot active
Send status of dimming valuelistat dimming end
Save scenelistnot active
Switch offlistactive
Absolute dimminglistactive
Switching on speedunsignedInt 0…1202
Switching off speedunsignedInt 0…1202
Brightness valuelist10%
Dimming speed for absolute dimmingunsignedInt 0…12010
Brightnesslist0%
Startup timeunsignedInt 2…2402
Switch chanel off with relative dimminglistnot active
Behavior after bus power resetlistlast value
Send "Operation" cycliclistnot active
Setting channelslistindividual
Day/Night objectlistactive, request after reset
Value for Day/NightlistDay = 1 / Night = 0
Toggle light Day/Nightlistreacts to next switch on
Automatic changeover of summertimelistactive
Location determination bylistplace
CountrylistGermany
TownlistAntwerp
Latitudelistnorth
Latitude in degrees [0° - 90°]unsignedInt 0…9050
Latitude in minutes [0' - 59']unsignedInt 0…5956
Longitudelisteast
Longitude in degrees [0° - 180°]unsignedInt 0…1806
Longitude in minutes [0' - 59']unsignedInt 0…5957
Time difference from Universal Time (UTC + ...)list(UTC +01:00) Amsterdam, Berlin, Bern, Rome, Vienna
TownlistAalborg
TownlistEngelskirchen
TownlistHelsinki
TownlistAjaccio (Corsika)
TownlistAthens
TownlistBirmingham
TownlistCork
TownlistBari
TownlistLuxembourg
TownlistAmsterdam
TownlistBergen
TownlistFeldkirch
TownlistBreslau
TownlistBraga
TownlistMoskow
TownlistGoteborg
TownlistBasel
TownlistBarcelona
TownlistPrague
Switching on speed for DayunsignedInt 0…1202
Switching off speed for DayunsignedInt 0…1202
Switching on speed for NightunsignedInt 0…1202
Switching off speed for NightunsignedInt 0…1202
Send status of dimming value when blockedlistactive
Dimming range under limit value at switching on/offlistskip
Switch onlistactive
Relative dimminglistactive
Sceneslistactive
Central objectslistnot active
Actionlistbrightness value
Dimming speedunsignedInt 0…144005
Bit Scene 1listnot active
Action at "On"listbrightness value
Action at "Off"listhold value / no change
Bit Scene 2listnot active
Bit Scene 3listnot active
Bit Scene 4listnot active
Block object 1 - datapoint typelistnot active
Action at object value = 1listblock
Action at object value Force OFFlistblock -> Off
Action at object value = 0listblock
Action at object value Force ONlistblock
Action at object value Force Endlistunblock/enable
Block object 2 - datapoint typelistnot active
Block object 2 -> Action at lockinglistbrightness value
Block object 2 -> Action at unlockinglistvalue before locking
Dimming speedunsignedInt 0…1202
Activation timelist1,0 s
Switch on behaviourlistsettable switch on value
Switch on valuelist100%
Switch on value for Daylist100%
Switch on value for Nightlistsame as day
Channel A + Blistactive
Release time block object 1 (0=not active)unsignedInt 0…320000
Release time block object 2 (0=not active)unsignedInt 0…320000
Dimming speed for relative dimmingunsignedInt 1…12010
Dimming speed for absolute dimmingunsignedInt 0…1201
Dimming speedlistglobal settings
Action at dimming value = 0%listblock
Switching timeslistTime
Action at unlockinglistvalue before locking
Time dependent dimminglistnot active
Time 1listsunrise +- 0min
Time 2listsunrise +- 0min
Time 3listsunrise +- 0min
Time 4listsunrise +- 0min
Time 5listsunrise +- 0min
Time 6listsunset +- 0min
Time 7listsunset +- 0min
Time 8listsunset +- 0min
Time 9listsunset +- 0min
Time 10listsunset +- 0min
Time 1list00:00
Time 2list00:00
Time 3list00:00
Time 4list00:00
Time 5list00:00
Time 6list00:00
Time 8list00:00
Time 9list00:00
Time 10list00:00
Time 7list00:00
Fallback time of brightnesslistno fallback
Behavior at control object "Off"listdeactivation
Switch on behavior for Daylistsettable switch on value
Start time for dimmin procedurelistsunrise +- 0min
Energy saving mode, switch off LED's on the device afterlistnot active
Description of objectstext
Load typelistLED 230V eco/universal (trailing-edge)
Dimming curvelistLED B (recommended)
Change switch-on value via objectlistnot active
Time for dimming downlistsoft dimming (1s)
Prewarning objectlistnot active
Time factor for object "Staircase light with time"list1 s
Power measurement / Diagnosislistnot active
Active powerlistnot active
Object selectionlist4Byte DPT 14.056 Power (W)
Send value at changelist5%
Send value cycliclistno send
Active power meterlistnot active
Object selectionlist4Byte DPT 13.010 Active Energy (Wh)
Send current meter reading every…list10 Wh
Send current meter reading every…list1 kWh
Diagnosislistnot active
Send error objects cycliclistnot active
Mains filterlistactive
Error objectslistnot active
Error object Overtemperaturelistactive
Error object Overload / Short circuitlistactive
Error object Power errorlistactive
Error object Load failurelistactive
Reset the object valuelistdevice restart
Send status objects cyclicallylistnot active
Limiting the dimming range of the illuminantlistnot active
Minimum control value (corresponds to 0% of status Dimming value)list0%
Maximum control value (corresponds to 100% of status Dimming value)list100%
Action for brightness change via relative or absolute dimminglistTime dependent dimming is interrupted
Object "Staircase light with time"listnot active
Cold Start / StartUp (for LEDs and ECL) (from R5.2)listactive
Activation valuelist20%

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Dimming 2-fold 2.3 latest$001C8C752026-11-25244 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH AKD-0201.02 Dimming Actuator 2-fold (AKD-0201.02), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from MDT technologies GmbH