GWA9140

GEWISS · Order number GWA9140 · Climate control devices › Fan Coil Actuators

Download .knxprod KNX FAN COIL ACTUATOR - DIN RAIL 1.2 · 142 KB

Product

ManufacturerGEWISS
Product nameGWA9140
Order numberGWA9140
Product textKNX FAN COIL ACTUATOR - DIN RAIL
HardwareKNX FAN COIL ACTUATOR - DIN RAIL
MediumTwisted Pair
Bus current (mA)7.5
Rail mountedYes
Width (mm)70
RegistrationCertified · 2020-04-01
Languagesde-DE, en-US, es-ES, it-IT, fr-FR, nl-NL
Catalog entryM-0019_H-4920200-1-O0048_HP-492B-12-EFF4-O0048_CI-GWA9140-1
FingerprintEFF4
SHA-256fd57c013df42236e9f36ebc10b6f10a9020db32bcc0dde6d820e03b726792b77
First seen2026-11-25
Markets59 markets

Application program: KNX FAN COIL ACTUATOR - DIN RAIL 1.2

Application number$492B
Version1.2
Mask versionMV-0021 (2.1)
KNX Data SecureNo
Minimum ETS version4.0
Parameters183
Group objects55
Group objects (55)
NoNameFunctionSizeDPTFlags
0Actuating value heatingreceive1 ByteCRWU
0Actuating value heating/coolingtransmit1 ByteCRTU
0Actuating value heating/coolingreceive1 ByteCRWU
0Actuating value heatingtransmit1 ByteCRTU
0Actuating value coolingtransmit1 ByteCRTU
0Actuating value for fanreceive1 ByteCRWU
0Actuating value coolingreceive1 ByteCRWU
1enable cooling1 = enable cooling1 BitCRWU
1Actuating value coolingreceive1 ByteCRWU
1Heating/coolingHeating = 0, Cooling = 11 BitCRWU
1Actuating value coolingtransmit1 ByteCRTU
1disable heating1 = heating disabled1 BitCRWU
2Heating statusreport1 BitCRTU
3Cooling statusreport1 BitCRTU
4Fan stepreport1 ByteCRTU
5Auxilliary relaySwitching1 BitCRWU
5Auxilliary relay statusreport1 BitCRTU
6Lock additional ventilation1 = lock1 BitCRWU
7Fan lock1 = lock1 BitCRWU
8Forced fan stepfan control with % value1 ByteCRWU
9Limitation of fan step in %0=fan OFF 1..100%=max.step1 ByteCRWU
10Fan offreport1 BitCRTU
11Fan step 1report1 BitCRTU
12Fan step 2report1 BitCRTU
13Fan step 3report1 BitCRTU
14Status of window contact at E1report1 BitCRTU
14Actual value from E1report2 BytesCRTU
15Fan auto/forcedreceive: auto=1, forced=01 BitCRWU
15Fan auto/forcedreceive: forced=1, auto=01 BitCRWU
16Drip tray monitoring statusreport1 BitCRTU
16Drip tray monitoring statusinput1 BitCRWU
16Status of window contact at E2report1 BitCRTU
17Dew point alarminput1 BitCRWU
18Outdoor temperatureinput2 BytesCRWU
19Adjust set pointdelta in K2 BytesCRTU
19Adjust set pointvalue in °C2 BytesCRTU
20sensor failuresensor failure1 BitCRTU
20Actuating value loss1 = actuating value loss1 BitCRTU
21Operating mode presetoperating mode preset1 ByteCRWU
21Night mode <-> Standby1 = night mode1 BitCRWU
22Presenceinput for presence signal1 BitCRWU
22Comfort1 = comfort mode1 BitCRWU
23Windowinput for window contact1 BitCRWU
23Frost protection1 = frost protection1 BitCRWU
24Current operating modetransmit1 ByteCRTU
25Manual adjustmentreceive2 BytesCRWU
26Base set pointreceive2 BytesCRWU
27Current set point valuetransmit2 BytesCRTU
28Heating/coolingswitch1 BitCRWU
29No energy medium1 = wrong energy medium1 BitCRTU
29heating required but heating disabled1 = heating disabled1 BitCRTU
29cooling required but cooling disabled1 = cooling disabled1 BitCRTU
30Fan duty time since last filter changeTime in hours2 BytesCRTU
31Change filter1 = change 0 = Reset1 BitCRWTU
32Testmode activereport1 BitCRTU
Parameters (129)
ParameterTypeDefault
1. Download OKlistyes
Download bereits bearbeitet ?listno
GenerallistPage
Supported functionslistheating and cooling
Only ventilationlistyes
Heating installationlistfan coil
Model of heat exchangerlistfan coil
Cooling installationlistfan coil
Kind of installationlist2-pipe system
Kind of used controlerlistremote controller
Test modelistdisabled
Report filter changelistno
activate monitoring of actuating valuelistno
Switch fan between Auto and forced modelistvia obj. Auto/forced, forced = 1
FanlistPage
Number of fan stepslist3 steps
Switch-on threshold for fan step 1list10 %
Switch-on threshold for fan step 2list40 %
Switch-on threshold for fan step 3list70 %
Fan starting strategylistdirectly
Switching delay between 2 fan stepslist0,5 s
Minimum time to stay within a fan steplist2 min
Hysteresis between the fan stepslist10 %
Additional ventilationlistno
Warm startlistno warm start
Follow-up time for utilisation of the remaining energylistno follow-up
Cyclical transmission of fan steplistFormat %, don´t transmit cyclically
Heating valvelistPage
Heating/cooling valvelistPage
Cooling valvelistPage
Type of valvelist3-point valve
Direction of control action of valvelistnormal
Runtime for 100 % travel (5 .. 2000s)unsignedInt 5…200090
PWM timelist5 min
Time for the heating valve to closelist3 min
Time for the valve to closelist3 min
Time for the cooling valve to closelist3 min
New position at change oflist5 %
Open for actuating value abovelist0,4 %
Minimum valve positionlist0 %
Maximum valve position abovelist50 %
Maximum valve positionlist100 %
Cyclical transmission of heating statuslistdon´t transmit cyclically
Delay between heating and coolinglist0 min
Cyclical transmission of cooling status everylistdon´t transmit cyclically
Cyclical transmission of heating/cooling statuslistdon´t transmit cyclically
Auxilliary relaylistPage
Switch ON auxilliary relaylistvia object
Cyclical transmission of aux. relay status everylistdon´t transmit cyclically
E1listPage
E1 in case of remote controllerlistyes
E1 in case of internal controllerlistyes
Function of E1listE1 = window contact
Direction of operation of window contactlistcontact closed = window closed
Actual value offset in 0.1 K (-50..50)signedInt -50…500
Transmission of actual value at change oflistevery 0,5 K
Cyclical transmission of window contactlistdon´t transmit cyclically
Cyclical transmission of actual valuelistdon´t transmit cyclically
Actuating value in case of sensor failure or short circuitlist20 %
Report sensor failure (1 = failure)listonly if object value = 1
Report sensor failure (1 = failure)listonly if object value = 1
Report cyclicallylistevery 30 min
Drip tray monitoringlistPage
E2listPage
Source for drip tray monitoringlistE2
Direction of operation of contactlistcontact closed = condensate
Direction of action of E2listcontact closed = condensate
Direction of operation of contactlistcontact closed = window closed
Behaviour in case of drip tray alarmlistcooling and fan OFF
Cyclical transmission of alarm statuslistdon´t transmit cyclically
Cyclical transmission of E2 statuslistdon´t transmit cyclically
Set point adjustmentlistPage
Set point adjustmentlistyes
Set point adjustment fromlist25 °C
Adjustmentlist1 K per 3 K outdoor temperature
Format of the adjustment valuelistrelative
Base set point without adjustmentlist21 °C
Cyclical transmission of set point adjustmentlistdon´t transmit cyclically
Use set point adjustment for regulationlistno
Set point valueslistPage
Set point valueslistyes
Base set point after resetlist21 °C
Reduction in standby operating modelist2 K
Reduction in standby operating mode at heatinglist2 K
Reduction in night operating modelist5 K
Reduction in night operating mode at heatinglist5 K
Set point value for frost protection modelist6 °C
Set point value for frost protection (at heating)list6 °C
Dead zone between heating and coolinglist2 K
Cyclical transmission of current set point valuelistdon´t transmit cyclically
Increasing in standby mode at coolinglist2 K
Increasing in standby modelist2 K
Increasing in night mode at coolinglist5 K
Increasing in night modelist5 K
Set point value for heat protection (at cooling)list42 °C ( = no heat protection)
Set point value for heat protectionlist42 °C ( = no heat protection)
Current set point value in comfort modelisttransmit actual temp. setpoint (heating<>cooling)
RegulationlistPage
Regulationlistyes
Setting of control parametersliststandard
Proportional band of heating controllerlist2 K
Integral action time constant of heating controllerlist150 min
Proportional band of cooling controllerlist4 K
Integral time of cooling controllerlist90 min
Cyclical transmission of actuating value everylist15 min
Heating/coolinglistauto
Report, when no energy mediumlistonly if object value = 1
Transmission of actuating valuelistat change of 5 %
Report, when heating required but heating disabledlistonly if object value = 1
Report, when cooling required but cooling disabledlistonly if object value = 1
Operating mode and operationlistPage
Operating modelistyes
Operating mode after resetliststandby
Cyclical transmission of current op. mode everylistdon´t transmit cyclically
Mode setting objectslistnew: operating mode, presence, window state
Kind of presence detectorlistpresence detector
Time for comfort extensionlist2 h
Limitation of manual value increasing/decreasinglist+/- 3 K
Filter monitoringlistPage
Message for filter change after duty time of (1..127 weeks)unsignedInt 1…12712
transmit filter replacement cyclicallylistonly at filter change
transmit fan duty time (in hours)listnever transmit (reading is possible)
Cycle time for filter replacement and fan duty timelistevery 60 min
Monitor actuating valuelistyes
Actuating value losslistPage
Monitoring time for actuating valuelist60 min
Substitute actuating value emergency programlist20 %
Report actuating value loss cyclically (1 = no act. value)listonly if object value = 1
Objects 15 and 20 visiblelistyes

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX FAN COIL ACTUATOR - DIN RAIL 1.2 latest$492BEFF42026-11-25142 KBDownload

About this file

This is the official ETS product database for the GEWISS GWA9140 (GWA9140), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.