Product

ManufacturerHugo Müller GmbH & Co KG
Product name[GS70, GS60, GS20, GS10, TS10 knx] Room climate control and air quality sensors
Order numberGS70, GS60, GS20, GS10, TS10 knx
Product textGS70, GS60, GS20, GS10, TS10 knx
HardwareGS70, GS60, GS20, GS10, TS10 knx
MediumTwisted Pair
Bus current (mA)8
Rail mountedNo
RegistrationRegistered · 2020-05-12
Languagesde-DE, en-US
Catalog entryM-00FC_H-LP503.5F508-1_HP-7000-10-9FB1_CI-GS70.2C.20GS60.2C.20GS20.2C.20GS10.2C.20TS10.20knx-2
Fingerprint9FB1
SHA-256236d825a60155b4b0c9094249d0dd14e326c8d67f30a5c3d2377e3936435f8ca
First seen2026-11-25
Markets56 markets

Application program: GS70, GS60, GS20, GS10, TS10 knx 1.0

Application number$7000
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version4.0
Parameters591
Group objects155
Group objects (155)
NoNameFunctionSizeDPTFlags
1Send '0' in operationOutput1 BitDPT.1CT
1Send '1' in operationOutput1 BitDPT.1CT
2Request statusInput1 BitDPT.1CW
3operating hours counter[s]Output4 BytesDPT.13CT
4Request operating hours counterInput1 BitDPT.1CW
5PM-Sensor Alarm: Too low voltageOutput1 BitDPT.1CT
16T: heat alarmOutput1 BitDPT.1CT
17T: frost alarmOutput1 BitDPT.1CT
18RTC: external temperature value 1Input2 BytesDPT.9CW
19RTC: external temperature value 2Input2 BytesDPT.9CW
20RTC: comfort temperatureInput2 BytesDPT.9CW
21RTC: standby setback when heatingInput2 BytesDPT.9CW
22RTC: eco setback when heatingInput2 BytesDPT.9CW
23RTC: standby increment when coolingInput2 BytesDPT.9CW
24RTC: eco increment when coolingInput2 BytesDPT.9CW
25RTC: current set point temperatureOutput2 BytesDPT.9CT
26RTC: comfort temperature +/- 0,1KInput1 BitDPT.1CW
27RTC: comfort temperature +/- 0,5KInput1 BitDPT.1CW
28RTC: standby setback when heating +/- 0,1KInput1 BitDPT.1CW
29RTC: eco setback when heating +/- 0,1KInput1 BitDPT.1CW
30RTC: standby increment when cooling +/- 0,1KInput1 BitDPT.1CW
31RTC: eco increment when cooling +/- 0,1KInput1 BitDPT.1CW
32RTC: HVAC Mode: 1=comf, 2=stdb, 3=ecoInput1 ByteDPT.20CW
33RTC: HVAC Mode: 1=comf, 2=stdb, 3=ecoOutput1 ByteDPT.20CT
34RTC: comfort mode enableInput1 BitDPT.1CW
35RTC: standby mode enableInput1 BitDPT.1CW
36RTC: eco mode enableInput1 BitDPT.1CW
37RTC: status heatingOutput1 BitDPT.1CT
38RTC: status coolingOutput1 BitDPT.1CT
39RTC: control value main level heatingOutput1 ByteDPT.5CT
39RTC: control value main level heatingOutput1 BitDPT.1CT
40RTC: control value extra level heatingOutput1 ByteDPT.5CT
40RTC: control value extra level heatingOutput1 BitDPT.1CT
41RTC: control value main level coolingOutput1 ByteDPT.5CT
41RTC: control value main level coolingOutput1 BitDPT.1CT
42RTC: control value extra level coolingOutput1 ByteDPT.5CT
42RTC: control value extra level coolingOutput1 BitDPT.1CT
43RTC: guide value [°C]Input2 BytesDPT.9CW
44RTC: blocking object heatingInput1 BitDPT.1CW
45RTC: blocking object coolingInput1 BitDPT.1CW
46RTC: blocking object extra level heatingInput1 BitDPT.1CW
47RTC: blocking object extra level coolingInput1 BitDPT.1CW
48PMCMP: Particulate matter value 1 [µg/m3]Input2 BytesDPT.9CW
49PMCMP: Particulate matter value 2 [µg/m3]Input2 BytesDPT.9CW
50PMCMP: Particulate matter comparator outputOutput1 BitDPT.1CT
51HUMCMP: Absolute humidity value 1 [g/m3]Input2 BytesDPT.9CW
51HUMCMP: Relative humidity value 1 [%]Input1 ByteDPT.5CW
52HUMCMP: Temperature value 1 [°C]Input2 BytesDPT.9CW
53HUMCMP: Absolute humidity value 2 [g/m3]Input2 BytesDPT.9CW
53HUMCMP: Relative humidity value 2 [%]Input1 ByteDPT.5CW
54HUMCMP: Temperature value 2 [°C]Input2 BytesDPT.9CW
55HUMCMP: Humidity comparator outputOutput1 BitDPT.1CT
56DEWP: dew point temperature [°C]Output2 BytesDPT.9CT
57DEWP: dew point alarm enabled (switching object)Output1 BitDPT.1CT
57DEWP: dew point alarm enabled (priority)Output2 BitDPT.2CT
57DEWP: dew point alarm enabled (0...100%)Output1 ByteDPT.5CT
57DEWP: dew point alarm enabled (0...255)Output1 ByteDPT.5CT
57DEWP: dew point alarm enabled scene (1...64)Output1 ByteDPT.17CT
58DEWP: request dew point temperatureInput1 BitDPT.1CW
59P: absolute air pressure [Pa]Output2 BytesDPT.9CT
60P: relative air pressure [Pa]Output2 BytesDPT.9CT
61P: air pressure sensor errorOutput1 BitDPT.1CT
62P: request absolute air pressureInput1 BitDPT.1CW
63P: request relative air pressureInput1 BitDPT.1CW
64VAVC: control value (0...255)Output1 ByteDPT.5CT
64VAVC: control value (0...100%)Output1 ByteDPT.5CT
65VAVC: external object (0…100%)Input1 ByteDPT.5CW
66VAVC: blocking objectInput1 BitDPT.1CW
67PMC: Particulate matter external value 1 [µg/m3]Input2 BytesDPT.9CW
68PMC: Particulate matter external value 2 [µg/m3]Input2 BytesDPT.9CW
69PMC: Control value (0...255)Output1 ByteDPT.5CT
69PMC: Control value (0...100%)Output1 ByteDPT.5CT
69PMC: Scene (1...64)Output1 ByteDPT.17CT
70PMC: Control value level 1 (switching object)Output1 BitDPT.1CT
70PMC: Control value level 1 (priority)Output2 BitDPT.2CT
71PMC: Control value level 2 (switching object)Output1 BitDPT.1CT
71PMC: Control value level 2 (priority)Output2 BitDPT.2CT
72PMC: Control value level 3 (switching object)Output1 BitDPT.1CT
72PMC: Control value level 3 (priority)Output2 BitDPT.2CT
73PMC: Base set point [µg/m3]Input2 BytesDPT.9CW
74GO_CTL_0_SETPOINT_VAL_PROCGO_CTL_0_SETPOINT_VAL_PROC1 ByteDPT.5CW
75PMC: Blocking object level 1Input1 BitDPT.1CW
76PMC: Blocking object level 2Input1 BitDPT.1CW
77PMC: Blocking object level 3Input1 BitDPT.1CW
78PMC: Blocking objectInput1 BitDPT.1CW
79VOCC: VOC external value 1 [µg/m3]Input2 BytesDPT.9CW
80VOCC: VOC external value 2 [µg/m3]Input2 BytesDPT.9CW
81VOCC: control value (0...255)Output1 ByteDPT.5CT
81VOCC: control value (0...100%)Output1 ByteDPT.5CT
81VOCC: scene (1...64)Output1 ByteDPT.17CT
82VOCC: control value level 1 (switching object)Output1 BitDPT.1CT
82VOCC: control value level 1 (priority)Output2 BitDPT.2CT
83VOCC: control value level 2 (switching object)Output1 BitDPT.1CT
83VOCC: control value level 2 (priority)Output2 BitDPT.2CT
84VOCC: control value level 3 (switching object)Output1 BitDPT.1CT
84VOCC: control value level 3 (priority)Output2 BitDPT.2CT
85VOCC: base set point [µg/m3]Input2 BytesDPT.9CW
86GO_CTL_1_SETPOINT_VAL_PROCGO_CTL_1_SETPOINT_VAL_PROC1 ByteDPT.5CW
87VOCC: blocking object level 1Input1 BitDPT.1CW
88VOCC: blocking object level 2Input1 BitDPT.1CW
89VOCC: blocking object level 3Input1 BitDPT.1CW
90VOCC: blocking objectInput1 BitDPT.1CW
91RHC: humidity external value 1 [%]Input1 ByteDPT.5CW
92RHC: external humidity value 2 [%]Input1 ByteDPT.5CW
93RHC: control value (0...255)Output1 ByteDPT.5CT
93RHC: control value (0...100%)Output1 ByteDPT.5CT
93RHC: scene (1...64)Output1 ByteDPT.17CT
94RHC: control value level 1 (switching object)Output1 BitDPT.1CT
94RHC: control value level 1 (priority)Output2 BitDPT.2CT
95RHC: control value level 2 (switching object)Output1 BitDPT.1CT
95RHC: control value level 2 (priority)Output2 BitDPT.2CT
96RHC: control value level 3 (switching object)Output1 BitDPT.1CT
96RHC: control value level 3 (priority)Output2 BitDPT.2CT
97RHC: base set point [%]Input2 BytesDPT.9CW
98RHC: base set point (1 byte) [%]Input1 ByteDPT.5CW
99RHC: blocking object level 1Input1 BitDPT.1CW
100RHC: blocking object level 2Input1 BitDPT.1CW
101RHC: blocking object level 3Input1 BitDPT.1CW
102RHC: blocking objectInput1 BitDPT.1CW
103PM: particulate matter value [µg/m3]Output2 BytesDPT.9CT
104GO_SENSOR_0_INTERN_PROCGO_SENSOR_0_INTERN_PROC1 ByteDPT.5CT
105PM: request PM valueInput1 BitDPT.1CW
106PM: sensor errorOutput1 BitDPT.1CT
107GO_SENSOR_0_CALI_VENTILATION_START_STOPGO_SENSOR_0_CALI_VENTILATION_START_STOP1 BitDPT.1CW
108PM: min valueOutput2 BytesDPT.9CT
109PM: max valueOutput2 BytesDPT.9CT
110PM: request min/max valuesInput1 BitDPT.1CW
111PM: reset min/max valuesInput1 BitDPT.1CW
112VOC: VOC value [µg/m3]Output2 BytesDPT.9CT
113GO_SENSOR_1_INTERN_PROCGO_SENSOR_1_INTERN_PROC1 ByteDPT.5CT
114VOC: request VOC valueInput1 BitDPT.1CW
115VOC: sensor errorOutput1 BitDPT.1CT
116VOC: calibrationInput1 BitDPT.1CW
117VOC: min valueOutput2 BytesDPT.9CT
118VOC: max valueOutput2 BytesDPT.9CT
119VOC: request min/max valuesInput1 BitDPT.1CW
120VOC: reset min/max valuesInput1 BitDPT.1CW
121rH: humidity value [%]Output2 BytesDPT.9CT
122rH: humidity value (1 byte) [%]Output1 ByteDPT.5CT
123rH: request humidity valueInput1 BitDPT.1CW
124rH: sensor error Output1 BitDPT.1CT
125GO_SENSOR_2_CALI_VENTILATION_START_STOPGO_SENSOR_2_CALI_VENTILATION_START_STOP1 BitDPT.1CW
126rH: min valueOutput2 BytesDPT.9CT
127rH: max valueOutput2 BytesDPT.9CT
128rH: request min/max valuesInput1 BitDPT.1CW
129rH: reset min/max valuesInput1 BitDPT.1CW
130T: temperature value [°C]Output2 BytesDPT.9CT
131GO_SENSOR_3_INTERN_PROCGO_SENSOR_3_INTERN_PROC1 ByteDPT.5CT
132T: request temperature valueInput1 BitDPT.1CW
133T: sensor error Output1 BitDPT.1CT
134GO_SENSOR_3_CALI_VENTILATION_START_STOPGO_SENSOR_3_CALI_VENTILATION_START_STOP1 BitDPT.1CW
135T: temperature min valueOutput2 BytesDPT.9CT
136T: temperature max valueOutput2 BytesDPT.9CT
137T: request min/max temperature valuesInput1 BitDPT.1CW
138T: reset min/max temperature valuesInput1 BitDPT.1CW
Parameters (287)
ParameterTypeDefault
VariantlistPlease select variant
PAR_ALLGEMEIN_CHANNEL_ACTIVElistinactive
PAR_FD_CHANNEL_ACTIVElistinactive
PAR_VOC_CHANNEL_ACTIVElistinactive
PAR_RH_CHANNEL_ACTIVElistinactive
PAR_TEMPERATURE_CHANNEL_ACTIVElistinactive
PAR_DEWPOINT_CHANNEL_ACTIVElistinactive
PAR_PRESSURE_CHANNEL_ACTIVElistinactive
PAR_VAV_CHANNEL_ACTIVElistinactive
Send in operationlistinactive
Send 'in operation' cyclicallylistevery minute
PID_HARDWARE_TYPE_PARAMETERlist
Particulate matter sensorlistdisabled
Value offsetunsignedInt 0…655350
PAR_DUMMY_PB_SENSOR_0_SETTINGSBLOCK_30unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_0_SETTINGSBLOCK_30unsignedInt 0…2551
Error particulate matter sensorlistdon't notify
PAR_SENSOR_0_BUS_CALIBRATION_USElistno
PAR_DUMMY_PB_SENSOR_0_SETTINGSBLOCK_50unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_0_SETTINGSBLOCK_50unsignedInt 0…2551
Send particulate matter value when changinglistdisabled
Send particulate matter value cyclicallylistdisabled
PAR_DUMMY_PB_SENSOR_0_SETTINGSBLOCK_60unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_0_SETTINGSBLOCK_60unsignedInt 0…2551
Send particulate matter min/max values when changinglistdisabled
Send particulate matter min/max values cyclicallylistdisabled
Type of particulate matter controllistdisabled
PAR_CTL_0_ACTlistdisabled
PAR_CTL_0_VIS_STEP1listdisabled
PAR_CTL_0_VIS_STEP2listdisabled
PAR_CTL_0_VIS_STEP3listdisabled
PAR_CTL_0_VIS_ONE_STEPlistdisabled
PAR_CTL_0_SEND_CYCLIC_ACTlistdisabled
Allow to change base set-point via buslistno
Hysteresis (symmetrical)list2.5 µg/m3
Control value output formatlistpercent
Control value output formatlistswitching command
PAR_CTL_0_ACTUATING_VAL_FORMATlistswitching command
PAR_CTL_0_OUT_GO_NUMBERunsignedInt 0…2550
PAR_CTL_0_SEND_BY_CHANGE_FORMATunsignedInt 0…2550
PAR_CTL_0_OUTPUT_ACTlistdisabled
Sensor value 1listinternal sensor
Sensor value 2listdisabled
Include value 2listwith 50% proportion
Particulate matter sensor threshold 1list8.5 µg/m3
Switching command below threshold 1listoff
Switching command above threshold 1liston
Control value in case of sensor errorlistoff
Priority below threshold 1liststop priority
Priority above threshold 1liston with priority
Control value in case of sensor errorliststop priority
Blocking objectlistdisabled
Behavior when unblockinglistdon't send
Behavior when blockinglistdon't send
Switching Command when blockinglistoff
Priority when blockingliststop priority
Particulate matter sensor threshold 2listthreshold 1 + 5.0 µg/m3
Switching command below threshold 2listoff
Switching command above threshold 2liston
Priority below threshold 2liststop priority
Priority above threshold 2liston with priority
Particulate matter sensor threshold 3listthreshold 2 + 5.0 µg/m3
Switching command below threshold 3listoff
Switching command above threshold 3liston
Priority below threshold 3liststop priority
Priority above threshold 3liston with priority
Switching command when blockinglistoff
Value when below threshold 1 (0…255)unsignedInt 0…2550
Percent below threshold 1unsignedInt 0…1000
Scene below threshold 1 (1…64)unsignedInt 1…641
PercentunsignedInt 0…1000
Value (0…255)unsignedInt 0…2550
Scene (1…64)unsignedInt 1…641
Control value in case of sensor error (0...255)unsignedInt 0…2550
Control value in case of sensor errorlist0%
Scene in case of sensor error (1...64)unsignedInt 1…641
Percent when blocking (0…100%)unsignedInt 0…1000
Value when blocking (0…255)unsignedInt 0…2550
Scene when blocking (1…64)unsignedInt 1…641
Set-pointlist50 µg/m3
Proportional bandlist25 µg/m3
Reset time (1...15 min)list15 min.
Min. Control valuelist0%
Min. Control valuelist0
Max. Control valuelist100%
Max. Control valuelist255
Send control value when change-overlistdisabled
Send control value when changinglistdisabled
Send control value cyclicallylistevery minute
Comparatorlistdisabled
Value 1listinternal sensor
Value 2listvia bus (communication object)
Output when Value 1 < Value 2list0 (unblock)
Output when errorlist1 (block)
Send output value when changinglistdisabled
Send output value cyclicallylistdisabled
PAR_FD_SENS_VAL_USEDlistdisabled
VOC sensorlistdisabled
PAR_SENSOR_1_OFFSETunsignedInt 0…655350
PAR_DUMMY_PB_SENSOR_1_SETTINGSBLOCK_30unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_1_SETTINGSBLOCK_30unsignedInt 0…2551
Error VOC sensorlistdon't notify
PAR_DUMMY_PB_SENSOR_1_SETTINGSBLOCK_40unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_1_SETTINGSBLOCK_40unsignedInt 0…2551
Enable calibration via buslistno
PAR_DUMMY_PB_SENSOR_1_SETTINGSBLOCK_50unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_1_SETTINGSBLOCK_50unsignedInt 0…2551
Send VOC value when changinglistdisabled
Send VOC value cyclicallylistdisabled
PAR_DUMMY_PB_SENSOR_1_SETTINGSBLOCK_60unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_1_SETTINGSBLOCK_60unsignedInt 0…2551
Send VOC min/max values when changinglistdisabled
Send VOC min/max values cyclicallylistdisabled
Type of VOC controllistdisabled
PAR_CTL_1_ACTlistdisabled
PAR_CTL_1_VIS_STEP1listdisabled
PAR_CTL_1_VIS_STEP2listdisabled
PAR_CTL_1_VIS_STEP3listdisabled
PAR_CTL_1_VIS_ONE_STEPlistdisabled
PAR_CTL_1_SEND_CYCLIC_ACTlistdisabled
Hysteresis (symmetrical)list50 µg/m3
PAR_CTL_1_ACTUATING_VAL_FORMATlistswitching command
PAR_CTL_1_OUT_GO_NUMBERunsignedInt 0…2550
PAR_CTL_1_SEND_BY_CHANGE_FORMATunsignedInt 0…2550
PAR_CTL_1_OUTPUT_ACTlistdisabled
VOC threshold 1list1000 µg/m3
VOC threshold 2listthreshold 1 + 500 µg/m3
VOC threshold 3listthreshold 2 + 1000 µg/m3
Set-pointlist1000 µg/m3
Proportional bandlist500 µg/m3
Reset time (15...240 min)list15 min.
Min. control valuelist0%
Min. control valuelist0
Max. control valuelist100%
Max. control valuelist255
send control value cyclicallylistevery minute
Relative humidity sensorlistdisabled
Value offsetlist0%
PAR_DUMMY_PB_SENSOR_2_SETTINGSBLOCK_30unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_2_SETTINGSBLOCK_30unsignedInt 0…2551
Error humidity sensorlistdon't notify
PAR_SENSOR_2_BUS_CALIBRATION_USElistno
PAR_DUMMY_PB_SENSOR_2_SETTINGSBLOCK_50unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_2_SETTINGSBLOCK_50unsignedInt 0…2551
Send relative humidity when changinglistdisabled
Send relative humidity cyclicallylistdisabled
PAR_DUMMY_PB_SENSOR_2_SETTINGSBLOCK_60unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_2_SETTINGSBLOCK_60unsignedInt 0…2551
Send rH min/max values when changinglistdisabled
Send rH min/max values cyclicallylistdisabled
Control typelistdisabled
PAR_CTL_2_ACTlistdisabled
PAR_CTL_2_VIS_STEP1listdisabled
PAR_CTL_2_VIS_STEP2listdisabled
PAR_CTL_2_VIS_STEP3listdisabled
PAR_CTL_2_VIS_ONE_STEPlistdisabled
PAR_CTL_2_SEND_CYCLIC_ACTlistdisabled
Hysteresis (symmetrical)list5%
PAR_CTL_2_ACTUATING_VAL_FORMATlistswitching command
PAR_CTL_2_OUT_GO_NUMBERunsignedInt 0…2550
PAR_CTL_2_SEND_BY_CHANGE_FORMATunsignedInt 0…2550
PAR_CTL_2_Output_ACTlistdisabled
rH threshold 1list20%
rH threshold 2listthreshold 1 + 10%
rH threshold 3listthreshold 2 + 10%
Set-point (10...95%rH)list30%
Proportional band (10...40%rH)list20%
Reset time (15...240 min.)list15 min.
Value 2listabsolute humidity in [g/m3] via bus (communication object)
Temperature sensorlistdisabled
Value offset [0,1K], (-5K...+5K)signedInt -50…500
PAR_DUMMY_PB_SENSOR_3_SETTINGSBLOCK_30unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_3_SETTINGSBLOCK_30unsignedInt 0…2551
Error temperature sensorlistdon't notify
PAR_SENSOR_3_BUS_CALIBRATION_USElistno
PAR_DUMMY_PB_SENSOR_3_SETTINGSBLOCK_50unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_3_SETTINGSBLOCK_50unsignedInt 0…2551
Send temperature when changinglistdisabled
Send temperature cyclicallylistdisabled
PAR_DUMMY_PB_SENSOR_3_SETTINGSBLOCK_60unsignedInt 0…2551
PAR_DUMMY_HELP_PB_SENSOR_3_SETTINGSBLOCK_60unsignedInt 0…2551
Send min/max temperature values when changinglistdisabled
Send min/max temperature values cyclicallylistdisabled
Frost alarmlistdisabled
Frost alarm when temperaturelist<1°C
Send frost alarm when change of statuslistdisabled
Send frost alarm cyclicallylistdisabled
Heat alarmlistdisabled
Heat alarm when temperaturelist>30°C
Send heat alarm when change of statuslistdisabled
Send heat alarm cyclicallylistdisabled
Select heating and/or coolinglistinactive
PAR_RTR_ACTlistdisabled
PAR_RTR_ACT_MAIN_ST_HEATlistdisabled
PAR_RTR_ACT_MAIN_ST_COOLlistdisabled
Extra level heating enablelistdisabled
Guide heatinglistdisabled
Heating demand for displaylistno
Extra level cooling enablelistdisabled
Guide coolinglistdisabled
Cooling demand for displaylistno
Operating mode after resetlistComfort
PAR_RTR_GUIDING_ACTlistdisabled
Blocking object heating mode: enablelistdisabled
Blocking object cooling mode: enablelistdisabled
Blocking object extra level heating: enablelistdisabled
Blocking object extra level cooling: enablelistdisabled
Temperature measurement value 1listinternal sensor
Temperature measurement value 2listdisabled
Comfort temperature [0,1°C], (18…30°C)unsignedInt 180…300180
Standby setback heating [0,1K], (0..10K)unsignedInt 0…1000
Eco setback heating [0,1K], (0..10K)unsignedInt 0…1000
Standby increment cooling [0,1K], (0..10K)unsignedInt 0…1000
Eco increment cooling [0,1K], (0..10K)unsignedInt 0…1000
Interval to main level heating [0,1K], (0...-10K)signedInt -100…0-10
Interval to main level cooling [0,1K], (0...10K)unsignedInt 0…10010
Send set-point temperature when changinglistdisabled
Send set-point temperature cyclicallylistdisabled
Dead zone between heating and cooling [0,1K], (0...10K)unsignedInt 0…10020
Min. guide value heating (-50°C...+50°C)signedInt -50…500
Max. guide value heating (-50°C...+50°C)signedInt -50…500
Max. increment of set-point for min. guide value heating (0K...+10K)signedInt 0…100
Min. guide value cooling (-50°C...+50°C)signedInt -50…500
Max. guide value cooling (-50°C...+50°C)signedInt -50…500
Max. setback of set-point for max. guide value cooling (0K…+10K)signedInt 0…100
Control typelistPI
Control direction of control valuelistnormal
Proportional band (1...8K)unsignedInt 1…85
Hysteresis (symmetrical) [0,1K], (0,5...5K)unsignedInt 5…505
PWM cycle (5...30Min)unsignedInt 5…305
PAR_SEP_RTR_MAIN_ST_HEAT_40unsignedInt 0…2551
Send control value when changinglistenabled
Send control value when blockedlistdon't send
Control value when blockedlist0%
Control value when blockedunsignedInt 0…2550
Control value when blockedlistoff
PAR_SEP_RTR_EXTRA_ST_HEAT_40unsignedInt 0…2551
PAR_SEP_RTR_MAIN_ST_COOL_40unsignedInt 0…2551
PAR_SEP_RTR_EXTRA_ST_COOL_40unsignedInt 0…2551
Dew point sensorlistdisabled
Dend dew point temp. when changinglistdisabled
Send dew point temp. cyclicallylistdisabled
Dew point alarmlistdisabled
Dew point alarm advancelist1K
Dew point alarm hysteresis (symmetrical)list1K hysteresis
Send dew point alarm when change of statuslistdisabled
Send dew point alarm cyclicallylistdisabled
Type of telegram for dew point alarmlistswitching command
Switching command when dew point alarmlistoff
Priority when dew point alarmliststop priority
Percent when dew point alarm (0…100%)unsignedInt 0…1000
Value when dew point alarm (0…255)unsignedInt 0…2550
Scene when dew point alarm (1...64)unsignedInt 1…641
Switching command at the end of dew point alarmlistoff
Priority at the end of dew point alarmliststop priority
Percent at the end of dew point alarm (0…100%)unsignedInt 0…1000
Value at the end of dew point alarm (0…255)unsignedInt 0…2550
Scene at the end of dew point alarm (1…64)unsignedInt 1…641
Air pressure sensorlistdisabled
Error air pressure sensorlistdon't notify
Send absolute air pressure when changinglistdisabled
Send absolute air pressure cyclicallylistdisabled
Send relative air pressure when changinglistdisabled
Send relative air pressure cyclicallylistdisabled
PAR_P_ACT_PRELlistdisabled
Height [m. a. s. l.] (0…5000m)unsignedInt 0…5000700
PAR_VAVR_VIEWlistdisabled
PAR_VAVR_ACTlistdisabled
PAR_VAVR_MAIN_HEAT_VISIBLElistdisabled
PAR_VAVR_MAIN_COOL_VISIBLElistdisabled
PAR_VAVR_EXTRA_HEAT_VISIBLElistdisabled
PAR_VAVR_EXTRA_COOL_VISIBLElistdisabled
VOC control includelistdisabled
Particulate matter control includelistdisabled
Relative humidity control includelistdisabled
Main level heating includelistdisabled
Extra level heating includelistdisabled
Main level cooling includelistdisabled
Extra level cooling includelistdisabled
No PI control or external value activetext<--- Info
External object includelistdisabled
PAR_SEP_VAVR_30unsignedInt 0…2551
PAR_SEP_VAVR_30_WENN_CHOOSEunsignedInt 0…2551
Send VAVC control value when changinglistdisabled
Send VAVC control value cyclicallylistdisabled
PAR_SEP_VAVR_40unsignedInt 0…2551
PAR_SEP_VAVR_40_WENN_CHOOSEunsignedInt 0…2551

Version history

ApplicationApp noFingerprintFirst seenSizeFile
GS70, GS60, GS20, GS10, TS10 knx 1.0 latest$70009FB12026-11-25122 KBDownload

About this file

This is the official ETS product database for the Hugo Müller GmbH & Co KG [GS70, GS60, GS20, GS10, TS10 knx] Room climate control and air quality sensors (GS70, GS60, GS20, GS10, TS10 knx), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.