KNX Database

GWA9103

GEWISS · Order number GWA9103 · Actuators › Switching actuators, 3 outputs

Download .knxprod KNX Actuator 3 channels 16AX with energy measurement S 1.0 1.0 · 173 KB

Product

ManufacturerGEWISS
Product nameGWA9103
Order numberGWA9103
Product textKNX Actuator 3 channels 16AX with energy measurement
HardwareKNX Actuator 3 channels 16AX with energy meter - DIN
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)72
RegistrationCertified · 2020-07-06
Languagesde-DE, en-US, es-ES, it-IT
Catalog entryM-0019_H-A9103-0_HP-5129-10-6533_CI-GWA9103-1
Fingerprint6533
SHA-2560155dfcc0f0d2976fec5978356b6b33b5883fc152be8877c4db3dab457b17edf
First seen2026-11-25
Markets59 markets

Application program: KNX Actuator 3 channels 16AX with energy measurement S 1.0 1.0

Application number$5129
Version1.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters603
Group objects276
Group objects (276)
NoNameFunctionSizeDPTFlags
0Ch.1 - StatusOn/Off status1 Bit1.1 switchCRT
0Ch.1 - StatusOn/Off status1 Bit1.1 switchCR
1Ch.1 - SwitchOn/Off1 Bit1.1 switchCW
2Ch.1 - Delayed switchingOn/Off1 Bit1.1 switchCW
3Ch.1 - Delay on activationSet value2 Bytes7.5 time (s)CW
4Ch.1 - Delay on deactivationSet value2 Bytes7.5 time (s)CW
5Ch.1 - Timed switchStart/Stop1 Bit1.10 start/stopCW
6Ch.1 - Stairs light activation timeSet value2 Bytes7.5 time (s)CW
7Ch.1 - BlinkingSwitching On/Off1 Bit1.1 switchCW
8Ch.1 - SceneExecute/Store1 Byte18.1 scene controlCW
8Ch.1 - SceneExecute1 Byte17.1 scene numberCW
9Ch.1 - Scene storing enablingEnable/Disable1 Bit1.3 enableCW
10Ch.1 - Logic input 1Logic function input1 Bit1.2 booleanCWTU
11Ch.1 - Logic input 2Logic function input1 Bit1.2 booleanCWTU
12Ch.1 - Logic input 3Logic function input1 Bit1.2 booleanCWTU
13Ch.1 - Logic input 4Logic function input1 Bit1.2 booleanCWTU
14Ch.1 - Logic input 5Logic function input1 Bit1.2 booleanCWTU
15Ch.1 - Logic input 6Logic function input1 Bit1.2 booleanCWTU
16Ch.1 - Logic input 7Logic function input1 Bit1.2 booleanCWTU
17Ch.1 - Logic input 8Logic function input1 Bit1.2 booleanCWTU
18Ch.1 - Logical operation outcomeLogic1 Bit1.2 booleanCRT
19Ch.1 - Enable loads control slave functionEnable/Disable1 Bit1.2 booleanCW
20Ch.1 - Loads control slave function enabling statusSwitching On/Off1 Bit1.3 enableCRT
21Ch.1 - Slave switching for loads control1=Load lock/0=Load unlock1 Bit1.1 switchCW
22Ch.1 - Slave status for loads control1=Locked/0=Unlocked1 Bit1.1 switchCRT
23Ch.1 - Enable absorption limit thresholdEnable/Disable1 Bit1.2 booleanCW
24Ch.1 - Absorption limit threshold enabling statusSwitching On/Off1 Bit1.3 enableCRT
25Ch.1 - Limit absorption threshold value inputValue in watt [W]4 Bytes14.56 power (W)CW
25Ch.1 - Absorption limit threshold adjustment1=Increase/0=Decrease1 Bit1.7 stepCW
26Ch.1 - Absorption limit threshold current valueValue in Watt [W]4 Bytes14.56 power (W)CRT
27Ch.1 - Absorption limit threshold exceededValue 1/01 Bit1.2 booleanCRT
28Ch.1 - Period above absorption limit threshold counterValue 0 .. 2147483647 [s]4 Bytes13.100 time lag (s)CRT
28Ch.1 - Period above absorption limit threshold counterValue 0 .. 65535 [min]2 Bytes7.6 time (min)CRT
28Ch.1 - Period above absorption limit threshold counterValue 0 .. 65535 [h]2 Bytes7.7 time (h)CRT
28Ch.1 - Period above absorption limit threshold counterValue 0 .. 2147483647 [s]4 Bytes13.100 time lag (s)CR
28Ch.1 - Period above absorption limit threshold counterValue 0 .. 65535 [min]2 Bytes7.6 time (min)CR
28Ch.1 - Period above absorption limit threshold counterValue 0 .. 65535 [h]2 Bytes7.7 time (h)CR
29Ch.1 - Period above absorption limit threshold counter overflowOverflow status1 Bit1.2 booleanCRT
30Ch.1 - Period above absorption limit threshold counter reset1=Reset/0=No action1 Bit1.15 resetCW
31Ch.1 - Absorption limit threshold number of exceedances counterValue 0 .. 655352 Bytes7.1 pulsesCRT
31Ch.1 - Absorption limit threshold number of exceedances counterValue 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
31Ch.1 - Absorption limit threshold number of exceedances counterValue 0 .. 655352 Bytes7.1 pulsesCR
31Ch.1 - Absorption limit threshold number of exceedances counterValue 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CR
32Ch.1 - Absorption limit threshold number of exceedances counter overflowOverflow status1 Bit1.2 booleanCRT
33Ch.1 - Absorption limit threshold number of exceedances counter reset1=Reset/0=No action1 Bit1.15 resetCW
34Ch.1 - SafetyMonitoring1 Bit1.2 booleanCW
35Ch.1 - Safety statusSwitching On/Off1 Bit1.3 enableCRT
36Ch.1 - Priority commandOn/Off forced positioning2 Bit2.1 switch controlCW
37Ch.1 - Priority command statusOn/Off forced positioning status2 Bit2.1 switch controlCRT
38Ch.1 - BlockSwitching On/Off1 Bit1.2 booleanCW
39Ch.1 - Block statusActive/Not active1 Bit1.3 enableCRT
40Ch.1 - Operating time counterValue 0 .. 2147483647 [s]4 Bytes13.100 time lag (s)CRT
40Ch.1 - Operating time counterValue 0 .. 2147483647 [s]4 Bytes13.100 time lag (s)CR
40Ch.1 - Operating time counterValue 0 .. 65535 [min]2 Bytes7.6 time (min)CRT
40Ch.1 - Operating time counterValue 0 .. 65535 [min]2 Bytes7.6 time (min)CR
40Ch.1 - Operating time counterValue 0 .. 65535 [h]2 Bytes7.7 time (h)CRT
40Ch.1 - Operating time counterValue 0 .. 65535 [h]2 Bytes7.7 time (h)CR
41Ch.1 - Operating time counter overflowOverflow status1 Bit1.2 booleanCRT
42Ch.1 - Operating time counter reset1=Reset/0=No action1 Bit1.15 resetCW
43Ch.1 - Switching operation counterValue 0 .. 655352 Bytes7.1 pulsesCRT
43Ch.1 - Switching operation counterValue 0 .. 655352 Bytes7.1 pulsesCR
43Ch.1 - Switching operation counterValue 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
43Ch.1 - Switching operation counterValue 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CR
44Ch.1 - Switching operation counter overflowOverflow status1 Bit1.2 booleanCRT
45Ch.1 - Switching operation counter reset1=Reset/0=No action1 Bit1.15 resetCW
46Ch.1 - Active consumed energy primary counterValue in watt hours [Wh]4 Bytes13.10 active energy (Wh)CRT
46Ch.1 - Active consumed energy primary counterValue in kilowatt hours [kWh]4 Bytes13.13 active energy (kWh)CRT
46Ch.1 - Active consumed energy primary counterValue in watt hours [Wh]4 Bytes13.10 active energy (Wh)CR
46Ch.1 - Active consumed energy primary counterValue in kilowatt hours [kWh]4 Bytes13.13 active energy (kWh)CR
47Ch.1 - Active consumed energy primary counter overflowOverflow status1 Bit1.2 booleanCRT
48Ch.1 - Active consumed energy primary counter reset1=Reset/0=No action1 Bit1.15 resetCW
49Ch.1 - Active consumed energy differential counterValue in watt hours [Wh]4 Bytes13.10 active energy (Wh)CRT
49Ch.1 - Active consumed energy differential counterValue in kilowatt hours [kWh]4 Bytes13.13 active energy (kWh)CRT
49Ch.1 - Active consumed energy differential counterValue in watt hours [Wh]4 Bytes13.10 active energy (Wh)CR
49Ch.1 - Active consumed energy differential counterValue in kilowatt hours [kWh]4 Bytes13.13 active energy (kWh)CR
50Ch.1 - Active consumed energy differential counter trigger1=Start counting/0=Stop1 Bit1.10 start/stopCW
51Ch.1 - Active consumed energy differential counter overflowOverflow status1 Bit1.2 booleanCRT
52Ch.1 - Active consumed energy differential counter reset1=Reset/0=No action1 Bit1.15 resetCW
53Ch.1 - Measured active powerValue in Watt [W]4 Bytes14.56 power (W)CRT
53Ch.1 - Measured active powerValue in Watt [W]4 Bytes14.56 power (W)CR
54Ch.1 - Measured reactive powerValue in volts amps reactive [var]4 BytesDPT.14CRT
54Ch.1 - Measured reactive powerValue in volts amps reactive [var]4 BytesDPT.14CR
55Ch.1 - Measured apparent powerValue in Volt Ampere [va]4 BytesDPT.14CRT
55Ch.1 - Measured apparent powerValue in Volt Ampere [va]4 BytesDPT.14CR
56Ch.1 - Measured power factorValue -1 .. +14 Bytes14.57 power factor (cos Φ)CRT
56Ch.1 - Measured power factorValue -1 .. +14 Bytes14.57 power factor (cos Φ)CR
57Ch.1 - Measured RMS voltageValue in Volt [V]2 Bytes9.20 voltage (mV)CRT
57Ch.1 - Measured RMS voltageValue in Volt [V]2 Bytes9.20 voltage (mV)CR
58Ch.1 - Measured RMS currentValue in Ampere [A]2 Bytes9.21 current (mA)CRT
58Ch.1 - Measured RMS currentValue in Ampere [A]2 Bytes9.21 current (mA)CR
59Ch.1 - Measured frequencyValue in Hertz [HZ]4 Bytes14.33 frequency (Hz)CRT
59Ch.1 - Measured frequencyValue in Hertz [HZ]4 Bytes14.33 frequency (Hz)CR
60Ch.2 - StatusOn/Off status1 Bit1.1 switchCR
60Ch.2 - StatusOn/Off status1 Bit1.1 switchCRT
61Ch.2 - SwitchOn/Off1 Bit1.1 switchCW
62Ch.2 - Delayed switchingOn/Off1 Bit1.1 switchCW
63Ch.2 - Delay on activationSet value2 Bytes7.5 time (s)CW
64Ch.2 - Delay on deactivationSet value2 Bytes7.5 time (s)CW
65Ch.2 - Timed switchStart/Stop1 Bit1.10 start/stopCW
66Ch.2 - Stairs light activation timeSet value2 Bytes7.5 time (s)CW
67Ch.2 - BlinkingSwitching On/Off1 Bit1.1 switchCW
68Ch.2 - SceneExecute1 Byte17.1 scene numberCW
68Ch.2 - SceneExecute/Store1 Byte18.1 scene controlCW
69Ch.2 - Scene storing enablingEnable/Disable1 Bit1.3 enableCW
70Ch.2 - Logic input 1Logic function input1 Bit1.2 booleanCWTU
71Ch.2 - Logic input 2Logic function input1 Bit1.2 booleanCWTU
72Ch.2 - Logic input 3Logic function input1 Bit1.2 booleanCWTU
73Ch.2 - Logic input 4Logic function input1 Bit1.2 booleanCWTU
74Ch.2 - Logic input 5Logic function input1 Bit1.2 booleanCWTU
75Ch.2 - Logic input 6Logic function input1 Bit1.2 booleanCWTU
76Ch.2 - Logic input 7Logic function input1 Bit1.2 booleanCWTU
77Ch.2 - Logic input 8Logic function input1 Bit1.2 booleanCWTU
78Ch.2 - Logical operation outcomeLogic1 Bit1.2 booleanCRT
79Ch.2 - Enable loads control slave functionEnable/Disable1 Bit1.2 booleanCW
80Ch.2 - Loads control slave function enabling statusSwitching On/Off1 Bit1.3 enableCRT
81Ch.2 - Slave switching for loads control1=Load lock/0=Load unlock1 Bit1.1 switchCW
82Ch.2 - Slave status for loads control1=Locked/0=Unlocked1 Bit1.1 switchCRT
83Ch.2 - Enable absorption limit thresholdEnable/Disable1 Bit1.2 booleanCW
84Ch.2 - Absorption limit threshold enabling statusSwitching On/Off1 Bit1.3 enableCRT
85Ch.2 - Limit absorption threshold value inputValue in watt [W]4 Bytes14.56 power (W)CW
85Ch.2 - Absorption limit threshold adjustment1=Increase/0=Decrease1 Bit1.7 stepCW
86Ch.2 - Absorption limit threshold current valueValue in Watt [W]4 Bytes14.56 power (W)CRT
87Ch.2 - Absorption limit threshold exceededValue 1/01 Bit1.2 booleanCRT
88Ch.2 - Period above absorption limit threshold counterValue 0 .. 2147483647 [s]4 Bytes13.100 time lag (s)CR
88Ch.2 - Period above absorption limit threshold counterValue 0 .. 65535 [min]2 Bytes7.6 time (min)CR
88Ch.2 - Period above absorption limit threshold counterValue 0 .. 65535 [h]2 Bytes7.7 time (h)CR
88Ch.2 - Period above absorption limit threshold counterValue 0 .. 2147483647 [s]4 Bytes13.100 time lag (s)CRT
88Ch.2 - Period above absorption limit threshold counterValue 0 .. 65535 [min]2 Bytes7.6 time (min)CRT
88Ch.2 - Period above absorption limit threshold counterValue 0 .. 65535 [h]2 Bytes7.7 time (h)CRT
89Ch.2 - Period above absorption limit threshold counter overflowOverflow status1 Bit1.2 booleanCRT
90Ch.2 - Period above absorption limit threshold counter reset1=Reset/0=No action1 Bit1.15 resetCW
91Ch.2 - Absorption limit threshold number of exceedances counterValue 0 .. 655352 Bytes7.1 pulsesCR
91Ch.2 - Absorption limit threshold number of exceedances counterValue 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CR
91Ch.2 - Absorption limit threshold number of exceedances counterValue 0 .. 655352 Bytes7.1 pulsesCRT
91Ch.2 - Absorption limit threshold number of exceedances counterValue 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
92Ch.2 - Absorption limit threshold number of exceedances counter overflowOverflow status1 Bit1.2 booleanCRT
93Ch.2 - Absorption limit threshold number of exceedances counter reset1=Reset/0=No action1 Bit1.15 resetCW
94Ch.2 - SafetyMonitoring1 Bit1.2 booleanCW
95Ch.2 - Safety statusSwitching On/Off1 Bit1.3 enableCRT
96Ch.2 - Priority commandOn/Off forced positioning2 Bit2.1 switch controlCW
97Ch.2 - Priority command statusOn/Off forced positioning status2 Bit2.1 switch controlCRT
98Ch.2 - BlockSwitching On/Off1 Bit1.2 booleanCW
99Ch.2 - Block statusActive/Not active1 Bit1.3 enableCRT
100Ch.2 - Operating time counterValue 0 .. 2147483647 [s]4 Bytes13.100 time lag (s)CR
100Ch.2 - Operating time counterValue 0 .. 65535 [min]2 Bytes7.6 time (min)CR
100Ch.2 - Operating time counterValue 0 .. 65535 [h]2 Bytes7.7 time (h)CR
100Ch.2 - Operating time counterValue 0 .. 2147483647 [s]4 Bytes13.100 time lag (s)CRT
100Ch.2 - Operating time counterValue 0 .. 65535 [min]2 Bytes7.6 time (min)CRT
100Ch.2 - Operating time counterValue 0 .. 65535 [h]2 Bytes7.7 time (h)CRT
101Ch.2 - Operating time counter overflowOverflow status1 Bit1.2 booleanCRT
102Ch.2 - Operating time counter reset1=Reset/0=No action1 Bit1.15 resetCW
103Ch.2 - Switching operation counterValue 0 .. 655352 Bytes7.1 pulsesCR
103Ch.2 - Switching operation counterValue 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CR
103Ch.2 - Switching operation counterValue 0 .. 655352 Bytes7.1 pulsesCRT
103Ch.2 - Switching operation counterValue 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
104Ch.2 - Switching operation counter overflowOverflow status1 Bit1.2 booleanCRT
105Ch.2 - Switching operation counter reset1=Reset/0=No action1 Bit1.15 resetCW
106Ch.2 - Active consumed energy primary counterValue in watt hours [Wh]4 Bytes13.10 active energy (Wh)CR
106Ch.2 - Active consumed energy primary counterValue in kilowatt hours [kWh]4 Bytes13.13 active energy (kWh)CR
106Ch.2 - Active consumed energy primary counterValue in watt hours [Wh]4 Bytes13.10 active energy (Wh)CRT
106Ch.2 - Active consumed energy primary counterValue in kilowatt hours [kWh]4 Bytes13.13 active energy (kWh)CRT
107Ch.2 - Active consumed energy primary counter overflowOverflow status1 Bit1.2 booleanCRT
108Ch.2 - Active consumed energy primary counter reset1=Reset/0=No action1 Bit1.15 resetCW
109Ch.2 - Active consumed energy differential counterValue in watt hours [Wh]4 Bytes13.10 active energy (Wh)CR
109Ch.2 - Active consumed energy differential counterValue in kilowatt hours [kWh]4 Bytes13.13 active energy (kWh)CR
109Ch.2 - Active consumed energy differential counterValue in watt hours [Wh]4 Bytes13.10 active energy (Wh)CRT
109Ch.2 - Active consumed energy differential counterValue in kilowatt hours [kWh]4 Bytes13.13 active energy (kWh)CRT
110Ch.2 - Active consumed energy differential counter trigger1=Start counting/0=Stop1 Bit1.10 start/stopCW
111Ch.2 - Active consumed energy differential counter overflowOverflow status1 Bit1.2 booleanCRT
112Ch.2 - Active consumed energy differential counter reset1=Reset/0=No action1 Bit1.15 resetCW
113Ch.2 - Measured active powerValue in Watt [W]4 Bytes14.56 power (W)CR
113Ch.2 - Measured active powerValue in Watt [W]4 Bytes14.56 power (W)CRT
114Ch.2 - Measured reactive powerValue in volts amps reactive [var]4 BytesDPT.14CR
114Ch.2 - Measured reactive powerValue in volts amps reactive [var]4 BytesDPT.14CRT
115Ch.2 - Measured apparent powerValue in Volt Ampere [va]4 BytesDPT.14CR
115Ch.2 - Measured apparent powerValue in Volt Ampere [va]4 BytesDPT.14CRT
116Ch.2 - Measured power factorValue -1 .. +14 Bytes14.57 power factor (cos Φ)CR
116Ch.2 - Measured power factorValue -1 .. +14 Bytes14.57 power factor (cos Φ)CRT
117Ch.2 - Measured RMS voltageValue in Volt [V]2 Bytes9.20 voltage (mV)CRT
117Ch.2 - Measured RMS voltageValue in Volt [V]2 Bytes9.20 voltage (mV)CR
118Ch.2 - Measured RMS currentValue in Ampere [A]2 Bytes9.21 current (mA)CRT
118Ch.2 - Measured RMS currentValue in Ampere [A]2 Bytes9.21 current (mA)CR
119Ch.2 - Measured frequencyValue in Hertz [HZ]4 Bytes14.33 frequency (Hz)CRT
119Ch.2 - Measured frequencyValue in Hertz [HZ]4 Bytes14.33 frequency (Hz)CR
120Ch.3 - StatusOn/Off status1 Bit1.1 switchCR
120Ch.3 - StatusOn/Off status1 Bit1.1 switchCRT
121Ch.3 - SwitchOn/Off1 Bit1.1 switchCW
122Ch.3 - Delayed switchingOn/Off1 Bit1.1 switchCW
123Ch.3 - Delay on activationSet value2 Bytes7.5 time (s)CW
124Ch.3 - Delay on deactivationSet value2 Bytes7.5 time (s)CW
125Ch.3 - Timed switchStart/Stop1 Bit1.10 start/stopCW
126Ch.3 - Stairs light activation timeSet value2 Bytes7.5 time (s)CW
127Ch.3 - BlinkingSwitching On/Off1 Bit1.1 switchCW
128Ch.3 - SceneExecute1 Byte17.1 scene numberCW
128Ch.3 - SceneExecute/Store1 Byte18.1 scene controlCW
129Ch.3 - Scene storing enablingEnable/Disable1 Bit1.3 enableCW
130Ch.3 - Logic input 1Logic function input1 Bit1.2 booleanCWTU
131Ch.3 - Logic input 2Logic function input1 Bit1.2 booleanCWTU
132Ch.3 - Logic input 3Logic function input1 Bit1.2 booleanCWTU
133Ch.3 - Logic input 4Logic function input1 Bit1.2 booleanCWTU
134Ch.3 - Logic input 5Logic function input1 Bit1.2 booleanCWTU
135Ch.3 - Logic input 6Logic function input1 Bit1.2 booleanCWTU
136Ch.3 - Logic input 7Logic function input1 Bit1.2 booleanCWTU
137Ch.3 - Logic input 8Logic function input1 Bit1.2 booleanCWTU
138Ch.3 - Logical operation outcomeLogic1 Bit1.2 booleanCRT
139Ch.3 - Enable loads control slave functionEnable/Disable1 Bit1.2 booleanCW
140Ch.3 - Loads control slave function enabling statusSwitching On/Off1 Bit1.3 enableCRT
141Ch.3 - Slave switching for loads control1=Load lock/0=Load unlock1 Bit1.1 switchCW
142Ch.3 - Slave status for loads control1=Locked/0=Unlocked1 Bit1.1 switchCRT
143Ch.3 - Enable absorption limit thresholdEnable/Disable1 Bit1.2 booleanCW
144Ch.3 - Absorption limit threshold enabling statusSwitching On/Off1 Bit1.3 enableCRT
145Ch.3 - Limit absorption threshold value inputValue in watt [W]4 Bytes14.56 power (W)CW
145Ch.3 - Absorption limit threshold adjustment1=Increase/0=Decrease1 Bit1.7 stepCW
146Ch.3 - Absorption limit threshold current valueValue in Watt [W]4 Bytes14.56 power (W)CRT
147Ch.3 - Absorption limit threshold exceededValue 1/01 Bit1.2 booleanCRT
148Ch.3 - Period above absorption limit threshold counterValue 0 .. 2147483647 [s]4 Bytes13.100 time lag (s)CR
148Ch.3 - Period above absorption limit threshold counterValue 0 .. 65535 [min]2 Bytes7.6 time (min)CR
148Ch.3 - Period above absorption limit threshold counterValue 0 .. 65535 [h]2 Bytes7.7 time (h)CR
148Ch.3 - Period above absorption limit threshold counterValue 0 .. 2147483647 [s]4 Bytes13.100 time lag (s)CRT
148Ch.3 - Period above absorption limit threshold counterValue 0 .. 65535 [min]2 Bytes7.6 time (min)CRT
148Ch.3 - Period above absorption limit threshold counterValue 0 .. 65535 [h]2 Bytes7.7 time (h)CRT
149Ch.3 - Period above absorption limit threshold counter overflowOverflow status1 Bit1.2 booleanCRT
150Ch.3 - Period above absorption limit threshold counter reset1=Reset/0=No action1 Bit1.15 resetCW
151Ch.3 - Absorption limit threshold number of exceedances counterValue 0 .. 655352 Bytes7.1 pulsesCR
151Ch.3 - Absorption limit threshold number of exceedances counterValue 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CR
151Ch.3 - Absorption limit threshold number of exceedances counterValue 0 .. 655352 Bytes7.1 pulsesCRT
151Ch.3 - Absorption limit threshold number of exceedances counterValue 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
152Ch.3 - Absorption limit threshold number of exceedances counter overflowOverflow status1 Bit1.2 booleanCRT
153Ch.3 - Absorption limit threshold number of exceedances counter reset1=Reset/0=No action1 Bit1.15 resetCW
154Ch.3 - SafetyMonitoring1 Bit1.2 booleanCW
155Ch.3 - Safety statusSwitching On/Off1 Bit1.3 enableCRT
156Ch.3 - Priority commandOn/Off forced positioning2 Bit2.1 switch controlCW
157Ch.3 - Priority command statusOn/Off forced positioning status2 Bit2.1 switch controlCRT
158Ch.3 - BlockSwitching On/Off1 Bit1.2 booleanCW
159Ch.3 - Block statusActive/Not active1 Bit1.3 enableCRT
160Ch.3 - Operating time counterValue 0 .. 2147483647 [s]4 Bytes13.100 time lag (s)CR
160Ch.3 - Operating time counterValue 0 .. 65535 [min]2 Bytes7.6 time (min)CR
160Ch.3 - Operating time counterValue 0 .. 65535 [h]2 Bytes7.7 time (h)CR
160Ch.3 - Operating time counterValue 0 .. 2147483647 [s]4 Bytes13.100 time lag (s)CRT
160Ch.3 - Operating time counterValue 0 .. 65535 [min]2 Bytes7.6 time (min)CRT
160Ch.3 - Operating time counterValue 0 .. 65535 [h]2 Bytes7.7 time (h)CRT
161Ch.3 - Operating time counter overflowOverflow status1 Bit1.2 booleanCRT
162Ch.3 - Operating time counter reset1=Reset/0=No action1 Bit1.15 resetCW
163Ch.3 - Switching operation counterValue 0 .. 655352 Bytes7.1 pulsesCR
163Ch.3 - Switching operation counterValue 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CR
163Ch.3 - Switching operation counterValue 0 .. 655352 Bytes7.1 pulsesCRT
163Ch.3 - Switching operation counterValue 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
164Ch.3 - Switching operation counter overflowOverflow status1 Bit1.2 booleanCRT
165Ch.3 - Switching operation counter reset1=Reset/0=No action1 Bit1.15 resetCW
166Ch.3 - Active consumed energy primary counterValue in watt hours [Wh]4 Bytes13.10 active energy (Wh)CR
166Ch.3 - Active consumed energy primary counterValue in kilowatt hours [kWh]4 Bytes13.13 active energy (kWh)CR
166Ch.3 - Active consumed energy primary counterValue in watt hours [Wh]4 Bytes13.10 active energy (Wh)CRT
166Ch.3 - Active consumed energy primary counterValue in kilowatt hours [kWh]4 Bytes13.13 active energy (kWh)CRT
167Ch.3 - Active consumed energy primary counter overflowOverflow status1 Bit1.2 booleanCRT
168Ch.3 - Active consumed energy primary counter reset1=Reset/0=No action1 Bit1.15 resetCW
169Ch.3 - Active consumed energy differential counterValue in watt hours [Wh]4 Bytes13.10 active energy (Wh)CR
169Ch.3 - Active consumed energy differential counterValue in kilowatt hours [kWh]4 Bytes13.13 active energy (kWh)CR
169Ch.3 - Active consumed energy differential counterValue in watt hours [Wh]4 Bytes13.10 active energy (Wh)CRT
169Ch.3 - Active consumed energy differential counterValue in kilowatt hours [kWh]4 Bytes13.13 active energy (kWh)CRT
170Ch.3 - Active consumed energy differential counter trigger1=Start counting/0=Stop1 Bit1.10 start/stopCW
171Ch.3 - Active consumed energy differential counter overflowOverflow status1 Bit1.2 booleanCRT
172Ch.3 - Active consumed energy differential counter reset1=Reset/0=No action1 Bit1.15 resetCW
173Ch.3 - Measured active powerValue in Watt [W]4 Bytes14.56 power (W)CR
173Ch.3 - Measured active powerValue in Watt [W]4 Bytes14.56 power (W)CRT
174Ch.3 - Measured reactive powerValue in volts amps reactive [var]4 BytesDPT.14CR
174Ch.3 - Measured reactive powerValue in volts amps reactive [var]4 BytesDPT.14CRT
175Ch.3 - Measured apparent powerValue in Volt Ampere [va]4 BytesDPT.14CR
175Ch.3 - Measured apparent powerValue in Volt Ampere [va]4 BytesDPT.14CRT
176Ch.3 - Measured power factorValue -1 .. +14 Bytes14.57 power factor (cos Φ)CR
176Ch.3 - Measured power factorValue -1 .. +14 Bytes14.57 power factor (cos Φ)CRT
177Ch.3 - Measured RMS voltageValue in Volt [V]2 Bytes9.20 voltage (mV)CRT
177Ch.3 - Measured RMS voltageValue in Volt [V]2 Bytes9.20 voltage (mV)CR
178Ch.3 - Measured RMS currentValue in Ampere [A]2 Bytes9.21 current (mA)CRT
178Ch.3 - Measured RMS currentValue in Ampere [A]2 Bytes9.21 current (mA)CR
179Ch.3 - Measured frequencyValue in Hertz [HZ]4 Bytes14.33 frequency (Hz)CRT
179Ch.3 - Measured frequencyValue in Hertz [HZ]4 Bytes14.33 frequency (Hz)CR
Parameters (180)
ParameterTypeDefault
Transmission delay after startlist11.. 21 seconds (depending on physical address)
- Scene storing on long operationlistenabled
- Scene number (0.. 63)unsignedInt 0…630
Channel 1 local key functionliston/off switching
Channel 1listdisable
- Sending on pressing detectionlistcyclical switching
- Sending on pressing detectionlisttiming start
- Sending on pressing detectionlistactive on forcing
- Sending on pressing detectionlistactivation
- Sending on release detectionlistno effect
Relay status after bus voltage recoverylistas before voltage drop
Relay status at bus voltage failurelistno change
Relay status after application downloadlistopen (with NO)/closed (with NC)
- Status transmission on bus voltage recoverylistdisable
Status information transmissionlistsending on change
Contact typelistnormally open (NO)
Block functionlistdeactivated
Forced positioning functionlistdeactivated
Safety functionlistdeactivated
Scenes functionlistdeactivated
Blinking functionlistdeactivated
Stairs light functionlistdeactivated
Delay on activation/deactivation functionlistdeactivated
Logic functionlistdeactivated
Delay setting for switching off from buslistdisable
Retriggerable delay on deactivationlistno
Delay on deactivation [seconds]unsignedInt 0…595
Delay on deactivation [minutes]unsignedInt 0…590
Delay on deactivation [hours]unsignedInt 0…240
Delay setting for switching on from buslistdisable
Retriggerable delay on activationlistno
Delay on switching on [seconds]unsignedInt 0…595
Delay on switching on [minutes]unsignedInt 0…590
Delay on switching on [hours]unsignedInt 0…240
Mode activation valuelist"1" value
Stairs light activation time setting from buslistdisable
- Multiplicative factor maximum valueunsignedInt 2…55
Command of activation during timinglistrestart
Timing stop functionlistdisable
- Load deactivation durationunsignedInt 5…155
Activation time [seconds]unsignedInt 0…595
Activation time [minutes]unsignedInt 0…590
Activation time [hours]unsignedInt 0…240
- Timed activation delay lengthlist1 s
- Prewarning time lengthlist15 s
Delay on timed activationlistdisabled
Prewarning timelistdisabled
Blinking mode on bus voltage recoverylistas before voltage drop
Relay status on switching blinking mode offlistno change
Deactivation time [seconds]unsignedInt 0…595
Deactivation time [minutes]unsignedInt 0…590
Scenes storing enablinglistenable
Scene 8 relay start statuslistopen (with NO)/closed (with NC)
Scene 7 relay start statuslistopen (with NO)/closed (with NC)
Scene 6 relay start statuslistopen (with NO)/closed (with NC)
Scene 5 relay start statuslistopen (with NO)/closed (with NC)
Scene 4 relay start statuslistopen (with NO)/closed (with NC)
Scene 3 relay start statuslistopen (with NO)/closed (with NC)
Scene 2 relay start statuslistopen (with NO)/closed (with NC)
Scene 1 relay start statuslistopen (with NO)/closed (with NC)
Scene number 8listunassigned
Scene number 7listunassigned
Scene number 6listunassigned
Scene number 5listunassigned
Scene number 4listunassigned
Scene number 3listunassigned
Scene number 2listunassigned
Scene number 1listunassigned
Logic function outcome feedbacklistdisabled
Logic input 4 value at bus voltage recoverylistas before voltage drop
Logic input 3 value at bus voltage recoverylistas before voltage drop
Logic input 2 value at bus voltage recoverylistas before voltage drop
Logic input 1 value at bus voltage recoverylistas before voltage drop
Logic input 4 value at downloadlist"0" value
Logic input 3 value at downloadlist"0" value
Logic input 2 value at downloadlist"0" value
Logic input 1 value at downloadlist"0" value
NOT operation for logic input 4listdisable
NOT operation for logic input 3listdisable
NOT operation for logic input 2listdisable
NOT operation for logic input 1listdisable
Logical operation to executelistAND
Execute logical operation with the objectlistswitching
The outcome of the operation with logic inputs stands forlistnew logic input
The logic input value stands forlistnew logic input
Operation between logic inputslistAND
Logic inputs numberlist1
NOT operation for logic input 5listdisable
NOT operation for logic input 6listdisable
NOT operation for logic input 7listdisable
NOT operation for logic input 8listdisable
Logic input 5 value at downloadlist"0" value
Logic input 6 value at downloadlist"0" value
Logic input 7 value at downloadlist"0" value
Logic input 8 value at downloadlist"0" value
Logic input 5 value at bus voltage recoverylistas before voltage drop
Logic input 6 value at bus voltage recoverylistas before voltage drop
Logic input 7 value at bus voltage recoverylistas before voltage drop
Logic input 8 value at bus voltage recoverylistas before voltage drop
Scene commandslistindependent from logic function
Blinking switching on/off commandslistindependent from logic function
Timed activation commandslistindependent from logic function
Delayed switching commandslistindependent from logic function
Switching (on/off) commandslistindependent from logic function
Safety on bus tension recovery functionlistas before voltage drop
Monitoring time [seconds]unsignedInt 0…590
Monitoring time [minutes]unsignedInt 0…595
Relay status after safetylistfollows last command received
Relay status on safetylistopen (with NO)/closed (with NC)
Control methodlistperiodic transmission absence
Block on bus tension recovery functionlistas before voltage drop
Block on download functionlistdeactivated
Relay status on block deactivationlistfollows last command received
Relay status on active blocklistopen (with NO)/closed (with NC)
Block activation valuelist"1" value
Forcing status on bus voltage recoverylistas before voltage drop
Relay status on forced positioning endlistfollows last command received
Increase the operating time counter value iflistcontact is closed
Operating time counter value formatlist4 bytes (seconds)
Counter value sending conditionlistsend in case of change
- Minimum counter variation for sending valueunsignedInt 1…10010
- Counter sending periodunsignedInt 1…25515
Overflow valueunsignedInt 0…6553565535
Counter functionlistdeactivated
Switching operations counter value formatlist4 bytes unsigned values
Overflow valueunsignedInt 0…42949672954294967295
Overflow valueunsignedInt 0…21474836472147483647
Load control - slave functionlistdeactivated
Absorption limit thresholdlistdeactivated
Load control slave function activation valuelist"1" value
Relay status following load reconnection commandlistfollows last command received
Loads control function on downloadlistdeactivated
Loads control function at bus voltage recoverylistas before voltage drop
Threshold enable valuelist"1" value
Threshold enable status on bus voltage recoverylistas before voltage drop
Absorption limit threshold initial valueunsignedInt 1…3600800
Absorption limit threshold hysteresisunsignedInt 1…1000100
Change the threshold via bus throughlistabsolute value setting
- Threshold adjustment step via busunsignedInt 1…250100
Automatic deactivation of the load upon exceeding the absorption thresholdlistenabled
Exceeded absorption threshold signalinglistdisabled
- Upon exceeding the limit thresholdlistsend "1"
- On return below limit thresholdlistsend "0"
- Reporting periodunsignedInt 1…25515
Format of the period above absorption limit threshold counterlist4 bytes (seconds)
- Overflow valueunsignedInt 0…21474836472147483647
- Overflow valueunsignedInt 0…6553565535
Format of the number of exceedances of the absorption limit threshold counterlist4 bytes unsigned values
- Overflow valueunsignedInt 0…42949672954294967295
Absorption limit threshold on downloadlistactive
Consumed active energy countinglistdisabled
Counter formatlistwatt hour (Wh)
Counters Formatlistwatt hour (Wh)
Primary counter initial valueunsignedInt 0…21474836470
Reset counter on downloadlistno
Primary counter sending conditionlistsend in case of change
Reset counters on downloadlistno
- Minimum primary counter variation for sending valuelist50 Wh
- Primary counter sending periodunsignedInt 1…25515
Differential counter overflow valueunsignedInt 0…21474836472147483647
Differential counter sending conditionlistsend in case of change
- Minimum differential counter variation for sending valuelist50 Wh
- Differential counter sending periodunsignedInt 1…25515
Start/Stop differential counting from buslistdisable
Reporting of the consumed power (active/reactive/apparent) valueslistsending on change
- Minimum consumed power variation for sending valuelist50 (W/VA/VAR)
Power factor reportinglistsending on change
- Minimum power factor variation for sending valuelist0,2
Reporting of the RMS voltage valuelistsending on change
- Minimum RMS voltage variation for sending valuelist5 Volt
Reporting of the RMS current valuelistsending on change
- Minimum RMS current variation for sending valuelist0,5 Ampere
Frequency reportinglistsending on change
- Minimum frequency variation for sending valuelist5 Hertz
Reporting of electrical measurements upon bus voltage recoverylistenable
Channel 2listdisable
Channel 3listdisable
Channel 2 local key functionliston/off switching
Channel 3 local key functionliston/off switching
- Time limit for staying above threshold before automatic load deactivationunsignedInt 0…301

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX Actuator 3 channels 16AX with energy measurement S 1.0 1.0 latest$512965332026-11-25173 KBDownload

About this file

This is the official ETS product database for the GEWISS GWA9103 (GWA9103), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from GEWISS

All GEWISS products