| 0 | Day/Hour input | Update day/hour | 3 Bytes | 10.1 time of day | CWTU |
| 1 | Daylight saving time input | 1= daylight saving/0= standard | 1 Bit | 1.1 switch | CW |
| 2 | Enabling slave function | Enable/Disable | 1 Bit | 1.3 enable | CW |
| 3 | HVAC mode input | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CW |
| 3 | Setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 3 | Setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 3 | Setpoint input | °F value | 2 Bytes | 9.27 temperature (°F) | CW |
| 3 | Setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 4 | Setpoint temporary forcing regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 5 | HVAC off mode input | Enable/Disable | 1 Bit | 1.3 enable | CW |
| 6 | HVAC economy mode input | Enable/Disable | 1 Bit | 1.3 enable | CW |
| 7 | HVAC precomfort mode input | Enable/Disable | 1 Bit | 1.3 enable | CW |
| 8 | HVAC comfort mode input | Enable/Disable | 1 Bit | 1.3 enable | CW |
| 9 | Functioning type input | Heating/Air cooling | 1 Bit | 1.100 heating/cooling | CW |
| 10 | Enable dead zone | Enable/Disable | 1 Bit | 1.3 enable | CW |
| 11 | Heating anti-freeze setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 11 | Heating anti-freeze setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 11 | Heating anti-freeze setpoint input | °F value | 2 Bytes | 9.27 temperature (°F) | CW |
| 11 | Heating anti-freeze setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 12 | Heating economy setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 12 | Heating economy setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 12 | Heating economy setpoint input | °F value | 2 Bytes | 9.27 temperature (°F) | CW |
| 12 | Heating economy setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 13 | Heating precomfort setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 13 | Heating precomfort setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 13 | Heating precomfort setpoint input | °F value | 2 Bytes | 9.27 temperature (°F) | CW |
| 13 | Heating precomfort setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 14 | Heating comfort setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 14 | Heating comfort setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 14 | Heating comfort setpoint input | °F value | 2 Bytes | 9.27 temperature (°F) | CW |
| 14 | Heating comfort setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 15 | Air-cooling high temp. protection setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 15 | Air-cooling high temp. protection setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 15 | Air-cooling high temp. protection setpoint input | °F value | 2 Bytes | 9.27 temperature (°F) | CW |
| 15 | Air-cooling high temp. protec. setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 16 | Air-cooling economy setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 16 | Air-cooling economy setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 16 | Air-cooling economy setpoint input | °F value | 2 Bytes | 9.27 temperature (°F) | CW |
| 16 | Air-cooling economy setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 17 | Air-cooling precomfort setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 17 | Air-cooling precomfort setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 17 | Air-cooling precomfort setpoint input | °F value | 2 Bytes | 9.27 temperature (°F) | CW |
| 17 | Air-cooling precomfort setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 18 | Air-cooling comfort setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 18 | Air-cooling comfort setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 18 | Air-cooling comfort setpoint input | °F value | 2 Bytes | 9.27 temperature (°F) | CW |
| 18 | Air-cooling comfort setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 19 | Heating valve switch | On/Off | 1 Bit | 1.1 switch | CRT |
| 19 | % command valve heating | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 19 | Heating/Air cooling valve switch | On/Off | 1 Bit | 1.1 switch | CRT |
| 19 | Heating/air cooling valve % command | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 20 | Heating valve status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 20 | Heating valve % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 20 | Heating/air cooling valve status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 20 | Heating/Air cooling valve % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 21 | V1 fan switching heating | On/Off | 1 Bit | 1.1 switch | CRT |
| 21 | % command fancoil speed heating | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 22 | V2 fan switching heating | On/Off | 1 Bit | 1.1 switch | CRT |
| 23 | V3 fan switching heating | On/Off | 1 Bit | 1.1 switch | CRT |
| 24 | Heating fan V1 status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 24 | Heating fancoil speed % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 25 | Heating fan V2 status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 26 | Heating fan V3 status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 27 | Heating 2° stage switching | On/Off | 1 Bit | 1.1 switch | CRT |
| 27 | % command 2° stage heating | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 28 | Heating 2° stage feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 28 | Heating 2° stage valve % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 29 | Air cooling valve % command | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 29 | Air cooling valve switch | On/Off | 1 Bit | 1.1 switch | CRT |
| 30 | Air cooling valve % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 30 | Air cooling valve status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 31 | % command fancoil speed air cooling | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 31 | V1 fan switching air cooling | On/Off | 1 Bit | 1.1 switch | CRT |
| 32 | V2 fan switching air cooling | On/Off | 1 Bit | 1.1 switch | CRT |
| 33 | V3 fan switching air cooling | On/Off | 1 Bit | 1.1 switch | CRT |
| 34 | Air cooling fancoil speed % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 34 | Air cooling fan V1 status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 35 | Air cooling fan V2 status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 36 | Air cooling fan V3 status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 37 | % command 2° stage air cooling | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 37 | Air cooling 2° stage switching | On/Off | 1 Bit | 1.1 switch | CRT |
| 38 | Air cooling 2° stage valve % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 38 | Air cooling 2° stage feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 39 | Fancoil mode input | Automatic/manual | 1 Bit | 1.1 switch | CW |
| 40 | Fan coil mode report | Automatic/manual | 1 Bit | 1.1 switch | CRT |
| 41 | KNX external sensor input | Value °C | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 41 | KNX external sensor input | °K value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 41 | KNX external sensor input | °F value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 41 | KNX floor sensor input | Value °C | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 41 | KNX floor sensor input | °K value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 41 | KNX floor sensor input | °F value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 42 | Auxiliary sensor measured temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 42 | Auxiliary sensor measured temperature | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 42 | Auxiliary sensor measured temperature | °F value | 2 Bytes | 9.27 temperature (°F) | CR |
| 42 | Auxiliary sensor measured temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 42 | Auxiliary sensor measured temperature | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 42 | Auxiliary sensor measured temperature | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 43 | Measured temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 43 | Measured temperature | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 43 | Measured temperature | °F value | 2 Bytes | 9.27 temperature (°F) | CR |
| 43 | Measured temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 43 | Measured temperature | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 43 | Measured temperature | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 44 | HVAC mode feedback | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CR |
| 44 | HVAC mode feedback | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CRT |
| 44 | Functioning setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 44 | Functioning setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 44 | Functioning setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CR |
| 44 | Functioning setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 44 | Functioning setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 44 | Functioning setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 45 | HVAC off mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CR |
| 45 | HVAC off mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CRT |
| 46 | HVAC economy mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CR |
| 46 | HVAC economy mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CRT |
| 47 | HVAC precomfort mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CR |
| 47 | HVAC precomfort mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CRT |
| 48 | HVAC comfort mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CR |
| 48 | HVAC comfort mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CRT |
| 49 | Functioning type feedback | Heating/Air cooling | 1 Bit | 1.100 heating/cooling | CRT |
| 49 | Functioning type feedback | Heating/Air cooling | 1 Bit | 1.100 heating/cooling | CR |
| 50 | Heating anti-freeze setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 50 | Heating anti-freeze setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 50 | Heating anti-freeze setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 50 | Heating anti-freeze setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 50 | Heating anti-freeze setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 50 | Heating anti-freeze setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CR |
| 51 | Heating economy setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 51 | Heating economy setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 51 | Heating economy setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 51 | Heating economy setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 51 | Heating economy setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 51 | Heating economy setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CR |
| 52 | Heating precomfort setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 52 | Heating precomfort setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 52 | Heating precomfort setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 52 | Heating precomfort setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 52 | Heating precomfort setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 52 | Heating precomfort setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CR |
| 53 | Heating comfort setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 53 | Heating comfort setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 53 | Heating comfort setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 53 | Heating comfort setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 53 | Heating comfort setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 53 | Heating comfort setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CR |
| 54 | Air cond. high temp. protection setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 54 | Air cond. high temp. protection setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 54 | Air cond. high temp. protection setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 54 | Air cond. high temp. protection setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 54 | Air cond. high temp. protection setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 54 | Air cond. high temp. protection setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CR |
| 55 | Air cooling economy setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 55 | Air cooling economy setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 55 | Air cooling economy setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 55 | Air cooling economy setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 55 | Air cooling economy setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 55 | Air cooling economy setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CR |
| 56 | Air cooling precomfort setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 56 | Air cooling precomfort setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 56 | Air cooling precomfort setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 56 | Air cooling precomfort setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 56 | Air cooling precomfort setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 56 | Air cooling precomfort setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CR |
| 57 | Air cooling comfort setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 57 | Air cooling comfort setpoint feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 57 | Air cooling comfort setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 57 | Air cooling comfort setpoint feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 57 | Air cooling comfort setpoint feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 57 | Air cooling comfort setpoint feedback | °F value | 2 Bytes | 9.1 temperature (°C) | CR |
| 58 | Current setpoint report | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 58 | Current setpoint report | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 58 | Current setpoint report | °F value | 2 Bytes | 9.27 temperature (°F) | CR |
| 58 | Current setpoint report | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 58 | Current setpoint report | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 58 | Current setpoint report | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 59 | Thermostat functioning feedback | Slave/Stand alone | 1 Bit | 1.1 switch | CR |
| 59 | Thermostat functioning feedback | Slave/Stand alone | 1 Bit | 1.1 switch | CRT |
| 60 | Feedbacks sending trigger | Send feedbacks | 1 Bit | 1.17 trigger | CW |
| 61 | Thermostat scene | Execute/Store | 1 Byte | 18.1 scene control | CW |
| 62 | Input aux 1 - Dimmer status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 62 | Input aux 1 - Status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 62 | Input aux 1 - Movement feedback | Increase/Decrease | 1 Bit | 1.8 up/down | CW |
| 63 | Input aux 1 - 14 byte value | Characters ISO 8859-1 | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 63 | Input aux 1 - 1 bit value | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 63 | Input aux 1 - 2 bit value | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 63 | Input aux 1 - 1 byte value | Unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 63 | Input aux 1 - 1 byte value | Signed value | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 63 | Input aux 1 - 1 byte value | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 63 | Input aux 1 - 1 byte value | HVAC mode | 1 Byte | 20.102 HVAC mode | CRT |
| 63 | Input aux 1 - 2 byte value | Unsigned value | 2 Bytes | 7.1 pulses | CRT |
| 63 | Input aux 1 - 2 byte value | Signed value | 2 Bytes | 8.1 pulses difference | CRT |
| 63 | Input aux 1 - 4 byte value | Unsigned value | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 63 | Input aux 1 - 4 byte value | Signed value | 4 Bytes | 13.1 counter pulses (signed) | CRT |
| 63 | Input aux 1 - Switching | On/Off | 1 Bit | 1.1 switch | CRT |
| 63 | Input aux 1 - Shutter movement | Up/Down | 1 Bit | 1.8 up/down | CRT |
| 63 | Input aux 1 - Scene | Execute/Store | 1 Byte | 18.1 scene control | CRT |
| 63 | Input aux 1 - Window status feedback | Open/Closed | 1 Bit | 1.19 window/door | CRT |
| 63 | Input aux 1 - Window status feedback | Open/Closed | 1 Bit | 1.19 window/door | CR |
| 63 | Inputs aux 1/2 - Switching | On/Off | 1 Bit | 1.1 switch | CRT |
| 63 | Inputs aux 1/2 - Shutter movement | Up/Down | 1 Bit | 1.8 up/down | CRT |
| 64 | Input aux 1 - Brightness control | Increase/Decrease | 4 Bit | 3.7 dimming control | CRT |
| 64 | Input aux 1 - Shutter stop/Louvres control | Stop/Step | 1 Bit | 1.7 step | CRT |
| 64 | Input aux 1 - Scene storing trigger | Store | 1 Bit | 1.17 trigger | CW |
| 64 | Inputs aux 1/2 - Brightness control | Increase/Decrease | 4 Bit | 3.7 dimming control | CRT |
| 64 | Inputs aux 1/2 - Shutter stop/Louvres control | Stop/Step | 1 Bit | 1.7 step | CRT |
| 65 | Input aux 2 - Dimmer status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 65 | Input aux 2 - Status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 65 | Input aux 2 - Movement feedback | Increase/Decrease | 1 Bit | 1.8 up/down | CW |
| 66 | Input aux 2 - 14 byte value | Characters ISO 8859-1 | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 66 | Input aux 2 - 1 bit value | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 66 | Input aux 2 - 2 bit value | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 66 | Input aux 2 - 1 byte value | Unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 66 | Input aux 2 - 1 byte value | Signed value | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 66 | Input aux 2 - 1 byte value | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 66 | Input aux 2 - 1 byte value | HVAC mode | 1 Byte | 20.102 HVAC mode | CRT |
| 66 | Input aux 2 - 2 byte value | Unsigned value | 2 Bytes | 7.1 pulses | CRT |
| 66 | Input aux 2 - 2 byte value | Signed value | 2 Bytes | 8.1 pulses difference | CRT |
| 66 | Input aux 2 - 4 byte value | Unsigned value | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 66 | Input aux 2 - 4 byte value | Signed value | 4 Bytes | 13.1 counter pulses (signed) | CRT |
| 66 | Input aux 2 - Switching | On/Off | 1 Bit | 1.1 switch | CRT |
| 66 | Input aux 2 - Shutter movement | Up/Down | 1 Bit | 1.8 up/down | CRT |
| 66 | Input aux 2 - Scene | Execute/Store | 1 Byte | 18.1 scene control | CRT |
| 67 | Input aux 2 - Brightness control | Increase/Decrease | 4 Bit | 3.7 dimming control | CRT |
| 67 | Input aux 2 - Shutter stop/Louvres control | Stop/Step | 1 Bit | 1.7 step | CRT |
| 67 | Input aux 2 - Scene storing trigger | Store | 1 Bit | 1.17 trigger | CW |
| 68 | Output aux - Status | On/Off | 1 Bit | 1.1 switch | CR |
| 68 | Output aux - Status | On/Off | 1 Bit | 1.1 switch | CRT |
| 69 | Output aux - Switching | On/Off | 1 Bit | 1.1 switch | CW |
| 70 | Output aux - Timed switching | Start/Stop | 1 Bit | 1.10 start/stop | CW |
| 71 | Output aux - Priority command | On/Off forced positioning | 2 Bit | 2.1 switch control | CW |
| 72 | Output aux - Scene | Execute/Store | 1 Byte | 18.1 scene control | CW |
| 73 | Setpoint regulation range setting | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 74 | Device 1 - Send HVAC mode | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CRT |
| 74 | Device 1 - Setpoint sending | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 74 | Device 1 - Setpoint sending | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 74 | Device 1 - Setpoint sending | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 75 | Device 1 - Send functioning type | Heating/Air cooling | 1 Bit | 1.100 heating/cooling | CRT |
| 76 | Device 1 - Functioning type status feedback | Heating/Air cooling | 1 Bit | 1.100 heating/cooling | CWTU |
| 77 | Device 1 - HVAC mode status feedback | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CWTU |
| 77 | Device 1 - Reference setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 77 | Device 1 - Reference setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 77 | Device 1 - Reference setpoint input | °F value | 2 Bytes | 9.1 temperature (°C) | CW |
| 78 | Device 1 - Setpoint status feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 78 | Device 1 - Setpoint status feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 78 | Device 1 - Setpoint status feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 79 | Device 1 - Measured temperature status feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 79 | Device 1 - Measured temperature status feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 79 | Device 1 - Measured temperature status feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 80 | Device 1 - Measured relative humidity feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CWTU |
| 81 | Device 2 - Setpoint sending | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 81 | Device 2 - Setpoint sending | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 81 | Device 2 - Setpoint sending | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 81 | Device 2 - Send HVAC mode | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CRT |
| 82 | Device 2 - Send functioning type | Heating/Air cooling | 1 Bit | 1.100 heating/cooling | CRT |
| 83 | Device 2 - Functioning type status feedback | Heating/Air cooling | 1 Bit | 1.100 heating/cooling | CWTU |
| 84 | Device 2 - HVAC mode status feedback | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CWTU |
| 84 | Device 2 - Reference setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 84 | Device 2 - Reference setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 84 | Device 2 - Reference setpoint input | °F value | 2 Bytes | 9.1 temperature (°C) | CW |
| 85 | Device 2 - Setpoint status feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 85 | Device 2 - Setpoint status feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 85 | Device 2 - Setpoint status feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 86 | Device 2 - Measured temperature status feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 86 | Device 2 - Measured temperature status feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 86 | Device 2 - Measured temperature status feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 87 | Device 2 - Measured relative humidity feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CWTU |
| 88 | Device 3 - Send HVAC mode | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CRT |
| 88 | Device 3 - Setpoint sending | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 88 | Device 3 - Setpoint sending | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 88 | Device 3 - Setpoint sending | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 89 | Device 3 - Send functioning type | Heating/Air cooling | 1 Bit | 1.100 heating/cooling | CRT |
| 90 | Device 3 - Functioning type status feedback | Heating/Air cooling | 1 Bit | 1.100 heating/cooling | CWTU |
| 91 | Device 3 - HVAC mode status feedback | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CWTU |
| 91 | Device 3 - Reference setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 91 | Device 3 - Reference setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 91 | Device 3 - Reference setpoint input | °F value | 2 Bytes | 9.1 temperature (°C) | CW |
| 92 | Device 3 - Setpoint status feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 92 | Device 3 - Setpoint status feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 92 | Device 3 - Setpoint status feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 93 | Device 3 - Measured temperature status feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 93 | Device 3 - Measured temperature status feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 93 | Device 3 - Measured temperature status feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 94 | Device 3 - Measured relative humidity feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CWTU |
| 95 | Device 4 - Send HVAC mode | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CRT |
| 95 | Device 4 - Setpoint sending | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 95 | Device 4 - Setpoint sending | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 95 | Device 4 - Setpoint sending | °F value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 96 | Device 4 - Send functioning type | Heating/Air cooling | 1 Bit | 1.100 heating/cooling | CRT |
| 97 | Device 4 - Functioning type status feedback | Heating/Air cooling | 1 Bit | 1.100 heating/cooling | CWTU |
| 98 | Device 4 - HVAC mode status feedback | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CWTU |
| 98 | Device 4 - Reference setpoint input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 98 | Device 4 - Reference setpoint input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 98 | Device 4 - Reference setpoint input | °F value | 2 Bytes | 9.1 temperature (°C) | CW |
| 99 | Device 4 - Setpoint status feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 99 | Device 4 - Setpoint status feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 99 | Device 4 - Setpoint status feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 100 | Device 4 - Measured temperature status feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 100 | Device 4 - Measured temperature status feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 100 | Device 4 - Measured temperature status feedback | °F value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 101 | Device 4 - Measured relative humidity feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CWTU |
| 102 | Humidity external sensor input | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CWTU |
| 103 | Relative humidity measured | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 103 | Relative humidity measured | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CR |
| 104 | Relative humidity estimated | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 104 | Relative humidity estimated | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CR |
| 105 | Specific humidity | Value [g/kg] | 4 Bytes | 14.5 amplitude | CRT |
| 105 | Specific humidity | Value [g/kg] | 4 Bytes | 14.5 amplitude | CR |
| 106 | Dew point temperature | Value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 106 | Dew point temperature | Value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 106 | Dew point temperature | Value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 106 | Dew point temperature | Value [°C] | 2 Bytes | 9.1 temperature (°C) | CR |
| 106 | Dew point temperature | Value [°K] | 2 Bytes | 9.2 temperature difference (K) | CR |
| 106 | Dew point temperature | Value [°F] | 2 Bytes | 9.27 temperature (°F) | CR |
| 107 | Dew point temperature alarm enabling | Enable/Disable | 1 Bit | 1.2 boolean | CW |
| 108 | Dew point temperature alarm enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 109 | Dew point temperature alarm limit regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 110 | Dew point temperature alarm threshold feedback | Value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 110 | Dew point temperature alarm threshold feedback | Value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 110 | Dew point temperature alarm threshold feedback | Value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 111 | Dew point temperature alarm output | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 111 | Dew point temperature alarm output | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 111 | Dew point temperature alarm output | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 111 | Dew point temperature alarm output | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 111 | Dew point temperature alarm output | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 111 | Dew point temperature alarm output | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 111 | Dew point temperature alarm output | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 111 | Dew point temperature alarm output | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 112 | Relative humidity threshold 1 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 112 | Relative humidity threshold 1 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 113 | Relative humidity threshold 1 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 114 | Relative humidity threshold 1 value input | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CW |
| 114 | Relative humidity threshold 1 value regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 115 | Relative humidity threshold 1 feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 116 | Relative humidity threshold 1 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 116 | Relative humidity threshold 1 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 116 | Relative humidity threshold 1 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 116 | Relative humidity threshold 1 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 116 | Relative humidity threshold 1 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 116 | Relative humidity threshold 1 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 116 | Relative humidity threshold 1 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 116 | Relative humidity threshold 1 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 116 | Relative humidity threshold 1 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 116 | Relative humidity threshold 1 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 116 | Relative humidity threshold 1 output A | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 117 | Relative humidity threshold 1 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 117 | Output A relative humidity threshold 1 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 117 | Output A relative humidity threshold 1 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 117 | Output A relative humidity threshold 1 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 117 | Output A relative humidity threshold 1 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 118 | Relative humidity threshold 1 output B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 118 | Relative humidity threshold 1 output B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 118 | Relative humidity threshold 1 output B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 118 | Relative humidity threshold 1 output B | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 118 | Relative humidity threshold 1 output B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 118 | Relative humidity threshold 1 output B | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 118 | Relative humidity threshold 1 output B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 118 | Relative humidity threshold 1 output B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 118 | Relative humidity threshold 1 output B | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 118 | Relative humidity threshold 1 output B | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 118 | Relative humidity threshold 1 output B | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 119 | Relative humidity threshold 1 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 119 | Output B relative humidity threshold 1 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 119 | Output B relative humidity threshold 1 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 119 | Output B relative humidity threshold 1 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 119 | Output B relative humidity threshold 1 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 120 | Relative humidity threshold 1 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 120 | Relative humidity threshold 1 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 120 | Relative humidity threshold 1 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 120 | Relative humidity threshold 1 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 120 | Relative humidity threshold 1 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 120 | Relative humidity threshold 1 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 120 | Relative humidity threshold 1 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 120 | Relative humidity threshold 1 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 120 | Relative humidity threshold 1 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 120 | Relative humidity threshold 1 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 120 | Relative humidity threshold 1 output C | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 121 | Relative humidity threshold 1 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 121 | Output C relative humidity threshold 1 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 121 | Output C relative humidity threshold 1 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 121 | Output C relative humidity threshold 1 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 121 | Output C relative humidity threshold 1 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 122 | Relative humidity threshold 1 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 122 | Relative humidity threshold 1 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 122 | Relative humidity threshold 1 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 122 | Relative humidity threshold 1 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 122 | Relative humidity threshold 1 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 122 | Relative humidity threshold 1 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 122 | Relative humidity threshold 1 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 122 | Relative humidity threshold 1 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 122 | Relative humidity threshold 1 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 122 | Relative humidity threshold 1 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 122 | Relative humidity threshold 1 output D | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 123 | Relative humidity threshold 1 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 123 | Output D relative humidity threshold 1 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 123 | Output D relative humidity threshold 1 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 123 | Output D relative humidity threshold 1 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 123 | Output D relative humidity threshold 1 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 124 | Relative humidity threshold 2 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 124 | Relative humidity threshold 2 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 125 | Relative humidity threshold 2 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 126 | Relative humidity threshold 2 value input | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CW |
| 126 | Relative humidity threshold 2 value regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 127 | Relative humidity threshold 2 feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 128 | Relative humidity threshold 2 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 128 | Relative humidity threshold 2 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 128 | Relative humidity threshold 2 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 128 | Relative humidity threshold 2 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 128 | Relative humidity threshold 2 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | Relative humidity threshold 2 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 128 | Relative humidity threshold 2 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 128 | Relative humidity threshold 2 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 128 | Relative humidity threshold 2 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 128 | Relative humidity threshold 2 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 128 | Relative humidity threshold 2 output A | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 129 | Relative humidity threshold 2 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 129 | Output A relative humidity threshold 2 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 129 | Output A relative humidity threshold 2 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 129 | Output A relative humidity threshold 2 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 129 | Output A relative humidity threshold 2 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 130 | Relative humidity threshold 2 output B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 130 | Relative humidity threshold 2 output B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 130 | Relative humidity threshold 2 output B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 130 | Relative humidity threshold 2 output B | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 130 | Relative humidity threshold 2 output B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 130 | Relative humidity threshold 2 output B | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 130 | Relative humidity threshold 2 output B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 130 | Relative humidity threshold 2 output B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 130 | Relative humidity threshold 2 output B | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 130 | Relative humidity threshold 2 output B | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 130 | Relative humidity threshold 2 output B | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 131 | Relative humidity threshold 2 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 131 | Output B relative humidity threshold 2 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 131 | Output B relative humidity threshold 2 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 131 | Output B relative humidity threshold 2 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 131 | Output B relative humidity threshold 2 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 132 | Relative humidity threshold 2 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 132 | Relative humidity threshold 2 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 132 | Relative humidity threshold 2 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 132 | Relative humidity threshold 2 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 132 | Relative humidity threshold 2 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 132 | Relative humidity threshold 2 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 132 | Relative humidity threshold 2 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 132 | Relative humidity threshold 2 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 132 | Relative humidity threshold 2 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 132 | Relative humidity threshold 2 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 132 | Relative humidity threshold 2 output C | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 133 | Relative humidity threshold 2 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 133 | Output C relative humidity threshold 2 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 133 | Output C relative humidity threshold 2 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 133 | Output C relative humidity threshold 2 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 133 | Output C relative humidity threshold 2 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 134 | Relative humidity threshold 2 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 134 | Relative humidity threshold 2 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 134 | Relative humidity threshold 2 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 134 | Relative humidity threshold 2 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 134 | Relative humidity threshold 2 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 134 | Relative humidity threshold 2 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 134 | Relative humidity threshold 2 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 134 | Relative humidity threshold 2 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 134 | Relative humidity threshold 2 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 134 | Relative humidity threshold 2 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 134 | Relative humidity threshold 2 output D | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 135 | Relative humidity threshold 2 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 135 | Output D relative humidity threshold 2 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 135 | Output D relative humidity threshold 2 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 135 | Output D relative humidity threshold 2 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 135 | Output D relative humidity threshold 2 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 136 | Relative humidity threshold 3 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 136 | Relative humidity threshold 3 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 137 | Relative humidity threshold 3 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 138 | Relative humidity threshold 3 value input | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CW |
| 138 | Relative humidity threshold 3 value regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 139 | Relative humidity threshold 3 feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 140 | Relative humidity threshold 3 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 140 | Relative humidity threshold 3 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 140 | Relative humidity threshold 3 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 140 | Relative humidity threshold 3 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 140 | Relative humidity threshold 3 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 140 | Relative humidity threshold 3 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 140 | Relative humidity threshold 3 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 140 | Relative humidity threshold 3 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 140 | Relative humidity threshold 3 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 140 | Relative humidity threshold 3 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 140 | Relative humidity threshold 3 output A | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 141 | Relative humidity threshold 3 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 141 | Output A relative humidity threshold 3 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 141 | Output A relative humidity threshold 3 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 141 | Output A relative humidity threshold 3 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 141 | Output A relative humidity threshold 3 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 142 | Relative humidity threshold 3 output B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 142 | Relative humidity threshold 3 output B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 142 | Relative humidity threshold 3 output B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 142 | Relative humidity threshold 3 output B | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 142 | Relative humidity threshold 3 output B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 142 | Relative humidity threshold 3 output B | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 142 | Relative humidity threshold 3 output B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 142 | Relative humidity threshold 3 output B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 142 | Relative humidity threshold 3 output B | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 142 | Relative humidity threshold 3 output B | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 142 | Relative humidity threshold 3 output B | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 143 | Relative humidity threshold 3 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 143 | Output B relative humidity threshold 3 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 143 | Output B relative humidity threshold 3 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 143 | Output B relative humidity threshold 3 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 143 | Output B relative humidity threshold 3 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 144 | Relative humidity threshold 3 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 144 | Relative humidity threshold 3 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 144 | Relative humidity threshold 3 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 144 | Relative humidity threshold 3 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 144 | Relative humidity threshold 3 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 144 | Relative humidity threshold 3 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 144 | Relative humidity threshold 3 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 144 | Relative humidity threshold 3 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 144 | Relative humidity threshold 3 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 144 | Relative humidity threshold 3 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 144 | Relative humidity threshold 3 output C | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 145 | Relative humidity threshold 3 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 145 | Output C relative humidity threshold 3 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 145 | Output C relative humidity threshold 3 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 145 | Output C relative humidity threshold 3 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 145 | Output C relative humidity threshold 3 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 146 | Relative humidity threshold 3 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 146 | Relative humidity threshold 3 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 146 | Relative humidity threshold 3 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 146 | Relative humidity threshold 3 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 146 | Relative humidity threshold 3 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 146 | Relative humidity threshold 3 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 146 | Relative humidity threshold 3 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 146 | Relative humidity threshold 3 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 146 | Relative humidity threshold 3 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 146 | Relative humidity threshold 3 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 146 | Relative humidity threshold 3 output D | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 147 | Relative humidity threshold 3 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 147 | Output D relative humidity threshold 3 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 147 | Output D relative humidity threshold 3 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 147 | Output D relative humidity threshold 3 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 147 | Output D relative humidity threshold 3 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 148 | Relative humidity threshold 4 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 148 | Relative humidity threshold 4 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 149 | Relative humidity threshold 4 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 150 | Relative humidity threshold 4 value input | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CW |
| 150 | Relative humidity threshold 4 value regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 151 | Relative humidity threshold 4 feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 152 | Relative humidity threshold 4 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 152 | Relative humidity threshold 4 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 152 | Relative humidity threshold 4 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 152 | Relative humidity threshold 4 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 152 | Relative humidity threshold 4 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 152 | Relative humidity threshold 4 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 152 | Relative humidity threshold 4 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 152 | Relative humidity threshold 4 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 152 | Relative humidity threshold 4 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 152 | Relative humidity threshold 4 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 152 | Relative humidity threshold 4 output A | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 153 | Relative humidity threshold 4 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 153 | Output A relative humidity threshold 4 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 153 | Output A relative humidity threshold 4 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 153 | Output A relative humidity threshold 4 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 153 | Output A relative humidity threshold 4 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 154 | Relative humidity threshold 4 output B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 154 | Relative humidity threshold 4 output B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 154 | Relative humidity threshold 4 output B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 154 | Relative humidity threshold 4 output B | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 154 | Relative humidity threshold 4 output B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 154 | Relative humidity threshold 4 output B | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 154 | Relative humidity threshold 4 output B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 154 | Relative humidity threshold 4 output B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 154 | Relative humidity threshold 4 output B | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 154 | Relative humidity threshold 4 output B | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 154 | Relative humidity threshold 4 output B | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 155 | Relative humidity threshold 4 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 155 | Output B relative humidity threshold 4 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 155 | Output B relative humidity threshold 4 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 155 | Output B relative humidity threshold 4 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 155 | Output B relative humidity threshold 4 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 156 | Relative humidity threshold 4 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 156 | Relative humidity threshold 4 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 156 | Relative humidity threshold 4 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 156 | Relative humidity threshold 4 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 156 | Relative humidity threshold 4 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 156 | Relative humidity threshold 4 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 156 | Relative humidity threshold 4 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 156 | Relative humidity threshold 4 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 156 | Relative humidity threshold 4 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 156 | Relative humidity threshold 4 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 156 | Relative humidity threshold 4 output C | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 157 | Relative humidity threshold 4 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 157 | Output C relative humidity threshold 4 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 157 | Output C relative humidity threshold 4 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 157 | Output C relative humidity threshold 4 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 157 | Output C relative humidity threshold 4 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 158 | Relative humidity threshold 4 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 158 | Relative humidity threshold 4 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 158 | Relative humidity threshold 4 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 158 | Relative humidity threshold 4 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 158 | Relative humidity threshold 4 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 158 | Relative humidity threshold 4 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 158 | Relative humidity threshold 4 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 158 | Relative humidity threshold 4 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 158 | Relative humidity threshold 4 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 158 | Relative humidity threshold 4 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 158 | Relative humidity threshold 4 output D | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 159 | Relative humidity threshold 4 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 159 | Output D relative humidity threshold 4 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 159 | Output D relative humidity threshold 4 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 159 | Output D relative humidity threshold 4 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 159 | Output D relative humidity threshold 4 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 160 | Relative humidity threshold 5 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 160 | Relative humidity threshold 5 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 161 | Relative humidity threshold 5 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 162 | Relative humidity threshold 5 value input | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CW |
| 162 | Relative humidity threshold 5 value regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 163 | Relative humidity threshold 5 feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 164 | Relative humidity threshold 5 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 164 | Relative humidity threshold 5 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 164 | Relative humidity threshold 5 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 164 | Relative humidity threshold 5 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 164 | Relative humidity threshold 5 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 164 | Relative humidity threshold 5 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 164 | Relative humidity threshold 5 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 164 | Relative humidity threshold 5 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 164 | Relative humidity threshold 5 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 164 | Relative humidity threshold 5 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 164 | Relative humidity threshold 5 output A | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 165 | Relative humidity threshold 5 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 165 | Output A relative humidity threshold 5 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 165 | Output A relative humidity threshold 5 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 165 | Output A relative humidity threshold 5 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 165 | Output A relative humidity threshold 5 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 166 | Relative humidity threshold 5 output B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 166 | Relative humidity threshold 5 output B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 166 | Relative humidity threshold 5 output B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 166 | Relative humidity threshold 5 output B | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 166 | Relative humidity threshold 5 output B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 166 | Relative humidity threshold 5 output B | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 166 | Relative humidity threshold 5 output B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 166 | Relative humidity threshold 5 output B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 166 | Relative humidity threshold 5 output B | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 166 | Relative humidity threshold 5 output B | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 166 | Relative humidity threshold 5 output B | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 167 | Relative humidity threshold 5 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 167 | Output B relative humidity threshold 5 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 167 | Output B relative humidity threshold 5 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 167 | Output B relative humidity threshold 5 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 167 | Output B relative humidity threshold 5 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 168 | Relative humidity threshold 5 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 168 | Relative humidity threshold 5 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 168 | Relative humidity threshold 5 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 168 | Relative humidity threshold 5 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 168 | Relative humidity threshold 5 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 168 | Relative humidity threshold 5 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 168 | Relative humidity threshold 5 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 168 | Relative humidity threshold 5 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 168 | Relative humidity threshold 5 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 168 | Relative humidity threshold 5 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 168 | Relative humidity threshold 5 output C | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 169 | Relative humidity threshold 5 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 169 | Output C relative humidity threshold 5 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 169 | Output C relative humidity threshold 5 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 169 | Output C relative humidity threshold 5 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 169 | Output C relative humidity threshold 5 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 170 | Relative humidity threshold 5 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 170 | Relative humidity threshold 5 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 170 | Relative humidity threshold 5 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 170 | Relative humidity threshold 5 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 170 | Relative humidity threshold 5 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 170 | Relative humidity threshold 5 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 170 | Relative humidity threshold 5 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 170 | Relative humidity threshold 5 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 170 | Relative humidity threshold 5 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 170 | Relative humidity threshold 5 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 170 | Relative humidity threshold 5 output D | Setpoint value [°F] | 2 Bytes | 9.27 temperature (°F) | CRT |
| 171 | Relative humidity threshold 5 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 171 | Output D relative humidity threshold 5 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 171 | Output D relative humidity threshold 5 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 171 | Output D relative humidity threshold 5 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 171 | Output D relative humidity threshold 5 reference | Setpoint [°F] | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 172 | Season selection input | 1=Summer / 0=Winter | 1 Bit | 1.2 boolean | CWTU |
| 172 | Season selection input | 1=Winter / 0=Summer | 1 Bit | 1.2 boolean | CWTU |
| 173 | Thermal comfort status feedback | 1=Comfortable/0=Uncomfortable | 1 Bit | 1.2 boolean | CRT |