| 1 | Time input | Update time | 3 Bytes | 10.1 time of day | CWTU |
| 2 | Daylight saving time input | 1 = daylight saving / 0 = standard | 1 Bit | 1.1 switch | CWT |
| 3 | Time sending | Send time | 3 Bytes | 10.1 time of day | CRT |
| 4 | Plate cleaning | Switching On/Off | 1 Bit | 1.1 switch | CWT |
| 5 | Enabling Slave function | Enable/Disable | 1 Bit | 1.3 enable | CWT |
| 6 | HVAC mode input | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CW |
| 6 | Setpoint input | °C Value | 2 Bytes | 9.1 temperature (°C) | CW |
| 6 | Setpoint input | K Value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 6 | Setpoint input | °F Value | 2 Bytes | 9.27 temperature (°F) | CW |
| 6 | Setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 7 | Setpoint temporary forcing regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 8 | Setpoint OFF input | Enable/Disable | 1 Bit | 1.3 enable | CW |
| 8 | HVAC off mode input | Enable/Disable | 1 Bit | 1.3 enable | CW |
| 9 | HVAC economy mode input | Enable/Disable | 1 Bit | 1.3 enable | CW |
| 10 | HVAC precomfort mode input | Enable/Disable | 1 Bit | 1.3 enable | CW |
| 11 | HVAC comfort mode input | Enable/Disable | 1 Bit | 1.3 enable | CW |
| 12 | Functioning type input | Heating/Air cooling | 1 Bit | 1.100 cooling/heating | CW |
| 13 | Enable dead zone | Enable/Disable | 1 Bit | 1.3 enable | CW |
| 14 | Heating anti-freeze setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 14 | Heating anti-freeze setpoint input | °C Value | 2 Bytes | 9.1 temperature (°C) | CW |
| 14 | Heating anti-freeze setpoint input | K Value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 14 | Heating anti-freeze setpoint input | °F Value | 2 Bytes | 9.27 temperature (°F) | CW |
| 15 | Heating economy setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 15 | Heating economy setpoint input | °C Value | 2 Bytes | 9.1 temperature (°C) | CW |
| 15 | Heating economy setpoint input | K Value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 15 | Heating economy setpoint input | °F Value | 2 Bytes | 9.27 temperature (°F) | CW |
| 16 | Heating precomfort setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 16 | Heating precomfort setpoint input | °C Value | 2 Bytes | 9.1 temperature (°C) | CW |
| 16 | Heating precomfort setpoint input | K Value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 16 | Heating precomfort setpoint input | °F Value | 2 Bytes | 9.27 temperature (°F) | CW |
| 17 | Heating comfort setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 17 | Heating comfort setpoint input | °C Value | 2 Bytes | 9.1 temperature (°C) | CW |
| 17 | Heating comfort setpoint input | K Value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 17 | Heating comfort setpoint input | °F Value | 2 Bytes | 9.27 temperature (°F) | CW |
| 18 | Air-cooling high temp. protection setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 18 | Air-cooling high temp. protection setpoint input | °C Value | 2 Bytes | 9.1 temperature (°C) | CW |
| 18 | Air-cooling high temp. protection setpoint input | K Value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 18 | Air-cooling high temp. protection setpoint input | °F Value | 2 Bytes | 9.27 temperature (°F) | CW |
| 19 | Air-cooling economy setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 19 | Air-cooling economy setpoint input | °C Value | 2 Bytes | 9.1 temperature (°C) | CW |
| 19 | Air-cooling economy setpoint input | K Value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 19 | Air-cooling economy setpoint input | °F Value | 2 Bytes | 9.27 temperature (°F) | CW |
| 20 | Air-cooling precomfort setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 20 | Air-cooling precomfort setpoint input | °C Value | 2 Bytes | 9.1 temperature (°C) | CW |
| 20 | Air-cooling precomfort setpoint input | K Value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 20 | Air-cooling precomfort setpoint input | °F Value | 2 Bytes | 9.27 temperature (°F) | CW |
| 21 | Air-cooling comfort setpoint regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 21 | Air-cooling comfort setpoint input | °C Value | 2 Bytes | 9.1 temperature (°C) | CW |
| 21 | Air-cooling comfort setpoint input | K Value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 21 | Air-cooling comfort setpoint input | °F Value | 2 Bytes | 9.27 temperature (°F) | CW |
| 22 | Setpoint regulation range setting | °C Value | 2 Bytes | 9.1 temperature (°C) | CW |
| 23 | Heating/cooling valve switch | On/Off | 1 Bit | 1.1 switch | CRT |
| 23 | % command valve heating/cooling | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 23 | Heating valve switch | On/Off | 1 Bit | 1.1 switch | CRT |
| 23 | % command valve heating | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 24 | Heating/air cooling valve status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 24 | Heating/air cooling valve % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 24 | Heating valve status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 24 | Heating valve % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 25 | V1 fan switching heating | On/Off | 1 Bit | 1.1 switch | CRT |
| 26 | V2 fan switching heating | On/Off | 1 Bit | 1.1 switch | CRT |
| 27 | V3 fan switching heating | On/Off | 1 Bit | 1.1 switch | CRT |
| 28 | Heating fan V1 status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 29 | Heating fan V2 status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 30 | Heating fan V3 status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 31 | Heating 2° stage switching | On/Off | 1 Bit | 1.1 switch | CRT |
| 31 | % command 2° stage heating | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 32 | Heating 2° stage feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 32 | Heating 2° stage valve % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 33 | Air cooling valve switch | On/Off | 1 Bit | 1.1 switch | CRT |
| 33 | % command valve air cooling | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 34 | Air cooling valve status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 34 | Air cooling valve % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 35 | V1 fan switching air cooling | On/Off | 1 Bit | 1.1 switch | CRT |
| 36 | V2 fan switching air cooling | On/Off | 1 Bit | 1.1 switch | CRT |
| 37 | V3 fan switching air cooling | On/Off | 1 Bit | 1.1 switch | CRT |
| 38 | Air cooling fan V1 status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 39 | Air cooling fan V2 status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 40 | Air cooling fan V3 status feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 41 | Air cooling 2° stage switching | On/Off | 1 Bit | 1.1 switch | CRT |
| 41 | % command 2° stage air cooling | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 42 | Air cooling 2° stage feedback | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 42 | Air cooling 2° stage valve % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 43 | Fan coil mode input | 1=Automatic / 0=Manual | 1 Bit | 1.1 switch | CW |
| 44 | Fan coil mode report | 1=Automatic / 0=Manual | 1 Bit | 1.1 switch | CRT |
| 45 | KNX external sensor input | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 45 | KNX external sensor input | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 45 | KNX external sensor input | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 45 | KNX floor sensor input | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 45 | KNX floor sensor input | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 45 | KNX floor sensor input | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 46 | Auxiliary external sensor measured temperature | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 46 | Auxiliary external sensor measured temperature | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 46 | Auxiliary external sensor measured temperature | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 47 | Measured temperature | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 47 | Measured temperature | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 47 | Measured temperature | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 48 | HVAC mode feedback | Eco/Precom/Comf/Off | 1 Byte | 20.102 HVAC mode | CRT |
| 48 | Functioning setpoint feedback | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 48 | Functioning setpoint feedback | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 48 | Functioning setpoint feedback | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 49 | HVAC off mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CRT |
| 49 | SETPOINT off mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CRT |
| 50 | HVAC economy mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CRT |
| 51 | HVAC precomfort mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CRT |
| 52 | HVAC comfort mode feedback | Enable/Disable | 1 Bit | 1.3 enable | CRT |
| 53 | Functioning type feedback | Heating/Air cooling | 1 Bit | 1.100 cooling/heating | CRT |
| 54 | Heating anti-freeze setpoint feedback | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 54 | Heating anti-freeze setpoint feedback | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 54 | Heating anti-freeze setpoint feedback | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 55 | Heating economy setpoint feedback | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 55 | Heating economy setpoint feedback | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 55 | Heating economy setpoint feedback | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 56 | Heating precomfort setpoint feedback | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 56 | Heating precomfort setpoint feedback | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 56 | Heating precomfort setpoint feedback | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 57 | Heating comfort setpoint feedback | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 57 | Heating comfort setpoint feedback | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 57 | Heating comfort setpoint feedback | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 58 | Air cond. high temp. protection setpoint feedback | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 58 | Air cond. high temp. protection setpoint feedback | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 58 | Air cond. high temp. protection setpoint feedback | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 59 | Air cooling economy setpoint feedback | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 59 | Air cooling economy setpoint feedback | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 59 | Air cooling economy setpoint feedback | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 60 | Air cooling precomfort setpoint feedback | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 60 | Air cooling precomfort setpoint feedback | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 60 | Air cooling precomfort setpoint feedback | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 61 | Air cooling comfort setpoint feedback | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 61 | Air cooling comfort setpoint feedback | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 61 | Air cooling comfort setpoint feedback | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 62 | Current setpoint report | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 62 | Current setpoint report | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 62 | Current setpoint report | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 63 | Thermostat functioning feedback | Slave/Stand alone | 1 Bit | 1.1 switch | CRT |
| 64 | Feedbacks sending trigger | Send feedbacks | 1 Bit | 1.17 trigger | CW |
| 65 | Thermostat scene | Execute/Store | 1 Byte | 18.1 scene control | CW |
| 66 | Humidity external sensor input | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CWTU |
| 67 | Relative humidity measured | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 68 | Specific humidity | Value [g/Kg] | 4 Bytes | 14.5 amplitude | CRT |
| 69 | Relative humidity threshold 1 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 69 | Relative humidity threshold 1 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 70 | Relative humidity threshold 1 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 71 | Relative humidity threshold 1 value regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 71 | Relative humidity threshold 1 value input | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CW |
| 72 | Relative humidity threshold 1 feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 73 | Relative humidity threshold 1 object A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 73 | Relative humidity threshold 1 object A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 73 | Relative humidity threshold 1 object A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 73 | Relative humidity threshold 1 object A | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 73 | Relative humidity threshold 1 object A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 73 | Relative humidity threshold 1 object A | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 73 | Relative humidity threshold 1 object A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 73 | Relative humidity threshold 1 object A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 73 | Relative humidity threshold 1 object A | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 73 | Relative humidity threshold 1 object A | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 73 | Relative humidity threshold 1 object A | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 74 | Relative humidity threshold 1 object A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 74 | Relative humidity threshold 1 object A status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 74 | Relative humidity threshold 1 object A status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 74 | Relative humidity threshold 1 object A status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 74 | Relative humidity threshold 1 object A status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 75 | Relative humidity threshold 1 object B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 75 | Relative humidity threshold 1 object B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 75 | Relative humidity threshold 1 object B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 75 | Relative humidity threshold 1 object B | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 75 | Relative humidity threshold 1 object B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 75 | Relative humidity threshold 1 object B | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 75 | Relative humidity threshold 1 object B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 75 | Relative humidity threshold 1 object B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 75 | Relative humidity threshold 1 object B | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 75 | Relative humidity threshold 1 object B | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 75 | Relative humidity threshold 1 object B | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 76 | Relative humidity threshold 1 object B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 76 | Relative humidity threshold 1 object B status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 76 | Relative humidity threshold 1 object B status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 76 | Relative humidity threshold 1 object B status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 76 | Relative humidity threshold 1 object B status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 77 | Relative humidity threshold 1 object C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 77 | Relative humidity threshold 1 object C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 77 | Relative humidity threshold 1 object C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 77 | Relative humidity threshold 1 object C | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 77 | Relative humidity threshold 1 object C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 77 | Relative humidity threshold 1 object C | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 77 | Relative humidity threshold 1 object C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 77 | Relative humidity threshold 1 object C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 77 | Relative humidity threshold 1 object C | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 77 | Relative humidity threshold 1 object C | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 77 | Relative humidity threshold 1 object C | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 78 | Relative humidity threshold 1 object C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 78 | Relative humidity threshold 1 object C status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 78 | Relative humidity threshold 1 object C status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 78 | Relative humidity threshold 1 object C status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 78 | Relative humidity threshold 1 object C status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 79 | Relative humidity threshold 1 object D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 79 | Relative humidity threshold 1 object D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 79 | Relative humidity threshold 1 object D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 79 | Relative humidity threshold 1 object D | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 79 | Relative humidity threshold 1 object D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 79 | Relative humidity threshold 1 object D | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 79 | Relative humidity threshold 1 object D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 79 | Relative humidity threshold 1 object D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 79 | Relative humidity threshold 1 object D | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 79 | Relative humidity threshold 1 object D | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 79 | Relative humidity threshold 1 object D | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 80 | Relative humidity threshold 1 object D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 80 | Relative humidity threshold 1 object D status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 80 | Relative humidity threshold 1 object D status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 80 | Relative humidity threshold 1 object D status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 80 | Relative humidity threshold 1 object D status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 81 | Relative humidity threshold 2 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 81 | Relative humidity threshold 2 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 82 | Relative humidity threshold 2 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 83 | Relative humidity threshold 2 value regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 83 | Relative humidity threshold 2 value input | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CW |
| 84 | Relative humidity threshold 2 feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 85 | Relative humidity threshold 2 object A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 85 | Relative humidity threshold 2 object A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 85 | Relative humidity threshold 2 object A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 85 | Relative humidity threshold 2 object A | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 85 | Relative humidity threshold 2 object A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 85 | Relative humidity threshold 2 object A | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 85 | Relative humidity threshold 2 object A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 85 | Relative humidity threshold 2 object A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 85 | Relative humidity threshold 2 object A | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 85 | Relative humidity threshold 2 object A | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 85 | Relative humidity threshold 2 object A | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 86 | Relative humidity threshold 2 object A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 86 | Relative humidity threshold 2 object A status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 86 | Relative humidity threshold 2 object A status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 86 | Relative humidity threshold 2 object A status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 86 | Relative humidity threshold 2 object A status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 87 | Relative humidity threshold 2 object B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 87 | Relative humidity threshold 2 object B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 87 | Relative humidity threshold 2 object B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 87 | Relative humidity threshold 2 object B | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 87 | Relative humidity threshold 2 object B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 87 | Relative humidity threshold 2 object B | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 87 | Relative humidity threshold 2 object B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 87 | Relative humidity threshold 2 object B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 87 | Relative humidity threshold 2 object B | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 87 | Relative humidity threshold 2 object B | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 87 | Relative humidity threshold 2 object B | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 88 | Relative humidity threshold 2 object B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 88 | Relative humidity threshold 2 object B status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 88 | Relative humidity threshold 2 object B status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 88 | Relative humidity threshold 2 object B status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 88 | Relative humidity threshold 2 object B status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 89 | Relative humidity threshold 2 object C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 89 | Relative humidity threshold 2 object C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 89 | Relative humidity threshold 2 object C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 89 | Relative humidity threshold 2 object C | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 89 | Relative humidity threshold 2 object C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 89 | Relative humidity threshold 2 object C | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 89 | Relative humidity threshold 2 object C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 89 | Relative humidity threshold 2 object C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 89 | Relative humidity threshold 2 object C | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 89 | Relative humidity threshold 2 object C | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 89 | Relative humidity threshold 2 object C | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 90 | Relative humidity threshold 2 object C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 90 | Relative humidity threshold 2 object C status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 90 | Relative humidity threshold 2 object C status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 90 | Relative humidity threshold 2 object C status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 90 | Relative humidity threshold 2 object C status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 91 | Relative humidity threshold 2 object D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 91 | Relative humidity threshold 2 object D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 91 | Relative humidity threshold 2 object D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 91 | Relative humidity threshold 2 object D | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 91 | Relative humidity threshold 2 object D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 91 | Relative humidity threshold 2 object D | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 91 | Relative humidity threshold 2 object D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 91 | Relative humidity threshold 2 object D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 91 | Relative humidity threshold 2 object D | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 91 | Relative humidity threshold 2 object D | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 91 | Relative humidity threshold 2 object D | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 92 | Relative humidity threshold 2 object D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 92 | Relative humidity threshold 2 object D status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 92 | Relative humidity threshold 2 object D status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 92 | Relative humidity threshold 2 object D status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 92 | Relative humidity threshold 2 object D status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 93 | Relative humidity threshold 3 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 93 | Relative humidity threshold 3 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 94 | Relative humidity threshold 3 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 95 | Relative humidity threshold 3 value regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 95 | Relative humidity threshold 3 value input | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CW |
| 96 | Relative humidity threshold 3 feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 97 | Relative humidity threshold 3 object A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 97 | Relative humidity threshold 3 object A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 97 | Relative humidity threshold 3 object A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 97 | Relative humidity threshold 3 object A | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 97 | Relative humidity threshold 3 object A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 97 | Relative humidity threshold 3 object A | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 97 | Relative humidity threshold 3 object A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 97 | Relative humidity threshold 3 object A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 97 | Relative humidity threshold 3 object A | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 97 | Relative humidity threshold 3 object A | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 97 | Relative humidity threshold 3 object A | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 98 | Relative humidity threshold 3 object A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 98 | Relative humidity threshold 3 object A status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 98 | Relative humidity threshold 3 object A status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 98 | Relative humidity threshold 3 object A status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 98 | Relative humidity threshold 3 object A status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 99 | Relative humidity threshold 3 object B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 99 | Relative humidity threshold 3 object B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 99 | Relative humidity threshold 3 object B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 99 | Relative humidity threshold 3 object B | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 99 | Relative humidity threshold 3 object B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 99 | Relative humidity threshold 3 object B | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 99 | Relative humidity threshold 3 object B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 99 | Relative humidity threshold 3 object B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 99 | Relative humidity threshold 3 object B | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 99 | Relative humidity threshold 3 object B | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 99 | Relative humidity threshold 3 object B | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 100 | Relative humidity threshold 3 object B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 100 | Relative humidity threshold 3 object B status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 100 | Relative humidity threshold 3 object B status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 100 | Relative humidity threshold 3 object B status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 100 | Relative humidity threshold 3 object B status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 101 | Relative humidity threshold 3 object C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 101 | Relative humidity threshold 3 object C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 101 | Relative humidity threshold 3 object C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 101 | Relative humidity threshold 3 object C | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 101 | Relative humidity threshold 3 object C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 101 | Relative humidity threshold 3 object C | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 101 | Relative humidity threshold 3 object C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 101 | Relative humidity threshold 3 object C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 101 | Relative humidity threshold 3 object C | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 101 | Relative humidity threshold 3 object C | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 101 | Relative humidity threshold 3 object C | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 102 | Relative humidity threshold 3 object C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 102 | Relative humidity threshold 3 object C status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 102 | Relative humidity threshold 3 object C status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 102 | Relative humidity threshold 3 object C status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 102 | Relative humidity threshold 3 object C status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 103 | Relative humidity threshold 3 object D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 103 | Relative humidity threshold 3 object D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 103 | Relative humidity threshold 3 object D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 103 | Relative humidity threshold 3 object D | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 103 | Relative humidity threshold 3 object D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 103 | Relative humidity threshold 3 object D | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 103 | Relative humidity threshold 3 object D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 103 | Relative humidity threshold 3 object D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 103 | Relative humidity threshold 3 object D | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 103 | Relative humidity threshold 3 object D | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 103 | Relative humidity threshold 3 object D | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 104 | Relative humidity threshold 3 object D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 104 | Relative humidity threshold 3 object D status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 104 | Relative humidity threshold 3 object D status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 104 | Relative humidity threshold 3 object D status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 104 | Relative humidity threshold 3 object D status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 105 | Relative humidity threshold 4 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 105 | Relative humidity threshold 4 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 106 | Relative humidity threshold 4 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 107 | Relative humidity threshold 4 value regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 107 | Relative humidity threshold 4 value input | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CW |
| 108 | Relative humidity threshold 4 feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 109 | Relative humidity threshold 4 object A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 109 | Relative humidity threshold 4 object A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 109 | Relative humidity threshold 4 object A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 109 | Relative humidity threshold 4 object A | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 109 | Relative humidity threshold 4 object A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 109 | Relative humidity threshold 4 object A | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 109 | Relative humidity threshold 4 object A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 109 | Relative humidity threshold 4 object A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 109 | Relative humidity threshold 4 object A | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 109 | Relative humidity threshold 4 object A | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 109 | Relative humidity threshold 4 object A | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 110 | Relative humidity threshold 4 object A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 110 | Relative humidity threshold 4 object A status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 110 | Relative humidity threshold 4 object A status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 110 | Relative humidity threshold 4 object A status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 110 | Relative humidity threshold 4 object A status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 111 | Relative humidity threshold 4 object B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 111 | Relative humidity threshold 4 object B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 111 | Relative humidity threshold 4 object B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 111 | Relative humidity threshold 4 object B | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 111 | Relative humidity threshold 4 object B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 111 | Relative humidity threshold 4 object B | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 111 | Relative humidity threshold 4 object B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 111 | Relative humidity threshold 4 object B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 111 | Relative humidity threshold 4 object B | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 111 | Relative humidity threshold 4 object B | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 111 | Relative humidity threshold 4 object B | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 112 | Relative humidity threshold 4 object B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 112 | Relative humidity threshold 4 object B status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 112 | Relative humidity threshold 4 object B status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 112 | Relative humidity threshold 4 object B status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 112 | Relative humidity threshold 4 object B status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 113 | Relative humidity threshold 4 object C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 113 | Relative humidity threshold 4 object C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 113 | Relative humidity threshold 4 object C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 113 | Relative humidity threshold 4 object C | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 113 | Relative humidity threshold 4 object C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 113 | Relative humidity threshold 4 object C | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 113 | Relative humidity threshold 4 object C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 113 | Relative humidity threshold 4 object C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 113 | Relative humidity threshold 4 object C | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 113 | Relative humidity threshold 4 object C | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 113 | Relative humidity threshold 4 object C | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 114 | Relative humidity threshold 4 object C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 114 | Relative humidity threshold 4 object C status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 114 | Relative humidity threshold 4 object C status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 114 | Relative humidity threshold 4 object C status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 114 | Relative humidity threshold 4 object C status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 115 | Relative humidity threshold 4 object D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 115 | Relative humidity threshold 4 object D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 115 | Relative humidity threshold 4 object D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 115 | Relative humidity threshold 4 object D | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 115 | Relative humidity threshold 4 object D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 115 | Relative humidity threshold 4 object D | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 115 | Relative humidity threshold 4 object D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 115 | Relative humidity threshold 4 object D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 115 | Relative humidity threshold 4 object D | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 115 | Relative humidity threshold 4 object D | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 115 | Relative humidity threshold 4 object D | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 116 | Relative humidity threshold 4 object D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 116 | Relative humidity threshold 4 object D status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 116 | Relative humidity threshold 4 object D status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 116 | Relative humidity threshold 4 object D status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 116 | Relative humidity threshold 4 object D status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 117 | Relative humidity threshold 5 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 117 | Relative humidity threshold 5 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 118 | Relative humidity threshold 5 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 119 | Relative humidity threshold 5 value regulation | 1 = Increase/0 = Decrease | 1 Bit | 1.7 step | CW |
| 119 | Relative humidity threshold 5 value input | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CW |
| 120 | Relative humidity threshold 5 feedback | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 121 | Relative humidity threshold 5 object A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 121 | Relative humidity threshold 5 object A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 121 | Relative humidity threshold 5 object A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 121 | Relative humidity threshold 5 object A | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 121 | Relative humidity threshold 5 object A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 121 | Relative humidity threshold 5 object A | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 121 | Relative humidity threshold 5 object A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 121 | Relative humidity threshold 5 object A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 121 | Relative humidity threshold 5 object A | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 121 | Relative humidity threshold 5 object A | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 121 | Relative humidity threshold 5 object A | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 122 | Relative humidity threshold 5 object A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 122 | Relative humidity threshold 5 object A status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 122 | Relative humidity threshold 5 object A status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 122 | Relative humidity threshold 5 object A status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 122 | Relative humidity threshold 5 object A status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 123 | Relative humidity threshold 5 object B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 123 | Relative humidity threshold 5 object B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 123 | Relative humidity threshold 5 object B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 123 | Relative humidity threshold 5 object B | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 123 | Relative humidity threshold 5 object B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 123 | Relative humidity threshold 5 object B | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 123 | Relative humidity threshold 5 object B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 123 | Relative humidity threshold 5 object B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 123 | Relative humidity threshold 5 object B | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 123 | Relative humidity threshold 5 object B | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 123 | Relative humidity threshold 5 object B | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 124 | Relative humidity threshold 5 object B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 124 | Relative humidity threshold 5 object B status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 124 | Relative humidity threshold 5 object B status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 124 | Relative humidity threshold 5 object B status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 124 | Relative humidity threshold 5 object B status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 125 | Relative humidity threshold 5 object C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 125 | Relative humidity threshold 5 object C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 125 | Relative humidity threshold 5 object C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 125 | Relative humidity threshold 5 object C | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 125 | Relative humidity threshold 5 object C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 125 | Relative humidity threshold 5 object C | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 125 | Relative humidity threshold 5 object C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 125 | Relative humidity threshold 5 object C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 125 | Relative humidity threshold 5 object C | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 125 | Relative humidity threshold 5 object C | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 125 | Relative humidity threshold 5 object C | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 126 | Relative humidity threshold 5 object C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 126 | Relative humidity threshold 5 object C status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 126 | Relative humidity threshold 5 object C status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 126 | Relative humidity threshold 5 object C status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 126 | Relative humidity threshold 5 object C status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 127 | Relative humidity threshold 5 object D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 127 | Relative humidity threshold 5 object D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 127 | Relative humidity threshold 5 object D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 127 | Relative humidity threshold 5 object D | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 127 | Relative humidity threshold 5 object D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 127 | Relative humidity threshold 5 object D | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 127 | Relative humidity threshold 5 object D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 127 | Relative humidity threshold 5 object D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 127 | Relative humidity threshold 5 object D | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 127 | Relative humidity threshold 5 object D | K Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 127 | Relative humidity threshold 5 object D | °F Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 128 | Relative humidity threshold 5 object D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 128 | Relative humidity threshold 5 object D status | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CWTU |
| 128 | Relative humidity threshold 5 object D status | °C Value | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 128 | Relative humidity threshold 5 object D status | K Value | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 128 | Relative humidity threshold 5 object D status | °F Value | 2 Bytes | 9.27 temperature (°F) | CWTU |
| 129 | Season selection input | 1=Summer / 0=Winter | 1 Bit | 1.2 boolean | CWTU |
| 129 | Season selection input - 1=winter / 0=summer | 1=Winter / 0=Summer | 1 Bit | 1.2 boolean | CWTU |
| 130 | Thermal comfort feedback - 1=Comfortable / 0=Uncomfortable | 1=Comfortable / 0=Uncomfortable | 1 Bit | 1.2 boolean | CRT |
| 131 | Logic input 1 | Logic function input | 1 Bit | 1.2 boolean | CWTU |
| 132 | Logic input 2 | Logic function input | 1 Bit | 1.2 boolean | CWTU |
| 133 | Logic input 3 | Logic function input | 1 Bit | 1.2 boolean | CWTU |
| 134 | Logic input 4 | Logic function input | 1 Bit | 1.2 boolean | CWTU |
| 135 | Logic input 5 | Logic function input | 1 Bit | 1.2 boolean | CWTU |
| 136 | Logic input 6 | Logic function input | 1 Bit | 1.2 boolean | CWTU |
| 137 | Logic input 7 | Logic function input | 1 Bit | 1.2 boolean | CWTU |
| 138 | Logic input 8 | Logic function input | 1 Bit | 1.2 boolean | CWTU |
| 139 | Logic operation output | Logic | 1 Bit | 1.2 boolean | CRT |
| 140 | Window contact status input | V(0 = window closed, 1 window opened) | 1 Bit | 1.19 window/door | CWTU |
| 140 | Window contact status input | V(0 = window opened, 1 window closed) | 1 Bit | 1.19 window/door | CWTU |
| 141 | Setpoint temporary forcing reset | Enable/Disable | 1 Bit | 1.2 boolean | CW |
| 142 | Heating fan speed % | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 143 | Heating fan speed % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 144 | Air cooling fan speed % | % Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 145 | Air cooling fan speed % feedback | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 146 | Relative humidity estimated | Value [% RH] | 2 Bytes | 9.7 humidity (%) | CRT |
| 147 | Dewpoint temperature | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 147 | Dewpoint temperature | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 147 | Dewpoint temperature | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 148 | Heating fan coil speed % input | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 149 | Air cooling fan coil input speed % | % Value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 151 | Dewpoint alarm regulation limit | Step | 1 Bit | 1.7 step | CW |
| 152 | Dewpoint alarm threshold feedback [°C] | °C Value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 152 | Dewpoint alarm threshold feedback [K] | K Value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 152 | Dewpoint alarm threshold feedback [°F] | °F Value | 2 Bytes | 9.27 temperature (°F) | CRT |
| 153 | Enabling dewpoint temperature alarm threshold | 1/0 value | 1 Bit | 1.2 boolean | CW |
| 154 | Enabling state dewpoint temperature alarm threshold | 1/0 value | 1 Bit | 1.3 enable | CRT |
| 155 | Dewpoint temperature alarm output | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 155 | Dewpoint temperature alarm output | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 155 | Dewpoint temperature alarm output | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 155 | Dewpoint temperature alarm output | Value [-128 .. +127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 155 | Dewpoint temperature alarm output | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 155 | Dewpoint temperature alarm output | HVAC mode (com/precom/eco/off) | 1 Byte | 20.102 HVAC mode | CRT |
| 155 | Dewpoint temperature alarm output | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 155 | Dewpoint temperature alarm output | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 156 | Warning 3 input feedback | On/Off | 1 Bit | 1.1 switch | CWTU |
| 157 | Warning 4 input feedback | On/Off | 1 Bit | 1.1 switch | CWTU |
| 158 | Warning 5 input feedback | On/Off | 1 Bit | 1.1 switch | CWTU |
| 159 | Warning 6 input feedback | On/Off | 1 Bit | 1.1 switch | CWTU |