KNX Database

GWA9141

GEWISS · Order number GWA9141 · Climate control devices › Fan Coil Actuators

Download .knxprod KNX FAN COIL ACTUATOR 0-10V - DIN RAIL 1.1 · 141 KB

Product

ManufacturerGEWISS
Product nameGWA9141
Order numberGWA9141
Product textKNX FAN COIL ACTUATOR 0-10V - DIN RAIL
HardwareKNX FAN COIL ACTUATOR 0-10V - DIN RAIL
MediumTwisted Pair
Bus current (mA)7
Rail mountedYes
Width (mm)70
RegistrationCertified · 2020-04-01
Languagesde-DE, en-US, es-ES, it-IT, fr-FR, nl-NL
Catalog entryM-0019_H-4920210-1-O0048_HP-492D-11-CAAA-O0048_CI-GWA9141.C2.A0-1
FingerprintCAAA
SHA-2563a6c9028a0cc2fd44421ca576e00a5780e0ece7485eb17301f06bdcaf49c0a2d
First seen2026-11-25
Markets59 markets

Application program: KNX FAN COIL ACTUATOR 0-10V - DIN RAIL 1.1

Application number$492D
Version1.1
Mask versionMV-0021 (2.1)
KNX Data SecureNo
Minimum ETS version4.0
Parameters152
Group objects62
Group objects (62)
NoNameFunctionSizeDPTFlags
0Actuating value heatingReceive1 Byte5.1 percentage (0..100%)CRWU
0Actuating value heating/coolingTransmit1 Byte5.1 percentage (0..100%)CRTU
0Actuating value heating/coolingReceive1 Byte5.1 percentage (0..100%)CRWU
0Actuating value heatingTransmit1 Byte5.1 percentage (0..100%)CRTU
0Actuating value coolingTransmit1 Byte5.1 percentage (0..100%)CRTU
0Actuating value for fanReceive1 Byte5.1 percentage (0..100%)CRWU
0Actuating value coolingReceive1 Byte5.1 percentage (0..100%)CRWU
1Enable cooling1 = Enable cooling1 Bit1.3 enableCRWU
1Actuating value coolingReceive1 Byte5.1 percentage (0..100%)CRWU
1Heating/coolingHeating = 1, Cooling = 01 Bit1.1 switchCRWU
1Actuating value coolingTransmit1 Byte5.1 percentage (0..100%)CRTU
1disable heating1 = Heating disabled1 Bit1.1 switchCRWU
1Heating / coolingHeating = 0, Cooling = 11 Bit1.1 switchCRWU
2Heating statusReport1 Bit1.1 switchCRTU
3Cooling statusReport1 Bit1.1 switchCRTU
4Fan stepReport1 Byte5.10 counter pulses (0..255)CRTU
4Fan speedReport1 Byte5.10 counter pulses (0..255)CRTU
5Auxilliary relaySwitching1 Bit1.1 switchCRWU
5Auxilliary relay statusReport1 Bit1.1 switchCRTU
6Lock additional ventilation1 = Lock1 Bit1.1 switchCRWU
7Fan lock1 = Lock1 Bit1.1 switchCRWU
8Forced fan stepFan control via level1 Byte5.1 percentage (0..100%)CRWU
8Fan speed in forced modeFan control with % value1 Byte5.1 percentage (0..100%)CRWU
8Forced fan stepFan control with % value1 Byte5.1 percentage (0..100%)CRWU
9Limitation of fan step (1-2-3)0=Fan OFF 1-3=max. level1 Byte5.10 counter pulses (0..255)CRWU
9Limitation of fan step in %0 = Fan OFF 1..100% = max.step1 Byte5.1 percentage (0..100%)CRWU
9Limitation of fan step in %0=Fan OFF 1..100%=max.1 Byte5.1 percentage (0..100%)CRWU
10Fan offReport1 Bit1.1 switchCRTU
11Fan step 1Report1 Bit1.1 switchCRTU
12Fan step 2Report1 Bit1.1 switchCRTU
13Fan step 3Report1 Bit1.1 switchCRTU
14Status of window contact at E1Report1 Bit1.1 switchCRTU
14Actual value from E1Report2 Bytes9.1 temperature (°C)CRTU
15Manual modeReceive: auto=1, forced=01 Bit1.1 switchCRWU
15Manual modeReceive: forced=1, auto=01 Bit1.1 switchCRWU
16Drip tray monitoring statusReport1 Bit1.1 switchCRTU
16Drip tray monitoring statusInput1 Bit1.1 switchCRWU
16Status of window contact at E2Report1 Bit1.1 switchCRTU
17Dew point alarmInput1 Bit1.1 switchCRWU
18Outdoor temperatureInput2 Bytes9.1 temperature (°C)CRWU
19Adjust set pointDelta in K2 Bytes9.2 temperature difference (K)CRTU
19Adjust set pointValue in °C2 Bytes9.1 temperature (°C)CRTU
20Sensor failureSensor failure1 Bit1.1 switchCRTU
20Actuating value loss1 = Actuating value loss1 Bit1.1 switchCRTU
21Operating mode presetoperating mode preset1 ByteCRWU
21Night mode <-> Standby1 = Night mode1 Bit1.1 switchCRWU
22PresenceInput for presence signal1 BitDPT.1CRWU
22Comfort1 = Comfort mode1 Bit1.1 switchCRWU
23WindowInput for window contact1 BitDPT.1CRWU
23Frost protection1 = Frost protection1 Bit1.1 switchCRWU
24Current operating modeTransmit1 ByteCRTU
25Manual adjustmentReceive2 Bytes9.2 temperature difference (K)CRWU
26Base set pointReceive2 Bytes9.1 temperature (°C)CRWU
27Current set point valueTransmit2 Bytes9.1 temperature (°C)CRTU
28Heating/coolingHeating = 1, Cooling = 01 Bit1.1 switchCRWU
28Heating/coolingHeating = 0, Cooling = 11 Bit1.1 switchCRWU
29No energy medium1 = Wrong energy medium1 Bit1.1 switchCRTU
29Heating required but heating disabled1 = Heating disabled1 Bit1.1 switchCRTU
29Cooling required but cooling disabled1 = Cooling disabled1 Bit1.1 switchCRTU
30Fan duty time since last filter changeTime in hours2 BytesDPT.7CRTU
31Change filter1 = Change 0 = Reset1 Bit1.1 switchCRWTU
32Testmode activeReport1 Bit1.3 enableCRTU
Parameters (123)
ParameterTypeDefault
GenerallistPage
Supported functionslistheating and cooling
Heating installationlistFan coil
Model of heat exchangerlistFan coil
Cooling installationlistFan coil
Kind of installationlist2-pipe system
Kind of used controlerlistremote controller
Format object heating/coolinglistDPT1.100 (Heating= 1 / Cooling=0)
Test modelistdisabled
Report filter changelistno
Activate monitoring of actuating valuelistno
Switch fan between Auto and forced modelistvia obj. Forced/auto, forced = 1
FanlistPage
Fan controllerliststandard (1-3 step)
Number of fan stepslist3 steps
Switch-on threshold for fan step 1list10 %
Switch ON thresholdlist10 %
Switch-on threshold for fan step 2list40 %
Switch-on threshold for fan step 3list70 %
Fan starting strategylistdirectly
Restart delay (for split-system air conditioners)listno delay (fan / fan coil unit)
Switching delay between 2 fan stepslist0,5 s
Minimum time to stay within a fan steplist2 min
Hysteresis between the fan stepslist10 %
Additional ventilationlistno
Value for supplementary ventilationlist40 %
Warm startlistno warm start
Follow-up time for utilisation of the remaining energylistno follow-up
Format compulsory control and limitationlistpercentage
Cyclical transmission of fan objectlistdon´t transmit cyclically
Cyclical transmission of fan steplistFormat %, don´t transmit cyclically
Heating valvelistPage
Heating/cooling valvelistPage
Cooling valvelistPage
Time for the valve to closelist3 min
New position at change oflist5 %
Open for actuating value abovelist0,4 %
Minimum valve positionlist0 %
Maximum valve position abovelist50 %
Maximum valve positionlist100 %
Cyclical transmission of heating statuslistdon´t transmit cyclically
Delay between heating and coolinglist0 min
Cyclical transmission of cooling status everylistdon´t transmit cyclically
Cyclical transmission of heating/cooling statuslistdon´t transmit cyclically
Auxilliary relaylistPage
Switch ON auxilliary relaylistvia object
Cyclical transmission of aux. relay status everylistdon´t transmit cyclically
E1listPage
Function of E1listE1 = window contact
Direction of operation of window contactlistContact closed = window closed
Actual value offset in 0.1 K (-50..50)signedInt -50…500
Transmission of actual value at change oflistevery 0,5 K
Cyclical transmission of window contactlistdon´t transmit cyclically
Cyclical transmission of actual valuelistdon´t transmit cyclically
Actuating value in case of sensor failure or short circuitlist20 %
Report sensor failure (1 = failure)listonly if object value = 1
Report cyclicallylistevery 30 min
Drip tray monitoringlistPage
E2listPage
Source for drip tray monitoringlistE2
Direction of operation of contactlistcontact closed = condensate
Direction of action of E2listcontact closed = condensate
Direction of operation of contactlistcontact closed = window closed
Behaviour in case of drip tray alarmlistcooling and fan OFF
Cyclical transmission of alarm statuslistdon´t transmit cyclically
Cyclical transmission of E2 statuslistdon´t transmit cyclically
Set point adjustmentlistPage
Set point adjustmentlistyes
Set point adjustment fromlist25 °C
Adjustmentlist1 K per 3 K outdoor temperature
Format of the adjustment valuelistrelative
Base set point without adjustmentlist21 °C
Cyclical transmission of set point adjustmentlistdon´t transmit cyclically
Use set point adjustment for regulationlistno
Set point valueslistPage
Base set point after resetlist21 °C
Reduction in standby operating modelist2 K
Reduction in standby operating mode at heatinglist2 K
Reduction in night operating modelist5 K
Reduction in night operating mode at heatinglist5 K
Set point value for frost protection modelist6 °C
Set point value for frost protection (at heating)list6 °C
Dead zone between heating and coolinglist2 K
Cyclical transmission of current set point valuelistdon´t transmit cyclically
Increasing in standby mode at coolinglist2 K
Increasing in standby modelist2 K
Increasing in night mode at coolinglist5 K
Increasing in night modelist5 K
Set point value for heat protection (at cooling)list42 °C ( = no heat protection)
Set point value for heat protectionlist42 °C ( = no heat protection)
Current set point value in comfort modelisttransmit actual temp. setpoint (heating<>cooling)
RegulationlistPage
Setting of control parametersliststandard
Proportional band of heating controllerlist2 K
Integral action time constant of heating controllerlist150 min
Proportional band of cooling controllerlist4 K
Integral time of cooling controllerlist90 min
Heating/coolinglistauto
Transmission of actuating valuelistat change of 5 %
Cyclical transmission of actuating value everylist15 min
Report, when no energy mediumlistonly if object value = 1
Report, when heating required but heating disabledlistonly if object value = 1
Report, when cooling required but cooling disabledlistonly if object value = 1
Operating mode and operationlistPage
Operating mode after resetliststandby
Cyclical transmission of current op. mode everylistdon´t transmit cyclically
Mode setting objectslistnew: operating mode, presence, window state
Kind of presence detectorlistpresence detector
Time for comfort extensionlist2 h
Manual offset applieslistfor comfort, standby and night
Limitation of manual value increasing/decreasinglist+/- 3 K
Filter monitoringlistPage
Message for filter change after duty time of (1..127 weeks)unsignedInt 1…12712
Transmit filter replacement cyclicallylistonly at filter change
Transmit fan duty time (in hours)listnever transmit (reading is possible)
Cycle time for filter replacement and fan duty timelistevery 60 min
Monitor actuating valuelistyes
Actuating value losslistPage
Monitoring time for actuating valuelist60 min
Substitute actuating value emergency programlist20 %
Report actuating value loss cyclically (1 = no act. value)listonly if object value = 1
Download bereits bearbeitet ?listno
1. Download OKlistyes

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX FAN COIL ACTUATOR 0-10V - DIN RAIL 1.1 latest$492DCAAA2026-11-25141 KBDownload

About this file

This is the official ETS product database for the GEWISS GWA9141 (GWA9141), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from GEWISS

All GEWISS products