GW13799H

GEWISS · Order number GW13799H · Climate control devices › Sonde da incasso

Download .knxprod KNX Temperature and Humidity probe S 1.2 1.2 · 296 KB

Product

ManufacturerGEWISS
Product nameGW13799H
Order numberGW13799H
Product textKNX Temperature and Humidity probe - Satin natural beige
HardwareSonda di termoregolazione e umidità KNX
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2020-12-04
Languagesde-DE, en-US, es-ES, it-IT
Catalog entryM-0019_H-10799H-0_HP-5309-12-B42B_CI-GW13799H-0
FingerprintB42B
SHA-256846424408056e0748f8e4cbce811f49e13e1dc898288c5a95a2f3234afe13802
First seen2026-11-25
Markets59 markets

Application program: KNX Temperature and Humidity probe S 1.2 1.2

Application number$5309
Version1.2
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters1011
Group objects603
Group objects (603)
NoNameFunctionSizeDPTFlags
0Setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
0HVAC mode inputEco/Precom/Comf/Off1 Byte20.102 HVAC modeCW
0Setpoint inputValue °C2 Bytes9.1 temperature (°C)CW
0Setpoint input°K value2 Bytes9.2 temperature difference (K)CW
0Setpoint input°F value2 Bytes9.27 temperature (°F)CW
1Setpoint temporary forcing regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
1Temporary setpoint forcing inputValue °C2 Bytes9.1 temperature (°C)CW
1Temporary setpoint forcing input°K value2 Bytes9.2 temperature difference (K)CW
1Temporary setpoint forcing input°F value2 Bytes9.27 temperature (°F)CW
2HVAC off mode inputEnable/Disable1 Bit1.3 enableCW
3HVAC economy mode inputEnable/Disable1 Bit1.3 enableCW
4HVAC precomfort mode inputEnable/Disable1 Bit1.3 enableCW
5HVAC comfort mode inputEnable/Disable1 Bit1.3 enableCW
6Functioning type inputHeating/Air cooling1 Bit1.100 heating/coolingCW
7Enable dead zoneEnable/Disable1 Bit1.3 enableCW
8Heating anti-freeze setpoint inputValue °C2 Bytes9.1 temperature (°C)CW
8Heating anti-freeze setpoint input°K value2 Bytes9.2 temperature difference (K)CW
8Heating anti-freeze setpoint input°F value2 Bytes9.27 temperature (°F)CW
8Heating anti-freeze setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
9Heating economy setpoint inputValue °C2 Bytes9.1 temperature (°C)CW
9Heating economy setpoint input°K value2 Bytes9.2 temperature difference (K)CW
9Heating economy setpoint input°F value2 Bytes9.27 temperature (°F)CW
9Heating economy setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
10Heating precomfort setpoint inputValue °C2 Bytes9.1 temperature (°C)CW
10Heating precomfort setpoint input°K value2 Bytes9.2 temperature difference (K)CW
10Heating precomfort setpoint input°F value2 Bytes9.27 temperature (°F)CW
10Heating precomfort setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
11Heating comfort setpoint inputValue °C2 Bytes9.1 temperature (°C)CW
11Heating comfort setpoint input°K value2 Bytes9.2 temperature difference (K)CW
11Heating comfort setpoint input°F value2 Bytes9.27 temperature (°F)CW
11Heating comfort setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
12Air-cooling high temp. protection setpoint inputValue °C2 Bytes9.1 temperature (°C)CW
12Air-cooling high temp. protection setpoint input°K value2 Bytes9.2 temperature difference (K)CW
12Air-cooling high temp. protection setpoint input°F value2 Bytes9.27 temperature (°F)CW
12Air-cooling high temp. protec. setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
13Air-cooling economy setpoint inputValue °C2 Bytes9.1 temperature (°C)CW
13Air-cooling economy setpoint input°K value2 Bytes9.2 temperature difference (K)CW
13Air-cooling economy setpoint input°F value2 Bytes9.27 temperature (°F)CW
13Air-cooling economy setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
14Air-cooling precomfort setpoint inputValue °C2 Bytes9.1 temperature (°C)CW
14Air-cooling precomfort setpoint input°K value2 Bytes9.2 temperature difference (K)CW
14Air-cooling precomfort setpoint input°F value2 Bytes9.27 temperature (°F)CW
14Air-cooling precomfort setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
15Air-cooling comfort setpoint inputValue °C2 Bytes9.1 temperature (°C)CW
15Air-cooling comfort setpoint input°K value2 Bytes9.2 temperature difference (K)CW
15Air-cooling comfort setpoint input°F value2 Bytes9.27 temperature (°F)CW
15Air-cooling comfort setpoint regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
16Heating valve switchOn/Off1 Bit1.1 switchCRT
16% command valve heating % Value1 Byte5.1 percentage (0..100%)CRT
16Heating/Air cooling valve switchOn/Off1 Bit1.1 switchCRT
16Heating/air cooling valve % command% Value1 Byte5.1 percentage (0..100%)CRT
17Heating valve status feedbackOn/Off status1 Bit1.1 switchCWTU
17Heating valve % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
17Heating/air cooling valve status feedbackOn/Off status1 Bit1.1 switchCWTU
17Heating/Air cooling valve % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
18V1 fan switching heatingOn/Off1 Bit1.1 switchCRT
18% command fancoil speed heating % Value1 Byte5.1 percentage (0..100%)CRT
19V2 fan switching heatingOn/Off1 Bit1.1 switchCRT
20V3 fan switching heatingOn/Off1 Bit1.1 switchCRT
21Heating fan V1 status feedbackOn/Off status1 Bit1.1 switchCWTU
21Heating fancoil speed % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
22Heating fan V2 status feedbackOn/Off status1 Bit1.1 switchCWTU
23Heating fan V3 status feedbackOn/Off status1 Bit1.1 switchCWTU
24Heating 2° stage switchingOn/Off1 Bit1.1 switchCRT
24% command 2° stage heating % Value1 Byte5.1 percentage (0..100%)CRT
25Heating 2° stage feedbackOn/Off status1 Bit1.1 switchCWTU
25Heating 2° stage valve % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
26Air cooling valve % command% Value1 Byte5.1 percentage (0..100%)CRT
26Air cooling valve switchOn/Off1 Bit1.1 switchCRT
27Air cooling valve % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
27Air cooling valve status feedbackOn/Off status1 Bit1.1 switchCWTU
28% command fancoil speed air cooling % Value1 Byte5.1 percentage (0..100%)CRT
28V1 fan switching air coolingOn/Off1 Bit1.1 switchCRT
29V2 fan switching air coolingOn/Off1 Bit1.1 switchCRT
30V3 fan switching air coolingOn/Off1 Bit1.1 switchCRT
31Air cooling fancoil speed % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
31Air cooling fan V1 status feedbackOn/Off status1 Bit1.1 switchCWTU
32Air cooling fan V2 status feedbackOn/Off status1 Bit1.1 switchCWTU
33Air cooling fan V3 status feedbackOn/Off status1 Bit1.1 switchCWTU
34% command 2° stage air cooling % Value1 Byte5.1 percentage (0..100%)CRT
34Air cooling 2° stage switchingOn/Off1 Bit1.1 switchCRT
35Air cooling 2° stage valve % feedback% Value1 Byte5.1 percentage (0..100%)CWTU
35Air cooling 2° stage feedbackOn/Off status1 Bit1.1 switchCWTU
36Fancoil mode inputAutomatic/manual1 Bit1.1 switchCW
37Fan coil mode reportAutomatic/manual1 Bit1.1 switchCRT
38KNX external sensor inputValue °C2 Bytes9.1 temperature (°C)CWTU
38KNX external sensor input°K value2 Bytes9.2 temperature difference (K)CWTU
38KNX external sensor input°F value2 Bytes9.27 temperature (°F)CWTU
38KNX floor sensor inputValue °C2 Bytes9.1 temperature (°C)CWTU
38KNX floor sensor input°K value2 Bytes9.2 temperature difference (K)CWTU
38KNX floor sensor input°F value2 Bytes9.27 temperature (°F)CWTU
39Auxiliary sensor measured temperatureValue °C2 Bytes9.1 temperature (°C)CR
39Auxiliary sensor measured temperature°K value2 Bytes9.2 temperature difference (K)CR
39Auxiliary sensor measured temperature°F value2 Bytes9.27 temperature (°F)CR
39Auxiliary sensor measured temperatureValue °C2 Bytes9.1 temperature (°C)CRT
39Auxiliary sensor measured temperature°K value2 Bytes9.2 temperature difference (K)CRT
39Auxiliary sensor measured temperature°F value2 Bytes9.27 temperature (°F)CRT
40Measured temperatureValue °C2 Bytes9.1 temperature (°C)CR
40Measured temperature°K value2 Bytes9.2 temperature difference (K)CR
40Measured temperature°F value2 Bytes9.27 temperature (°F)CR
40Measured temperatureValue °C2 Bytes9.1 temperature (°C)CRT
40Measured temperature°K value2 Bytes9.2 temperature difference (K)CRT
40Measured temperature°F value2 Bytes9.27 temperature (°F)CRT
41Functioning setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CR
41Functioning setpoint feedback°K value2 Bytes9.2 temperature difference (K)CR
41Functioning setpoint feedback°F value2 Bytes9.27 temperature (°F)CR
41Functioning setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CRT
41Functioning setpoint feedback°K value2 Bytes9.2 temperature difference (K)CRT
41Functioning setpoint feedback°F value2 Bytes9.27 temperature (°F)CRT
41HVAC mode feedbackEco/Precom/Comf/Off1 Byte20.102 HVAC modeCR
41HVAC mode feedbackEco/Precom/Comf/Off1 Byte20.102 HVAC modeCRT
42HVAC off mode feedbackEnable/Disable1 Bit1.3 enableCR
42HVAC off mode feedbackEnable/Disable1 Bit1.3 enableCRT
43HVAC economy mode feedbackEnable/Disable1 Bit1.3 enableCR
43HVAC economy mode feedbackEnable/Disable1 Bit1.3 enableCRT
44HVAC precomfort mode feedbackEnable/Disable1 Bit1.3 enableCR
44HVAC precomfort mode feedbackEnable/Disable1 Bit1.3 enableCRT
45HVAC comfort mode feedbackEnable/Disable1 Bit1.3 enableCR
45HVAC comfort mode feedbackEnable/Disable1 Bit1.3 enableCRT
46Functioning type feedbackHeating/Air cooling1 Bit1.100 heating/coolingCRT
46Functioning type feedbackHeating/Air cooling1 Bit1.100 heating/coolingCR
47Heating anti-freeze setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CR
47Heating anti-freeze setpoint feedback°K value2 Bytes9.2 temperature difference (K)CR
47Heating anti-freeze setpoint feedback°F value2 Bytes9.27 temperature (°F)CR
47Heating anti-freeze setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CRT
47Heating anti-freeze setpoint feedback°K value2 Bytes9.2 temperature difference (K)CRT
47Heating anti-freeze setpoint feedback°F value2 Bytes9.27 temperature (°F)CRT
48Heating economy setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CR
48Heating economy setpoint feedback°K value2 Bytes9.2 temperature difference (K)CR
48Heating economy setpoint feedback°F value2 Bytes9.27 temperature (°F)CR
48Heating economy setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CRT
48Heating economy setpoint feedback°K value2 Bytes9.2 temperature difference (K)CRT
48Heating economy setpoint feedback°F value2 Bytes9.27 temperature (°F)CRT
49Heating precomfort setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CR
49Heating precomfort setpoint feedback°K value2 Bytes9.2 temperature difference (K)CR
49Heating precomfort setpoint feedback°F value2 Bytes9.27 temperature (°F)CR
49Heating precomfort setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CRT
49Heating precomfort setpoint feedback°K value2 Bytes9.2 temperature difference (K)CRT
49Heating precomfort setpoint feedback°F value2 Bytes9.27 temperature (°F)CRT
50Heating comfort setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CR
50Heating comfort setpoint feedback°K value2 Bytes9.2 temperature difference (K)CR
50Heating comfort setpoint feedback°F value2 Bytes9.27 temperature (°F)CR
50Heating comfort setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CRT
50Heating comfort setpoint feedback°K value2 Bytes9.2 temperature difference (K)CRT
50Heating comfort setpoint feedback°F value2 Bytes9.27 temperature (°F)CRT
51Air cond. high temp. protection setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CR
51Air cond. high temp. protection setpoint feedback°K value2 Bytes9.2 temperature difference (K)CR
51Air cond. high temp. protection setpoint feedback°F value2 Bytes9.27 temperature (°F)CR
51Air cond. high temp. protection setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CRT
51Air cond. high temp. protection setpoint feedback°K value2 Bytes9.2 temperature difference (K)CRT
51Air cond. high temp. protection setpoint feedback°F value2 Bytes9.27 temperature (°F)CRT
52Air cooling economy setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CR
52Air cooling economy setpoint feedback°K value2 Bytes9.2 temperature difference (K)CR
52Air cooling economy setpoint feedback°F value2 Bytes9.27 temperature (°F)CR
52Air cooling economy setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CRT
52Air cooling economy setpoint feedback°K value2 Bytes9.2 temperature difference (K)CRT
52Air cooling economy setpoint feedback°F value2 Bytes9.27 temperature (°F)CRT
53Air cooling precomfort setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CR
53Air cooling precomfort setpoint feedback°K value2 Bytes9.2 temperature difference (K)CR
53Air cooling precomfort setpoint feedback°F value2 Bytes9.27 temperature (°F)CR
53Air cooling precomfort setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CRT
53Air cooling precomfort setpoint feedback°K value2 Bytes9.2 temperature difference (K)CRT
53Air cooling precomfort setpoint feedback°F value2 Bytes9.27 temperature (°F)CRT
54Air cooling comfort setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CR
54Air cooling comfort setpoint feedback°K value2 Bytes9.2 temperature difference (K)CR
54Air cooling comfort setpoint feedback°F value2 Bytes9.27 temperature (°F)CR
54Air cooling comfort setpoint feedbackValue °C2 Bytes9.1 temperature (°C)CRT
54Air cooling comfort setpoint feedback°K value2 Bytes9.2 temperature difference (K)CRT
54Air cooling comfort setpoint feedback°F value2 Bytes9.27 temperature (°F)CRT
55Current setpoint report°K value2 Bytes9.2 temperature difference (K)CR
55Current setpoint reportValue °C2 Bytes9.1 temperature (°C)CR
55Current setpoint report°F value2 Bytes9.27 temperature (°F)CR
55Current setpoint reportValue °C2 Bytes9.1 temperature (°C)CRT
55Current setpoint report°K value2 Bytes9.2 temperature difference (K)CRT
55Current setpoint report°F value2 Bytes9.27 temperature (°F)CRT
56Feedbacks sending triggerSend feedbacks1 Bit1.17 triggerCW
57KNX sensor sceneExecute/Store1 Byte18.1 scene controlCW
58Input aux 1 - Dimmer status feedbackOn/Off status1 Bit1.1 switchCWTU
58Input aux 1 - Status feedbackOn/Off status1 Bit1.1 switchCWTU
58Input aux 1 - Movement feedbackIncrease/Decrease1 Bit1.8 up/downCW
59Input aux 1 - 14 byte valueCharacters ISO 8859-114 Bytes16.1 Character String (ISO 8859-1)CRT
59Input aux 1 - 1 bit value1/0 value1 Bit1.1 switchCRT
59Input aux 1 - 2 bit valueOn/Off forced positioning2 Bit2.1 switch controlCRT
59Input aux 1 - 1 byte valueUnsigned value1 Byte5.10 counter pulses (0..255)CRT
59Input aux 1 - 1 byte valueSigned value1 Byte6.10 counter pulses (-128..127)CRT
59Input aux 1 - 1 byte value% Value1 Byte5.1 percentage (0..100%)CRT
59Input aux 1 - 1 byte valueHVAC mode1 Byte20.102 HVAC modeCRT
59Input aux 1 - 2 byte valueUnsigned value2 Bytes7.1 pulsesCRT
59Input aux 1 - 2 byte valueSigned value2 Bytes8.1 pulses differenceCRT
59Input aux 1 - 4 byte valueUnsigned value4 Bytes12.1 counter pulses (unsigned)CRT
59Input aux 1 - 4 byte valueSigned value4 Bytes13.1 counter pulses (signed)CRT
59Input aux 1 - SwitchingOn/Off1 Bit1.1 switchCRT
59Input aux 1 - Shutter movementUp/Down1 Bit1.8 up/downCRT
59Input aux 1 - SceneExecute/Store1 Byte18.1 scene controlCRT
59Input aux 1 - Window status feedbackOpen/Closed1 Bit1.2 booleanCR
59Input aux 1 - Window status feedbackOpen/Closed1 Bit1.2 booleanCRT
59Inputs aux 1/2 - SwitchingOn/Off1 Bit1.1 switchCRT
59Inputs aux 1/2 - Shutter movementUp/Down1 Bit1.8 up/downCRT
60Input aux 1 - Brightness controlIncrease/Decrease4 Bit3.7 dimming controlCRT
60Input aux 1 - Shutter stop/Louvres controlStop/Step1 Bit1.7 stepCRT
60Input aux 1 - Scene storing triggerStore1 Bit1.17 triggerCW
60Inputs aux 1/2 - Brightness controlIncrease/Decrease4 Bit3.7 dimming controlCRT
60Inputs aux 1/2 - Shutter stop/Louvres controlStop/Step1 Bit1.7 stepCRT
61Input aux 2 - Dimmer status feedbackOn/Off status1 Bit1.1 switchCWTU
61Input aux 2 - Status feedbackOn/Off status1 Bit1.1 switchCWTU
61Input aux 2 - Movement feedbackIncrease/Decrease1 Bit1.8 up/downCW
62Input aux 2 - 14 byte valueCharacters ISO 8859-114 Bytes16.1 Character String (ISO 8859-1)CRT
62Input aux 2 - 1 bit value1/0 value1 Bit1.1 switchCRT
62Input aux 2 - 2 bit valueOn/Off forced positioning2 Bit2.1 switch controlCRT
62Input aux 2 - 1 byte valueUnsigned value1 Byte5.10 counter pulses (0..255)CRT
62Input aux 2 - 1 byte valueSigned value1 Byte6.10 counter pulses (-128..127)CRT
62Input aux 2 - 1 byte value% Value1 Byte5.1 percentage (0..100%)CRT
62Input aux 2 - 1 byte valueHVAC mode1 Byte20.102 HVAC modeCRT
62Input aux 2 - 2 byte valueUnsigned value2 Bytes7.1 pulsesCRT
62Input aux 2 - 2 byte valueSigned value2 Bytes8.1 pulses differenceCRT
62Input aux 2 - 4 byte valueUnsigned value4 Bytes12.1 counter pulses (unsigned)CRT
62Input aux 2 - 4 byte valueSigned value4 Bytes13.1 counter pulses (signed)CRT
62Input aux 2 - SwitchingOn/Off1 Bit1.1 switchCRT
62Input aux 2 - Shutter movementUp/Down1 Bit1.8 up/downCRT
62Input aux 2 - SceneExecute/Store1 Byte18.1 scene controlCRT
63Input aux 2 - Brightness controlIncrease/Decrease4 Bit3.7 dimming controlCRT
63Input aux 2 - Shutter stop/Louvres controlStop/Step1 Bit1.7 stepCRT
63Input aux 2 - Scene storing triggerStore1 Bit1.17 triggerCW
64KNX external humidity sensor inputValue [% RH]2 Bytes9.7 humidity (%)CWTU
65Relative humidity measuredValue [% RH]2 Bytes9.7 humidity (%)CRT
65Relative humidity measuredValue [% RH]2 Bytes9.7 humidity (%)CR
66Relative humidity estimatedValue [% RH]2 Bytes9.7 humidity (%)CRT
66Relative humidity estimatedValue [% RH]2 Bytes9.7 humidity (%)CR
67Specific humidityValue [g/kg]4 Bytes14.5 amplitudeCRT
67Specific humidityValue [g/kg]4 Bytes14.5 amplitudeCR
68Dew point temperatureValue [°F]2 Bytes9.27 temperature (°F)CRT
68Dew point temperatureValue [°K]2 Bytes9.2 temperature difference (K)CRT
68Dew point temperatureValue [°C]2 Bytes9.1 temperature (°C)CRT
68Dew point temperatureValue [°C]2 Bytes9.1 temperature (°C)CR
68Dew point temperatureValue [°K]2 Bytes9.2 temperature difference (K)CR
68Dew point temperatureValue [°F]2 Bytes9.27 temperature (°F)CR
69Dew point temperature alarm enablingEnable/Disable1 Bit1.2 booleanCW
70Dew point temperature alarm enabling statusEnabled/Disabled1 Bit1.3 enableCRT
71Dew point temperature alarm limit regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
72Dew point temperature alarm threshold feedbackValue [°C]2 Bytes9.1 temperature (°C)CRT
72Dew point temperature alarm threshold feedbackValue [°K]2 Bytes9.2 temperature difference (K)CRT
72Dew point temperature alarm threshold feedbackValue [°F]2 Bytes9.27 temperature (°F)CRT
73Dew point temperature alarm outputValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
73Dew point temperature alarm outputOn/Off forced positioning2 Bit2.1 switch controlCRT
73Dew point temperature alarm output1/0 value1 Bit1.1 switchCRT
73Dew point temperature alarm outputValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
73Dew point temperature alarm outputValue [0 .. 65535]2 Bytes7.1 pulsesCRT
73Dew point temperature alarm outputValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
73Dew point temperature alarm outputHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
73Dew point temperature alarm outputValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
74Relative humidity threshold 1 enabling0=Enable/1=Disable1 Bit1.2 booleanCW
74Relative humidity threshold 1 enabling1=Enable/0=Disable1 Bit1.2 booleanCW
75Relative humidity threshold 1 enabling statusEnabled/Disabled1 Bit1.3 enableCRT
76Relative humidity threshold 1 value regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
76Relative humidity threshold 1 value inputValue [% RH]2 Bytes9.7 humidity (%)CW
77Relative humidity threshold 1 feedbackValue [% RH]2 Bytes9.7 humidity (%)CRT
78Relative humidity threshold 1 output AValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
78Relative humidity threshold 1 output AValue [0 .. 65535]2 Bytes7.1 pulsesCRT
78Relative humidity threshold 1 output AOn/Off forced positioning2 Bit2.1 switch controlCRT
78Relative humidity threshold 1 output AValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
78Relative humidity threshold 1 output AValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
78Relative humidity threshold 1 output A1/0 value1 Bit1.1 switchCRT
78Relative humidity threshold 1 output AHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
78Relative humidity threshold 1 output AValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
78Relative humidity threshold 1 output ASetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
78Relative humidity threshold 1 output ASetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
78Relative humidity threshold 1 output ASetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
79Relative humidity threshold 1 output A statusOn/Off status1 Bit1.1 switchCWTU
79Output A relative humidity threshold 1 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
79Output A relative humidity threshold 1 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
79Output A relative humidity threshold 1 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
79Output A relative humidity threshold 1 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
80Relative humidity threshold 1 output BValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
80Relative humidity threshold 1 output BValue [0 .. 65535]2 Bytes7.1 pulsesCRT
80Relative humidity threshold 1 output BOn/Off forced positioning2 Bit2.1 switch controlCRT
80Relative humidity threshold 1 output BValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
80Relative humidity threshold 1 output BValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
80Relative humidity threshold 1 output B1/0 value1 Bit1.1 switchCRT
80Relative humidity threshold 1 output BHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
80Relative humidity threshold 1 output BValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
80Relative humidity threshold 1 output BSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
80Relative humidity threshold 1 output BSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
80Relative humidity threshold 1 output BSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
81Output B relative humidity threshold 1 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
81Output B relative humidity threshold 1 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
81Output B relative humidity threshold 1 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
81Output B relative humidity threshold 1 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
81Relative humidity threshold 1 output B statusOn/Off status1 Bit1.1 switchCWTU
82Relative humidity threshold 1 output CValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
82Relative humidity threshold 1 output CValue [0 .. 65535]2 Bytes7.1 pulsesCRT
82Relative humidity threshold 1 output COn/Off forced positioning2 Bit2.1 switch controlCRT
82Relative humidity threshold 1 output CValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
82Relative humidity threshold 1 output CValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
82Relative humidity threshold 1 output C1/0 value1 Bit1.1 switchCRT
82Relative humidity threshold 1 output CHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
82Relative humidity threshold 1 output CValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
82Relative humidity threshold 1 output CSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
82Relative humidity threshold 1 output CSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
82Relative humidity threshold 1 output CSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
83Output C relative humidity threshold 1 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
83Output C relative humidity threshold 1 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
83Output C relative humidity threshold 1 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
83Output C relative humidity threshold 1 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
83Relative humidity threshold 1 output C statusOn/Off status1 Bit1.1 switchCWTU
84Relative humidity threshold 1 output DValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
84Relative humidity threshold 1 output DValue [0 .. 65535]2 Bytes7.1 pulsesCRT
84Relative humidity threshold 1 output DOn/Off forced positioning2 Bit2.1 switch controlCRT
84Relative humidity threshold 1 output DValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
84Relative humidity threshold 1 output DValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
84Relative humidity threshold 1 output D1/0 value1 Bit1.1 switchCRT
84Relative humidity threshold 1 output DHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
84Relative humidity threshold 1 output DValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
84Relative humidity threshold 1 output DSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
84Relative humidity threshold 1 output DSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
84Relative humidity threshold 1 output DSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
85Output D relative humidity threshold 1 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
85Output D relative humidity threshold 1 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
85Output D relative humidity threshold 1 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
85Output D relative humidity threshold 1 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
85Relative humidity threshold 1 output D statusOn/Off status1 Bit1.1 switchCWTU
86Relative humidity threshold 2 enabling0=Enable/1=Disable1 Bit1.2 booleanCW
86Relative humidity threshold 2 enabling1=Enable/0=Disable1 Bit1.2 booleanCW
87Relative humidity threshold 2 enabling statusEnabled/Disabled1 Bit1.3 enableCRT
88Relative humidity threshold 2 value regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
88Relative humidity threshold 2 value inputValue [% RH]2 Bytes9.7 humidity (%)CW
89Relative humidity threshold 2 feedbackValue [% RH]2 Bytes9.7 humidity (%)CRT
90Relative humidity threshold 2 output AValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
90Relative humidity threshold 2 output AValue [0 .. 65535]2 Bytes7.1 pulsesCRT
90Relative humidity threshold 2 output AOn/Off forced positioning2 Bit2.1 switch controlCRT
90Relative humidity threshold 2 output AValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
90Relative humidity threshold 2 output AValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
90Relative humidity threshold 2 output A1/0 value1 Bit1.1 switchCRT
90Relative humidity threshold 2 output AHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
90Relative humidity threshold 2 output AValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
90Relative humidity threshold 2 output ASetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
90Relative humidity threshold 2 output ASetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
90Relative humidity threshold 2 output ASetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
91Output A relative humidity threshold 2 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
91Output A relative humidity threshold 2 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
91Output A relative humidity threshold 2 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
91Output A relative humidity threshold 2 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
91Relative humidity threshold 2 output A statusOn/Off status1 Bit1.1 switchCWTU
92Relative humidity threshold 2 output BValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
92Relative humidity threshold 2 output BValue [0 .. 65535]2 Bytes7.1 pulsesCRT
92Relative humidity threshold 2 output BOn/Off forced positioning2 Bit2.1 switch controlCRT
92Relative humidity threshold 2 output BValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
92Relative humidity threshold 2 output BValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
92Relative humidity threshold 2 output B1/0 value1 Bit1.1 switchCRT
92Relative humidity threshold 2 output BHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
92Relative humidity threshold 2 output BValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
92Relative humidity threshold 2 output BSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
92Relative humidity threshold 2 output BSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
92Relative humidity threshold 2 output BSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
93Output B relative humidity threshold 2 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
93Output B relative humidity threshold 2 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
93Output B relative humidity threshold 2 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
93Output B relative humidity threshold 2 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
93Relative humidity threshold 2 output B statusOn/Off status1 Bit1.1 switchCWTU
94Relative humidity threshold 2 output CValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
94Relative humidity threshold 2 output CValue [0 .. 65535]2 Bytes7.1 pulsesCRT
94Relative humidity threshold 2 output COn/Off forced positioning2 Bit2.1 switch controlCRT
94Relative humidity threshold 2 output CValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
94Relative humidity threshold 2 output CValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
94Relative humidity threshold 2 output C1/0 value1 Bit1.1 switchCRT
94Relative humidity threshold 2 output CHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
94Relative humidity threshold 2 output CValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
94Relative humidity threshold 2 output CSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
94Relative humidity threshold 2 output CSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
94Relative humidity threshold 2 output CSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
95Output C relative humidity threshold 2 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
95Output C relative humidity threshold 2 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
95Output C relative humidity threshold 2 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
95Output C relative humidity threshold 2 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
95Relative humidity threshold 2 output C statusOn/Off status1 Bit1.1 switchCWTU
96Relative humidity threshold 2 output DValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
96Relative humidity threshold 2 output DValue [0 .. 65535]2 Bytes7.1 pulsesCRT
96Relative humidity threshold 2 output DOn/Off forced positioning2 Bit2.1 switch controlCRT
96Relative humidity threshold 2 output DValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
96Relative humidity threshold 2 output DValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
96Relative humidity threshold 2 output D1/0 value1 Bit1.1 switchCRT
96Relative humidity threshold 2 output DHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
96Relative humidity threshold 2 output DValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
96Relative humidity threshold 2 output DSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
96Relative humidity threshold 2 output DSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
96Relative humidity threshold 2 output DSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
97Output D relative humidity threshold 2 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
97Output D relative humidity threshold 2 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
97Output D relative humidity threshold 2 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
97Output D relative humidity threshold 2 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
97Relative humidity threshold 2 output D statusOn/Off status1 Bit1.1 switchCWTU
98Relative humidity threshold 3 enabling0=Enable/1=Disable1 Bit1.2 booleanCW
98Relative humidity threshold 3 enabling1=Enable/0=Disable1 Bit1.2 booleanCW
99Relative humidity threshold 3 enabling statusEnabled/Disabled1 Bit1.3 enableCRT
100Relative humidity threshold 3 value regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
100Relative humidity threshold 3 value inputValue [% RH]2 Bytes9.7 humidity (%)CW
101Relative humidity threshold 3 feedbackValue [% RH]2 Bytes9.7 humidity (%)CRT
102Relative humidity threshold 3 output AValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
102Relative humidity threshold 3 output AValue [0 .. 65535]2 Bytes7.1 pulsesCRT
102Relative humidity threshold 3 output AOn/Off forced positioning2 Bit2.1 switch controlCRT
102Relative humidity threshold 3 output AValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
102Relative humidity threshold 3 output AValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
102Relative humidity threshold 3 output A1/0 value1 Bit1.1 switchCRT
102Relative humidity threshold 3 output AHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
102Relative humidity threshold 3 output AValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
102Relative humidity threshold 3 output ASetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
102Relative humidity threshold 3 output ASetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
102Relative humidity threshold 3 output ASetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
103Output A relative humidity threshold 3 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
103Output A relative humidity threshold 3 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
103Output A relative humidity threshold 3 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
103Output A relative humidity threshold 3 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
103Relative humidity threshold 3 output A statusOn/Off status1 Bit1.1 switchCWTU
104Relative humidity threshold 3 output BValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
104Relative humidity threshold 3 output BValue [0 .. 65535]2 Bytes7.1 pulsesCRT
104Relative humidity threshold 3 output BOn/Off forced positioning2 Bit2.1 switch controlCRT
104Relative humidity threshold 3 output BValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
104Relative humidity threshold 3 output BValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
104Relative humidity threshold 3 output B1/0 value1 Bit1.1 switchCRT
104Relative humidity threshold 3 output BHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
104Relative humidity threshold 3 output BValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
104Relative humidity threshold 3 output BSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
104Relative humidity threshold 3 output BSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
104Relative humidity threshold 3 output BSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
105Output B relative humidity threshold 3 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
105Output B relative humidity threshold 3 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
105Output B relative humidity threshold 3 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
105Output B relative humidity threshold 3 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
105Relative humidity threshold 3 output B statusOn/Off status1 Bit1.1 switchCWTU
106Relative humidity threshold 3 output CValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
106Relative humidity threshold 3 output CValue [0 .. 65535]2 Bytes7.1 pulsesCRT
106Relative humidity threshold 3 output COn/Off forced positioning2 Bit2.1 switch controlCRT
106Relative humidity threshold 3 output CValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
106Relative humidity threshold 3 output CValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
106Relative humidity threshold 3 output C1/0 value1 Bit1.1 switchCRT
106Relative humidity threshold 3 output CHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
106Relative humidity threshold 3 output CValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
106Relative humidity threshold 3 output CSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
106Relative humidity threshold 3 output CSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
106Relative humidity threshold 3 output CSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
107Output C relative humidity threshold 3 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
107Output C relative humidity threshold 3 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
107Output C relative humidity threshold 3 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
107Output C relative humidity threshold 3 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
107Relative humidity threshold 3 output C statusOn/Off status1 Bit1.1 switchCWTU
108Relative humidity threshold 3 output DValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
108Relative humidity threshold 3 output DValue [0 .. 65535]2 Bytes7.1 pulsesCRT
108Relative humidity threshold 3 output DOn/Off forced positioning2 Bit2.1 switch controlCRT
108Relative humidity threshold 3 output DValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
108Relative humidity threshold 3 output DValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
108Relative humidity threshold 3 output D1/0 value1 Bit1.1 switchCRT
108Relative humidity threshold 3 output DHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
108Relative humidity threshold 3 output DValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
108Relative humidity threshold 3 output DSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
108Relative humidity threshold 3 output DSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
108Relative humidity threshold 3 output DSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
109Output D relative humidity threshold 3 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
109Output D relative humidity threshold 3 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
109Output D relative humidity threshold 3 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
109Output D relative humidity threshold 3 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
109Relative humidity threshold 3 output D statusOn/Off status1 Bit1.1 switchCWTU
110Relative humidity threshold 4 enabling0=Enable/1=Disable1 Bit1.2 booleanCW
110Relative humidity threshold 4 enabling1=Enable/0=Disable1 Bit1.2 booleanCW
111Relative humidity threshold 4 enabling statusEnabled/Disabled1 Bit1.3 enableCRT
112Relative humidity threshold 4 value regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
112Relative humidity threshold 4 value inputValue [% RH]2 Bytes9.7 humidity (%)CW
113Relative humidity threshold 4 feedbackValue [% RH]2 Bytes9.7 humidity (%)CRT
114Relative humidity threshold 4 output AValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
114Relative humidity threshold 4 output AValue [0 .. 65535]2 Bytes7.1 pulsesCRT
114Relative humidity threshold 4 output AOn/Off forced positioning2 Bit2.1 switch controlCRT
114Relative humidity threshold 4 output AValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
114Relative humidity threshold 4 output AValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
114Relative humidity threshold 4 output A1/0 value1 Bit1.1 switchCRT
114Relative humidity threshold 4 output AHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
114Relative humidity threshold 4 output AValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
114Relative humidity threshold 4 output ASetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
114Relative humidity threshold 4 output ASetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
114Relative humidity threshold 4 output ASetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
115Output A relative humidity threshold 4 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
115Output A relative humidity threshold 4 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
115Output A relative humidity threshold 4 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
115Output A relative humidity threshold 4 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
115Relative humidity threshold 4 output A statusOn/Off status1 Bit1.1 switchCWTU
116Relative humidity threshold 4 output BValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
116Relative humidity threshold 4 output BValue [0 .. 65535]2 Bytes7.1 pulsesCRT
116Relative humidity threshold 4 output BOn/Off forced positioning2 Bit2.1 switch controlCRT
116Relative humidity threshold 4 output BValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
116Relative humidity threshold 4 output BValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
116Relative humidity threshold 4 output B1/0 value1 Bit1.1 switchCRT
116Relative humidity threshold 4 output BHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
116Relative humidity threshold 4 output BValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
116Relative humidity threshold 4 output BSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
116Relative humidity threshold 4 output BSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
116Relative humidity threshold 4 output BSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
117Output B relative humidity threshold 4 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
117Output B relative humidity threshold 4 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
117Output B relative humidity threshold 4 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
117Output B relative humidity threshold 4 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
117Relative humidity threshold 4 output B statusOn/Off status1 Bit1.1 switchCWTU
118Relative humidity threshold 4 output CValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
118Relative humidity threshold 4 output CValue [0 .. 65535]2 Bytes7.1 pulsesCRT
118Relative humidity threshold 4 output COn/Off forced positioning2 Bit2.1 switch controlCRT
118Relative humidity threshold 4 output CValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
118Relative humidity threshold 4 output CValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
118Relative humidity threshold 4 output C1/0 value1 Bit1.1 switchCRT
118Relative humidity threshold 4 output CHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
118Relative humidity threshold 4 output CValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
118Relative humidity threshold 4 output CSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
118Relative humidity threshold 4 output CSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
118Relative humidity threshold 4 output CSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
119Output C relative humidity threshold 4 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
119Output C relative humidity threshold 4 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
119Output C relative humidity threshold 4 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
119Output C relative humidity threshold 4 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
119Relative humidity threshold 4 output C statusOn/Off status1 Bit1.1 switchCWTU
120Relative humidity threshold 4 output DValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
120Relative humidity threshold 4 output DValue [0 .. 65535]2 Bytes7.1 pulsesCRT
120Relative humidity threshold 4 output DOn/Off forced positioning2 Bit2.1 switch controlCRT
120Relative humidity threshold 4 output DValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
120Relative humidity threshold 4 output DValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
120Relative humidity threshold 4 output D1/0 value1 Bit1.1 switchCRT
120Relative humidity threshold 4 output DHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
120Relative humidity threshold 4 output DValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
120Relative humidity threshold 4 output DSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
120Relative humidity threshold 4 output DSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
120Relative humidity threshold 4 output DSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
121Output D relative humidity threshold 4 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
121Output D relative humidity threshold 4 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
121Output D relative humidity threshold 4 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
121Output D relative humidity threshold 4 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
121Relative humidity threshold 4 output D statusOn/Off status1 Bit1.1 switchCWTU
122Relative humidity threshold 5 enabling0=Enable/1=Disable1 Bit1.2 booleanCW
122Relative humidity threshold 5 enabling1=Enable/0=Disable1 Bit1.2 booleanCW
123Relative humidity threshold 5 enabling statusEnabled/Disabled1 Bit1.3 enableCRT
124Relative humidity threshold 5 value regulation1 = Increase/0 = Decrease1 Bit1.7 stepCW
124Relative humidity threshold 5 value inputValue [% RH]2 Bytes9.7 humidity (%)CW
125Relative humidity threshold 5 feedbackValue [% RH]2 Bytes9.7 humidity (%)CRT
126Relative humidity threshold 5 output AValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
126Relative humidity threshold 5 output AValue [0 .. 65535]2 Bytes7.1 pulsesCRT
126Relative humidity threshold 5 output AOn/Off forced positioning2 Bit2.1 switch controlCRT
126Relative humidity threshold 5 output AValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
126Relative humidity threshold 5 output AValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
126Relative humidity threshold 5 output A1/0 value1 Bit1.1 switchCRT
126Relative humidity threshold 5 output AHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
126Relative humidity threshold 5 output AValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
126Relative humidity threshold 5 output ASetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
126Relative humidity threshold 5 output ASetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
126Relative humidity threshold 5 output ASetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
127Output A relative humidity threshold 5 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
127Output A relative humidity threshold 5 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
127Output A relative humidity threshold 5 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
127Output A relative humidity threshold 5 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
127Relative humidity threshold 5 output A statusOn/Off status1 Bit1.1 switchCWTU
128Relative humidity threshold 5 output BValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
128Relative humidity threshold 5 output BValue [0 .. 65535]2 Bytes7.1 pulsesCRT
128Relative humidity threshold 5 output BOn/Off forced positioning2 Bit2.1 switch controlCRT
128Relative humidity threshold 5 output BValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
128Relative humidity threshold 5 output BValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
128Relative humidity threshold 5 output B1/0 value1 Bit1.1 switchCRT
128Relative humidity threshold 5 output BHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
128Relative humidity threshold 5 output BValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
128Relative humidity threshold 5 output BSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
128Relative humidity threshold 5 output BSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
128Relative humidity threshold 5 output BSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
129Output B relative humidity threshold 5 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
129Output B relative humidity threshold 5 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
129Output B relative humidity threshold 5 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
129Output B relative humidity threshold 5 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
129Relative humidity threshold 5 output B statusOn/Off status1 Bit1.1 switchCWTU
130Relative humidity threshold 5 output CValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
130Relative humidity threshold 5 output CValue [0 .. 65535]2 Bytes7.1 pulsesCRT
130Relative humidity threshold 5 output COn/Off forced positioning2 Bit2.1 switch controlCRT
130Relative humidity threshold 5 output CValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
130Relative humidity threshold 5 output CValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
130Relative humidity threshold 5 output C1/0 value1 Bit1.1 switchCRT
130Relative humidity threshold 5 output CHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
130Relative humidity threshold 5 output CValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
130Relative humidity threshold 5 output CSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
130Relative humidity threshold 5 output CSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
130Relative humidity threshold 5 output CSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
131Output C relative humidity threshold 5 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
131Output C relative humidity threshold 5 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
131Output C relative humidity threshold 5 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
131Output C relative humidity threshold 5 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
131Relative humidity threshold 5 output C statusOn/Off status1 Bit1.1 switchCWTU
132Relative humidity threshold 5 output DValue [-128 .. 127]1 Byte6.10 counter pulses (-128..127)CRT
132Relative humidity threshold 5 output DValue [0 .. 65535]2 Bytes7.1 pulsesCRT
132Relative humidity threshold 5 output DOn/Off forced positioning2 Bit2.1 switch controlCRT
132Relative humidity threshold 5 output DValue [-32768 .. 32767]2 Bytes8.1 pulses differenceCRT
132Relative humidity threshold 5 output DValue [0 .. 255]1 Byte5.10 counter pulses (0..255)CRT
132Relative humidity threshold 5 output D1/0 value1 Bit1.1 switchCRT
132Relative humidity threshold 5 output DHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCRT
132Relative humidity threshold 5 output DValue [0% .. 100%]1 Byte5.1 percentage (0..100%)CRT
132Relative humidity threshold 5 output DSetpoint value [°C]2 Bytes9.1 temperature (°C)CRT
132Relative humidity threshold 5 output DSetpoint value [°K]2 Bytes9.2 temperature difference (K)CRT
132Relative humidity threshold 5 output DSetpoint value [°F]2 Bytes9.27 temperature (°F)CRT
133Output D relative humidity threshold 5 referenceHVAC Mode (com/precom/eco/off)1 Byte20.102 HVAC modeCWTU
133Output D relative humidity threshold 5 referenceSetpoint [°C]2 Bytes9.1 temperature (°C)CWTU
133Output D relative humidity threshold 5 referenceSetpoint [°K]2 Bytes9.2 temperature difference (K)CWTU
133Output D relative humidity threshold 5 referenceSetpoint [°F]2 Bytes9.1 temperature (°C)CWTU
133Relative humidity threshold 5 output D statusOn/Off status1 Bit1.1 switchCWTU
134Season selection input1=Summer / 0=Winter1 Bit1.2 booleanCWTU
134Season selection input1=Winter / 0=Summer1 Bit1.2 booleanCWTU
135Thermal comfort status feedback1=Comfortable/0=Uncomfortable1 Bit1.2 booleanCRT
Parameters (233)
ParameterTypeDefault
ETS downloadlistBB
Input contacts functionlisttwo auxiliary inputs independent
Operation LEDlistenable
Status LED active loadlistenable
Remote control typelistHVAC mode
Commands format for HVAC mode settinglist1 byte
- Reception 1 bit mode con priority > actuallistkeep lower priority objects value
- Reception 1 bit mode con priority < actuallistupdate object value
HVAC mode setpoint modification via buslistdisable
- Setpoint regulation step [0.1°C]unsignedInt 1…205
Temporary setpoint forcing via buslistdisable
- Setpoint temporary forcing regulation step [0.1°C]unsignedInt 1…205
Change the functioning setpoint via bus throughlistabsolute value setting (°C)
- Imposta tipo di funzionamentolistenable
Imposta parametri da remotolistenable
Imposta tipo di funzionamentolistby local command or from bus
Control logic Heating/Air coolinglistdifferent (4 pipe)
Heating/Air cooling control algorithmlisttwo points ON-OFF
Heating/air cooling valve status feedbacklistenable
- Commands repetition period with disabled feedbacklist5 minutes
Ripeti comando su cambiamento stato attuatore RISClistenable
Fancoil valves managementlisttwo points ON-OFF
- Heating/air cooling valve status feedbacklistenable
-- Commands repetition period with disabled feedbacklist5 minutes
Fancoil speed modification via buslistdisable
Fancoil mode (automatic/manual) feedbacklistdisable
Heating control algorithmlisttwo points ON-OFF
Air cooling control algorithmlisttwo points ON-OFF
Regulation differential (tenth of °C)unsignedInt 1…202
Select heating systemlistfloor heating
- Proportional bandlist2.0 °C
- Integration timelist60 minutes
- Cycle timelist30 minutes
- Min. % variation for continuous command sendinglist5%
Fancoil speed numberlist3
- Regulation differential speed 1 (tenth of °C)unsignedInt 0…202
- Speed 1 inertia time (seconds)unsignedInt 0…100
Fancoil speed status feedbacklistenable
- Command repetition time fancoil speedlist5 minutes
- Regulation differential speed 2 (tenth of °C)unsignedInt 1…202
- Speed 2 inertia time (seconds)unsignedInt 0…100
- Regulation differential speed 3 (tenth of °C)unsignedInt 1…202
- Speed 3 inertia time (seconds)unsignedInt 0…100
Regulation differential valve (tenth of °C)unsignedInt 1…202
Heating 2° stagelistdisabled
- Operation limit 2° stage (tenths of °C)unsignedInt 10…10010
- Regulation differential 2° stage (tenth of °C)unsignedInt 1…202
Heating 2° stage feedbacklistenable
- Command repetition time 2° stage without feedbacklist5 minutes
Ripeti comando su cambiamento stato 2° stadio RISClistenable
Heating valve status feedbacklistenable
- Regulation differential valve (tenth of °C)unsignedInt 1…202
- Heating valve status feedbacklistenable
Select air cooling systemlistceiling cooling
- Proportional bandlist5.0 °C
- Integration timelist240 minutes
air cooling 2° stagelistdisabled
Air cooling 2° stage feedbacklistenable
Ripeti comando su cambiamento stato 2° stadio CONDlistenable
Air cooling valve status feedbacklistenable
Ripeti comando su cambiamento stato attuatore CONDlistenable
- Air cooling valve status feedbacklistenable
Comfort setpoint (tenths of °C)signedInt 50…400200
Precomfort setpoint (tenths of °C)signedInt 50…400180
Economy setpoint (tenths of °C)signedInt 50…400160
Antifreeze setpoint (tenths of °C)signedInt 20…7050
Comfort setpoint (tenths of °C)signedInt 50…400240
Precomfort setpoint (tenths of °C)signedInt 50…400260
Economy setpoint (tenths of °C)signedInt 50…400280
High temperature protection setpoint (tenths of °C)signedInt 300…400350
Temperature forcing behaviour at new setpoint receivinglistcancel temperature forcing
modify all the setpoints of the same functioning typelistno
modify contemporary the setpoint of the other functioning typelistno
Functioning setpoint (tenths of °C)signedInt 50…400200
Antifreeze setpoint for window contact (tenths of °C)signedInt 20…7050
Functioning setpoint (tenths of °C)signedInt 50…400240
High temperature protection setpoint for window contact (tenths of °C)signedInt 300…400350
Internal sensor correction factor (tenths of °C)signedInt -20…200
KNX external sensorlistdisabled
- Measure unit KNX external sensorlistCelsius degrees (°C)
- KNX ext. sensor incidence in measured temp. calculationlist10%
- KNX external sensor monitoring time [min] (0= no monitoring)unsignedInt 0…102
- Behaviour at KNX external sensor signal absencelistuse last value received
- KNX floor sensor measure unitlistCelsius degrees (°C)
- Threshold temperature temperature alarm (tenth of °C)unsignedInt 150…1000500
- Temperature alarm hysteresis (tenth of °C)unsignedInt 10…10030
- KNX floor sensor monitoring time [min] (0= no monitoring)unsignedInt 0…102
- Behaviour at KNX floor sensor signal absencelistactivate temperature alarm
Auxiliary external sensorlistenables temperature sensor
- Type of NTC sensor connectedlistfloating sensor (GW10800)
- Correction factor auxiliary sensor (tenths of °C)signedInt -20…200
- Auxiliary ext. sensor incidence in measured temp. calculationlist10%
- Behaviour at auxiliary external sensor signal absencelistuse last value received
- Auxiliary sensor measured temperaturelistdo not send
-- Measure unit auxiliary sensorlistCelsius degrees (°C)
-- Auxiliary sensor temperature min. variation for sending value [± 0.1 °C]unsignedInt 1…105
-- Auxiliary sensor temperature sending period [minutes]unsignedInt 1…2555
- Behaviour at auxiliary floor sensor signal absencelistactivate temperature alarm
- Temperature measured by auxiliary floor sensorlistdo not send
Measured temperaturelistdo not send
- Measure unitlistCelsius degrees (°C)
- Minimum variation for sending value [± 0.1 °C]unsignedInt 1…105
- Temperature sending period [minutes]unsignedInt 1…2555
HVAC mode feedbacklistdisabled
- 1 bit HVAC modeliston demand only
- 1 byte HVAC modeliston demand only
Functioning setpoint feedbacklistdisabled
Functioning type feedbacklistdisabled
Current setpoint reportlistdisabled
HVAC mode setpoint feedbacklistdisabled
Feedbacks sending trigger objectlistdisable
Scenes functionlistdisable
Scene number 1listunassigned
Scene number 2listunassigned
Scene number 3listunassigned
Scene number 4listunassigned
Scene number 5listunassigned
Scene number 6listunassigned
Scene number 7listunassigned
Scene number 8listunassigned
Parameters to memorize while storinglistHVAC mode only
Parameters to memorize while storinglistsetpoint only
Matched functionlistnone
Sending object formatlist1 bit
- Sending on contact closing detectionlist1
- Sending on contact opening detectionlistno effect
-- Status feedback objectlistdisabled
- Sending on contact closing detectionlistactivate on (down) forcing
- Sending on contact closing detectionlistvalue sending
-- Value (0 .. 255)unsignedInt 0…2550
-- Value (-128 .. +127)signedInt -128…1270
-- Value (0% .. 100%)unsignedInt 0…1000
- Sending on contact closing detectionlistcomfort
-- Value (0 .. 65535)unsignedInt 0…655350
-- Value (-32768 .. +32767)signedInt -32768…327670
-- Value (0 .. 4294967295)unsignedInt 0…42949672950
-- Value (-2147483648 .. +2147483647)signedInt -2147483648…21474836470
-- Value (characters ISO 8859-1)text
- Sending on short operation detectionlist1
- Sending on long operation detectionlistno effect
- Sending on short operation detectionlistvalue sending
- Sending on short operation detectionlistcomfort
Dimmer status feedback objectlistdisable
- Brightness dimming commands with dimmer onlistbrightness increase and decrease
Increase/decrease steplist12.5%
Cyclical sending period [x 0.1s]unsignedInt 3…505
Scene number (0 .. 63)unsignedInt 0…630
Scene storing by long operationlistenabled
Window statuslistclosed if contact is open
Send window contact status feedbacklistdisabled
Matched functionlistdimming with STOP telegram
Internal sensor correction factor [% RH]signedInt -10…100
External KNX humidity sensorlistdisable
- KNX external sensor incidence in measured humidity calculationlist10%
Measured relative humiditylistdo not send
- Minimum variation for sending value [% RH]list± 5 %
- Relative humidity value repetition time [minutes]unsignedInt 1…2555
Estimate the humidity at the temperature measured by the auxiliary probelistdisable
- Estimated relative humiditylistdo not send
-- Minimum variation for sending value [% RH]list± 5 %
-- Estimated relative humidity value repetition time [minutes]unsignedInt 1…2555
Specific humiditylistdo not send
- Minimum variation for sending valuelist± 5 g/Kg
- Specific relative humidity value repetition time [minutes]unsignedInt 1…2555
Relative humidity threshold 1listdisable
Measure used as reference:listmeasured relative humidity
Threshold logic functioning:listhumidification
C1 = Condition 1listRelative humidity <= Limit threshold - hysteresis
C2 = Condition 2listRelative humidity >= Limit threshold
C1 = Condition 1listRelative humidity >= Limit threshold + hysteresis
C2 = Condition 2listRelative humidity <= Limit threshold
Limit threshold starting value [% RH]unsignedInt 0…10050
Limit threshold hysteresis [% RH]unsignedInt 1…205
Change the threshold value via bus throughlistabsolute value
- Threshold regulation step via bus [%]unsignedInt 1…205
Enable/disable the humidity threshold via buslistno
- Threshold activation valuelistvalue "1"
- Threshold activation status after bus voltage recoverylistas before voltage drop
Oggetto A --------------------------------------listenable
Output formatlist1 bit
- On the occurrence of Condition 1listsends 1
- On the occurrence of Condition 2listno effect
- Relative humidity threshold output status feedbacklistenable
- Output commands cyclical repetitionlistdisable
-- Command repetition timelist5 minutes
- On the occurrence of Condition 1listsends active forcing on(down)
- On the occurrence of Condition 1listvalue sending
- On the occurrence of Condition 1listsends comfort
-- Offset (-3 .. 3)signedInt -3…31
- On the occurrence of Condition 1listsends current setpoint ± offset
-- Offset [0.1°C] (-300 .. 300)signedInt -300…30010
Object B --------------------------------------listdisable
Object C --------------------------------------listdisable
Object D --------------------------------------listdisable
Relative humidity threshold 2listdisable
Object B --------------------------------------listenable
Relative humidity threshold 3listdisable
Relative humidity threshold 4listdisable
Relative humidity threshold 5listdisable
Dew point temperaturelistdo not send
- Feedback measure unitlistCelsius degrees (°C)
- Sending feedback repetition time [minutes]unsignedInt 1…2555
Dew point temperature alarm feedback thresholdlistdisable
- Alarm feedback limit [tenths of °C]unsignedInt 0…10050
- Alarm feedback limit regulation step via bus [0.1°C]unsignedInt 1…1005
- Alarm threshold hysteresis [tenths of °C]unsignedInt 1…2010
- Alarm threshold feedback measure unitlistCelsius degrees (°C)
- Enable/disable the alarm threshold via buslistno
-- Threshold activation valuelistvalue "1"
-- Alarm threshold activation status after bus voltage recoverylistas before voltage drop
- Output formatlist1 bit
-- If Measure temperature < Threshold temperaturelistsends 1
-- If Measure temperature > Threshold temperature + Hysteresislistno effect
-- If Measure temperature < Threshold temperaturelistsends active forcing on(down)
-- If Measure temperature < Threshold temperaturelistvalue sending
--- Value (0 .. 255)unsignedInt 0…2550
--- Value (-128 .. +127)signedInt -128…1270
--- Value (0% .. 100%)unsignedInt 0…1000
-- If Measure temperature < Threshold temperaturelistsends comfort
--- Value (0 .. 65535)unsignedInt 0…655350
--- Value (-32768 .. +32767)signedInt -32768…327670
Enable thermal comfort status feedbacklistenable
The season summer/winterlistfollows active functioning type
- Logical value associated with the seasonslist1 = summer / 0 = winter
- Season active after an ETS downloadlistsummer
Maximum temperature [0.1 °C]signedInt 200…400260
Minimum temperature [0.1 °C]signedInt 100…300240
Maximum relative humidity [% RH]unsignedInt 50…9560
Minimum relative humidity [% RH]unsignedInt 10…4540
Maximum specific humidity [% RH]unsignedInt 50…220115
Maximum temperature [0.1 °C]signedInt 200…400220
Minimum temperature [0.1 °C]signedInt 100…300180
Minimum specific humidity [% RH]unsignedInt 50…220115

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX Temperature and Humidity probe S 1.2 1.2 latest$5309B42B2026-11-25296 KBDownload

About this file

This is the official ETS product database for the GEWISS GW13799H (GW13799H), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.