KNX Database
GVS CHAQ-03/55.2.0x KNX CO2 sensor,55mm

KNX CO2 sensor,55mm CHAQ-03/55.2.0x

GVS · Order number CHAQ-03/55.2.0x · Sensor › Air quality

Download .knxprod Temperature/Humidity/CO2 sensor with controller/1.0 1.0 · 190 KB

Product

ManufacturerGVS
Product nameKNX CO2 sensor,55mm
Order numberCHAQ-03/55.2.0x
HardwareKNX CO2 sensor,55mm
MediumTwisted Pair
Bus current (mA)17
Rail mountedNo
RegistrationCertified · 2023-11-02
Languagesde-DE, en-US
Catalog entryM-0085_H-CH23EA-1_HP-009A-10-3AB3_CI-CHAQ.2D03.2F55.2E2.2E0x-1
Fingerprint3AB3
SHA-256cb94756aca49225572a809ae2ef185fa293d36f5f489b5e12fd03a8b40b20eec
First seen2026-11-25
Markets69 markets

Application program: Temperature/Humidity/CO2 sensor with controller/1.0 1.0

Application number$009A
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureYes
Minimum ETS version5.0
Parameters386
Group objects231
Group objects (231)
NoNameFunctionSizeDPTFlags
0RTC 1 - {{0:...}}Power on/off 1 Bit1.1 switchCRW
0RTC 2 - {{0:...}}Power on/off 1 Bit1.1 switchCRW
0RTC 3 - {{0:...}}Power on/off 1 Bit1.1 switchCRW
1GeneralIn operation1 Bit1.1 switchCRT
1RTC 1 - {{0:...}}External temperature sensor2 Bytes9.1 temperature (°C)CWTU
1RTC 2 - {{0:...}}External temperature sensor2 Bytes9.1 temperature (°C)CWTU
1RTC 3 - {{0:...}}External temperature sensor2 Bytes9.1 temperature (°C)CWTU
2GeneralAlarm input1 Bit1.5 alarmCWTU
2RTC 1 - {{0:...}}Base setpoint adjustment2 Bytes9.1 temperature (°C)CW
2RTC 1 - {{0:...}}Current setpoint adjustment2 Bytes9.1 temperature (°C)CW
2RTC 2 - {{0:...}}Base setpoint adjustment2 Bytes9.1 temperature (°C)CW
2RTC 2 - {{0:...}}Current setpoint adjustment2 Bytes9.1 temperature (°C)CW
2RTC 3 - {{0:...}}Base setpoint adjustment2 Bytes9.1 temperature (°C)CW
2RTC 3 - {{0:...}}Current setpoint adjustment2 Bytes9.1 temperature (°C)CW
3GeneralAlarm acknowledge1 Bit1.16 acknowledgeCW
3RTC 1 - {{0:...}}Setpoint offset1 Bit1.7 stepCW
3RTC 2 - {{0:...}}Setpoint offset1 Bit1.7 stepCW
3RTC 3 - {{0:...}}Setpoint offset1 Bit1.7 stepCW
4RTC 1 - {{0:...}}Float offset value2 Bytes9.2 temperature difference (K)CW
4RTC 2 - {{0:...}}Float offset value2 Bytes9.2 temperature difference (K)CW
4RTC 3 - {{0:...}}Float offset value2 Bytes9.2 temperature difference (K)CW
5Internal sensorTemperature value2 Bytes9.1 temperature (°C)CRT
5RTC 1 - {{0:...}}Setpoint offset reset1 Bit1.15 resetCW
5RTC 2 - {{0:...}}Setpoint offset reset1 Bit1.15 resetCW
5RTC 3 - {{0:...}}Setpoint offset reset1 Bit1.15 resetCW
6Internal sensorLow temperature alarm1 Bit1.5 alarmCRT
6RTC 1 - {{0:...}}Heating/Cooling mode1 Bit1.100 cooling/heatingCW
6RTC 2 - {{0:...}}Heating/Cooling mode1 Bit1.100 cooling/heatingCW
6RTC 3 - {{0:...}}Heating/Cooling mode1 Bit1.100 cooling/heatingCW
7Internal sensorHigh temperature alarm1 Bit1.5 alarmCRT
7RTC 1 - {{0:...}}Operation mode1 Byte20.102 HVAC modeCW
7RTC 2 - {{0:...}}Operation mode1 Byte20.102 HVAC modeCW
7RTC 3 - {{0:...}}Operation mode1 Byte20.102 HVAC modeCW
8Internal sensorHumidity value2 Bytes9.7 humidity (%)CRT
8RTC 1 - {{0:...}}Comfort mode1 Bit1.3 enableCW
8RTC 2 - {{0:...}}Comfort mode1 Bit1.3 enableCW
8RTC 3 - {{0:...}}Comfort mode1 Bit1.3 enableCW
9Internal sensorLow humidity alarm1 Bit1.5 alarmCRT
9RTC 1 - {{0:...}}Economy mode1 Bit1.3 enableCW
9RTC 2 - {{0:...}}Economy mode1 Bit1.3 enableCW
9RTC 3 - {{0:...}}Economy mode1 Bit1.3 enableCW
10Internal sensorHigh humidity alarm1 Bit1.5 alarmCRT
10RTC 1 - {{0:...}}Frost/Heat protection mode1 Bit1.3 enableCW
10RTC 2 - {{0:...}}Frost/Heat protection mode1 Bit1.3 enableCW
10RTC 3 - {{0:...}}Frost/Heat protection mode1 Bit1.3 enableCW
11Internal sensorCO2 value2 Bytes9.8 parts/million (ppm)CRT
11RTC 1 - {{0:...}}Standby mode1 Bit1.3 enableCW
11RTC 2 - {{0:...}}Standby mode1 Bit1.3 enableCW
11RTC 3 - {{0:...}}Standby mode1 Bit1.3 enableCW
12Internal sensorCO2 error report1 Bit1.2 booleanCRT
12RTC 1 - {{0:...}}Extended comfort mode1 Bit1.16 acknowledgeCW
12RTC 2 - {{0:...}}Extended comfort mode1 Bit1.16 acknowledgeCW
12RTC 3 - {{0:...}}Extended comfort mode1 Bit1.16 acknowledgeCW
13Internal sensorLow CO2 alarm1 Bit1.5 alarmCRT
13RTC 1 - {{0:...}}Fan automatic operation1 Bit1.3 enableCW
13RTC 2 - {{0:...}}Fan automatic operation1 Bit1.3 enableCW
13RTC 3 - {{0:...}}Fan automatic operation1 Bit1.3 enableCW
14Internal sensorHigh CO2 alarm1 Bit1.5 alarmCRT
14RTC 1 - {{0:...}}Window contact1 Bit1.19 window/doorCWU
14RTC 2 - {{0:...}}Window contact1 Bit1.19 window/doorCWU
14RTC 3 - {{0:...}}Window contact1 Bit1.19 window/doorCWU
15RTC 1 - {{0:...}}Presence detector1 Bit1.18 occupancyCWU
15RTC 2 - {{0:...}}Presence detector1 Bit1.18 occupancyCWU
15RTC 3 - {{0:...}}Presence detector1 Bit1.18 occupancyCWU
16RTC 1 - {{0:...}}Heating/Cooling mode, status1 Bit1.100 cooling/heatingCRT
16RTC 2 - {{0:...}}Heating/Cooling mode, status1 Bit1.100 cooling/heatingCRT
16RTC 3 - {{0:...}}Heating/Cooling mode, status1 Bit1.100 cooling/heatingCRT
17RTC 1 - {{0:...}}Operation mode, status1 Byte20.102 HVAC modeCRT
17RTC 2 - {{0:...}}Operation mode, status1 Byte20.102 HVAC modeCRT
17RTC 3 - {{0:...}}Operation mode, status1 Byte20.102 HVAC modeCRT
18RTC 1 - {{0:...}}Comfort mode, status1 Bit1.3 enableCRT
18RTC 2 - {{0:...}}Comfort mode, status1 Bit1.3 enableCRT
18RTC 3 - {{0:...}}Comfort mode, status1 Bit1.3 enableCRT
19RTC 1 - {{0:...}}Economy mode, status1 Bit1.3 enableCRT
19RTC 2 - {{0:...}}Economy mode, status1 Bit1.3 enableCRT
19RTC 3 - {{0:...}}Economy mode, status1 Bit1.3 enableCRT
20RTC 1 - {{0:...}}Frost/Heat protection mode, status1 Bit1.3 enableCRT
20RTC 2 - {{0:...}}Frost/Heat protection mode, status1 Bit1.3 enableCRT
20RTC 3 - {{0:...}}Frost/Heat protection mode, status1 Bit1.3 enableCRT
21RTC 1 - {{0:...}}Standby mode, status1 Bit1.3 enableCRT
21RTC 2 - {{0:...}}Standby mode, status1 Bit1.3 enableCRT
21RTC 3 - {{0:...}}Standby mode, status1 Bit1.3 enableCRT
22RTC 1 - {{0:...}}Actual temperature, status2 Bytes9.1 temperature (°C)CRT
22RTC 2 - {{0:...}}Actual temperature, status2 Bytes9.1 temperature (°C)CRT
22RTC 3 - {{0:...}}Actual temperature, status2 Bytes9.1 temperature (°C)CRT
23Input 1 - {{0:Temperature probe}}Actual temperature, Sensor2 Bytes9.1 temperature (°C)CRT
23Input 1 - {{0:Switch sensor}}Switch1 Bit1.1 switchCRWTU
23Input 1 - {{0:Switch sensor}}Close, Switch1 Bit1.1 switchCRWTU
23Input 1 - {{0:Switch sensor}}Short, Switch1 Bit1.1 switchCRWTU
23Input 1 - {{0:Scene control}}Scene1 Byte18.1 scene controlCT
23Input 1 - {{0:Scene control}}Close, Scene1 Byte18.1 scene controlCT
23Input 1 - {{0:Scene control}}Short, Scene1 Byte18.1 scene controlCT
23Input 1 - {{0:Send String}}String14 Bytes16.1 Character String (ISO 8859-1)CT
23Input 1 - {{0:Send String}}Close, String14 Bytes16.1 Character String (ISO 8859-1)CT
23Input 1 - {{0:Send String}}Short, String14 Bytes16.1 Character String (ISO 8859-1)CT
23RTC 1 - {{0:...}}Base temperature setpoint, status2 Bytes9.1 temperature (°C)CRT
23RTC 2 - {{0:...}}Base temperature setpoint, status2 Bytes9.1 temperature (°C)CRT
23RTC 3 - {{0:...}}Base temperature setpoint, status2 Bytes9.1 temperature (°C)CRT
24Input 1 - {{0:Temperature probe}}Temperature error report, Sensor1 Bit1.5 alarmCRT
24Input 1 - {{0:Switch sensor}}Open, Switch1 Bit1.1 switchCRWTU
24Input 1 - {{0:Switch sensor}}Long, Switch1 Bit1.1 switchCRWTU
24Input 1 - {{0:Scene control}}Open, Scene1 Byte18.1 scene controlCT
24Input 1 - {{0:Scene control}}Long, Scene1 Byte18.1 scene controlCT
24Input 1 - {{0:Send String}}Open, String14 Bytes16.1 Character String (ISO 8859-1)CT
24Input 1 - {{0:Send String}}Long, String14 Bytes16.1 Character String (ISO 8859-1)CT
24RTC 1 - {{0:...}}Setpoint offset, status2 Bytes9.2 temperature difference (K)CRT
24RTC 2 - {{0:...}}Setpoint offset, status2 Bytes9.2 temperature difference (K)CRT
24RTC 3 - {{0:...}}Setpoint offset, status2 Bytes9.2 temperature difference (K)CRT
25Input 1 - {{0:Switch sensor}}Disable1 Bit1.3 enableCW
25Input 1 - {{0:Scene control}}Disable1 Bit1.3 enableCW
25Input 1 - {{0:Send String}}Disable1 Bit1.3 enableCW
25RTC 1 - {{0:...}}Current temperature setpoint, status2 Bytes9.1 temperature (°C)CRT
25RTC 2 - {{0:...}}Current temperature setpoint, status2 Bytes9.1 temperature (°C)CRT
25RTC 3 - {{0:...}}Current temperature setpoint, status2 Bytes9.1 temperature (°C)CRT
26Input 2 - {{0:Temperature probe}}Actual temperature, Sensor2 Bytes9.1 temperature (°C)CRT
26Input 2 - {{0:Switch sensor}}Switch1 Bit1.1 switchCRWTU
26Input 2 - {{0:Switch sensor}}Close, Switch1 Bit1.1 switchCRWTU
26Input 2 - {{0:Switch sensor}}Short, Switch1 Bit1.1 switchCRWTU
26Input 2 - {{0:Scene control}}Scene1 Byte18.1 scene controlCT
26Input 2 - {{0:Scene control}}Close, Scene1 Byte18.1 scene controlCT
26Input 2 - {{0:Scene control}}Short, Scene1 Byte18.1 scene controlCT
26Input 2 - {{0:Send String}}String14 Bytes16.1 Character String (ISO 8859-1)CT
26Input 2 - {{0:Send String}}Close, String14 Bytes16.1 Character String (ISO 8859-1)CT
26Input 2 - {{0:Send String}}Short, String14 Bytes16.1 Character String (ISO 8859-1)CT
26RTC 1 - {{0:...}}Heating control value1 Bit1.1 switchCRT
26RTC 1 - {{0:...}}Heating control value1 Byte5.1 percentage (0..100%)CRT
26RTC 1 - {{0:...}}Heating/Cooling control value1 Bit1.1 switchCRT
26RTC 1 - {{0:...}}Heating/Cooling control value1 Byte5.1 percentage (0..100%)CRT
26RTC 2 - {{0:...}}Heating control value1 Bit1.1 switchCRT
26RTC 2 - {{0:...}}Heating control value1 Byte5.1 percentage (0..100%)CRT
26RTC 2 - {{0:...}}Heating/Cooling control value1 Bit1.1 switchCRT
26RTC 2 - {{0:...}}Heating/Cooling control value1 Byte5.1 percentage (0..100%)CRT
26RTC 3 - {{0:...}}Heating control value1 Bit1.1 switchCRT
26RTC 3 - {{0:...}}Heating control value1 Byte5.1 percentage (0..100%)CRT
26RTC 3 - {{0:...}}Heating/Cooling control value1 Bit1.1 switchCRT
26RTC 3 - {{0:...}}Heating/Cooling control value1 Byte5.1 percentage (0..100%)CRT
27Input 2 - {{0:Temperature probe}}Temperature error report, Sensor1 Bit1.5 alarmCRT
27Input 2 - {{0:Switch sensor}}Open, Switch1 Bit1.1 switchCRWTU
27Input 2 - {{0:Switch sensor}}Long, Switch1 Bit1.1 switchCRWTU
27Input 2 - {{0:Scene control}}Open, Scene1 Byte18.1 scene controlCT
27Input 2 - {{0:Scene control}}Long, Scene1 Byte18.1 scene controlCT
27Input 2 - {{0:Send String}}Open, String14 Bytes16.1 Character String (ISO 8859-1)CT
27Input 2 - {{0:Send String}}Long, String14 Bytes16.1 Character String (ISO 8859-1)CT
27RTC 1 - {{0:...}}Cooling control value1 Bit1.1 switchCRT
27RTC 1 - {{0:...}}Cooling control value1 Byte5.1 percentage (0..100%)CRT
27RTC 2 - {{0:...}}Cooling control value1 Bit1.1 switchCRT
27RTC 2 - {{0:...}}Cooling control value1 Byte5.1 percentage (0..100%)CRT
27RTC 3 - {{0:...}}Cooling control value1 Bit1.1 switchCRT
27RTC 3 - {{0:...}}Cooling control value1 Byte5.1 percentage (0..100%)CRT
28Input 2 - {{0:Switch sensor}}Disable1 Bit1.3 enableCW
28Input 2 - {{0:Scene control}}Disable1 Bit1.3 enableCW
28Input 2 - {{0:Send String}}Disable1 Bit1.3 enableCW
28RTC 1 - {{0:...}}Fan speed1 Byte5.100 fan stage (0..255)CT
28RTC 1 - {{0:...}}Fan speed1 Byte5.1 percentage (0..100%)CT
28RTC 2 - {{0:...}}Fan speed1 Byte5.100 fan stage (0..255)CT
28RTC 2 - {{0:...}}Fan speed1 Byte5.1 percentage (0..100%)CT
28RTC 3 - {{0:...}}Fan speed1 Byte5.100 fan stage (0..255)CT
28RTC 3 - {{0:...}}Fan speed1 Byte5.1 percentage (0..100%)CT
29RTC 1 - {{0:...}}Fan speed low1 Bit1.1 switchCT
29RTC 2 - {{0:...}}Fan speed low1 Bit1.1 switchCT
29RTC 3 - {{0:...}}Fan speed low1 Bit1.1 switchCT
30RTC 1 - {{0:...}}Fan speed medium1 Bit1.1 switchCT
30RTC 2 - {{0:...}}Fan speed medium1 Bit1.1 switchCT
30RTC 3 - {{0:...}}Fan speed medium1 Bit1.1 switchCT
31RTC 1 - {{0:...}}Fan speed high1 Bit1.1 switchCT
31RTC 2 - {{0:...}}Fan speed high1 Bit1.1 switchCT
31RTC 3 - {{0:...}}Fan speed high1 Bit1.1 switchCT
32RTC 1 - {{0:...}}Fan speed off1 Bit1.1 switchCT
32RTC 2 - {{0:...}}Fan speed off1 Bit1.1 switchCT
32RTC 3 - {{0:...}}Fan speed off1 Bit1.1 switchCT
33RTC 1 - {{0:...}}Additional heating control value1 Byte5.1 percentage (0..100%)CRT
33RTC 1 - {{0:...}}Additional heating control value1 Bit1.1 switchCRT
33RTC 1 - {{0:...}}Additional heating/cooling control value1 Byte5.1 percentage (0..100%)CRT
33RTC 1 - {{0:...}}Additional heating/cooling control value1 Bit1.1 switchCRT
33RTC 2 - {{0:...}}Additional heating control value1 Byte5.1 percentage (0..100%)CRT
33RTC 2 - {{0:...}}Additional heating control value1 Bit1.1 switchCRT
33RTC 2 - {{0:...}}Additional heating/cooling control value1 Byte5.1 percentage (0..100%)CRT
33RTC 2 - {{0:...}}Additional heating/cooling control value1 Bit1.1 switchCRT
33RTC 3 - {{0:...}}Additional heating control value1 Byte5.1 percentage (0..100%)CRT
33RTC 3 - {{0:...}}Additional heating control value1 Bit1.1 switchCRT
33RTC 3 - {{0:...}}Additional heating/cooling control value1 Byte5.1 percentage (0..100%)CRT
33RTC 3 - {{0:...}}Additional heating/cooling control value1 Bit1.1 switchCRT
34RTC 1 - {{0:...}}Additional cooling control value1 Byte5.1 percentage (0..100%)CRT
34RTC 1 - {{0:...}}Additional cooling control value1 Bit1.1 switchCRT
34RTC 2 - {{0:...}}Additional cooling control value1 Byte5.1 percentage (0..100%)CRT
34RTC 2 - {{0:...}}Additional cooling control value1 Bit1.1 switchCRT
34RTC 3 - {{0:...}}Additional cooling control value1 Byte5.1 percentage (0..100%)CRT
34RTC 3 - {{0:...}}Additional cooling control value1 Bit1.1 switchCRT
134Relative humidity LevelExternal sensor value 12 Bytes9.7 humidity (%)CWTU
135Relative humidity LevelExternal sensor value 22 Bytes9.7 humidity (%)CWTU
136Relative humidity LevelExternal sensor value 32 Bytes9.7 humidity (%)CWTU
137Relative humidity LevelActual sensor value2 Bytes9.7 humidity (%)CRT
138Relative humidity LevelOutput value3 Bytes232.600 RGB value 3x(0..255)CRT
138Relative humidity LevelOutput value1 Byte5.10 counter pulses (0..255)CRT
138Relative humidity LevelOutput value1 Byte5.1 percentage (0..100%)CRT
138Relative humidity LevelOutput value1 Byte17.1 scene numberCRT
138Relative humidity LevelOutput value of level 11 Bit1.1 switchCRT
139Relative humidity LevelOutput value of level 21 Bit1.1 switchCRT
140Relative humidity LevelOutput value of level 31 Bit1.1 switchCRT
141Relative humidity LevelOutput value of level 41 Bit1.1 switchCRT
142Relative humidity LevelAlarm message14 Bytes16.1 Character String (ISO 8859-1)CT
143CO2 LevelExternal sensor value 12 Bytes9.8 parts/million (ppm)CWTU
144CO2 LevelExternal sensor value 22 Bytes9.8 parts/million (ppm)CWTU
145CO2 LevelExternal sensor value 32 Bytes9.8 parts/million (ppm)CWTU
146CO2 LevelActual sensor value2 Bytes9.8 parts/million (ppm)CRT
147CO2 LevelOutput value of level 11 Bit1.1 switchCRT
147CO2 LevelOutput value1 Byte5.1 percentage (0..100%)CRT
147CO2 LevelOutput value1 Byte5.10 counter pulses (0..255)CRT
147CO2 LevelOutput value1 Byte17.1 scene numberCRT
147CO2 LevelOutput value3 Bytes232.600 RGB value 3x(0..255)CRT
148CO2 LevelOutput value of level 21 Bit1.1 switchCRT
149CO2 LevelOutput value of level 31 Bit1.1 switchCRT
150CO2 LevelOutput value of level 41 Bit1.1 switchCRT
151CO2 LevelAlarm message14 Bytes16.1 Character String (ISO 8859-1)CT
170Relative humidity controllerController on/off1 Bit1.1 switchCW
172Relative humidity controllerExternal sensor value2 Bytes9.7 humidity (%)CWTU
173Relative humidity controllerController status1 Bit1.1 switchCRT
174Relative humidity controllerActual sensor value2 Bytes9.7 humidity (%)CRT
175Relative humidity controllerControl value1 Byte5.10 counter pulses (0..255)CRT
175Relative humidity controllerControl value1 Byte5.1 percentage (0..100%)CRT
176Relative humidity controllerControl stop1 Byte5.10 counter pulses (0..255)CW
176Relative humidity controllerControl stop1 Byte5.1 percentage (0..100%)CW
177CO2 controllerController on/off1 Bit1.1 switchCW
178CO2 controllerSetpoint adjustment2 Bytes9.8 parts/million (ppm)CRW
179CO2 controllerExternal sensor value2 Bytes9.8 parts/million (ppm)CWTU
180CO2 controllerController status1 Bit1.1 switchCRT
181CO2 controllerActual sensor value2 Bytes9.8 parts/million (ppm)CRT
182CO2 controllerControl value1 Byte5.1 percentage (0..100%)CRT
182CO2 controllerControl value1 Byte5.10 counter pulses (0..255)CRT
183CO2 controllerControl stop1 Byte5.1 percentage (0..100%)CW
183CO2 controllerControl stop1 Byte5.10 counter pulses (0..255)CW
Parameters (268)
ParameterTypeDefault
Send delay after voltage recovery [0..15]unsignedInt 0…155
Send cycle of In operation telegram [1..240,0=inactive]unsignedInt 0…2400
Status object read request after restartunsignedInt 0…11
Input interfaceunsignedInt 0…10
Temperature calibrationlist0.0
Send temperature when the result change bylist1.0
Cyclically send temperature [0...255,0=inactive]unsignedInt 0…25510
Send alarm telegram for low/high temperaturelistNo respond
Threshold value for low temperature alarm [0..15]list0
Threshold value for high temperature alarm [30..45]list45
Humidity calibrationlist0
Send humidity when the result change by [0..20,0=inactive]unsignedInt 0…205
Cyclically send humidity [0..255,0=inactive]unsignedInt 0…25510
Send alarm telegram for low/high humiditylistNo respond
Threshold value for low humidity alarm [5..50]unsignedInt 5…505
Threshold value for high humidity alarm [55..85]unsignedInt 55…8585
Function of input 1listBI: Switch sensor
Function of input 2listDisable
Description (max 30char.)text
B value of temperature sensor (must refer to the characteristic of component)list3950
Cyclically send temperature [0...255]unsignedInt 0…2550
Reply error of sensor measurementlistNo respond
Object value of errorlist0=no error/1=error
Lower threshold value for error reportlist0
Upper threshold value for error reportlist60
Distinction between short and long operationlistNo
Reaction on close the contactlistTOGGLE
Reaction on open the contactlistNo reaction
Send object value after voltage recovery (valid if reaction is not toggle)listNo
Number of objectslist1
Long operation after [3..25]unsignedInt 3…255
Connected contact typelistNormally open
Reaction on short operationlistTOGGLE
Reaction on long operationlistNo reaction
Disable functionlistDisable
Reaction on close the contactlistRecall scene
8 bit scene numberlistScene No.1
Reaction on short operationlistRecall scene
Reaction on close the contactlistSend Value
String (14byte) valuetextHello, world !
Send object value after voltage recoverylistNo
Reaction on short operationlistSend Value
Room temperature controllerunsignedInt 0…10
Air Quality Level functionunsignedInt 0…10
Air Quality controllerunsignedInt 0…10
CO2 calibrationlist0
Send CO2 when the result changelist50
Cyclically send CO2 [0..255,0=inactive]unsignedInt 0…25510
Threshold value for low CO2 alarm [400..2000]unsignedInt 400…2000400
Threshold value for high CO2 alarm [400..2000]unsignedInt 400…20002000
Report error when sensor failureunsignedInt 0…10
Send alarm telegram for low/high CO2listNo respond
RTC 1unsignedInt 0…10
RTC 2unsignedInt 0…10
RTC 3unsignedInt 0…10
Relative humidity level functionlistDisable
Reference internal sensorunsignedInt 0…11
Number of reference external sensorlist0
Number of reference external sensorlist1
Calculation typelistWeight average
Weighting of internal sensorlist50
Weighting of external sensor 1list20
Weighting of external sensor 2list20
Weighting of external sensor 3list10
Time period for request external sensor [0...255,0=inactive]unsignedInt 0…25510
Send value when the result change bylist5
Cyclically send value [0..255,0=inactive]unsignedInt 0…2550
Control typelist1bit
Object datatypelist1byte percentage value
Cyclically send output value [0..255,0=inactive]unsignedInt 0…2550
Hysteresis threshold value in +/- [1..10]list5
Send additional alarm messageunsignedInt 0…10
Threshold value 1 for level 1unsignedInt 0…10020
Threshold value 2 for level 2unsignedInt 0…10040
Threshold value 3 for level 3unsignedInt 0…10050
Threshold value 4 for level 4unsignedInt 0…10060
If humidity value < threshold value 1, sendlistOFF
If humidity value >= threshold value 1, sendlistON
If sensor failure, sendlistNothing
If humidity value < threshold value 2, sendlistOFF
If humidity value >= threshold value 2, sendlistON
If humidity value < threshold value 3, sendlistOFF
If humidity value >= threshold value 3, sendlistON
If humidity value < threshold value 4, sendlistOFF
If humidity value >= threshold value 4, sendlistON
Threshold value 1 (Level 1<->Level 2)unsignedInt 0…10020
Threshold value 2 (Level 2<->Level 3)unsignedInt 0…10040
Threshold value 3 (Level 3<->Level 4)unsignedInt 0…10050
If humidity value < threshold value 1, sendlistSend value
Valuelist0
ValueunsignedInt 0…2550
ValuelistScene No.1
Valuecolor#00FF00
Alarm messagetextAlarm 1
If threshold value 1 <= humidity value < threshold value 2, sendlistSend value
Valuelist33
ValueunsignedInt 0…2551
ValuelistScene No.2
Valuecolor#FFFF00
Alarm messagetextAlarm 2
If threshold value 2 <= humidity value < threshold value 3, sendlistSend value
Valuelist67
ValueunsignedInt 0…2552
ValuelistScene No.3
Valuecolor#FF8000
Alarm messagetextAlarm 3
If humidity value >= threshold value 3, sendlistSend value
Valuelist100
ValueunsignedInt 0…2553
ValuelistScene No.4
Valuecolor#FF0000
Alarm messagetextAlarm 4
If humidity value >= threshold value 1, sendlistSend value
If humidity value >= threshold value 2, sendlistSend value
ValuelistScene No.5
CO2 level functionlistDisable
Send value when the result change bylist50
Hysteresis threshold value in +/- [50..300]unsignedInt 50…30050
Threshold value 1 for level 1unsignedInt 1…2000350
If CO2 value < threshold value 1, sendlistOFF
If CO2 value >= threshold value 1, sendlistON
Threshold value 2 for level 2unsignedInt 1…2000450
If CO2 value < threshold value 2, sendlistOFF
If CO2 value >= threshold value 2, sendlistON
Threshold value 3 for level 3unsignedInt 1…20001000
If CO2 value < threshold value 3, sendlistOFF
If CO2 value >= threshold value 3, sendlistON
Threshold value 4 for level 4unsignedInt 1…20001500
If CO2 value < threshold value 4, sendlistOFF
If CO2 value >= threshold value 4, sendlistON
Threshold value 1 (Level 1<->Level 2)unsignedInt 1…2000350
Threshold value 2 (Level 2<->Level 3)unsignedInt 1…2000450
Threshold value 3 (Level 3<->Level 4)unsignedInt 1…20001000
If CO2 value < threshold value 1, sendlistSend value
If threshold value 1 <= CO2 value < threshold value 2, sendlistSend value
If threshold value 2 <= CO2 value < threshold value 3, sendlistSend value
If CO2 value >= threshold value 3, sendlistSend value
Relative humidity controller functionlistDisable
Relative humidity reference fromlistInternal sensor
Combination ratiolist50% Internal to 50% External
Control typelist1byte
Cyclically send control value [0..255,0=inactive]unsignedInt 0…2550
Control value for step 0list0
Control value for step 0unsignedInt 0…2550
Control value for step 1list33
Control value for step 1unsignedInt 0…2551
Control value for step 2list67
Control value for step 2unsignedInt 0…2552
Control value for step 3list100
Control value for step 3unsignedInt 0…2553
Threshold value 1 (step 0<->step 1)unsignedInt 0…10020
Threshold value 2 (step 1<->step 2)unsignedInt 0…10040
Threshold value 3 (step 2<->step 3)unsignedInt 0…10050
Minimum time in step control [0..65535]unsignedInt 0…655350
If sensor failure, sendlist0
If sensor failure, sendunsignedInt 0…2550
Stop functionunsignedInt 0…10
Controller automatically restart after [0..255,0=inactive]unsignedInt 0…2550
Behaviour when controller offlistNothing
CO2 controller functionlistDisable
CO2 reference fromlistInternal sensor
Threshold value 1 (step 0<->step 1)unsignedInt 1…2000350
Threshold value 2 (step 1<->step 2)unsignedInt 1…2000450
Threshold value 3 (step 2<->step 3)unsignedInt 1…20001000
Setpoint CO2 valueunsignedInt 1…1500500
Setpoint value can be changed via busunsignedInt 0…10
Proportional rangelist100
Reset time [15..240]unsignedInt 15…24015
Minimum control valuelist0
Minimum control valueunsignedInt 0…2550
Maximum control valuelist100
Maximum control valueunsignedInt 0…255255
Sensor Failure Para display or notunsignedInt 0…10
Send value when the control value change by [0..100,0=inactive]list5
Send value when the control value change by [0..255,0=inactive]unsignedInt 0…25515
Control value lower than the minimum valuelist0%=0%, otherwise=Minimum value
Control value lower than the minimum valuelist0=0, otherwise=Minimum value
Alarm functionunsignedInt 0…10
Alarm tone time periodlist10s
Alarm tone time automatically repeat interval timelist1min
Acknowledge from buslistDisable
Room temperature reference fromlistInternal sensor
Time period for request room temperature sensor [0...255]unsignedInt 0…25510
Control value after temp. error[0..100] (if 2-point control, set value '0'=0, set value '>0'=1)unsignedInt 0…1000
Room temperature control modelistHeating
Heating/Cooling switchoverlistVia object
Heating/Cooling status after downloadlistHeating
Heating/Cooling status after voltage recoverylistAs before voltage failure
Room temperature control systemlist4 pipes system
Operation modeunsignedInt 0…10
Initial setpoint temperaturelist20.0
Temperature error tip_setpoint/MaxunsignedInt 0…10
Temperature error tip_setpoint/MinunsignedInt 0…10
Upper dead zonelist2.0
Lower dead zonelist2.0
Controller status after downloadlistComfort mode
Controller status after voltage recoverylistAs before voltage failure
Extended comfort mode [0..255,0=inactive]unsignedInt 0…2550
1 bit object function for operation modeunsignedInt 0…10
1 bit object for standby modeunsignedInt 0…11
Fan speed auto.control functionunsignedInt 0…10
Window contact input functionunsignedInt 0…10
Delay for window contact [0..65535]unsignedInt 0…6553515
Controller mode for open windowlistFrost/heat protection
Bus presence detector functionunsignedInt 0…10
Setpoint method for operating modelistAbsolute
Base setpoint temperaturelist20.0
Additional setpoint offset for setpoint adjustmentlistDisable
Step of setpoint offsetlist0.5K
Min. setpoint offset [-10..0]signedInt -10…0-5
Max. setpoint offset [0..10]unsignedInt 0…105
Reduced heating in standby mode [0..10]list2
Reduced heating in economy mode [0..10]list4
Setpoint temperature in frost protection mode [5..10]list7
Increased cooling in standby mode [0..10]list2
Increased cooling in economy mode [0..10]list4
Setpoint temperature in heat protection mode [30..37]list35
Min. setpoint temperature [5..37]list11
Max. setpoint temperature [5..37]list32
Setpoint temperature in comfort mode [5..37]list21
Setpoint temperature in standby mode [5..37]list19
Setpoint temperature in economy mode [5..37]list17
Setpoint temperature in comfort mode [5..37]list23
Setpoint temperature in standby mode [5..37]list25
Setpoint temperature in economy mode [5..37]list27
Minimum zone between heating and cooling setpointlist2.0
Type of heating controllistSwitching on/off(use 2-point control)
Invert control valuelistNo
Lower Hysteresis [0..200]unsignedInt 0…20010
Upper Hysteresis [0..200]unsignedInt 0…20010
PWM cycle time [1..255]unsignedInt 1…25515
Heating speedlistHot water heating(5K/150min)
Proportional range [10..100]unsignedInt 0…10040
Reset time [0..255]unsignedInt 0…255150
Send control value on change by [0..100,0=inactive]unsignedInt 0…1005
Cyclically send control value [0..255]unsignedInt 0…25510
Type of cooling controllistSwitching on/off(use 2-point control)
Cooling speedlistCooling ceiling (5K/240min)
Proportional range [10..100]unsignedInt 10…10040
Type of heating/cooling controllistSwitching on/off(use 2-point control)
Auto. operation on object valuelistAuto=1/Man.=0
Object datatype of 1byte fan speedlistPercentage (DPT_5.001)
Output value for fan speed lowunsignedInt 1…2551
Output value for fan speed mediumunsignedInt 1…2552
Output value for fan speed highunsignedInt 1…2553
Output value for fan speed lowunsignedInt 1…10033
Output value for fan speed mediumunsignedInt 1…10067
Output value for fan speed highunsignedInt 1…100100
1 bit object function for fan speedunsignedInt 0…10
1 bit object for fan speed offunsignedInt 0…10
Threshold value speed OFF<-->low [1..255]unsignedInt 1…25580
Threshold value speed low<-->medium [1..255]unsignedInt 1…255150
Threshold value speed medium<-->high [1..255]unsignedInt 1…255200
Hysteresis threshold value in +/-[0..50]unsignedInt 0…5010
Temperature difference speed OFF<-->low [1..200]unsignedInt 0…20020
Temperature difference speed low<-->medium [1..200]unsignedInt 0…20030
Temperature difference speed medium<-->high [1..200]unsignedInt 0…20040
Hysteresis temperature difference in [0..50]unsignedInt 0…5010
Minimum time in fan speed [0..65535]unsignedInt 0…6553560
Additional heatingunsignedInt 0…10
Invert control valueunsignedInt 0…10
Temperature difference to switch on additional heating [-100..-5]signedInt -100…-5-25
Hysteresis to switch off additional heating [-20..-1]signedInt -20…-1-5
Cyclically send control value [0..255]unsignedInt 0…2550
Additional coolingunsignedInt 0…10
Temperature difference to switch on additional cooling [5..100]unsignedInt 5…10025
Hysteresis to switch off additional cooling [1..20]unsignedInt 1…205
Additional heating/coolingunsignedInt 0…10

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Temperature/Humidity/CO2 sensor with controller/1.0 1.0 latest$009A3AB32026-11-25190 KBDownload

About this file

This is the official ETS product database for the GVS KNX CO2 sensor,55mm (CHAQ-03/55.2.0x), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from GVS

All GVS products