GW16976CB

GEWISS · Order number GW16976CB · Climate control devices › Thermostats

Download .knxprod KNX Thermostat THERMO ICE - Wall mounted - S 1.0 [SECURE] 1.0 · 307 KB

Product

ManufacturerGEWISS
Product nameGW16976CB
Order numberGW16976CB
Product textKNX Thermostat THERMO ICE - Wall mounted - White
HardwareKNX Thermostat THERMO ICE - Wall mounted
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2020-10-02
Languagesen-US, de-DE, es-ES, it-IT
Catalog entryM-0019_H-16976Cx-0_HP-530A-10-A3A0_CI-GW16976CB-1
FingerprintA3A0
SHA-2561d7c322ba6b3c614b62655787281ddb83747752d05d09c0a6b5ac8b4a6ade828
First seen2026-11-25
Markets59 markets

Application program: KNX Thermostat THERMO ICE - Wall mounted - S 1.0 [SECURE] 1.0

Application number$530A
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureYes
Minimum ETS version5.0
Parameters1003
Group objects533
Group objects (533)
NoNameFunctionSizeDPTFlags
1Time inputUpdate time3 Bytes10.1 time of dayCWTU
2Daylight saving time input1 = daylight saving / 0 = standard1 Bit1.1 switchCWT
3Time sendingSend time3 Bytes10.1 time of dayCRT
4Plate cleaningSwitching On/Off1 Bit1.1 switchCWT
5Enabling Slave functionEnable/Disable1 Bit1.3 enableCWT
6HVAC mode inputEco/Precom/Comf/Off1 Byte20.102 HVAC modeCW
6Setpoint input°C Value2 Bytes9.1 temperature (°C)CW
6Setpoint inputK Value2 Bytes9.2 temperature difference (K)CW
6Setpoint input°F Value2 Bytes9.27 temperature (°F)CW
6Setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
7Setpoint temporary forcing regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
8Setpoint OFF inputEnable/Disable1 Bit1.3 enableCW
8HVAC off mode inputEnable/Disable1 Bit1.3 enableCW
9HVAC economy mode inputEnable/Disable1 Bit1.3 enableCW
10HVAC precomfort mode inputEnable/Disable1 Bit1.3 enableCW
11HVAC comfort mode inputEnable/Disable1 Bit1.3 enableCW
12Functioning type inputHeating/Air cooling1 Bit1.100 cooling/heatingCW
13Enable dead zoneEnable/Disable1 Bit1.3 enableCW
14Heating anti-freeze setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
14Heating anti-freeze setpoint input°C Value2 Bytes9.1 temperature (°C)CW
14Heating anti-freeze setpoint inputK Value2 Bytes9.2 temperature difference (K)CW
14Heating anti-freeze setpoint input°F Value2 Bytes9.27 temperature (°F)CW
15Heating economy setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
15Heating economy setpoint input°C Value2 Bytes9.1 temperature (°C)CW
15Heating economy setpoint inputK Value2 Bytes9.2 temperature difference (K)CW
15Heating economy setpoint input°F Value2 Bytes9.27 temperature (°F)CW
16Heating precomfort setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
16Heating precomfort setpoint input°C Value2 Bytes9.1 temperature (°C)CW
16Heating precomfort setpoint inputK Value2 Bytes9.2 temperature difference (K)CW
16Heating precomfort setpoint input°F Value2 Bytes9.27 temperature (°F)CW
17Heating comfort setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
17Heating comfort setpoint input°C Value2 Bytes9.1 temperature (°C)CW
17Heating comfort setpoint inputK Value2 Bytes9.2 temperature difference (K)CW
17Heating comfort setpoint input°F Value2 Bytes9.27 temperature (°F)CW
18Air-cooling high temp. protection setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
18Air-cooling high temp. protection setpoint input°C Value2 Bytes9.1 temperature (°C)CW
18Air-cooling high temp. protection setpoint inputK Value2 Bytes9.2 temperature difference (K)CW
18Air-cooling high temp. protection setpoint input°F Value2 Bytes9.27 temperature (°F)CW
19Air-cooling economy setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
19Air-cooling economy setpoint input°C Value2 Bytes9.1 temperature (°C)CW
19Air-cooling economy setpoint inputK Value2 Bytes9.2 temperature difference (K)CW
19Air-cooling economy setpoint input°F Value2 Bytes9.27 temperature (°F)CW
20Air-cooling precomfort setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
20Air-cooling precomfort setpoint input°C Value2 Bytes9.1 temperature (°C)CW
20Air-cooling precomfort setpoint inputK Value2 Bytes9.2 temperature difference (K)CW
20Air-cooling precomfort setpoint input°F Value2 Bytes9.27 temperature (°F)CW
21Air-cooling comfort setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
21Air-cooling comfort setpoint input°C Value2 Bytes9.1 temperature (°C)CW
21Air-cooling comfort setpoint inputK Value2 Bytes9.2 temperature difference (K)CW
21Air-cooling comfort setpoint input°F Value2 Bytes9.27 temperature (°F)CW
22Setpoint regulation range setting°C Value2 Bytes9.1 temperature (°C)CW
23Heating/cooling valve switchOn/Off1 Bit1.1 switchCRT
23% command valve heating/cooling% Value1 Byte5.1 percentage (0..100%)CRT
23Heating valve switchOn/Off1 Bit1.1 switchCRT
23% command valve heating% Value1 Byte5.1 percentage (0..100%)CRT
24Heating/air cooling valve status feedbackOn/Off status1 Bit1.1 switchCWTU
24Heating/air cooling valve % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
24Heating valve status feedbackOn/Off status1 Bit1.1 switchCWTU
24Heating valve % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
25V1 fan switching heatingOn/Off1 Bit1.1 switchCRT
26V2 fan switching heatingOn/Off1 Bit1.1 switchCRT
27V3 fan switching heatingOn/Off1 Bit1.1 switchCRT
28Heating fan V1 status feedbackOn/Off status1 Bit1.1 switchCWTU
29Heating fan V2 status feedbackOn/Off status1 Bit1.1 switchCWTU
30Heating fan V3 status feedbackOn/Off status1 Bit1.1 switchCWTU
31Heating 2° stage switchingOn/Off1 Bit1.1 switchCRT
31% command 2° stage heating% Value1 Byte5.1 percentage (0..100%)CRT
32Heating 2° stage feedbackOn/Off status1 Bit1.1 switchCWTU
32Heating 2° stage valve % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
33Air cooling valve switchOn/Off1 Bit1.1 switchCRT
33% command valve air cooling% Value1 Byte5.1 percentage (0..100%)CRT
34Air cooling valve status feedbackOn/Off status1 Bit1.1 switchCWTU
34Air cooling valve % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
35V1 fan switching air coolingOn/Off1 Bit1.1 switchCRT
36V2 fan switching air coolingOn/Off1 Bit1.1 switchCRT
37V3 fan switching air coolingOn/Off1 Bit1.1 switchCRT
38Air cooling fan V1 status feedbackOn/Off status1 Bit1.1 switchCWTU
39Air cooling fan V2 status feedbackOn/Off status1 Bit1.1 switchCWTU
40Air cooling fan V3 status feedbackOn/Off status1 Bit1.1 switchCWTU
41Air cooling 2° stage switchingOn/Off1 Bit1.1 switchCRT
41% command 2° stage air cooling% Value1 Byte5.1 percentage (0..100%)CRT
42Air cooling 2° stage feedbackOn/Off status1 Bit1.1 switchCWTU
42Air cooling 2° stage valve % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
43Fan coil mode input1=Automatic / 0=Manual1 Bit1.1 switchCW
44Fan coil mode report1=Automatic / 0=Manual1 Bit1.1 switchCRT
45KNX external sensor input°C Value2 Bytes9.1 temperature (°C)CWTU
45KNX external sensor inputK Value2 Bytes9.2 temperature difference (K)CWTU
45KNX external sensor input°F Value2 Bytes9.27 temperature (°F)CWTU
45KNX floor sensor input°C Value2 Bytes9.1 temperature (°C)CWTU
45KNX floor sensor inputK Value2 Bytes9.2 temperature difference (K)CWTU
45KNX floor sensor input°F Value2 Bytes9.27 temperature (°F)CWTU
46Auxiliary external sensor measured temperature°C Value2 Bytes9.1 temperature (°C)CRT
46Auxiliary external sensor measured temperatureK Value2 Bytes9.2 temperature difference (K)CRT
46Auxiliary external sensor measured temperature°F Value2 Bytes9.27 temperature (°F)CRT
47Measured temperature°C Value2 Bytes9.1 temperature (°C)CRT
47Measured temperatureK Value2 Bytes9.2 temperature difference (K)CRT
47Measured temperature°F Value2 Bytes9.27 temperature (°F)CRT
48HVAC mode feedbackEco/Precom/Comf/Off1 Byte20.102 HVAC modeCRT
48Functioning setpoint feedback°C Value2 Bytes9.1 temperature (°C)CRT
48Functioning setpoint feedbackK Value2 Bytes9.2 temperature difference (K)CRT
48Functioning setpoint feedback°F Value2 Bytes9.27 temperature (°F)CRT
49HVAC off mode feedbackEnable/Disable1 Bit1.3 enableCRT
49SETPOINT off mode feedbackEnable/Disable1 Bit1.3 enableCRT
50HVAC economy mode feedbackEnable/Disable1 Bit1.3 enableCRT
51HVAC precomfort mode feedbackEnable/Disable1 Bit1.3 enableCRT
52HVAC comfort mode feedbackEnable/Disable1 Bit1.3 enableCRT
53Functioning type feedbackHeating/Air cooling1 Bit1.100 cooling/heatingCRT
54Heating anti-freeze setpoint feedback°C Value2 Bytes9.1 temperature (°C)CRT
54Heating anti-freeze setpoint feedbackK Value2 Bytes9.2 temperature difference (K)CRT
54Heating anti-freeze setpoint feedback°F Value2 Bytes9.27 temperature (°F)CRT
55Heating economy setpoint feedback°C Value2 Bytes9.1 temperature (°C)CRT
55Heating economy setpoint feedbackK Value2 Bytes9.2 temperature difference (K)CRT
55Heating economy setpoint feedback°F Value2 Bytes9.27 temperature (°F)CRT
56Heating precomfort setpoint feedback°C Value2 Bytes9.1 temperature (°C)CRT
56Heating precomfort setpoint feedbackK Value2 Bytes9.2 temperature difference (K)CRT
56Heating precomfort setpoint feedback°F Value2 Bytes9.27 temperature (°F)CRT
57Heating comfort setpoint feedback°C Value2 Bytes9.1 temperature (°C)CRT
57Heating comfort setpoint feedbackK Value2 Bytes9.2 temperature difference (K)CRT
57Heating comfort setpoint feedback°F Value2 Bytes9.27 temperature (°F)CRT
58Air cond. high temp. protection setpoint feedback°C Value2 Bytes9.1 temperature (°C)CRT
58Air cond. high temp. protection setpoint feedbackK Value2 Bytes9.2 temperature difference (K)CRT
58Air cond. high temp. protection setpoint feedback°F Value2 Bytes9.27 temperature (°F)CRT
59Air cooling economy setpoint feedback°C Value2 Bytes9.1 temperature (°C)CRT
59Air cooling economy setpoint feedbackK Value2 Bytes9.2 temperature difference (K)CRT
59Air cooling economy setpoint feedback°F Value2 Bytes9.27 temperature (°F)CRT
60Air cooling precomfort setpoint feedback°C Value2 Bytes9.1 temperature (°C)CRT
60Air cooling precomfort setpoint feedbackK Value2 Bytes9.2 temperature difference (K)CRT
60Air cooling precomfort setpoint feedback°F Value2 Bytes9.27 temperature (°F)CRT
61Air cooling comfort setpoint feedback°C Value2 Bytes9.1 temperature (°C)CRT
61Air cooling comfort setpoint feedbackK Value2 Bytes9.2 temperature difference (K)CRT
61Air cooling comfort setpoint feedback°F Value2 Bytes9.27 temperature (°F)CRT
62Current setpoint report°C Value2 Bytes9.1 temperature (°C)CRT
62Current setpoint reportK Value2 Bytes9.2 temperature difference (K)CRT
62Current setpoint report°F Value2 Bytes9.27 temperature (°F)CRT
63Thermostat functioning feedbackSlave/Stand alone1 Bit1.1 switchCRT
64Feedbacks sending triggerSend feedbacks1 Bit1.17 triggerCW
65Thermostat sceneExecute/Store1 Byte18.1 scene controlCW
66Humidity external sensor inputValue [% RH]2 Bytes9.7 humidity (%)CWTU
67Relative humidity measuredValue [% RH]2 Bytes9.7 humidity (%)CRT
68Specific humidityValue [g/Kg]4 Bytes14.5 amplitudeCRT
69Relative humidity threshold 1 enabling0=Enable/1=Disable1 Bit1.2 booleanCW
69Relative humidity threshold 1 enabling1=Enable/0=Disable1 Bit1.2 booleanCW
70Relative humidity threshold 1 enabling statusEnabled/Disabled1 Bit1.3 enableCRT
71Relative humidity threshold 1 value regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
71Relative humidity threshold 1 value inputValue [% RH]2 Bytes9.7 humidity (%)CW
72Relative humidity threshold 1 feedbackValue [% RH]2 Bytes9.7 humidity (%)CRT
73Relative humidity threshold 1 object A1/0 value1 Bit1.1 switchCRT
73Relative humidity threshold 1 object AOn/Off forced positioning2 Bit2.1 switch controlCRT
73Relative humidity threshold 1 object AValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
73Relative humidity threshold 1 object AValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
73Relative humidity threshold 1 object AValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
73Relative humidity threshold 1 object AHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
73Relative humidity threshold 1 object AValue [0 .. 65535]2 Bytes7.1 pulsesCRT
73Relative humidity threshold 1 object AValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
73Relative humidity threshold 1 object A°C Value2 Bytes9.1 temperature (°C)CRT
73Relative humidity threshold 1 object AK Value2 Bytes9.1 temperature (°C)CRT
73Relative humidity threshold 1 object A°F Value2 Bytes9.1 temperature (°C)CRT
74Relative humidity threshold 1 object A statusOn/Off status1 Bit1.1 switchCWTU
74Relative humidity threshold 1 object A statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
74Relative humidity threshold 1 object A status°C Value2 Bytes9.1 temperature (°C)CWTU
74Relative humidity threshold 1 object A statusK Value2 Bytes9.2 temperature difference (K)CWTU
74Relative humidity threshold 1 object A status°F Value2 Bytes9.27 temperature (°F)CWTU
75Relative humidity threshold 1 object B1/0 value1 Bit1.1 switchCRT
75Relative humidity threshold 1 object BOn/Off forced positioning2 Bit2.1 switch controlCRT
75Relative humidity threshold 1 object BValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
75Relative humidity threshold 1 object BValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
75Relative humidity threshold 1 object BValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
75Relative humidity threshold 1 object BHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
75Relative humidity threshold 1 object BValue [0 .. 65535]2 Bytes7.1 pulsesCRT
75Relative humidity threshold 1 object BValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
75Relative humidity threshold 1 object B°C Value2 Bytes9.1 temperature (°C)CRT
75Relative humidity threshold 1 object BK Value2 Bytes9.1 temperature (°C)CRT
75Relative humidity threshold 1 object B°F Value2 Bytes9.1 temperature (°C)CRT
76Relative humidity threshold 1 object B statusOn/Off status1 Bit1.1 switchCWTU
76Relative humidity threshold 1 object B statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
76Relative humidity threshold 1 object B status°C Value2 Bytes9.1 temperature (°C)CWTU
76Relative humidity threshold 1 object B statusK Value2 Bytes9.2 temperature difference (K)CWTU
76Relative humidity threshold 1 object B status°F Value2 Bytes9.27 temperature (°F)CWTU
77Relative humidity threshold 1 object C1/0 value1 Bit1.1 switchCRT
77Relative humidity threshold 1 object COn/Off forced positioning2 Bit2.1 switch controlCRT
77Relative humidity threshold 1 object CValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
77Relative humidity threshold 1 object CValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
77Relative humidity threshold 1 object CValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
77Relative humidity threshold 1 object CHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
77Relative humidity threshold 1 object CValue [0 .. 65535]2 Bytes7.1 pulsesCRT
77Relative humidity threshold 1 object CValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
77Relative humidity threshold 1 object C°C Value2 Bytes9.1 temperature (°C)CRT
77Relative humidity threshold 1 object CK Value2 Bytes9.1 temperature (°C)CRT
77Relative humidity threshold 1 object C°F Value2 Bytes9.1 temperature (°C)CRT
78Relative humidity threshold 1 object C statusOn/Off status1 Bit1.1 switchCWTU
78Relative humidity threshold 1 object C statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
78Relative humidity threshold 1 object C status°C Value2 Bytes9.1 temperature (°C)CWTU
78Relative humidity threshold 1 object C statusK Value2 Bytes9.2 temperature difference (K)CWTU
78Relative humidity threshold 1 object C status°F Value2 Bytes9.27 temperature (°F)CWTU
79Relative humidity threshold 1 object D1/0 value1 Bit1.1 switchCRT
79Relative humidity threshold 1 object DOn/Off forced positioning2 Bit2.1 switch controlCRT
79Relative humidity threshold 1 object DValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
79Relative humidity threshold 1 object DValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
79Relative humidity threshold 1 object DValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
79Relative humidity threshold 1 object DHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
79Relative humidity threshold 1 object DValue [0 .. 65535]2 Bytes7.1 pulsesCRT
79Relative humidity threshold 1 object DValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
79Relative humidity threshold 1 object D°C Value2 Bytes9.1 temperature (°C)CRT
79Relative humidity threshold 1 object DK Value2 Bytes9.1 temperature (°C)CRT
79Relative humidity threshold 1 object D°F Value2 Bytes9.1 temperature (°C)CRT
80Relative humidity threshold 1 object D statusOn/Off status1 Bit1.1 switchCWTU
80Relative humidity threshold 1 object D statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
80Relative humidity threshold 1 object D status°C Value2 Bytes9.1 temperature (°C)CWTU
80Relative humidity threshold 1 object D statusK Value2 Bytes9.2 temperature difference (K)CWTU
80Relative humidity threshold 1 object D status°F Value2 Bytes9.27 temperature (°F)CWTU
81Relative humidity threshold 2 enabling0=Enable/1=Disable1 Bit1.2 booleanCW
81Relative humidity threshold 2 enabling1=Enable/0=Disable1 Bit1.2 booleanCW
82Relative humidity threshold 2 enabling statusEnabled/Disabled1 Bit1.3 enableCRT
83Relative humidity threshold 2 value regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
83Relative humidity threshold 2 value inputValue [% RH]2 Bytes9.7 humidity (%)CW
84Relative humidity threshold 2 feedbackValue [% RH]2 Bytes9.7 humidity (%)CRT
85Relative humidity threshold 2 object A1/0 value1 Bit1.1 switchCRT
85Relative humidity threshold 2 object AOn/Off forced positioning2 Bit2.1 switch controlCRT
85Relative humidity threshold 2 object AValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
85Relative humidity threshold 2 object AValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
85Relative humidity threshold 2 object AValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
85Relative humidity threshold 2 object AHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
85Relative humidity threshold 2 object AValue [0 .. 65535]2 Bytes7.1 pulsesCRT
85Relative humidity threshold 2 object AValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
85Relative humidity threshold 2 object A°C Value2 Bytes9.1 temperature (°C)CRT
85Relative humidity threshold 2 object AK Value2 Bytes9.1 temperature (°C)CRT
85Relative humidity threshold 2 object A°F Value2 Bytes9.1 temperature (°C)CRT
86Relative humidity threshold 2 object A statusOn/Off status1 Bit1.1 switchCWTU
86Relative humidity threshold 2 object A statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
86Relative humidity threshold 2 object A status°C Value2 Bytes9.1 temperature (°C)CWTU
86Relative humidity threshold 2 object A statusK Value2 Bytes9.2 temperature difference (K)CWTU
86Relative humidity threshold 2 object A status°F Value2 Bytes9.27 temperature (°F)CWTU
87Relative humidity threshold 2 object B1/0 value1 Bit1.1 switchCRT
87Relative humidity threshold 2 object BOn/Off forced positioning2 Bit2.1 switch controlCRT
87Relative humidity threshold 2 object BValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
87Relative humidity threshold 2 object BValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
87Relative humidity threshold 2 object BValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
87Relative humidity threshold 2 object BHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
87Relative humidity threshold 2 object BValue [0 .. 65535]2 Bytes7.1 pulsesCRT
87Relative humidity threshold 2 object BValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
87Relative humidity threshold 2 object B°C Value2 Bytes9.1 temperature (°C)CRT
87Relative humidity threshold 2 object BK Value2 Bytes9.1 temperature (°C)CRT
87Relative humidity threshold 2 object B°F Value2 Bytes9.1 temperature (°C)CRT
88Relative humidity threshold 2 object B statusOn/Off status1 Bit1.1 switchCWTU
88Relative humidity threshold 2 object B statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
88Relative humidity threshold 2 object B status°C Value2 Bytes9.1 temperature (°C)CWTU
88Relative humidity threshold 2 object B statusK Value2 Bytes9.2 temperature difference (K)CWTU
88Relative humidity threshold 2 object B status°F Value2 Bytes9.27 temperature (°F)CWTU
89Relative humidity threshold 2 object C1/0 value1 Bit1.1 switchCRT
89Relative humidity threshold 2 object COn/Off forced positioning2 Bit2.1 switch controlCRT
89Relative humidity threshold 2 object CValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
89Relative humidity threshold 2 object CValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
89Relative humidity threshold 2 object CValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
89Relative humidity threshold 2 object CHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
89Relative humidity threshold 2 object CValue [0 .. 65535]2 Bytes7.1 pulsesCRT
89Relative humidity threshold 2 object CValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
89Relative humidity threshold 2 object C°C Value2 Bytes9.1 temperature (°C)CRT
89Relative humidity threshold 2 object CK Value2 Bytes9.1 temperature (°C)CRT
89Relative humidity threshold 2 object C°F Value2 Bytes9.1 temperature (°C)CRT
90Relative humidity threshold 2 object C statusOn/Off status1 Bit1.1 switchCWTU
90Relative humidity threshold 2 object C statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
90Relative humidity threshold 2 object C status°C Value2 Bytes9.1 temperature (°C)CWTU
90Relative humidity threshold 2 object C statusK Value2 Bytes9.2 temperature difference (K)CWTU
90Relative humidity threshold 2 object C status°F Value2 Bytes9.27 temperature (°F)CWTU
91Relative humidity threshold 2 object D1/0 value1 Bit1.1 switchCRT
91Relative humidity threshold 2 object DOn/Off forced positioning2 Bit2.1 switch controlCRT
91Relative humidity threshold 2 object DValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
91Relative humidity threshold 2 object DValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
91Relative humidity threshold 2 object DValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
91Relative humidity threshold 2 object DHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
91Relative humidity threshold 2 object DValue [0 .. 65535]2 Bytes7.1 pulsesCRT
91Relative humidity threshold 2 object DValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
91Relative humidity threshold 2 object D°C Value2 Bytes9.1 temperature (°C)CRT
91Relative humidity threshold 2 object DK Value2 Bytes9.1 temperature (°C)CRT
91Relative humidity threshold 2 object D°F Value2 Bytes9.1 temperature (°C)CRT
92Relative humidity threshold 2 object D statusOn/Off status1 Bit1.1 switchCWTU
92Relative humidity threshold 2 object D statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
92Relative humidity threshold 2 object D status°C Value2 Bytes9.1 temperature (°C)CWTU
92Relative humidity threshold 2 object D statusK Value2 Bytes9.2 temperature difference (K)CWTU
92Relative humidity threshold 2 object D status°F Value2 Bytes9.27 temperature (°F)CWTU
93Relative humidity threshold 3 enabling0=Enable/1=Disable1 Bit1.2 booleanCW
93Relative humidity threshold 3 enabling1=Enable/0=Disable1 Bit1.2 booleanCW
94Relative humidity threshold 3 enabling statusEnabled/Disabled1 Bit1.3 enableCRT
95Relative humidity threshold 3 value regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
95Relative humidity threshold 3 value inputValue [% RH]2 Bytes9.7 humidity (%)CW
96Relative humidity threshold 3 feedbackValue [% RH]2 Bytes9.7 humidity (%)CRT
97Relative humidity threshold 3 object A1/0 value1 Bit1.1 switchCRT
97Relative humidity threshold 3 object AOn/Off forced positioning2 Bit2.1 switch controlCRT
97Relative humidity threshold 3 object AValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
97Relative humidity threshold 3 object AValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
97Relative humidity threshold 3 object AValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
97Relative humidity threshold 3 object AHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
97Relative humidity threshold 3 object AValue [0 .. 65535]2 Bytes7.1 pulsesCRT
97Relative humidity threshold 3 object AValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
97Relative humidity threshold 3 object A°C Value2 Bytes9.1 temperature (°C)CRT
97Relative humidity threshold 3 object AK Value2 Bytes9.1 temperature (°C)CRT
97Relative humidity threshold 3 object A°F Value2 Bytes9.1 temperature (°C)CRT
98Relative humidity threshold 3 object A statusOn/Off status1 Bit1.1 switchCWTU
98Relative humidity threshold 3 object A statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
98Relative humidity threshold 3 object A status°C Value2 Bytes9.1 temperature (°C)CWTU
98Relative humidity threshold 3 object A statusK Value2 Bytes9.2 temperature difference (K)CWTU
98Relative humidity threshold 3 object A status°F Value2 Bytes9.27 temperature (°F)CWTU
99Relative humidity threshold 3 object B1/0 value1 Bit1.1 switchCRT
99Relative humidity threshold 3 object BOn/Off forced positioning2 Bit2.1 switch controlCRT
99Relative humidity threshold 3 object BValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
99Relative humidity threshold 3 object BValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
99Relative humidity threshold 3 object BValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
99Relative humidity threshold 3 object BHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
99Relative humidity threshold 3 object BValue [0 .. 65535]2 Bytes7.1 pulsesCRT
99Relative humidity threshold 3 object BValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
99Relative humidity threshold 3 object B°C Value2 Bytes9.1 temperature (°C)CRT
99Relative humidity threshold 3 object BK Value2 Bytes9.1 temperature (°C)CRT
99Relative humidity threshold 3 object B°F Value2 Bytes9.1 temperature (°C)CRT
100Relative humidity threshold 3 object B statusOn/Off status1 Bit1.1 switchCWTU
100Relative humidity threshold 3 object B statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
100Relative humidity threshold 3 object B status°C Value2 Bytes9.1 temperature (°C)CWTU
100Relative humidity threshold 3 object B statusK Value2 Bytes9.2 temperature difference (K)CWTU
100Relative humidity threshold 3 object B status°F Value2 Bytes9.27 temperature (°F)CWTU
101Relative humidity threshold 3 object C1/0 value1 Bit1.1 switchCRT
101Relative humidity threshold 3 object COn/Off forced positioning2 Bit2.1 switch controlCRT
101Relative humidity threshold 3 object CValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
101Relative humidity threshold 3 object CValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
101Relative humidity threshold 3 object CValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
101Relative humidity threshold 3 object CHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
101Relative humidity threshold 3 object CValue [0 .. 65535]2 Bytes7.1 pulsesCRT
101Relative humidity threshold 3 object CValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
101Relative humidity threshold 3 object C°C Value2 Bytes9.1 temperature (°C)CRT
101Relative humidity threshold 3 object CK Value2 Bytes9.1 temperature (°C)CRT
101Relative humidity threshold 3 object C°F Value2 Bytes9.1 temperature (°C)CRT
102Relative humidity threshold 3 object C statusOn/Off status1 Bit1.1 switchCWTU
102Relative humidity threshold 3 object C statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
102Relative humidity threshold 3 object C status°C Value2 Bytes9.1 temperature (°C)CWTU
102Relative humidity threshold 3 object C statusK Value2 Bytes9.2 temperature difference (K)CWTU
102Relative humidity threshold 3 object C status°F Value2 Bytes9.27 temperature (°F)CWTU
103Relative humidity threshold 3 object D1/0 value1 Bit1.1 switchCRT
103Relative humidity threshold 3 object DOn/Off forced positioning2 Bit2.1 switch controlCRT
103Relative humidity threshold 3 object DValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
103Relative humidity threshold 3 object DValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
103Relative humidity threshold 3 object DValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
103Relative humidity threshold 3 object DHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
103Relative humidity threshold 3 object DValue [0 .. 65535]2 Bytes7.1 pulsesCRT
103Relative humidity threshold 3 object DValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
103Relative humidity threshold 3 object D°C Value2 Bytes9.1 temperature (°C)CRT
103Relative humidity threshold 3 object DK Value2 Bytes9.1 temperature (°C)CRT
103Relative humidity threshold 3 object D°F Value2 Bytes9.1 temperature (°C)CRT
104Relative humidity threshold 3 object D statusOn/Off status1 Bit1.1 switchCWTU
104Relative humidity threshold 3 object D statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
104Relative humidity threshold 3 object D status°C Value2 Bytes9.1 temperature (°C)CWTU
104Relative humidity threshold 3 object D statusK Value2 Bytes9.2 temperature difference (K)CWTU
104Relative humidity threshold 3 object D status°F Value2 Bytes9.27 temperature (°F)CWTU
105Relative humidity threshold 4 enabling0=Enable/1=Disable1 Bit1.2 booleanCW
105Relative humidity threshold 4 enabling1=Enable/0=Disable1 Bit1.2 booleanCW
106Relative humidity threshold 4 enabling statusEnabled/Disabled1 Bit1.3 enableCRT
107Relative humidity threshold 4 value regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
107Relative humidity threshold 4 value inputValue [% RH]2 Bytes9.7 humidity (%)CW
108Relative humidity threshold 4 feedbackValue [% RH]2 Bytes9.7 humidity (%)CRT
109Relative humidity threshold 4 object A1/0 value1 Bit1.1 switchCRT
109Relative humidity threshold 4 object AOn/Off forced positioning2 Bit2.1 switch controlCRT
109Relative humidity threshold 4 object AValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
109Relative humidity threshold 4 object AValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
109Relative humidity threshold 4 object AValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
109Relative humidity threshold 4 object AHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
109Relative humidity threshold 4 object AValue [0 .. 65535]2 Bytes7.1 pulsesCRT
109Relative humidity threshold 4 object AValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
109Relative humidity threshold 4 object A°C Value2 Bytes9.1 temperature (°C)CRT
109Relative humidity threshold 4 object AK Value2 Bytes9.1 temperature (°C)CRT
109Relative humidity threshold 4 object A°F Value2 Bytes9.1 temperature (°C)CRT
110Relative humidity threshold 4 object A statusOn/Off status1 Bit1.1 switchCWTU
110Relative humidity threshold 4 object A statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
110Relative humidity threshold 4 object A status°C Value2 Bytes9.1 temperature (°C)CWTU
110Relative humidity threshold 4 object A statusK Value2 Bytes9.2 temperature difference (K)CWTU
110Relative humidity threshold 4 object A status°F Value2 Bytes9.27 temperature (°F)CWTU
111Relative humidity threshold 4 object B1/0 value1 Bit1.1 switchCRT
111Relative humidity threshold 4 object BOn/Off forced positioning2 Bit2.1 switch controlCRT
111Relative humidity threshold 4 object BValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
111Relative humidity threshold 4 object BValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
111Relative humidity threshold 4 object BValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
111Relative humidity threshold 4 object BHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
111Relative humidity threshold 4 object BValue [0 .. 65535]2 Bytes7.1 pulsesCRT
111Relative humidity threshold 4 object BValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
111Relative humidity threshold 4 object B°C Value2 Bytes9.1 temperature (°C)CRT
111Relative humidity threshold 4 object BK Value2 Bytes9.1 temperature (°C)CRT
111Relative humidity threshold 4 object B°F Value2 Bytes9.1 temperature (°C)CRT
112Relative humidity threshold 4 object B statusOn/Off status1 Bit1.1 switchCWTU
112Relative humidity threshold 4 object B statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
112Relative humidity threshold 4 object B status°C Value2 Bytes9.1 temperature (°C)CWTU
112Relative humidity threshold 4 object B statusK Value2 Bytes9.2 temperature difference (K)CWTU
112Relative humidity threshold 4 object B status°F Value2 Bytes9.27 temperature (°F)CWTU
113Relative humidity threshold 4 object C1/0 value1 Bit1.1 switchCRT
113Relative humidity threshold 4 object COn/Off forced positioning2 Bit2.1 switch controlCRT
113Relative humidity threshold 4 object CValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
113Relative humidity threshold 4 object CValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
113Relative humidity threshold 4 object CValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
113Relative humidity threshold 4 object CHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
113Relative humidity threshold 4 object CValue [0 .. 65535]2 Bytes7.1 pulsesCRT
113Relative humidity threshold 4 object CValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
113Relative humidity threshold 4 object C°C Value2 Bytes9.1 temperature (°C)CRT
113Relative humidity threshold 4 object CK Value2 Bytes9.1 temperature (°C)CRT
113Relative humidity threshold 4 object C°F Value2 Bytes9.1 temperature (°C)CRT
114Relative humidity threshold 4 object C statusOn/Off status1 Bit1.1 switchCWTU
114Relative humidity threshold 4 object C statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
114Relative humidity threshold 4 object C status°C Value2 Bytes9.1 temperature (°C)CWTU
114Relative humidity threshold 4 object C statusK Value2 Bytes9.2 temperature difference (K)CWTU
114Relative humidity threshold 4 object C status°F Value2 Bytes9.27 temperature (°F)CWTU
115Relative humidity threshold 4 object D1/0 value1 Bit1.1 switchCRT
115Relative humidity threshold 4 object DOn/Off forced positioning2 Bit2.1 switch controlCRT
115Relative humidity threshold 4 object DValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
115Relative humidity threshold 4 object DValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
115Relative humidity threshold 4 object DValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
115Relative humidity threshold 4 object DHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
115Relative humidity threshold 4 object DValue [0 .. 65535]2 Bytes7.1 pulsesCRT
115Relative humidity threshold 4 object DValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
115Relative humidity threshold 4 object D°C Value2 Bytes9.1 temperature (°C)CRT
115Relative humidity threshold 4 object DK Value2 Bytes9.1 temperature (°C)CRT
115Relative humidity threshold 4 object D°F Value2 Bytes9.1 temperature (°C)CRT
116Relative humidity threshold 4 object D statusOn/Off status1 Bit1.1 switchCWTU
116Relative humidity threshold 4 object D statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
116Relative humidity threshold 4 object D status°C Value2 Bytes9.1 temperature (°C)CWTU
116Relative humidity threshold 4 object D statusK Value2 Bytes9.2 temperature difference (K)CWTU
116Relative humidity threshold 4 object D status°F Value2 Bytes9.27 temperature (°F)CWTU
117Relative humidity threshold 5 enabling0=Enable/1=Disable1 Bit1.2 booleanCW
117Relative humidity threshold 5 enabling1=Enable/0=Disable1 Bit1.2 booleanCW
118Relative humidity threshold 5 enabling statusEnabled/Disabled1 Bit1.3 enableCRT
119Relative humidity threshold 5 value regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
119Relative humidity threshold 5 value inputValue [% RH]2 Bytes9.7 humidity (%)CW
120Relative humidity threshold 5 feedbackValue [% RH]2 Bytes9.7 humidity (%)CRT
121Relative humidity threshold 5 object A1/0 value1 Bit1.1 switchCRT
121Relative humidity threshold 5 object AOn/Off forced positioning2 Bit2.1 switch controlCRT
121Relative humidity threshold 5 object AValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
121Relative humidity threshold 5 object AValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
121Relative humidity threshold 5 object AValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
121Relative humidity threshold 5 object AHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
121Relative humidity threshold 5 object AValue [0 .. 65535]2 Bytes7.1 pulsesCRT
121Relative humidity threshold 5 object AValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
121Relative humidity threshold 5 object A°C Value2 Bytes9.1 temperature (°C)CRT
121Relative humidity threshold 5 object AK Value2 Bytes9.1 temperature (°C)CRT
121Relative humidity threshold 5 object A°F Value2 Bytes9.1 temperature (°C)CRT
122Relative humidity threshold 5 object A statusOn/Off status1 Bit1.1 switchCWTU
122Relative humidity threshold 5 object A statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
122Relative humidity threshold 5 object A status°C Value2 Bytes9.1 temperature (°C)CWTU
122Relative humidity threshold 5 object A statusK Value2 Bytes9.2 temperature difference (K)CWTU
122Relative humidity threshold 5 object A status°F Value2 Bytes9.27 temperature (°F)CWTU
123Relative humidity threshold 5 object B1/0 value1 Bit1.1 switchCRT
123Relative humidity threshold 5 object BOn/Off forced positioning2 Bit2.1 switch controlCRT
123Relative humidity threshold 5 object BValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
123Relative humidity threshold 5 object BValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
123Relative humidity threshold 5 object BValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
123Relative humidity threshold 5 object BHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
123Relative humidity threshold 5 object BValue [0 .. 65535]2 Bytes7.1 pulsesCRT
123Relative humidity threshold 5 object BValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
123Relative humidity threshold 5 object B°C Value2 Bytes9.1 temperature (°C)CRT
123Relative humidity threshold 5 object BK Value2 Bytes9.1 temperature (°C)CRT
123Relative humidity threshold 5 object B°F Value2 Bytes9.1 temperature (°C)CRT
124Relative humidity threshold 5 object B statusOn/Off status1 Bit1.1 switchCWTU
124Relative humidity threshold 5 object B statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
124Relative humidity threshold 5 object B status°C Value2 Bytes9.1 temperature (°C)CWTU
124Relative humidity threshold 5 object B statusK Value2 Bytes9.2 temperature difference (K)CWTU
124Relative humidity threshold 5 object B status°F Value2 Bytes9.27 temperature (°F)CWTU
125Relative humidity threshold 5 object C1/0 value1 Bit1.1 switchCRT
125Relative humidity threshold 5 object COn/Off forced positioning2 Bit2.1 switch controlCRT
125Relative humidity threshold 5 object CValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
125Relative humidity threshold 5 object CValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
125Relative humidity threshold 5 object CValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
125Relative humidity threshold 5 object CHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
125Relative humidity threshold 5 object CValue [0 .. 65535]2 Bytes7.1 pulsesCRT
125Relative humidity threshold 5 object CValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
125Relative humidity threshold 5 object C°C Value2 Bytes9.1 temperature (°C)CRT
125Relative humidity threshold 5 object CK Value2 Bytes9.1 temperature (°C)CRT
125Relative humidity threshold 5 object C°F Value2 Bytes9.1 temperature (°C)CRT
126Relative humidity threshold 5 object C statusOn/Off status1 Bit1.1 switchCWTU
126Relative humidity threshold 5 object C statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
126Relative humidity threshold 5 object C status°C Value2 Bytes9.1 temperature (°C)CWTU
126Relative humidity threshold 5 object C statusK Value2 Bytes9.2 temperature difference (K)CWTU
126Relative humidity threshold 5 object C status°F Value2 Bytes9.27 temperature (°F)CWTU
127Relative humidity threshold 5 object D1/0 value1 Bit1.1 switchCRT
127Relative humidity threshold 5 object DOn/Off forced positioning2 Bit2.1 switch controlCRT
127Relative humidity threshold 5 object DValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
127Relative humidity threshold 5 object DValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
127Relative humidity threshold 5 object DValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
127Relative humidity threshold 5 object DHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
127Relative humidity threshold 5 object DValue [0 .. 65535]2 Bytes7.1 pulsesCRT
127Relative humidity threshold 5 object DValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
127Relative humidity threshold 5 object D°C Value2 Bytes9.1 temperature (°C)CRT
127Relative humidity threshold 5 object DK Value2 Bytes9.1 temperature (°C)CRT
127Relative humidity threshold 5 object D°F Value2 Bytes9.1 temperature (°C)CRT
128Relative humidity threshold 5 object D statusOn/Off status1 Bit1.1 switchCWTU
128Relative humidity threshold 5 object D statusHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
128Relative humidity threshold 5 object D status°C Value2 Bytes9.1 temperature (°C)CWTU
128Relative humidity threshold 5 object D statusK Value2 Bytes9.2 temperature difference (K)CWTU
128Relative humidity threshold 5 object D status°F Value2 Bytes9.27 temperature (°F)CWTU
129Season selection input1=Summer / 0=Winter1 Bit1.2 booleanCWTU
129Season selection input - 1=winter / 0=summer1=Winter / 0=Summer1 Bit1.2 booleanCWTU
130Thermal comfort feedback - 1=Comfortable / 0=Uncomfortable1=Comfortable / 0=Uncomfortable1 Bit1.2 booleanCRT
131Logic input 1Logic function input1 Bit1.2 booleanCWTU
132Logic input 2Logic function input1 Bit1.2 booleanCWTU
133Logic input 3Logic function input1 Bit1.2 booleanCWTU
134Logic input 4Logic function input1 Bit1.2 booleanCWTU
135Logic input 5Logic function input1 Bit1.2 booleanCWTU
136Logic input 6Logic function input1 Bit1.2 booleanCWTU
137Logic input 7Logic function input1 Bit1.2 booleanCWTU
138Logic input 8Logic function input1 Bit1.2 booleanCWTU
139Logic operation outputLogic1 Bit1.2 booleanCRT
140Window contact status input V(0 = window closed, 1 window opened)1 Bit1.19 window/doorCWTU
140Window contact status inputV(0 = window opened, 1 window closed)1 Bit1.19 window/doorCWTU
141Setpoint temporary forcing resetEnable/Disable1 Bit1.2 booleanCW
142Heating fan speed %% Value1 Byte5.1 percentage (0..100%)CRT
143Heating fan speed % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
144Air cooling fan speed %% Value1 Byte5.1 percentage (0..100%)CRT
145Air cooling fan speed % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
146Relative humidity estimatedValue [% RH]2 Bytes9.7 humidity (%)CRT
147Dewpoint temperature°C Value2 Bytes9.1 temperature (°C)CRT
147Dewpoint temperatureK Value2 Bytes9.2 temperature difference (K)CRT
147Dewpoint temperature°F Value2 Bytes9.27 temperature (°F)CRT
148Heating fan coil speed % input% Value1 Byte5.1 percentage (0..100%)CWTU
149Air cooling fan coil input speed %% Value1 Byte5.1 percentage (0..100%)CWTU
151Dewpoint alarm regulation limitStep1 Bit1.7 stepCW
152Dewpoint alarm threshold feedback [°C]°C Value2 Bytes9.1 temperature (°C)CRT
152Dewpoint alarm threshold feedback [K]K Value2 Bytes9.2 temperature difference (K)CRT
152Dewpoint alarm threshold feedback [°F]°F Value2 Bytes9.27 temperature (°F)CRT
153Enabling dewpoint temperature alarm threshold1/0 value1 Bit1.2 booleanCW
154Enabling state dewpoint temperature alarm threshold1/0 value1 Bit1.3 enableCRT
155Dewpoint temperature alarm output1/0 value1 Bit1.1 switchCRT
155Dewpoint temperature alarm outputOn/Off forced positioning2 Bit2.1 switch controlCRT
155Dewpoint temperature alarm outputValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
155Dewpoint temperature alarm outputValue [-128 .. +127]1 Byte6.10 counter pulses (-128..127)CRT
155Dewpoint temperature alarm outputValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
155Dewpoint temperature alarm outputHVAC mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
155Dewpoint temperature alarm outputValue [0 .. 65535]2 Bytes7.1 pulsesCRT
155Dewpoint temperature alarm outputValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
156Warning 3 input feedbackOn/Off1 Bit1.1 switchCWTU
157Warning 4 input feedbackOn/Off1 Bit1.1 switchCWTU
158Warning 5 input feedbackOn/Off1 Bit1.1 switchCWTU
159Warning 6 input feedbackOn/Off1 Bit1.1 switchCWTU
Parameters (350)
ParameterTypeDefault
PAR_TEST_TYPE_CONTROLlistHVAC mode
PAR_TEST_SETPOINT_FORCING_VIA_BUSlistdisable
PAR_TEST_HEATING_ALGORITHMlisttwo points ON-OFF
PAR_TEST_HEATING_VALVE_FEEDBACKlistenable
PAR_TEST_FUNCTIONING_TYPElistFALSE
PAR_TEST_HEATING_FANCOIL_VALVE_MANAGEMENTlisttwo points ON-OFF
PAR_TEST_AIR_COOLING_FANCOIL_VALVE_MANAGEMENTlisttwo points ON-OFF
PAR_TEST_FANCOIL_MODElistdisable
PAR_TEST_HEATING_FANCOIL_PI_OPERATION_LIMITlistFALSE
PAR_TEST_AIR_COOLING_FANCOIL_PI_OPERATION_LIMITlistFALSE
PAR_TEST_REMOTE_PARAMETERS_SETTINGlistdisable
PID_HARDWARE_TYPE_PARAMETERlist
PARAM_DO_MASTER_RESETlistAPP_FIRST_BOOT
Delay time from power on and first transmissionlist11..21 seconds (depends on physical address)
Thermostat functioning [P28]liststand alone
Functioning type settinglistby local command or from bus
Parameters local modificationlistbasic parameters only
Parameters local modificationlistdisabled
Base parameters values overwrite during downloadlistyes
Advanced parameters values overwrite during downloadlistyes
Plate cleaning functionlistenable
Inhibition time [s]unsignedInt 10…24030
Hour modification via buslistdisable
Hour sending via buslistdisabled
Hour sending periodlist1 week
Set daylight saving time from buslistdisable
Object "Daylight saving time" value at ETS downloadliststandard time
Stand alone control typelistHVAC mode
Master/Slave control typelistHVAC mode
Remote parameters settinglistdisable
Remote parameters settinglistenable
Change the functioning setpoint via bus throughlistabsolute value setting [°C]
Setpoint regulation step [0.1 °C]unsignedInt 1…205
Temporary setpoint forcing via buslistdisable
Setpoint temporary forcing regulation step [0.1 °C]unsignedInt 1…205
Reset temporary setpoint forcing via buslistdisable
Commands format for HVAC mode remote settinglist1 byte
Priority between objects for HVAC mode remote settinglistenable
Reception 1 bit mode with priority > actuallistkeep lower priority objects value
Reception 1 bit mode with priority < actuallistupdate object value
HVAC mode setpoint modification via buslistdisable
Allow local switching offlistdisable
Reactivate device bylistlocal control only
Set functioning typelistdisable
Control logic Heating/Air coolinglistdifferent (4 pipe)
Heating/Air cooling control algorithmlisttwo points ON-OFF
Heating control algorithmlisttwo points ON-OFF
Fan coil valves managementlisttwo points ON-OFF
Heating/Air cooling valve status feedbacklistenable
Commands repetition period with disabled feedbacklist5 minutes
Air cooling control algorithmlisttwo points ON-OFF
Fan coil speed modification via buslistdisable
Fan coil mode (automatic/manual) feedbacklistdisable
Regulation differential [tenths of °C] [P12]unsignedInt 1…202
Select heating systemlistfloor heating
Proportional band [P8]list3.5 °C
Proportional band [P8]list3.0 °C
Proportional band [P8]list2.0 °C
Integration time [P9]list150 minutes
Integration time [P9]list240 minutes
Integration time [P9]list90 minutes
Integration time [P9]list100 minutes
Integration time [P9]list60 minutes
Cycle time [P10]list20 minutes
Min % variation for continuous sending [P11]list5%
Fan coil speed numberunsignedInt 1…33
Regulation differential speed 1 [tenths of °C] [P17]unsignedInt 1…202
Regulation differential speed 2 [tenths of °C] [P18]unsignedInt 1…202
Regulation differential speed 3 [tenths of °C] [P19]unsignedInt 1…202
Speed 1 inertia time (seconds) [P20]unsignedInt 0…100
Speed 2 inertia time (seconds) [P21]unsignedInt 0…100
Speed 3 inertia time (seconds) [P22]unsignedInt 0…100
Proportional band [P23]list2.0 °C
Integration time [P24]list60 minutes
Min % variation for continuous sending [P25]list5%
Fan coil speed status feedbacklistenable
Fan coil valve managementlisttwo points ON-OFF
Regulation differential valve [tenths of °C] [P13]unsignedInt 1…202
Operation limit fan coil [tenths of °C] [P26]unsignedInt 1…202
Valvelistset the parameters manually
Proportional band [P14]list2.0 °C
Integration time [P15]list60 minutes
Min % variation for continuous sending [P16]list5%
Heating valve status feedbacklistenable
Heating 2° stagelistdisabled
Operation limit 2° stage [tenths of °C]unsignedInt 10…10010
Regulation differential 2° stage [tenths of °C] [P27]unsignedInt 1…202
Heating 2° stage feedbacklistenable
Command repetition time 2° stage without feedbacklist5 minutes
PAR_TEST_AIR_COOLING_ALGORITHMlisttwo points ON-OFF
Select air cooling systemlistceiling cooling
Proportional band [P8]list5.0 °C
Proportional band [P8]list4.0 °C
Cycle time [P10]list30 minutes
Air cooling valve status feedbacklistenable
Air cooling 2° stagelistdisabled
Air cooling 2° stage feedbacklistenable
Comfort setpoint [tenths of °C]unsignedInt 101…349200
Functioning setpoint [tenths of °C]unsignedInt 101…349200
Precomfort setpoint [tenths of °C]unsignedInt 101…349180
Economy setpoint [tenths of °C]unsignedInt 101…349160
Antifreeze setpoint [tenths of °C] [P1]unsignedInt 20…10050
Antifreeze setpoint after manual switching off [tenths of °C]unsignedInt 20…10050
Comfort setpoint [tenths of °C]unsignedInt 101…349240
Functioning setpoint [tenths of °C]unsignedInt 101…349240
Precomfort setpoint [tenths of °C]unsignedInt 101…349260
Economy setpoint [tenths of °C]unsignedInt 101…349280
High temperature protection setpoint [tenths of °C] [P1]unsignedInt 350…400350
High temperature protection setpoint [tenths of °C]unsignedInt 350…400350
Temporary forcing behavior at new setpoint reception from BUSlistcancel temporary forcing
Temporary forcing behavior at new setpoint receptionlistcancel temporary forcing
Manual forcing rangelist± 3.0
Setpoint variation range for manual forcinglistunlimited
Manual forcing range variation objectlistdisable
Update all setpoints of same typelistno
Update also the setpoints of the other typelistno
Internal sensor correction factor [tenths of °C] [P42]signedInt -50…500
KNX temperature sensor functionlistdisabled
KNX sensor measurement unitlistCelsius degrees °C)
KNX sensor surveillance time [min] (0=no surveillance)unsignedInt 0…102
Behavior in case of no signal from KNX sensorlistuse last received value
Behavior in case of no signal from KNX sensorlistactivate temperature alarm
Weight of KNX external sensor in measured temperaturelist10%
Temperature alarm threshold [tenths of °C]unsignedInt 150…1000500
Temperature alarm hysteresis [tenths of °C]unsignedInt 10…10030
Auxiliary temperature sensor functionlistdisabled
Type of NTC sensor connectedlistwired sensor (GW10800)
Auxiliary sensor correction factor [tenths of °C]signedInt -20…200
Behavior in case of no signal from auxiliary sensorlistuse last received value
Behavior in case of no signal from auxiliary sensorlistactivate temperature alarm
Auxiliary sensor measured temperaturelistdo not send
Measure unitlistCelsius degrees °C)
Minimum variation for sending value [± 0.1 °C]unsignedInt 1…105
Temperature sending period [minutes]unsignedInt 1…2555
Weight of auxiliary sensor in measured temperaturelist10%
Measured temperaturelistdo not send
HVAC mode feedbacklistdisabled
1 bit HVAC modeliston demand only
1 byte HVAC modeliston demand only
Functioning setpoint feedbacklistdisabled
Functioning type feedbacklistdisabled
Current setpoint reportlistdisabled
Thermostat functioning feedbacklistdisabled
HVAC mode setpoint feedbacklistdisabled
Setpoint OFF mode feedbacklistdisabled
Feedbacks sending trigger objectlistdisable
Scenes functionlistdisable
Scene number 1listunassigned
Scene number 2listunassigned
Scene number 3listunassigned
Scene number 4listunassigned
Scene number 5listunassigned
Scene number 6listunassigned
Scene number 7listunassigned
Scene number 8listunassigned
Parameters to memorize while storinglistHVAC mode only
Parameters to memorize while storinglistsetpoint only
Internal sensor correction factor [% UR] [P43]signedInt -10…100
Relative humidity measuredlistdo not send
Minimum variation for sending value [% RH]list± 5%
Value repetition time [minutes]unsignedInt 1…2555
KNX external humidity sensorlistdisable
Weight of KNX sensor in measured humidity relativelist10%
KNX external sensor monitoring time [min] (0= no monitoring)unsignedInt 0…101
Behaviour at KNX external sensor signal absencelistuse last received value
Humidity estimation modelistdisabled
Weight of relative humidity estimated in the calculation of humidity measuredlist10%
Estimated humidity relativelistdo not send
Specific humiditylistdo not send
Minimum variation for sending value [g/Kg]list± 5 g/Kg
PAR_TEST_1_OBJ_A_RESULT_1listFALSE
PAR_TEST_2_OBJ_A_RESULT_1listFALSE
PAR_TEST_3_OBJ_A_RESULT_1listFALSE
PAR_TEST_4_OBJ_A_RESULT_1listFALSE
PAR_TEST_1_OBJ_B_RESULT_1listFALSE
PAR_TEST_2_OBJ_B_RESULT_1listFALSE
PAR_TEST_3_OBJ_B_RESULT_1listFALSE
PAR_TEST_4_OBJ_B_RESULT_1listFALSE
PAR_TEST_1_OBJ_C_RESULT_1listFALSE
PAR_TEST_2_OBJ_C_RESULT_1listFALSE
PAR_TEST_3_OBJ_C_RESULT_1listFALSE
PAR_TEST_4_OBJ_C_RESULT_1listFALSE
PAR_TEST_1_OBJ_D_RESULT_1listFALSE
PAR_TEST_2_OBJ_D_RESULT_1listFALSE
PAR_TEST_3_OBJ_D_RESULT_1listFALSE
PAR_TEST_4_OBJ_D_RESULT_1listFALSE
Relative humidity threshold 1 [P29]listdisable
Measure to use as referencelistmeasured relative humidity
Threshold logic functioninglisthumidification
C1 = Condition 1listRelative humidity <= Limit threshold - hysteresis
C1 = Condition 1listRelative humidity >= Limit threshold + hysteresis
C2 = Condition 2listRelative humidity >= Limit threshold
C2 = Condition 2listRelative humidity <= Limit threshold
Limit threshold starting value [% RH] [P34]unsignedInt 0…10050
Limit threshold hysteresis [% RH]unsignedInt 1…205
Change the threshold value via bus throughlistabsolute value
Threshold regulation step via bus [%]unsignedInt 1…205
Enable/disable the humidity threshold (via bus and device menu)listno
Threshold activation valuelistvalue "0"
Threshold activation status after bus voltage recoverylistas before voltage drop
Output formatlist1 bit
On the occurrence of Condition 1listsends 1
On the occurrence of Condition 1listsends active forcing on(down)
On the occurrence of Condition 1listvalue sending
On the occurrence of Condition 1listsends comfort
On the occurrence of Condition 1listsends current setpoint ± offset
Value (0 .. 255)unsignedInt 0…2550
Value (-128 .. 127)signedInt -128…1270
Value (0% .. 100%)unsignedInt 0…1000
Value (0 .. 65535)unsignedInt 0…655350
Value (-32768 .. +32767)signedInt -32768…327670
Offset(-3 .. +3)signedInt -3…31
Offset [0.1 °C] (-300 .. +300)signedInt -300…30010
On the occurrence of Condition 2listno effect
Relative humidity threshold output status feedbacklistenable
object Commands cyclical repetitionlistenable
------------------------------listdisable
PAR_TEST_1_OBJ_A_RESULT_2listFALSE
PAR_TEST_2_OBJ_A_RESULT_2listFALSE
PAR_TEST_3_OBJ_A_RESULT_2listFALSE
PAR_TEST_4_OBJ_A_RESULT_2listFALSE
PAR_TEST_1_OBJ_B_RESULT_2listFALSE
PAR_TEST_2_OBJ_B_RESULT_2listFALSE
PAR_TEST_3_OBJ_B_RESULT_2listFALSE
PAR_TEST_4_OBJ_B_RESULT_2listFALSE
PAR_TEST_1_OBJ_C_RESULT_2listFALSE
PAR_TEST_2_OBJ_C_RESULT_2listFALSE
PAR_TEST_3_OBJ_C_RESULT_2listFALSE
PAR_TEST_4_OBJ_C_RESULT_2listFALSE
PAR_TEST_1_OBJ_D_RESULT_2listFALSE
PAR_TEST_2_OBJ_D_RESULT_2listFALSE
PAR_TEST_3_OBJ_D_RESULT_2listFALSE
PAR_TEST_4_OBJ_D_RESULT_2listFALSE
Relative humidity threshold 2 [P30]listdisable
Limit threshold starting value [% RH] [P35]unsignedInt 0…10050
PAR_TEST_1_OBJ_A_RESULT_3listFALSE
PAR_TEST_2_OBJ_A_RESULT_3listFALSE
PAR_TEST_3_OBJ_A_RESULT_3listFALSE
PAR_TEST_4_OBJ_A_RESULT_3listFALSE
PAR_TEST_1_OBJ_B_RESULT_3listFALSE
PAR_TEST_2_OBJ_B_RESULT_3listFALSE
PAR_TEST_3_OBJ_B_RESULT_3listFALSE
PAR_TEST_4_OBJ_B_RESULT_3listFALSE
PAR_TEST_1_OBJ_C_RESULT_3listFALSE
PAR_TEST_2_OBJ_C_RESULT_3listFALSE
PAR_TEST_3_OBJ_C_RESULT_3listFALSE
PAR_TEST_4_OBJ_C_RESULT_3listFALSE
PAR_TEST_1_OBJ_D_RESULT_3listFALSE
PAR_TEST_2_OBJ_D_RESULT_3listFALSE
PAR_TEST_3_OBJ_D_RESULT_3listFALSE
PAR_TEST_4_OBJ_D_RESULT_3listFALSE
Relative humidity threshold 3 [P31]listdisable
Limit threshold starting value [% RH] [P36]unsignedInt 0…10050
PAR_TEST_1_OBJ_A_RESULT_4listFALSE
PAR_TEST_2_OBJ_A_RESULT_4listFALSE
PAR_TEST_3_OBJ_A_RESULT_4listFALSE
PAR_TEST_4_OBJ_A_RESULT_4listFALSE
PAR_TEST_1_OBJ_B_RESULT_4listFALSE
PAR_TEST_2_OBJ_B_RESULT_4listFALSE
PAR_TEST_3_OBJ_B_RESULT_4listFALSE
PAR_TEST_4_OBJ_B_RESULT_4listFALSE
PAR_TEST_1_OBJ_C_RESULT_4listFALSE
PAR_TEST_2_OBJ_C_RESULT_4listFALSE
PAR_TEST_3_OBJ_C_RESULT_4listFALSE
PAR_TEST_4_OBJ_C_RESULT_4listFALSE
PAR_TEST_1_OBJ_D_RESULT_4listFALSE
PAR_TEST_2_OBJ_D_RESULT_4listFALSE
PAR_TEST_3_OBJ_D_RESULT_4listFALSE
PAR_TEST_4_OBJ_D_RESULT_4listFALSE
Relative humidity threshold 4 [P32]listdisable
Limit threshold starting value [% RH] [P37]unsignedInt 0…10050
PAR_TEST_1_OBJ_A_RESULT_5listFALSE
PAR_TEST_2_OBJ_A_RESULT_5listFALSE
PAR_TEST_3_OBJ_A_RESULT_5listFALSE
PAR_TEST_4_OBJ_A_RESULT_5listFALSE
PAR_TEST_1_OBJ_B_RESULT_5listFALSE
PAR_TEST_2_OBJ_B_RESULT_5listFALSE
PAR_TEST_3_OBJ_B_RESULT_5listFALSE
PAR_TEST_4_OBJ_B_RESULT_5listFALSE
PAR_TEST_1_OBJ_C_RESULT_5listFALSE
PAR_TEST_2_OBJ_C_RESULT_5listFALSE
PAR_TEST_3_OBJ_C_RESULT_5listFALSE
PAR_TEST_4_OBJ_C_RESULT_5listFALSE
PAR_TEST_1_OBJ_D_RESULT_5listFALSE
PAR_TEST_2_OBJ_D_RESULT_5listFALSE
PAR_TEST_3_OBJ_D_RESULT_5listFALSE
PAR_TEST_4_OBJ_D_RESULT_5listFALSE
Relative humidity threshold 5 [P33]listdisable
Limit threshold starting value [% RH] [P38]unsignedInt 0…10050
Enable thermal sensor feedbacklistdisable
Summer/Winter seasonlistfollow active heat/cool mode
Logic values used to represent seasonslist1 = summer / 0 = winter
Active season after ETS downloadlistsummer
Maximum temperature [0.1 °C]unsignedInt 200…400260
Minimum temperature [0.1 °C]unsignedInt 100…300240
Maximum relative humidity [% UR]unsignedInt 50…9560
Minimum relative humidity [% UR]unsignedInt 10…4540
Maximum specific humidity [0.1 g/Kg]unsignedInt 50…220115
Maximum temperature [0.1 °C]unsignedInt 200…400220
Minimum temperature [0.1 °C]unsignedInt 100…300180
Dewpoint temperaturelistdo not send
Feedback sending period [minutes]unsignedInt 1…2555
Dewpoint temperature alarm feedback [P39]listdisable
Alarm threshold feedback measure unitlistCelsius degrees °C)
Limit alarm feedback [tenths of °C] [P40]unsignedInt 0…10050
Limit alarm feedback regulation step [0.1 °C]unsignedInt 1…205
Alarm threshold hysteresis [tenths of °C] [P41]unsignedInt 1…2010
Activate/Deactivate alarm threshold (from bus and local menu)listno
Alarm threshold valuelistvalue "1"
Alarm threshold state at bus recoverylistas before voltage drop
C1 = Condition 1listIf measured Temperature < threshold Temperature
C2 = Condition 2listIf measured Temperature > threshold Temperature + value of hysteresis
object Commands cyclical repetitionlistdisable
Commands repetition periodlist5 minutes
Circular slider modality in temperature reference regulation [P7]listTemporary forcing of current setpoint
Circular slider modality in temperature reference regulation [P7]listChange configuration value of current setpoint
Temperature measure unit [P2]listCelsius degrees [°C]
Proximity Sensor [P5]listenable
Display information rotation in stand-by [P6]listenable
Display activation in stand-bylistenable
- Backlight brightness intensity percentage value [P3]list80%
Sound effect for "Touch" events [P4]listenable
KNX window external contactlistdisable
Logical interpretation of the open window statuslistStandard (0 = window closed, 1 window opened)
Delay time for the action of window contact (hours)unsignedInt 0…110
Delay time for the action of window contact (minutes)unsignedInt 0…591
Delay time for the action of window contact (seconds)unsignedInt 0…590
Logic Functionlistdisable
Logic input 1listenable
NOT operation for logic input 1listdisable
Logic input 2listenable
NOT operation for logic input 2listdisable
Logic input 3listdisable
NOT operation for logic input 3listdisable
Logic input 4listdisable
NOT operation for logic input 4listdisable
Logic input 5listdisable
NOT operation for logic input 5listdisable
Logic input 6listdisable
NOT operation for logic input 6listdisable
Logic input 7listdisable
NOT operation for logic input 7listdisable
Logic input 8listdisable
NOT operation for logic input 8listdisable
Operation between logic inputslistAND
The logic operation is computedlistwhenever an input value is received
Calculation periodunsignedInt 1…2551
Generate the result of the logic operationlistwhenever the logic is evaluated
If the result of the logic operation is TRUElistsends "1"
If the result of the logic operation is FALSElistsends "0"

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX Thermostat THERMO ICE - Wall mounted - S 1.0 [SECURE] 1.0 latest$530AA3A02026-11-25307 KBDownload

About this file

This is the official ETS product database for the GEWISS GW16976CB (GW16976CB), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.