KNX Database
GVS 1ARCDx19BA ARCD-xx/16.2(xx=04/08/12)

ARCD-xx/16.2(xx=04/08/12) 1ARCDx19BA

GVS · Order number 1ARCDx19BA · Actuator › Switch

Switch Actuator with current detection,4/8/12-Fold

Download .knxprod Switch Actuator with current detection,4/8/12-Fold 2.0 · 218 KB

Product

ManufacturerGVS
Product nameARCD-xx/16.2(xx=04/08/12)
Order number1ARCDx19BA
Product textSwitch Actuator with current detection,4/8/12-Fold
HardwareARCD-xx/16.2
MediumTwisted Pair
Bus current (mA)12
Rail mountedYes
RegistrationCertified · 2019-04-19
Languagesen-US
Catalog entryM-0085_H-AR19BA-1_HP-0041-20-7F4A_CI-1ARCDx19BA-1
Fingerprint7F4A
SHA-256566de4d22c369ffe1fbe20f69763e62efdfbb420e6bb308b51df518f6d17d158
First seen2026-11-25
Markets69 markets

Application program: Switch Actuator with current detection,4/8/12-Fold 2.0

Application number$0041
Version2.0
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters1901
Group objects466
Group objects (466)
NoNameFunctionSizeDPTFlags
1GeneralIn operation1 Bit1.1 switchCRT
2GeneralSafety priority 11 Bit1.3 enableCWU
3GeneralSafety priority 21 Bit1.3 enableCWU
4Output AReply the switch status, A1 Bit1.1 switchCRT
4Output ASend the switch status, A1 Bit1.1 switchCRT
4Output AReply status of contact , A1 Bit1.1 switchCRT
5Output ASwitch, A1 Bit1.1 switchCW
5Output AOn-Off of regulating , A1 Bit1.1 switchCW
6Output AStatus (continuous),1 bit , A1 Bit1.1 switchCRT
6Output ASwitch out with delay, A1 Bit1.1 switchCW
6Output ASwitch out with flashing, A1 Bit1.1 switchCW
6Output AOutput of staircase lighting, A1 Bit1.1 switchCW
7Output ASwitch time function, A1 Bit1.3 enableCW
8Output AWarning of staircase , A1 Bit1.5 alarmCT
8Output AReport fault, regulating , A1 Bit1.5 alarmCRT
9Output ADuration of staircase , A2 Bytes7.5 time (s)CRW
10Output ACall preset 1/2 , A1 Bit1.22 sceneCW
11Output AStore preset 1/2, A1 Bit1.22 sceneCW
11Output ATrigger switch regularly , A1 Bit1.3 enableCW
12Output AInput 1 of logic , A1 Bit1.2 booleanCW
13Output AInput 2 of logic , A1 Bit1.2 booleanCW
14Output AStatus (continuous),1 byte, A1 Byte5.1 percentage (0..100%)CRT
14Output AScene handle, A1 Byte18.1 scene controlCW
15Output AContinuous of regulating , A1 Byte5.1 percentage (0..100%)CW
15Output AChange threshold 1, A1 Byte5.10 counter pulses (0..255)CW
16Output AThreshold input , A1 Byte5.10 counter pulses (0..255)CW
17Output AForced output , A1 Bit1.1 switchCW
17Output AForced output , A2 Bit2.1 switch controlCW
17Output AForced operation,regulating, A1 Bit1.3 enableCW
18Output BReply the switch status, B1 Bit1.1 switchCRT
18Output BSend the switch status, B1 Bit1.1 switchCRT
18Output BReply status of contact , B1 Bit1.1 switchCRT
19Output BSwitch, B1 Bit1.1 switchCW
19Output BOn-Off of regulating , B1 Bit1.1 switchCW
20Output BStatus (continuous),1 bit , B1 Bit1.1 switchCRT
20Output BSwitch out with delay, B1 Bit1.1 switchCW
20Output BSwitch out with flashing, B1 Bit1.1 switchCW
20Output BOutput of staircase lighting, B1 Bit1.1 switchCW
21Output BSwitch time function, B1 Bit1.3 enableCW
22Output BWarning of staircase , B1 Bit1.5 alarmCT
22Output BReport fault, regulating , B1 Bit1.5 alarmCRT
23Output BDuration of staircase , B2 Bytes7.5 time (s)CRW
24Output BCall preset 1/2 , B1 Bit1.22 sceneCW
25Output BStore preset 1/2, B1 Bit1.22 sceneCW
25Output BTrigger switch regularly , B1 Bit1.3 enableCW
26Output BInput 1 of logic , B1 Bit1.2 booleanCW
27Output BInput 2 of logic , B1 Bit1.2 booleanCW
28Output BStatus (continuous),1 byte, B1 Byte5.1 percentage (0..100%)CRT
28Output BScene handle, B1 Byte18.1 scene controlCW
29Output BContinuous of regulating , B1 Byte5.1 percentage (0..100%)CW
29Output BChange threshold 1, B1 Byte5.10 counter pulses (0..255)CW
30Output BThreshold input , B1 Byte5.10 counter pulses (0..255)CW
31Output BForced output , B1 Bit1.1 switchCW
31Output BForced output , B2 Bit2.1 switch controlCW
31Output BForced operation,regulating, B1 Bit1.3 enableCW
32Output CReply the switch status, C1 Bit1.1 switchCRT
32Output CSend the switch status, C1 Bit1.1 switchCRT
32Output CReply status of contact , C1 Bit1.1 switchCRT
33Output CSwitch, C1 Bit1.1 switchCW
33Output COn-Off of regulating , C1 Bit1.1 switchCW
34Output CSwitch out with delay, C1 Bit1.1 switchCW
34Output CSwitch out with flashing, C1 Bit1.1 switchCW
34Output COutput of staircase lighting, C1 Bit1.1 switchCW
34Output CStatus (continuous),1 bit , C1 Bit1.1 switchCRT
35Output CSwitch time function, C1 Bit1.3 enableCW
36Output CWarning of staircase , C1 Bit1.5 alarmCT
36Output CReport fault, regulating , C1 Bit1.5 alarmCRT
37Output CDuration of staircase , C2 Bytes7.5 time (s)CRW
38Output CCall preset 1/2 , C1 Bit1.22 sceneCW
39Output CStore preset 1/2, C1 Bit1.22 sceneCW
39Output CTrigger switch regularly , C1 Bit1.3 enableCW
40Output CInput 1 of logic , C1 Bit1.2 booleanCW
41Output CInput 2 of logic , C1 Bit1.2 booleanCW
42Output CScene handle, C1 Byte18.1 scene controlCW
42Output CStatus (continuous),1 byte, C1 Byte5.1 percentage (0..100%)CRT
43Output CChange threshold 1, C1 Byte5.10 counter pulses (0..255)CW
43Output CContinuous of regulating , C1 Byte5.1 percentage (0..100%)CW
44Output CThreshold input , C1 Byte5.10 counter pulses (0..255)CW
45Output CForced output , C1 Bit1.1 switchCW
45Output CForced operation,regulating, C1 Bit1.3 enableCW
45Output CForced output , C2 Bit2.1 switch controlCW
46Output DReply the switch status, D1 Bit1.1 switchCRT
46Output DSend the switch status, D1 Bit1.1 switchCRT
46Output DReply status of contact , D1 Bit1.1 switchCRT
47Output DSwitch, D1 Bit1.1 switchCW
47Output DOn-Off of regulating , D1 Bit1.1 switchCW
48Output DSwitch out with delay, D1 Bit1.1 switchCW
48Output DSwitch out with flashing, D1 Bit1.1 switchCW
48Output DOutput of staircase lighting, D1 Bit1.1 switchCW
48Output DStatus (continuous),1 bit , D1 Bit1.1 switchCRT
49Output DSwitch time function, D1 Bit1.3 enableCW
50Output DWarning of staircase , D1 Bit1.5 alarmCT
50Output DReport fault, regulating , D1 Bit1.5 alarmCRT
51Output DDuration of staircase , D2 Bytes7.5 time (s)CRW
52Output DCall preset 1/2 , D1 Bit1.22 sceneCW
53Output DStore preset 1/2, D1 Bit1.22 sceneCW
53Output DTrigger switch regularly , D1 Bit1.3 enableCW
54Output DInput 1 of logic , D1 Bit1.2 booleanCW
55Output DInput 2 of logic , D1 Bit1.2 booleanCW
56Output DScene handle, D1 Byte18.1 scene controlCW
56Output DStatus (continuous),1 byte, D1 Byte5.1 percentage (0..100%)CRT
57Output DChange threshold 1, D1 Byte5.10 counter pulses (0..255)CW
57Output DContinuous of regulating , D1 Byte5.1 percentage (0..100%)CW
58Output DThreshold input , D1 Byte5.10 counter pulses (0..255)CW
59Output DForced output , D1 Bit1.1 switchCW
59Output DForced operation,regulating, D1 Bit1.3 enableCW
59Output DForced output , D2 Bit2.1 switch controlCW
60Output EReply the switch status, E1 Bit1.1 switchCRT
60Output ESend the switch status, E1 Bit1.1 switchCRT
60Output EReply status of contact , E1 Bit1.1 switchCRT
61Output ESwitch, E1 Bit1.1 switchCW
61Output EOn-Off of regulating , E1 Bit1.1 switchCW
62Output ESwitch out with delay, E1 Bit1.1 switchCW
62Output ESwitch out with flashing, E1 Bit1.1 switchCW
62Output EOutput of staircase lighting, E1 Bit1.1 switchCW
62Output EStatus (continuous),1 bit , E1 Bit1.1 switchCRT
63Output ESwitch time function, E1 Bit1.3 enableCW
64Output EWarning of staircase , E1 Bit1.5 alarmCT
64Output EReport fault, regulating , E1 Bit1.5 alarmCRT
65Output EDuration of staircase , E2 Bytes7.5 time (s)CRW
66Output ECall preset 1/2 , E1 Bit1.22 sceneCW
67Output EStore preset 1/2, E1 Bit1.22 sceneCW
67Output ETrigger switch regularly , E1 Bit1.3 enableCW
68Output EInput 1 of logic , E1 Bit1.2 booleanCW
69Output EInput 2 of logic , E1 Bit1.2 booleanCW
70Output EScene handle, E1 Byte18.1 scene controlCW
70Output EStatus (continuous),1 byte, E1 Byte5.1 percentage (0..100%)CRT
71Output EChange threshold 1, E1 Byte5.10 counter pulses (0..255)CW
71Output EContinuous of regulating , E1 Byte5.1 percentage (0..100%)CW
72Output EThreshold input , E1 Byte5.10 counter pulses (0..255)CW
73Output EForced output , E1 Bit1.1 switchCW
73Output EForced output , E2 Bit2.1 switch controlCW
73Output EForced operation,regulating, E1 Bit1.3 enableCW
74Output FReply the switch status, F1 Bit1.1 switchCRT
74Output FSend the switch status, F1 Bit1.1 switchCRT
74Output FReply status of contact , F1 Bit1.1 switchCRT
75Output FSwitch, F1 Bit1.1 switchCW
75Output FOn-Off of regulating , F1 Bit1.1 switchCW
76Output FSwitch out with delay, F1 Bit1.1 switchCW
76Output FSwitch out with flashing, F1 Bit1.1 switchCW
76Output FOutput of staircase lighting, F1 Bit1.1 switchCW
76Output FStatus (continuous),1 bit , F1 Bit1.1 switchCRT
77Output FSwitch time function, F1 Bit1.3 enableCW
78Output FWarning of staircase , F1 Bit1.5 alarmCT
78Output FReport fault, regulating , F1 Bit1.5 alarmCRT
79Output FDuration of staircase , F2 Bytes7.5 time (s)CRW
80Output FCall preset 1/2 , F1 Bit1.22 sceneCW
81Output FStore preset 1/2, F1 Bit1.22 sceneCW
81Output FTrigger switch regularly , F1 Bit1.3 enableCW
82Output FInput 1 of logic , F1 Bit1.2 booleanCW
83Output FInput 2 of logic , F1 Bit1.2 booleanCW
84Output FScene handle, F1 Byte18.1 scene controlCW
84Output FStatus (continuous),1 byte, F1 Byte5.1 percentage (0..100%)CRT
85Output FChange threshold 1, F1 Byte5.10 counter pulses (0..255)CW
85Output FContinuous of regulating , F1 Byte5.1 percentage (0..100%)CW
86Output FThreshold input , F1 Byte5.10 counter pulses (0..255)CW
87Output FForced output , F1 Bit1.1 switchCW
87Output FForced output , F2 Bit2.1 switch controlCW
87Output FForced operation,regulating, F1 Bit1.3 enableCW
88Output GReply the switch status, G1 Bit1.1 switchCRT
88Output GSend the switch status, G1 Bit1.1 switchCRT
88Output GReply status of contact , G1 Bit1.1 switchCRT
89Output GSwitch, G1 Bit1.1 switchCW
89Output GOn-Off of regulating , G1 Bit1.1 switchCW
90Output GSwitch out with delay, G1 Bit1.1 switchCW
90Output GSwitch out with flashing, G1 Bit1.1 switchCW
90Output GOutput of staircase lighting, G1 Bit1.1 switchCW
90Output GStatus (continuous),1 bit , G1 Bit1.1 switchCRT
91Output GSwitch time function, G1 Bit1.3 enableCW
92Output GWarning of staircase , G1 Bit1.5 alarmCT
92Output GReport fault, regulating , G1 Bit1.5 alarmCRT
93Output GDuration of staircase , G2 Bytes7.5 time (s)CRW
94Output GCall preset 1/2 , G1 Bit1.22 sceneCW
95Output GStore preset 1/2, G1 Bit1.22 sceneCW
95Output GTrigger switch regularly , G1 Bit1.3 enableCW
96Output GInput 1 of logic , G1 Bit1.2 booleanCW
97Output GInput 2 of logic , G1 Bit1.2 booleanCW
98Output GScene handle, G1 Byte18.1 scene controlCW
98Output GStatus (continuous),1 byte, G1 Byte5.1 percentage (0..100%)CRT
99Output GChange threshold 1, G1 Byte5.10 counter pulses (0..255)CW
99Output GContinuous of regulating , G1 Byte5.1 percentage (0..100%)CW
100Output GThreshold input , G1 Byte5.10 counter pulses (0..255)CW
101Output GForced output , G1 Bit1.1 switchCW
101Output GForced output , G2 Bit2.1 switch controlCW
101Output GForced operation,regulating, G1 Bit1.3 enableCW
102Output HReply the switch status, H1 Bit1.1 switchCRT
102Output HSend the switch status, H1 Bit1.1 switchCRT
102Output HReply status of contact , H1 Bit1.1 switchCRT
103Output HSwitch, H1 Bit1.1 switchCW
103Output HOn-Off of regulating , H1 Bit1.1 switchCW
104Output HSwitch out with delay, H1 Bit1.1 switchCW
104Output HSwitch out with flashing, H1 Bit1.1 switchCW
104Output HOutput of staircase lighting, H1 Bit1.1 switchCW
104Output HStatus (continuous),1 bit , H1 Bit1.1 switchCRT
105Output HSwitch time function, H1 Bit1.3 enableCW
106Output HWarning of staircase , H1 Bit1.5 alarmCT
106Output HReport fault, regulating , H1 Bit1.5 alarmCRT
107Output HDuration of staircase , H2 Bytes7.5 time (s)CRW
108Output HCall preset 1/2 , H1 Bit1.22 sceneCW
109Output HStore preset 1/2, H1 Bit1.22 sceneCW
109Output HTrigger switch regularly , H1 Bit1.3 enableCW
110Output HInput 1 of logic , H1 Bit1.2 booleanCW
111Output HInput 2 of logic , H1 Bit1.2 booleanCW
112Output HScene handle, H1 Byte18.1 scene controlCW
112Output HStatus (continuous),1 byte, H1 Byte5.1 percentage (0..100%)CRT
113Output HChange threshold 1, H1 Byte5.10 counter pulses (0..255)CW
113Output HContinuous of regulating , H1 Byte5.1 percentage (0..100%)CW
114Output HThreshold input , H1 Byte5.10 counter pulses (0..255)CW
115Output HForced output , H1 Bit1.1 switchCW
115Output HForced output , H2 Bit2.1 switch controlCW
115Output HForced operation,regulating, H1 Bit1.3 enableCW
116Output IReply the switch status, I1 Bit1.1 switchCRT
116Output ISend the switch status, I1 Bit1.1 switchCRT
116Output IReply status of contact , I1 Bit1.1 switchCRT
117Output ISwitch, I1 Bit1.1 switchCW
117Output IOn-Off of regulating , I1 Bit1.1 switchCW
118Output ISwitch out with delay, I1 Bit1.1 switchCW
118Output ISwitch out with flashing, I1 Bit1.1 switchCW
118Output IOutput of staircase lighting, I1 Bit1.1 switchCW
118Output IStatus (continuous),1 bit , I1 Bit1.1 switchCRT
119Output ISwitch time function, I1 Bit1.3 enableCW
120Output IWarning of staircase , I1 Bit1.5 alarmCT
120Output IReport fault, regulating , I1 Bit1.5 alarmCRT
121Output IDuration of staircase , I2 Bytes7.5 time (s)CRW
122Output ICall preset 1/2 , I1 Bit1.22 sceneCW
123Output IStore preset 1/2, I1 Bit1.22 sceneCW
123Output ITrigger switch regularly , I1 Bit1.3 enableCW
124Output IInput 1 of logic , I1 Bit1.2 booleanCW
125Output IInput 2 of logic , I1 Bit1.2 booleanCW
126Output IScene handle, I1 Byte18.1 scene controlCW
126Output IStatus (continuous),1 byte, I1 Byte5.1 percentage (0..100%)CRT
127Output IChange threshold 1, I1 Byte5.10 counter pulses (0..255)CW
127Output IContinuous of regulating , I1 Byte5.1 percentage (0..100%)CW
128Output IThreshold input , I1 Byte5.10 counter pulses (0..255)CW
129Output IForced output , I1 Bit1.1 switchCW
129Output IForced operation,regulating, I1 Bit1.3 enableCW
129Output IForced output , I2 Bit2.1 switch controlCW
130Output JReply the switch status, J1 Bit1.1 switchCRT
130Output JSend the switch status, J1 Bit1.1 switchCRT
130Output JReply status of contact , J1 Bit1.1 switchCRT
131Output JSwitch, J1 Bit1.1 switchCW
131Output JOn-Off of regulating , J1 Bit1.1 switchCW
132Output JSwitch out with delay, J1 Bit1.1 switchCW
132Output JSwitch out with flashing, J1 Bit1.1 switchCW
132Output JOutput of staircase lighting, J1 Bit1.1 switchCW
132Output JStatus (continuous),1 bit , J1 Bit1.1 switchCRT
133Output JSwitch time function, J1 Bit1.3 enableCW
134Output JWarning of staircase , J1 Bit1.5 alarmCT
134Output JReport fault, regulating , J1 Bit1.5 alarmCRT
135Output JDuration of staircase , J2 Bytes7.5 time (s)CRW
136Output JCall preset 1/2 , J1 Bit1.22 sceneCW
137Output JStore preset 1/2, J1 Bit1.22 sceneCW
137Output JTrigger switch regularly , J1 Bit1.3 enableCW
138Output JInput 1 of logic , J1 Bit1.2 booleanCW
139Output JInput 2 of logic , J1 Bit1.2 booleanCW
140Output JScene handle, J1 Byte18.1 scene controlCW
140Output JStatus (continuous),1 byte, J1 Byte5.1 percentage (0..100%)CRT
141Output JChange threshold 1, J1 Byte5.10 counter pulses (0..255)CW
141Output JContinuous of regulating , J1 Byte5.1 percentage (0..100%)CW
142Output JThreshold input , J1 Byte5.10 counter pulses (0..255)CW
143Output JForced output , J1 Bit1.1 switchCW
143Output JForced operation,regulating, J1 Bit1.3 enableCW
143Output JForced output , J2 Bit2.1 switch controlCW
144Output KReply the switch status, K1 Bit1.1 switchCRT
144Output KSend the switch status, K1 Bit1.1 switchCRT
144Output KReply status of contact , K1 Bit1.1 switchCRT
145Output KSwitch, K1 Bit1.1 switchCW
145Output KOn-Off of regulating , K1 Bit1.1 switchCW
146Output KSwitch out with delay, K1 Bit1.1 switchCW
146Output KSwitch out with flashing, K1 Bit1.1 switchCW
146Output KOutput of staircase lighting, K1 Bit1.1 switchCW
146Output KStatus (continuous),1 bit , K1 Bit1.1 switchCRT
147Output KSwitch time function, K1 Bit1.3 enableCW
148Output KWarning of staircase , K1 Bit1.5 alarmCT
148Output KReport fault, regulating , K1 Bit1.5 alarmCRT
149Output KDuration of staircase , K2 Bytes7.5 time (s)CRW
150Output KCall preset 1/2 , K1 Bit1.22 sceneCW
151Output KStore preset 1/2, K1 Bit1.22 sceneCW
151Output KTrigger switch regularly , K1 Bit1.3 enableCW
152Output KInput 1 of logic , K1 Bit1.2 booleanCW
153Output KInput 2 of logic , K1 Bit1.2 booleanCW
154Output KScene handle, K1 Byte18.1 scene controlCW
154Output KStatus (continuous),1 byte, K1 Byte5.1 percentage (0..100%)CRT
155Output KChange threshold 1, K1 Byte5.10 counter pulses (0..255)CW
155Output KContinuous of regulating , K1 Byte5.1 percentage (0..100%)CW
156Output KThreshold input , K1 Byte5.10 counter pulses (0..255)CW
157Output KForced output , K1 Bit1.1 switchCW
157Output KForced operation,regulating, K1 Bit1.3 enableCW
157Output KForced output , K2 Bit2.1 switch controlCW
158Output LReply the switch status, L1 Bit1.1 switchCRT
158Output LSend the switch status, L1 Bit1.1 switchCRT
158Output LReply status of contact , L1 Bit1.1 switchCRT
159Output LSwitch, L1 Bit1.1 switchCW
159Output LOn-Off of regulating , L1 Bit1.1 switchCW
160Output LSwitch out with delay, L1 Bit1.1 switchCW
160Output LSwitch out with flashing, L1 Bit1.1 switchCW
160Output LOutput of staircase lighting, L1 Bit1.1 switchCW
160Output LStatus (continuous),1 bit , L1 Bit1.1 switchCRT
161Output LSwitch time function, L1 Bit1.3 enableCW
162Output LWarning of staircase , L1 Bit1.5 alarmCT
162Output LReport fault, regulating , L1 Bit1.5 alarmCRT
163Output LDuration of staircase , L2 Bytes7.5 time (s)CRW
164Output LCall preset 1/2 , L1 Bit1.22 sceneCW
165Output LStore preset 1/2, L1 Bit1.22 sceneCW
165Output LTrigger switch regularly , L1 Bit1.3 enableCW
166Output LInput 1 of logic , L1 Bit1.2 booleanCW
167Output LInput 2 of logic , L1 Bit1.2 booleanCW
168Output LScene handle, L1 Byte18.1 scene controlCW
168Output LStatus (continuous),1 byte, L1 Byte5.1 percentage (0..100%)CRT
169Output LChange threshold 1, L1 Byte5.10 counter pulses (0..255)CW
169Output LContinuous of regulating , L1 Byte5.1 percentage (0..100%)CW
170Output LThreshold input , L1 Byte5.10 counter pulses (0..255)CW
171Output LForced output , L1 Bit1.1 switchCW
171Output LForced operation,regulating, L1 Bit1.3 enableCW
171Output LForced output , L2 Bit2.1 switch controlCW
172Total currentTotal active energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
172Total currentTotal active energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
173Total currentValue of total current(A)4 Bytes14.19 electric current (A)CRT
173Total currentValue of total current(kW)2 Bytes9.24 power (kW)CRT
173Total currentValue of total current(mA)2 Bytes7.12 current (mA)CRT
173Total currentValue of total current(F_mA)2 Bytes9.21 current (mA)CRT
174Total currentExceedance of total load1 Bit1.1 switchCRWT
175Current ACurrent value(mA)2 Bytes7.12 current (mA)CRT
175Current ACurrent value(F_mA)2 Bytes9.21 current (mA)CRT
175Current ACurrent value(A)4 Bytes14.19 electric current (A)CRT
175Current ACurrent value(kW)2 Bytes9.24 power (kW)CRT
176Current AExceedance of load 1 Bit1.1 switchCRT
177Current ALower deviation of load1 Bit1.1 switchCRT
178Current ASwitch counter2 Bytes7.1 pulsesCRWT
178Current ASwitch counter4 Bytes12.1 counter pulses (unsigned)CRWT
179Current AOperation hours2 Bytes7.7 time (h)CRWT
179Current AOperation hours4 Bytes13.100 time lag (s)CRWT
180Current AActive energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
180Current AActive energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
181Current BCurrent value(mA)2 Bytes7.12 current (mA)CRT
181Current BCurrent value(F_mA)2 Bytes9.21 current (mA)CRT
181Current BCurrent value(A)4 Bytes14.19 electric current (A)CRT
181Current BCurrent value(kW)2 Bytes9.24 power (kW)CRT
182Current BExceedance of load 1 Bit1.1 switchCRT
183Current BLower deviation of load1 Bit1.1 switchCRT
184Current BSwitch counter2 Bytes7.1 pulsesCRWT
184Current BSwitch counter4 Bytes12.1 counter pulses (unsigned)CRWT
185Current BOperation hours2 Bytes7.7 time (h)CRWT
185Current BOperation hours4 Bytes13.100 time lag (s)CRWT
186Current BActive energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
186Current BActive energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
187Current CCurrent value(A)4 Bytes14.19 electric current (A)CRT
187Current CCurrent value(kW)2 Bytes9.24 power (kW)CRT
187Current CCurrent value(F_mA)2 Bytes9.21 current (mA)CRT
187Current CCurrent value(mA)2 Bytes7.12 current (mA)CRT
188Current CExceedance of load 1 Bit1.1 switchCRT
189Current CLower deviation of load1 Bit1.1 switchCRT
190Current CSwitch counter2 Bytes7.1 pulsesCRWT
190Current CSwitch counter4 Bytes12.1 counter pulses (unsigned)CRWT
191Current COperation hours2 Bytes7.7 time (h)CRWT
191Current COperation hours4 Bytes13.100 time lag (s)CRWT
192Current CActive energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
192Current CActive energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
193Current DCurrent value(A)4 Bytes14.19 electric current (A)CRT
193Current DCurrent value(kW)2 Bytes9.24 power (kW)CRT
193Current DCurrent value(F_mA)2 Bytes9.21 current (mA)CRT
193Current DCurrent value(mA)2 Bytes7.12 current (mA)CRT
194Current DExceedance of load 1 Bit1.1 switchCRT
195Current DLower deviation of load1 Bit1.1 switchCRT
196Current DSwitch counter2 Bytes7.1 pulsesCRWT
196Current DSwitch counter4 Bytes12.1 counter pulses (unsigned)CRWT
197Current DOperation hours2 Bytes7.7 time (h)CRWT
197Current DOperation hours4 Bytes13.100 time lag (s)CRWT
198Current DActive energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
198Current DActive energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
199Current ECurrent value(mA)2 Bytes7.12 current (mA)CRT
199Current ECurrent value(F_mA)2 Bytes9.21 current (mA)CRT
199Current ECurrent value(A)4 Bytes14.19 electric current (A)CRT
199Current ECurrent value(kW)2 Bytes9.24 power (kW)CRT
200Current EExceedance of load 1 Bit1.1 switchCRT
201Current ELower deviation of load1 Bit1.1 switchCRT
202Current ESwitch counter2 Bytes7.1 pulsesCRWT
202Current ESwitch counter4 Bytes12.1 counter pulses (unsigned)CRWT
203Current EOperation hours2 Bytes7.7 time (h)CRWT
203Current EOperation hours4 Bytes13.100 time lag (s)CRWT
204Current EActive energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
204Current EActive energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
205Current FCurrent value(mA)2 Bytes7.12 current (mA)CRT
205Current FCurrent value(F_mA)2 Bytes9.21 current (mA)CRT
205Current FCurrent value(A)4 Bytes14.19 electric current (A)CRT
205Current FCurrent value(kW)2 Bytes9.24 power (kW)CRT
206Current FExceedance of load 1 Bit1.1 switchCRT
207Current FLower deviation of load1 Bit1.1 switchCRT
208Current FSwitch counter2 Bytes7.1 pulsesCRWT
208Current FSwitch counter4 Bytes12.1 counter pulses (unsigned)CRWT
209Current FOperation hours2 Bytes7.7 time (h)CRWT
209Current FOperation hours4 Bytes13.100 time lag (s)CRWT
210Current FActive energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
210Current FActive energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
211Current GCurrent value(mA)2 Bytes7.12 current (mA)CRT
211Current GCurrent value(F_mA)2 Bytes9.21 current (mA)CRT
211Current GCurrent value(A)4 Bytes14.19 electric current (A)CRT
211Current GCurrent value(kW)2 Bytes9.24 power (kW)CRT
212Current GExceedance of load 1 Bit1.1 switchCRT
213Current GLower deviation of load1 Bit1.1 switchCRT
214Current GSwitch counter2 Bytes7.1 pulsesCRWT
214Current GSwitch counter4 Bytes12.1 counter pulses (unsigned)CRWT
215Current GOperation hours2 Bytes7.7 time (h)CRWT
215Current GOperation hours4 Bytes13.100 time lag (s)CRWT
216Current GActive energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
216Current GActive energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
217Current HCurrent value(mA)2 Bytes7.12 current (mA)CRT
217Current HCurrent value(F_mA)2 Bytes9.21 current (mA)CRT
217Current HCurrent value(A)4 Bytes14.19 electric current (A)CRT
217Current HCurrent value(kW)2 Bytes9.24 power (kW)CRT
218Current HExceedance of load 1 Bit1.1 switchCRT
219Current HLower deviation of load1 Bit1.1 switchCRT
220Current HSwitch counter2 Bytes7.1 pulsesCRWT
220Current HSwitch counter4 Bytes12.1 counter pulses (unsigned)CRWT
221Current HOperation hours2 Bytes7.7 time (h)CRWT
221Current HOperation hours4 Bytes13.100 time lag (s)CRWT
222Current HActive energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
222Current HActive energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
223Current ICurrent value(A)4 Bytes14.19 electric current (A)CRT
223Current ICurrent value(kW)2 Bytes9.24 power (kW)CRT
223Current ICurrent value(F_mA)2 Bytes9.21 current (mA)CRT
223Current ICurrent value(mA)2 Bytes7.12 current (mA)CRT
224Current IExceedance of load 1 Bit1.1 switchCRT
225Current ILower deviation of load1 Bit1.1 switchCRT
226Current ISwitch counter2 Bytes7.1 pulsesCRWT
226Current ISwitch counter4 Bytes12.1 counter pulses (unsigned)CRWT
227Current IOperation hours2 Bytes7.7 time (h)CRWT
227Current IOperation hours4 Bytes13.100 time lag (s)CRWT
228Current IActive energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
228Current IActive energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
229Current JCurrent value(A)4 Bytes14.19 electric current (A)CRT
229Current JCurrent value(kW)2 Bytes9.24 power (kW)CRT
229Current JCurrent value(F_mA)2 Bytes9.21 current (mA)CRT
229Current JCurrent value(mA)2 Bytes7.12 current (mA)CRT
230Current JExceedance of load 1 Bit1.1 switchCRT
231Current JLower deviation of load1 Bit1.1 switchCRT
232Current JSwitch counter2 Bytes7.1 pulsesCRWT
232Current JSwitch counter4 Bytes12.1 counter pulses (unsigned)CRWT
233Current JOperation hours2 Bytes7.7 time (h)CRWT
233Current JOperation hours4 Bytes13.100 time lag (s)CRWT
234Current JActive energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
234Current JActive energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
235Current KCurrent value(A)4 Bytes14.19 electric current (A)CRT
235Current KCurrent value(kW)2 Bytes9.24 power (kW)CRT
235Current KCurrent value(F_mA)2 Bytes9.21 current (mA)CRT
235Current KCurrent value(mA)2 Bytes7.12 current (mA)CRT
236Current KExceedance of load 1 Bit1.1 switchCRT
237Current KLower deviation of load1 Bit1.1 switchCRT
238Current KSwitch counter2 Bytes7.1 pulsesCRWT
238Current KSwitch counter4 Bytes12.1 counter pulses (unsigned)CRWT
239Current KOperation hours2 Bytes7.7 time (h)CRWT
239Current KOperation hours4 Bytes13.100 time lag (s)CRWT
240Current KActive energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
240Current KActive energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
241Current LCurrent value(A)4 Bytes14.19 electric current (A)CRT
241Current LCurrent value(kW)2 Bytes9.24 power (kW)CRT
241Current LCurrent value(F_mA)2 Bytes9.21 current (mA)CRT
241Current LCurrent value(mA)2 Bytes7.12 current (mA)CRT
242Current LExceedance of load 1 Bit1.1 switchCRT
243Current LLower deviation of load1 Bit1.1 switchCRT
244Current LSwitch counter2 Bytes7.1 pulsesCRWT
244Current LSwitch counter4 Bytes12.1 counter pulses (unsigned)CRWT
245Current LOperation hours2 Bytes7.7 time (h)CRWT
245Current LOperation hours4 Bytes13.100 time lag (s)CRWT
246Current LActive energy(Wh)4 Bytes13.10 active energy (Wh)CRWT
246Current LActive energy(kWh)4 Bytes13.13 active energy (kWh)CRWT
Parameters (127)
ParameterTypeDefault
Product typelist4-Fold Output
Relay drive typelistInverted(apply to Ver.2)
Operation delay after recovery of bus voltage(10..250s)unsignedInt 10…25010
Sending cycle of "In operation" telegram (1...240s , 0=inactive)unsignedInt 0…2400
Total currentlistInactive
Enable safety priority functionlistDisable
--Set safety priority 1:listInactive
Control period of safety priority 1(1..240s,0=inactive)unsignedInt 0…2400
--Set safety priority 2:listInactive
Control period of safety priority 2(1..240s,0=inactive)unsignedInt 0…2400
Priority of safety operationlistPriority of 2 is higher than that of 1
Note: Normal, object value of switch on/offlist"1"=switch on; "0"=switch off
Object selection for the current measurementlistValue in mA(DPT 7.012)
Factor for conversion into theoretical wattage kW: Current value x FactorunsignedInt 100…250230
Send current value value after changes valuelistNot active
Cyclic sendlistNo active
Monitoring exceedance of loadlistInactive
Factor for load monitoring(A)unsignedInt 1…2001
Hysteresis(%)unsignedInt 10…10010
Behavior at exceedinglistSend no telegram
Behavior at not exceedinglistSend no telegram
Send exceeding cyclicallistNo active
Total power meter function(Wh/kWh)listInactive
Object selection for power meterlistValue in Wh(DPT 13.010)
Sending object valuelistOnly request
Memory of all current detecting delete after download of applicationlistNo
Work mode of the channel islistSwitch actuator
If bus voltage recovery,contact islistUnchange
If bus voltage fail,contact islistUnchange
Object value of "switch" after bus voltage recoverylistNot write
Set the reply mode of switch statuslistTransmit after change
Object value of switch status :list0=contact open ; 1=contact close
Contact position if tele. value is "1" ("0" is opposite of "1" if changed)listClose
Special functions of Switch actuator mode islistInactive
Valve typelistNormal (de-energised closed)
If bus voltage recovery, valve position islist0%(OFF)
PWM cycle time for continuous control (1...240 minutes)unsignedInt 0…2403
PWM cycle time for continuous control (0...59 seconds)unsignedInt 0…590
Control telegram is received aslist1 bit ( on-off control )
Reply the status of channel for continuous controllistNothing
Reply the status of contact statelistNothing
Special functions of Heating actuator mode islistInactive
Function of "time" for switch islistDisable
Function of "preset" for switch islistDisable
Function of "logic" for switch islistDisable
Function of "scene" for switch islistDisable
Function of "threshold" for switch islistDisable
Function of "safety" for switch islistDisable
Function of "forced" for switch islistDisable
Function of "current" for switch islistDisable
The mode of time functionlistDelay switch
Delay for switch on : --(0...240 minutes)unsignedInt 0…2400
--(0...59 seconds)unsignedInt 0…590
Delay for switch off : --(0...240 minutes)unsignedInt 0…2400
Number of ON-impulses(1..255,0=no limited)unsignedInt 0…2550
Contact position after flashinglistUnchange
Control mode of flashinglistStart with "1" , Stop with "0"
Duration of staircase lighting --(0...1000 minutes)unsignedInt 0…10002
Control mode of staircase lightinglistStart with "0/1" , can not be stop
During the lighting time, if receive the "Start" telegram,listRestart duration of staircase lighting
Warning mode for ending of staircase lightinglistNothing
--The warning time for end of staircase lighting(0..59s)unsignedInt 0…590
Modify the duration via object(0..60059s)listDisable
Action for preset 1(object value=0)listNone
Action for preset 2(object value=1)listOFF
Setting for preset via telegram islistDisable
The input 0 (switch object) for logic islistDisable
The input 1 of logic islistDisable
Function type between input0 and input1listAND
Result is invertedlistNO
Value of input 1 after bus voltage recovery :list"0"
The input 2 of logic islistDisable
Function type between input2 and input0/1listAND
Value of input 2 after bus voltage recovery :list"0"
1> channel is assigned to (1..64,0=no allocation)unsignedInt 0…640
--Standard output value islistOFF
2> channel is assigned to (1..64,0=no allocation)unsignedInt 0…640
3> channel is assigned to (1..64,0=no allocation)unsignedInt 0…640
4> channel is assigned to (1..64,0=no allocation)unsignedInt 0…640
5> channel is assigned to (1..64,0=no allocation)unsignedInt 0…640
6> channel is assigned to (1..64,0=no allocation)unsignedInt 0…640
7> channel is assigned to (1..64,0=no allocation)unsignedInt 0…640
8> channel is assigned to (1..64,0=no allocation)unsignedInt 0…640
Threshold 1 valueunsignedInt 0…25580
Threshold 2 valueunsignedInt 0…255200
Change threshold 1 via object :listDisable
Threshold behaviourlistWithout hysteresis
--If falling below lower threshold, contact positionlistUnchange
--If exceeding upper threshold, contact positionlistUnchange
--If lower < object value < upper, contact positionlistUnchange
Setting of safetylistOn parameter-window "All General"
Contact position if safety priority 1listUnchange
Contact position if safety priority 2listUnchange
Forced operation typelist1bit
Contact position if forced operationlistUnchange
Load typelistResistive
Current correction(-1000..1000 mA)signedInt -1000…10000
Power meter function(Wh/kWh)listInactive
Object of current measurementlistValue in mA(DPT 7.012)
Add the channel to total current valuelistInactive
Send current value after changes valuelistNot active
Value range for load monitoringlist100 mA - 20 A
Factor for load monitoring x100 mAunsignedInt 1…2001
Hysteresis[%]unsignedInt 10…10010
Monitoring lower deviation of loadlistInactive
Behavior at deviatinglistSend no telegram
Behavior at not deviatinglistSend no telegram
Send falling below cyclicallistNo active
Counter functionlistInactive
Object of switch and operation hours counterlist4 byte Value
Switch count iflistRelay on
Hours count iflistRelay on
Send counter value in hoursunsignedInt 0…1000
Function for monitoring islistDisable
Function of forced operation islistDisable
Function of regular switch islistDisable
Function of safety operation islistDisable
Cyclic monitoring --in minutes (0...240 minutes)unsignedInt 0…24060
--in seconds (0...59 seconds)unsignedInt 0…590
Valve position during faultlistUnchange
Sending object "report fault" islistDisable
Valve position during forced operationlistUnchange
Time of switch regular in (0..255min)unsignedInt 0…25510
Automatic switch regularlylistDisable
Valve position during safety 1 operationlistUnchange
Valve position during safety 2 operationlistUnchange
Warning mode for ending of staircase lightinglistNothing

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Switch Actuator with current detection,4/8/12-Fold 2.0 latest$00417F4A2026-11-25218 KBDownload

About this file

This is the official ETS product database for the GVS ARCD-xx/16.2(xx=04/08/12) (1ARCDx19BA), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from GVS

All GVS products