GW12797
GEWISS · Order number GW12797 · Actuators › Dispositivi di uscita per tapparelle, 1ch
Download .knxprod Shutter actuator 1 ch. 8A S 1.1 1.1 · 76 KB
Product
| Manufacturer | GEWISS |
|---|---|
| Product name | GW12797 |
| Order number | GW12797 |
| Product text | Shutter actuator 1 ch. 8A - black |
| Hardware | Attuatori comando motore 1 canale 8A |
| Medium | Twisted Pair |
| Bus current (mA) | 8 |
| Rail mounted | No |
| Registration | Certified · 2020-12-04 |
| Languages | de-DE, en-US, es-ES, it-IT |
| Catalog entry | M-0019_H-10797-1_HP-5107-11-315E_CI-GW12797-1 |
| Fingerprint | 315E |
| SHA-256 | 8c9c1229b0154c88f738b36303ae202d93a1c5940c002fd933b2c52b89d60943 |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: Shutter actuator 1 ch. 8A S 1.1 1.1
| Application number | $5107 |
|---|---|
| Version | 1.1 |
| Mask version | MV-0021 (2.1) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 61 |
| Group objects | 12 |
Group objects (12)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Movement | Up/Down | 1 Bit | 1.8 up/down | CW |
| 1 | Shutter stop/Louvres step | Stop/Step | 1 Bit | 1.7 step | CW |
| 1 | Shutter stop | Stop | 1 Bit | 1.17 trigger | CW |
| 2 | Movement feedback | Increase/Decrease | 1 Bit | 1.8 up/down | CRT |
| 3 | Alarm 1 | Alarm input | 1 Bit | 1.5 alarm | CW |
| 4 | Alarm 2 | Alarm input | 1 Bit | 1.5 alarm | CW |
| 5 | Alarm 3 | Alarm input | 1 Bit | 1.5 alarm | CW |
| 6 | Priority command | Forced positioning up/down | 2 Bit | 2.8 direction control 1 | CW |
| 7 | Block | Switching on/off | 1 Bit | 1.2 boolean | CW |
| 8 | Scene | Execute/Store | 1 Byte | 18.1 scene control | CW |
| 9 | Position command | % Value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 10 | Position feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
Parameters (54)
| Parameter | Type | Default |
|---|---|---|
| RESET VALUE | list | zero |
| Operating mode | list | shutter |
| Movement maximum time [sec] | unsignedInt 0…3000 | 220 |
| Travel range time [sec] | unsignedInt 0…3000 | 180 |
| Movement in progress feedback | list | deactivated |
| Forced positioning function | list | deactivated |
| Block function | list | deactivated |
| Alarm function | list | deactivated |
| Position on forced positioning, block or alarm disactivation | list | no movement |
| Scenes function | list | deactivated |
| Movement object values | list | "0" = up / "1" = down |
| Stop minimum time for reversing | list | 500 ms |
| Shutter control movement time (n x 100 ms) | unsignedInt 1…120 | 3 |
| Night lighting | list | active |
| Local keys behaviour | list | enabled |
| Position command object | list | disabled |
| Position report object | list | disabled |
| Position on voltage recovery | list | no movement |
| Block activation value | list | "1" value |
| Action on active block | list | stop |
| Position on active alarm | list | shutter up |
| Number of coupled sensors | unsignedInt 0…3 | 0 |
| Alarm 1 activation value | list | "1" value |
| Alarm 2 activation value | list | "1" value |
| Alarm 3 activation value | list | "1" value |
| Monitoring time [min] | unsignedInt 1…60 | 30 |
| Scene number 1 | list | unassigned |
| Scene 1 storing | list | enabled |
| Starting position for scene 1 | list | 100% (shutter down) |
| Scene number 2 | list | unassigned |
| Scene 2 storing | list | enabled |
| Starting position for scene 2 | list | 100% (shutter down) |
| Scene number 3 | list | unassigned |
| Scene 3 storing | list | enabled |
| Starting position for scene 3 | list | 100% (shutter down) |
| Scene number 4 | list | unassigned |
| Scene 4 storing | list | enabled |
| Starting position for scene 4 | list | 100% (shutter down) |
| Scene number 5 | list | unassigned |
| Scene 5 storing | list | enabled |
| Starting position for scene 5 | list | 100% (shutter down) |
| Scene number 6 | list | unassigned |
| Scene 6 storing | list | enabled |
| Starting position for scene 6 | list | 100% (shutter down) |
| Scene number 7 | list | unassigned |
| Scene 7 storing | list | enabled |
| Starting position for scene 7 | list | 100% (shutter down) |
| Scene number 8 | list | unassigned |
| Scene 8 storing | list | enabled |
| Starting position for scene 8 | list | 100% (shutter down) |
| Shutter automatic movement | list | never |
| Number of pulses after up movement | unsignedInt 1…16 | 1 |
| Number of pulses after down movement | unsignedInt 1…16 | 1 |
| Time between 2 pulses for shutter movement (n x 100 ms) | unsignedInt 3…10 | 3 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Shutter actuator 1 ch. 8A S 1.1 1.1 latest | $5107 | 315E | 2026-11-25 | 76 KB | Download |
About this file
This is the official ETS product database for the GEWISS GW12797 (GW12797), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.