| 0 | <Input 1> Feedback | Off/On | 1 Bit | 1.1 switch | CW |
| 0 | <Input 1> Sequence Command A | Off/On | 1 Bit | 1.1 switch | CRT |
| 0 | <Input 1> Sequence Command A | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 0 | <Input 1> Sequence Command A | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 0 | <Input 1> Sequence Command A | HVAC Mode | 1 Byte | | CRT |
| 1 | <Input 2> Feedback | Off/On | 1 Bit | 1.1 switch | CW |
| 1 | <Input 2> Sequence Command A | Off/On | 1 Bit | 1.1 switch | CRT |
| 1 | <Input 2> Sequence Command A | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 1 | <Input 2> Sequence Command A | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 1 | <Input 2> Sequence Command A | HVAC Mode | 1 Byte | | CRT |
| 2 | <Input 1> Edge | Off/On | 1 Bit | 1.1 switch | CRWT |
| 2 | <Input 1> Edge | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 2 | <Input 1> Edge | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 2 | <Input 1> Edge | HVAC Mode | 1 Byte | | CRT |
| 2 | <Input 1> Short - Long Press | Off/On | 1 Bit | 1.1 switch | CRWT |
| 2 | <Input 1> Value Sending | HVAC Mode | 1 Byte | | CRT |
| 2 | <Input 1> Value Sending | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 2 | <Input 1> Value Sending | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 2 | <Input 1> Shutter Movement | Up/Down | 1 Bit | 1.8 up/down | CRWT |
| 2 | <Input 1> Dimming On/Off | Off/On | 1 Bit | 1.1 switch | CRWT |
| 2 | <Input 1> Recall/Learn Scene | Scene | 1 Byte | | CRT |
| 2 | <Input 1> Sequence Command B | Off/On | 1 Bit | 1.1 switch | CRT |
| 2 | <Input 1> Sequence Command B | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 2 | <Input 1> Sequence Command B | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 2 | <Input 1> Sequence Command B | HVAC Mode | 1 Byte | | CRT |
| 2 | <Input 1-2> Dimming On/Off | Off/On | 1 Bit | 1.1 switch | CRWT |
| 2 | <Input 1-2> Shutter Movement | Up/Down | 1 Bit | 1.8 up/down | CRWT |
| 3 | <Input 2> Edge | Off/On | 1 Bit | 1.1 switch | CRWT |
| 3 | <Input 2> Edge | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 3 | <Input 2> Edge | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 3 | <Input 2> Edge | HVAC Mode | 1 Byte | | CRT |
| 3 | <Input 2> Short - Long Press | Off/On | 1 Bit | 1.1 switch | CRWT |
| 3 | <Input 2> Value Sending | HVAC Mode | 1 Byte | | CRT |
| 3 | <Input 2> Value Sending | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 3 | <Input 2> Value Sending | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 3 | <Input 2> Shutter Movement | Up/Down | 1 Bit | 1.8 up/down | CRWT |
| 3 | <Input 2> Dimming On/Off | Off/On | 1 Bit | 1.1 switch | CRWT |
| 3 | <Input 2> Recall/Learn Scene | Scene | 1 Byte | | CRT |
| 3 | <Input 2> Sequence Command B | Off/On | 1 Bit | 1.1 switch | CRT |
| 3 | <Input 2> Sequence Command B | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 3 | <Input 2> Sequence Command B | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 3 | <Input 2> Sequence Command B | HVAC Mode | 1 Byte | | CRT |
| 4 | <Input 1> Long Press | Off/On | 1 Bit | 1.1 switch | CRWT |
| 4 | <Input 1> Long Press | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 4 | <Input 1> Long Press | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 4 | <Input 1> Long Press | HVAC Mode | 1 Byte | | CRT |
| 4 | <Input 1> Stop/Step | Step/Stop | 1 Bit | | CRT |
| 4 | <Input 1> Dimming | Dimming Control | 4 Bit | 3.7 dimming control | CRT |
| 4 | <Input 1> Send Learn Scene Trigger | Disable/Enable | 1 Bit | | CW |
| 4 | <Input 1> Sequence Command C | Off/On | 1 Bit | 1.1 switch | CRT |
| 4 | <Input 1> Sequence Command C | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 4 | <Input 1> Sequence Command C | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 4 | <Input 1> Sequence Command C | HVAC Mode | 1 Byte | | CRT |
| 4 | <Input 1-2> Dimming | Dimming Control | 4 Bit | 3.7 dimming control | CRT |
| 4 | <Input 1-2> Stop/Step | Step/Stop | 1 Bit | | CRT |
| 5 | <Input 2> Long Press | Off/On | 1 Bit | 1.1 switch | CRWT |
| 5 | <Input 2> Long Press | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 5 | <Input 2> Long Press | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 5 | <Input 2> Long Press | HVAC Mode | 1 Byte | | CRT |
| 5 | <Input 2> Stop/Step | Step/Stop | 1 Bit | | CRT |
| 5 | <Input 2> Dimming | Dimming Control | 4 Bit | 3.7 dimming control | CRT |
| 5 | <Input 2> Send Learn Scene Trigger | Disable/Enable | 1 Bit | | CW |
| 5 | <Input 2> Sequence Command C | Off/On | 1 Bit | 1.1 switch | CRT |
| 5 | <Input 2> Sequence Command C | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 5 | <Input 2> Sequence Command C | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 5 | <Input 2> Sequence Command C | HVAC Mode | 1 Byte | | CRT |
| 6 | <Output 1-2> Shutter Movement | Up/Down | 1 Bit | 1.8 up/down | CW |
| 6 | <Output 1> Relay Timing Command | Off/On | 1 Bit | 1.1 switch | CRW |
| 6 | <Output 1> Electric Valve Driver | Off/On | 1 Bit | 1.1 switch | CRW |
| 6 | <Output 1> Electric Valve Driver | Value % | 1 Byte | 5.1 percentage (0..100%) | CRW |
| 7 | <Output 1-2> Shutter Stop/Louvres | Stop/Step | 1 Bit | | CW |
| 7 | <Output 1> Relay Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 7 | <Output 1> Electric Valve Driver Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 7 | <Output 1> Electric Valve Driver Status | Value % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | <Output 1-2> Shutter Movement Feedback | Up/Down | 1 Bit | 1.8 up/down | CRT |
| 8 | <Output 2> Relay Timing Command | Off/On | 1 Bit | 1.1 switch | CRW |
| 8 | <Output 2> Electric Valve Driver | Off/On | 1 Bit | 1.1 switch | CRW |
| 8 | <Output 2> Electric Valve Driver | Value % | 1 Byte | 5.1 percentage (0..100%) | CRW |
| 9 | <Output 1-2> Shutter Lock Function | Disable/Enable | 1 Bit | 1.1 switch | CW |
| 9 | <Output 2> Relay Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 9 | <Output 2> Electric Valve Driver Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 9 | <Output 2> Electric Valve Driver Status | Value % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 10 | <Output 1-2> Shutter Alarm Function | Disable/Enable | 1 Bit | | CW |
| 10 | <Output 1> Lock Function | Disable/Enable | 1 Bit | 1.1 switch | CW |
| 10 | <Output 1> Logic Function | Logic | 1 Bit | 1.2 boolean | CW |
| 11 | <Output 1-2> Shutter Scene Function | Scene | 1 Byte | | CW |
| 11 | <Output 2> Lock Function | Disable/Enable | 1 Bit | 1.1 switch | CW |
| 11 | <Output 2> Logic Function | Logic | 1 Bit | 1.2 boolean | CW |
| 12 | <Output 1-2> Shutter Position Command | Position % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 12 | <Output 1> Scene | Scene | 1 Byte | | CW |
| 13 | <Output 1-2> Shutter Position Feedback | Feedback Position % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 13 | <Output 2> Scene | Scene | 1 Byte | | CW |
| 14 | <Output 1> Relay Command | Off/On | 1 Bit | 1.1 switch | CRW |
| 15 | <Output 2> Relay Command | Off/On | 1 Bit | 1.1 switch | CRW |
| 16 | <Input 3> T. Sensor - Trigger 1 | Off/On | 1 Bit | 1.1 switch | CRT |
| 16 | <Remote Control Button 1> Sequence Command A | Off/On | 1 Bit | 1.1 switch | CRWT |
| 16 | <Input 3> Thermostat - Heat/Cool Mode | Heat/Cool | 1 Bit | | CW |
| 16 | <Input 3> Thermostat - Heat/Cool Mode Feedback | Heat/Cool | 1 Bit | | CRT |
| 16 | <Remote Control Button 1> Sequence Command A | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 16 | <Remote Control Button 1> Sequence Command A | HVAC Mode | 1 Byte | | CRT |
| 16 | <Remote Control Button 1> Sequence Command A | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 16 | <Remote Control Button 1> Value Sending | Off/On | 1 Bit | 1.1 switch | CRWT |
| 16 | <Remote Control Button 1> Value Sending | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 16 | <Remote Control Button 1> Value Sending | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 16 | <Remote Control Button 1> Value Sending | HVAC Mode | 1 Byte | | CRT |
| 16 | <Remote Control Button 1> Recall Scene | Scene | 1 Byte | | CT |
| 17 | <Input 3> T. Sensor - Trigger 2 | Off/On | 1 Bit | 1.1 switch | CRT |
| 17 | <Input 3> Thermostat - Window Contact | Close/Open | 1 Bit | | CW |
| 17 | <Remote Control Button 2> Sequence Command A | Off/On | 1 Bit | 1.1 switch | CRWT |
| 17 | <Remote Control Button 2> Sequence Command A | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 17 | <Remote Control Button 2> Sequence Command A | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 17 | <Remote Control Button 2> Sequence Command A | HVAC Mode | 1 Byte | | CRT |
| 17 | <Remote Control Button 2> Value Sending | Off/On | 1 Bit | 1.1 switch | CRWT |
| 17 | <Remote Control Button 2> Value Sending | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 17 | <Remote Control Button 2> Value Sending | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 17 | <Remote Control Button 2> Value Sending | HVAC Mode | 1 Byte | | CRT |
| 17 | <Remote Control Button 2> Recall Scene | Scene | 1 Byte | | CT |
| 18 | <Input 3> T. Sensor - Enable Trig. T1/T2 | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 18 | <Input 3> Thermostat - Comfort Mode | Disable/Enable | 1 Bit | 1.1 switch | CW |
| 18 | <Remote Control Button 3> Sequence Command A | Off/On | 1 Bit | 1.1 switch | CRWT |
| 18 | <Remote Control Button 3> Sequence Command A | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 18 | <Remote Control Button 3> Sequence Command A | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 18 | <Remote Control Button 3> Sequence Command A | HVAC Mode | 1 Byte | | CRT |
| 18 | <Remote Control Button 3> Value Sending | Off/On | 1 Bit | 1.1 switch | CRWT |
| 18 | <Remote Control Button 3> Value Sending | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 18 | <Remote Control Button 3> Value Sending | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 18 | <Remote Control Button 3> Value Sending | HVAC Mode | 1 Byte | | CRT |
| 18 | <Remote Control Button 3> Recall Scene | Scene | 1 Byte | | CT |
| 19 | <Input 3> Thermostat - HVAC Mode | Comf/Standby/Eco/B.protection | 1 Byte | | CW |
| 19 | <Input 3> Thermostat - Base Setpoint | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 20 | <Input 3> Thermostat - Actual Setpoint | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 21 | <Input 3> T. Sensor - Actual Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 21 | <Input 3> Thermostat - Actual Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 22 | <Input 3> Thermostat - Additional Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 23 | <Input 3> Thermostat - Setpoint Adjustment | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 23 | <Input 3> Thermostat - Setpoint Adjustment | Value °C | 1 Bit | | CW |
| 24 | <Input 3> Fan Coil Valve Heat/Cool | Off/On | 1 Bit | 1.1 switch | CRT |
| 24 | <Input 3> Fan Coil Heating Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 24 | <Input 3> Fan Coil Heating/Cooling Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 24 | <Input 3> Thermostat - Heating | Off/On | 1 Bit | 1.1 switch | CRT |
| 24 | <Input 3> Thermostat - Heating | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 24 | <Remote Control Button 4> Sequence Command A | Off/On | 1 Bit | 1.1 switch | CRWT |
| 24 | <Remote Control Button 4> Sequence Command A | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 24 | <Remote Control Button 4> Sequence Command A | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 24 | <Remote Control Button 4> Value Sending | Off/On | 1 Bit | 1.1 switch | CRWT |
| 24 | <Remote Control Button 4> Value Sending | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 24 | <Remote Control Button 4> Value Sending | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 24 | <Remote Control Button 4> Value Sending | HVAC Mode | 1 Byte | | CRT |
| 24 | <Remote Control Button 4> Recall Scene | Scene | 1 Byte | | CT |
| 24 | <Remote Control Button 4> Sequence Command A | HVAC Mode | 1 Byte | | CRT |
| 25 | <Input 3> Thermostat - Cooling Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 25 | <Remote Control Buttons 5-8> Dimmer On/Off | Off/On | 1 Bit | 1.1 switch | CRWT |
| 25 | <Input 3> Fan Coil Cooling Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 25 | <Input 3> Thermostat - Cooling | Off/On | 1 Bit | 1.1 switch | CRT |
| 25 | <Input 3> Thermostat - Cooling | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 25 | <Remote Control Buttons 5-8> Shutter Movement | Up/Down | 1 Bit | 1.8 up/down | CRWT |
| 25 | <Remote Control Button 5> Value Sending | Off/On | 1 Bit | 1.1 switch | CRWT |
| 25 | <Remote Control Button 5> Value Sending | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 25 | <Remote Control Button 5> Value Sending | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 25 | <Remote Control Button 5> Value Sending | HVAC Mode | 1 Byte | | CRT |
| 25 | <Remote Control Button 5> Recall Scene | Scene | 1 Byte | | CT |
| 25 | <Remote Control Button 5-6-7-8> Value HVAC | HVAC Mode | 1 Byte | | CRT |
| 25 | <Remote Control Button 5-6-7-8> Set MAN Mode | Set Manual Mode (0) | 1 Bit | | CRT |
| 26 | <Input 3> Fan Coil Speed 1 | Off/On | 1 Bit | 1.1 switch | CRT |
| 26 | <Remote Control Buttons 6-7> Dimming | Dimming Control | 4 Bit | 3.7 dimming control | CRT |
| 26 | <Input 3> Continuous Control % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 26 | <Remote Control Buttons 6-7> Stop/Step | Step/Stop | 1 Bit | | CRT |
| 26 | <Remote Control Button 6> Value Sending | Off/On | 1 Bit | 1.1 switch | CRWT |
| 26 | <Remote Control Button 6> Value Sending | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 26 | <Remote Control Button 6> Value Sending | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 26 | <Remote Control Button 6> Value Sending | HVAC Mode | 1 Byte | | CRT |
| 26 | <Remote Control Button 6> Recall Scene | Scene | 1 Byte | | CT |
| 26 | <Remote Control Button 5-6-7-8> Force Fan Speed | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 27 | <Input 3> Fan Coil Speed 2 | Off/On | 1 Bit | 1.1 switch | CRT |
| 27 | <Input 3> Thermostat - Set Man/Auto Mode | Manual (0) / Auto (1) | 1 Bit | | CW |
| 27 | <Remote Control Button 7> Value Sending | Off/On | 1 Bit | 1.1 switch | CRWT |
| 27 | <Remote Control Button 7> Value Sending | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 27 | <Remote Control Button 7> Value Sending | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 27 | <Remote Control Button 7> Value Sending | HVAC Mode | 1 Byte | | CRT |
| 27 | <Remote Control Button 7> Recall Scene | Scene | 1 Byte | | CT |
| 28 | <Input 3> Fan Coil Speed 3 | Off/On | 1 Bit | 1.1 switch | CRT |
| 28 | <Input 3> Thermostat - Force Value in Man Mode | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 28 | <Remote Control Button 8> Value Sending | Off/On | 1 Bit | 1.1 switch | CRWT |
| 28 | <Remote Control Button 8> Value Sending | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 28 | <Remote Control Button 8> Value Sending | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 28 | <Remote Control Button 8> Value Sending | HVAC Mode | 1 Byte | | CRT |
| 28 | <Remote Control Button 8> Recall Scene | Scene | 1 Byte | | CT |
| 29 | <Input 3> Thermostat - SP Economy Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 29 | <Input 3> Thermostat - Setpoint Economy | Value °C | 2 Bytes | 9.1 temperature (°C) | CWT |
| 30 | <Input 3> Thermostat - SP Standby Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 30 | <Input 3> Thermostat - Setpoint Standby | Value °C | 2 Bytes | 9.1 temperature (°C) | CWT |
| 31 | <Input 3> Thermostat - SP Comfort Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 31 | <Input 3> Thermostat - Setpoint Comfort | Value °C | 2 Bytes | 9.1 temperature (°C) | CWT |
| 32 | <Input 3> Thermostat - SP Economy Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 33 | <Input 3> Thermostat - SP Standby Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 34 | <Input 3> Thermostat - SP Comfort Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 35 | <Input 3> Thermostat - OFF Thermostat | Off/On | 1 Bit | | CW |
| 35 | <Remote Control Button 1> Sequence Command B | Off/On | 1 Bit | 1.1 switch | CRWT |
| 35 | <Remote Control Button 1> Sequence Command B | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 35 | <Remote Control Button 1> Sequence Command B | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 35 | <Remote Control Button 1> Sequence Command B | HVAC Mode | 1 Byte | | CRT |
| 36 | <Remote Control Button 2> Sequence Command B | Off/On | 1 Bit | 1.1 switch | CRWT |
| 36 | <Remote Control Button 2> Sequence Command B | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 36 | <Remote Control Button 2> Sequence Command B | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 36 | <Remote Control Button 2> Sequence Command B | HVAC Mode | 1 Byte | | CRT |
| 37 | <Remote Control Button 3> Sequence Command B | Off/On | 1 Bit | 1.1 switch | CRWT |
| 37 | <Remote Control Button 3> Sequence Command B | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 37 | <Remote Control Button 3> Sequence Command B | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 37 | <Remote Control Button 3> Sequence Command B | HVAC Mode | 1 Byte | | CRT |
| 38 | <Remote Control Button 4> Sequence Command B | Off/On | 1 Bit | 1.1 switch | CRWT |
| 38 | <Remote Control Button 4> Sequence Command B | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 38 | <Remote Control Button 4> Sequence Command B | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 38 | <Remote Control Button 4> Sequence Command B | HVAC Mode | 1 Byte | | CRT |
| 39 | <Input 3> Temperature Alarm | Alarm | 1 Bit | | CRT |
| 39 | Enable / Disable Infrared Receiver | Disable/Enable | 1 Bit | 1.3 enable | CW |