| 0 | <Global All> All Valve Closed | All Valve Closed | 1 Bit | 1.1 switch | CRT |
| 1 | <Global All> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 2 | <Global All> Scene | Scene | 1 Byte | 18.1 scene control | CW |
| 3 | <Global All> Dyn Scene | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 4 | <Global All> Heat/Cool | Heat/Cool | 1 Bit | 1.100 heating/cooling | CW |
| 5 | <Global Single> Command | Off/On | 1 Bit | 1.1 switch | CW |
| 6 | <Global Shutter> Up/Down | Up/Down | 1 Bit | 1.8 up/down | CW |
| 7 | <Global Shutter> Shutter % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 8 | <Global Shutter> Louvre % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 9 | <Global Shutter> Alarm 1 | No alarm/Alarm | 1 Bit | 1.5 alarm | CW |
| 10 | <Global Shutter> Alarm 2 | No alarm/Alarm | 1 Bit | 1.5 alarm | CW |
| 11 | <Global Shutter> Alarm 3 | No alarm/Alarm | 1 Bit | 1.5 alarm | CW |
| 12 | <Temperature 1> Alarm | No alarm/Alarm | 1 Bit | 1.5 alarm | CRT |
| 13 | <Temperature 2> Alarm | No alarm/Alarm | 1 Bit | 1.5 alarm | CRT |
| 14 | <Temperature 3> Alarm | No alarm/Alarm | 1 Bit | 1.5 alarm | CRT |
| 15 | <Temperature 4> Alarm | No alarm/Alarm | 1 Bit | 1.5 alarm | CRT |
| 16 | <Output B1 | 01-02> Scene | Scene | 1 Byte | 18.1 scene control | CW |
| 16 | <Output B1 | 01-02> Command value | 0 - 2 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 16 | <Output C1 | 01-03> Command value | 0 - 3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 16 | <Output C1 | 01-03> Scene | Scene | 1 Byte | 18.1 scene control | CW |
| 16 | <Output D1 | 01-04> Command value | 0 - 4 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 16 | <Output A1 | 01> Timing | Off/On | 1 Bit | 1.1 switch | CW |
| 16 | <Output A1 | 01> Open/Close | Open/Close | 1 Bit | 1.1 switch | CW |
| 16 | <Output B1 | 01-02> Open/Close | Open/Close | 1 Bit | 1.1 switch | CW |
| 16 | <Output B1 | 01-02> Valve | Off/On | 1 Bit | 1.1 switch | CW |
| 16 | <Output C1 | 01-03> Valve | Off/On | 1 Bit | 1.1 switch | CW |
| 16 | <Output C1 | 01-03> Heating Valve | Heating | 1 Bit | 1.1 switch | CW |
| 16 | <Output D1 | 01-04> Valve | Off/On | 1 Bit | 1.1 switch | CW |
| 16 | <Output D1 | 01-04> Heating Valve | Heating | 1 Bit | 1.1 switch | CW |
| 17 | <Output A1 | 01> Scene | Scene | 1 Byte | 18.1 scene control | CW |
| 17 | <Output A1 | 01> PWM % | PWM % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 17 | <Output B1 | 01-02> Value Status | 0 - 2 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 17 | <Output B1 | 01-02> Position % | Position % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 17 | <Output C1 | 01-03> Value Status | 0 - 3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 17 | <Output D1 | 01-04> Value Status | 0 - 4 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 17 | <Output B1 | 01-02> Up/Down | Up/Down | 1 Bit | 1.8 up/down | CW |
| 17 | <Output B1 | 01-02> Valve Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 17 | <Output C1 | 01-03> Valve Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 17 | <Output C1 | 01-03> Heating Valve Status | Heating | 1 Bit | 1.1 switch | CRT |
| 17 | <Output C1 | 01-03> Up/Down | Up/Down | 1 Bit | 1.8 up/down | CW |
| 17 | <Output D1 | 01-04> Valve Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 17 | <Output D1 | 01-04> Heating Valve Status | Heating | 1 Bit | 1.1 switch | CRT |
| 18 | <Output A1 | 01> Command | Off/On | 1 Bit | 1.1 switch | CW |
| 18 | <Output A1 | 01> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 18 | <Output B1 | 01-02> Step/Stop | Step/Stop | 1 Bit | 1.7 step | CW |
| 18 | <Output B1 | 01-02> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 18 | <Output B1 | 01-02> Position 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 18 | <Output C1 | 01-03> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 18 | <Output C1 | 01-03> Cooling Valve | Cooling | 1 Bit | 1.1 switch | CW |
| 18 | <Output C1 | 01-03> Step/Stop | Step/Stop | 1 Bit | 1.7 step | CW |
| 18 | <Output D1 | 01-04> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 18 | <Output D1 | 01-04> Cooling Valve | Cooling | 1 Bit | 1.1 switch | CW |
| 19 | <Output B1 | 01-02> Shutter % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 19 | <Output C1 | 01-03> Shutter % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 19 | <Output A1 | 01> Logic | Logic | 1 Bit | 1.1 switch | CW |
| 19 | <Output A1 | 01> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 19 | <Output A1 | 01> Status | Open/Close | 1 Bit | 1.1 switch | CRT |
| 19 | <Output B1 | 01-02> Command 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 19 | <Output B1 | 01-02> Position 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 19 | <Output C1 | 01-03> Command 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 19 | <Output C1 | 01-03> Cooling Valve Status | Cooling | 1 Bit | 1.1 switch | CRT |
| 19 | <Output D1 | 01-04> Command 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 19 | <Output D1 | 01-04> Cooling Valve Status | Cooling | 1 Bit | 1.1 switch | CRT |
| 20 | <Output A1 | 01> PWM Status % | PWM % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 20 | <Output B1 | 01-02> Louvre % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 20 | <Output B1 | 01-02> Command % | Value % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 20 | <Output C1 | 01-03> Command % | Value % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 20 | <Output C1 | 01-03> Louvre % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 20 | <Output D1 | 01-04> Command % | Value % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 20 | <Output A1 | 01> Counter Reset | Off/On | 1 Bit | 1.15 reset | CW |
| 20 | <Output B1 | 01-02> Status 1 | Off/On | 1 Bit | 1.1 switch | CRT |
| 20 | <Output B1 | 01-02> Position 3 | Off/On | 1 Bit | 1.1 switch | CW |
| 20 | <Output C1 | 01-03> Status 1 | Off/On | 1 Bit | 1.1 switch | CRT |
| 20 | <Output D1 | 01-04> Status 1 | Off/On | 1 Bit | 1.1 switch | CRT |
| 21 | <Output B1 | 01-02> Speed Status % | Value % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 21 | <Output C1 | 01-03> Speed Status % | Value % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 21 | <Output D1 | 01-04> Speed Status % | Value % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 21 | <Output A1 | 01> Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 21 | <Output B1 | 01-02> Auto Movement | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 21 | <Output B1 | 01-02> Command 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 21 | <Output B1 | 01-02> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 21 | <Output C1 | 01-03> Command 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 21 | <Output C1 | 01-03> Auto Movement | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 21 | <Output D1 | 01-04> Command 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 22 | <Output A1 | 01> Counter | Counter | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 22 | <Output A1 | 01> Counter | Counter | 4 Bytes | 14.56 power (W) | CRT |
| 22 | <Output A1 | 01> Counter | Counter | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 22 | <Output A1 | 01> Counter | Counter | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 22 | <Output A1 | 01> Counter | Counter | 2 Bytes | 7.7 time (h) | CRT |
| 22 | <Output A1 | 01> Counter | Counter | 2 Bytes | 9.24 power (kW) | CRT |
| 22 | <Output B1 | 01-02> Presence/Sun | Off/On | 1 Bit | 1.1 switch | CW |
| 22 | <Output B1 | 01-02> Status 2 | Off/On | 1 Bit | 1.1 switch | CRT |
| 22 | <Output B1 | 01-02> Status | Open/Close | 1 Bit | 1.1 switch | CRT |
| 22 | <Output B1 | 01-02> Speed 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 22 | <Output C1 | 01-03> Status 2 | Off/On | 1 Bit | 1.1 switch | CRT |
| 22 | <Output C1 | 01-03> Speed 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 22 | <Output C1 | 01-03> Presence/Sun | Off/On | 1 Bit | 1.1 switch | CW |
| 22 | <Output D1 | 01-04> Status 2 | Off/On | 1 Bit | 1.1 switch | CRT |
| 22 | <Output D1 | 01-04> Speed 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 23 | <Output B1 | 01-02> Position Status % | Position % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 23 | <Output C2 | 02-04> Command value | 0 - 3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 23 | <Output C2 | 02-04> Scene | Scene | 1 Byte | 18.1 scene control | CW |
| 23 | <Output A2 | 02> Timing | Off/On | 1 Bit | 1.1 switch | CW |
| 23 | <Output A2 | 02> Open/Close | Open/Close | 1 Bit | 1.1 switch | CW |
| 23 | <Output B1 | 01-02> Alarm | No alarm/Alarm | 1 Bit | 1.5 alarm | CW |
| 23 | <Output B1 | 01-02> Speed 1 Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 23 | <Output C1 | 01-03> Command 3 | Off/On | 1 Bit | 1.1 switch | CW |
| 23 | <Output C1 | 01-03> Speed 1 Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 23 | <Output C2 | 02-04> Valve | Off/On | 1 Bit | 1.1 switch | CW |
| 23 | <Output C2 | 02-04> Heating Valve | Heating | 1 Bit | 1.1 switch | CW |
| 23 | <Output C1 | 01-03> Alarm | No alarm/Alarm | 1 Bit | 1.5 alarm | CW |
| 23 | <Output D1 | 01-04> Command 3 | Off/On | 1 Bit | 1.1 switch | CW |
| 23 | <Output D1 | 01-04> Speed 1 Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 24 | <Output A2 | 02> Scene | Scene | 1 Byte | 18.1 scene control | CW |
| 24 | <Output A2 | 02> PWM % | PWM % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 24 | <Output C2 | 02-04> Value Status | 0 - 3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 24 | <Output B1 | 01-02> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 24 | <Output B1 | 01-02> Opening Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 24 | <Output C1 | 01-03> Status 3 | Off/On | 1 Bit | 1.1 switch | CRT |
| 24 | <Output C1 | 01-03> Speed 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 24 | <Output C2 | 02-04> Valve Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 24 | <Output C2 | 02-04> Heating Valve Status | Heating | 1 Bit | 1.1 switch | CRT |
| 24 | <Output C1 | 01-03> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 24 | <Output C2 | 02-04> Up/Down | Up/Down | 1 Bit | 1.8 up/down | CW |
| 24 | <Output D1 | 01-04> Status 3 | Off/On | 1 Bit | 1.1 switch | CRT |
| 24 | <Output D1 | 01-04> Speed 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 25 | <Output A2 | 02> Command | Off/On | 1 Bit | 1.1 switch | CW |
| 25 | <Output A2 | 02> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 25 | <Output B1 | 01-02> Up/Down Status | Up/Down | 1 Bit | 1.8 up/down | CRT |
| 25 | <Output B1 | 01-02> Closing Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 25 | <Output C2 | 02-04> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 25 | <Output C1 | 01-03> Speed 2 Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 25 | <Output C2 | 02-04> Cooling Valve | Cooling | 1 Bit | 1.1 switch | CW |
| 25 | <Output C1 | 01-03> Up/Down Status | Up/Down | 1 Bit | 1.8 up/down | CRT |
| 25 | <Output C2 | 02-04> Step/Stop | Step/Stop | 1 Bit | 1.7 step | CW |
| 25 | <Output D1 | 01-04> Command 4 | Off/On | 1 Bit | 1.1 switch | CW |
| 25 | <Output D1 | 01-04> Speed 2 Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 26 | <Output B1 | 01-02> Shutter Status | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 26 | <Output C1 | 01-03> Shutter Status | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 26 | <Output C2 | 02-04> Shutter % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 26 | <Output A2 | 02> Logic | Logic | 1 Bit | 1.1 switch | CW |
| 26 | <Output A2 | 02> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 26 | <Output A2 | 02> Status | Open/Close | 1 Bit | 1.1 switch | CRT |
| 26 | <Output C2 | 02-04> Command 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 26 | <Output C2 | 02-04> Cooling Valve Status | Cooling | 1 Bit | 1.1 switch | CRT |
| 26 | <Output D1 | 01-04> Status 4 | Off/On | 1 Bit | 1.1 switch | CRT |
| 26 | <Output D1 | 01-04> Speed 3 | Off/On | 1 Bit | 1.1 switch | CW |
| 27 | <Output A2 | 02> PWM Status % | PWM % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 27 | <Output B1 | 01-02> Louvre Status | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 27 | <Output C2 | 02-04> Command % | Value % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 27 | <Output C1 | 01-03> Louvre Status | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 27 | <Output C2 | 02-04> Louvre % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 27 | <Output A2 | 02> Counter Reset | Off/On | 1 Bit | 1.15 reset | CW |
| 27 | <Output C2 | 02-04> Status 1 | Off/On | 1 Bit | 1.1 switch | CRT |
| 27 | <Output D1 | 01-04> Speed 3 Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 28 | <Output C2 | 02-04> Speed Status % | Value % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 28 | <Output A2 | 02> Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 28 | <Output B1 | 01-02> Rising Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 28 | <Output C2 | 02-04> Command 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 28 | <Output C1 | 01-03> Rising Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 28 | <Output C2 | 02-04> Auto Movement | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 29 | <Output A2 | 02> Counter | Counter | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 29 | <Output A2 | 02> Counter | Counter | 4 Bytes | 14.56 power (W) | CRT |
| 29 | <Output A2 | 02> Counter | Counter | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 29 | <Output A2 | 02> Counter | Counter | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 29 | <Output A2 | 02> Counter | Counter | 2 Bytes | 7.7 time (h) | CRT |
| 29 | <Output A2 | 02> Counter | Counter | 2 Bytes | 9.24 power (kW) | CRT |
| 29 | <Output B1 | 01-02> Lowering Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 29 | <Output B1 | 01-02> Enable Speed | Off/On | 1 Bit | 1.1 switch | CW |
| 29 | <Output C2 | 02-04> Status 2 | Off/On | 1 Bit | 1.1 switch | CRT |
| 29 | <Output C1 | 01-03> Enable Speed | Off/On | 1 Bit | 1.1 switch | CW |
| 29 | <Output C2 | 02-04> Speed 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 29 | <Output C1 | 01-03> Lowering Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 29 | <Output C2 | 02-04> Presence/Sun | Off/On | 1 Bit | 1.1 switch | CW |
| 29 | <Output D1 | 01-04> Enable Speed | Off/On | 1 Bit | 1.1 switch | CW |
| 30 | <Output B2 | 03-04> Scene | Scene | 1 Byte | 18.1 scene control | CW |
| 30 | <Output B2 | 03-04> Command value | 0 - 2 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 30 | <Output A3 | 03> Timing | Off/On | 1 Bit | 1.1 switch | CW |
| 30 | <Output A3 | 03> Open/Close | Open/Close | 1 Bit | 1.1 switch | CW |
| 30 | <Output B2 | 03-04> Open/Close | Open/Close | 1 Bit | 1.1 switch | CW |
| 30 | <Output B2 | 03-04> Valve | Off/On | 1 Bit | 1.1 switch | CW |
| 30 | <Output C2 | 02-04> Command 3 | Off/On | 1 Bit | 1.1 switch | CW |
| 30 | <Output C2 | 02-04> Speed 1 Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 30 | <Output C1 | 01-03> Up/Down AB1 | Up/Down | 1 Bit | 1.8 up/down | CW |
| 30 | <Output C2 | 02-04> Alarm | No alarm/Alarm | 1 Bit | 1.5 alarm | CW |
| 31 | <Output A3 | 03> Scene | Scene | 1 Byte | 18.1 scene control | CW |
| 31 | <Output A3 | 03> PWM % | PWM % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 31 | <Output B2 | 03-04> Value Status | 0 - 2 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 31 | <Output B2 | 03-04> Position % | Position % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 31 | <Output B2 | 03-04> Up/Down | Up/Down | 1 Bit | 1.8 up/down | CW |
| 31 | <Output B2 | 03-04> Valve Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 31 | <Output C2 | 02-04> Status 3 | Off/On | 1 Bit | 1.1 switch | CRT |
| 31 | <Output C2 | 02-04> Speed 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 31 | <Output C1 | 01-03> Step/Stop AB1 | Step/Stop | 1 Bit | 1.7 step | CW |
| 31 | <Output C2 | 02-04> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 32 | <Output A3 | 03> Command | Off/On | 1 Bit | 1.1 switch | CW |
| 32 | <Output A3 | 03> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 32 | <Output B2 | 03-04> Step/Stop | Step/Stop | 1 Bit | 1.7 step | CW |
| 32 | <Output B2 | 03-04> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 32 | <Output B2 | 03-04> Position 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 32 | <Output C2 | 02-04> Speed 2 Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 32 | <Output C2 | 02-04> Up/Down Status | Up/Down | 1 Bit | 1.8 up/down | CRT |
| 33 | <Output B2 | 03-04> Shutter % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 33 | <Output C2 | 02-04> Shutter Status | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 33 | <Output A3 | 03> Logic | Logic | 1 Bit | 1.1 switch | CW |
| 33 | <Output A3 | 03> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 33 | <Output A3 | 03> Status | Open/Close | 1 Bit | 1.1 switch | CRT |
| 33 | <Output B2 | 03-04> Command 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 33 | <Output B2 | 03-04> Position 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 34 | <Output A3 | 03> PWM Status % | PWM % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 34 | <Output B2 | 03-04> Louvre % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 34 | <Output B2 | 03-04> Command % | Value % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 34 | <Output C2 | 02-04> Louvre Status | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 34 | <Output A3 | 03> Counter Reset | Off/On | 1 Bit | 1.15 reset | CW |
| 34 | <Output B2 | 03-04> Status 1 | Off/On | 1 Bit | 1.1 switch | CRT |
| 34 | <Output B2 | 03-04> Position 3 | Off/On | 1 Bit | 1.1 switch | CW |
| 35 | <Output B2 | 03-04> Speed Status % | Value % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 35 | <Output A3 | 03> Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 35 | <Output B2 | 03-04> Auto Movement | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 35 | <Output B2 | 03-04> Command 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 35 | <Output B2 | 03-04> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 35 | <Output C2 | 02-04> Rising Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 36 | <Output A3 | 03> Counter | Counter | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 36 | <Output A3 | 03> Counter | Counter | 4 Bytes | 14.56 power (W) | CRT |
| 36 | <Output A3 | 03> Counter | Counter | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 36 | <Output A3 | 03> Counter | Counter | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 36 | <Output A3 | 03> Counter | Counter | 2 Bytes | 7.7 time (h) | CRT |
| 36 | <Output A3 | 03> Counter | Counter | 2 Bytes | 9.24 power (kW) | CRT |
| 36 | <Output B2 | 03-04> Presence/Sun | Off/On | 1 Bit | 1.1 switch | CW |
| 36 | <Output B2 | 03-04> Status 2 | Off/On | 1 Bit | 1.1 switch | CRT |
| 36 | <Output B2 | 03-04> Status | Open/Close | 1 Bit | 1.1 switch | CRT |
| 36 | <Output B2 | 03-04> Speed 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 36 | <Output C2 | 02-04> Enable Speed | Off/On | 1 Bit | 1.1 switch | CW |
| 36 | <Output C2 | 02-04> Lowering Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 37 | <Output B2 | 03-04> Position Status % | Position % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 37 | <Output A4 | 04> Timing | Off/On | 1 Bit | 1.1 switch | CW |
| 37 | <Output A4 | 04> Open/Close | Open/Close | 1 Bit | 1.1 switch | CW |
| 37 | <Output B2 | 03-04> Alarm | No alarm/Alarm | 1 Bit | 1.5 alarm | CW |
| 37 | <Output B2 | 03-04> Speed 1 Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 37 | <Output C2 | 02-04> Up/Down AB1 | Up/Down | 1 Bit | 1.8 up/down | CW |
| 38 | <Output A4 | 04> Scene | Scene | 1 Byte | 18.1 scene control | CW |
| 38 | <Output A4 | 04> PWM % | PWM % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 38 | <Output B2 | 03-04> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 38 | <Output B2 | 03-04> Opening Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 38 | <Output C2 | 02-04> Step/Stop AB1 | Step/Stop | 1 Bit | 1.7 step | CW |
| 39 | <Output A4 | 04> Command | Off/On | 1 Bit | 1.1 switch | CW |
| 39 | <Output A4 | 04> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 39 | <Output B2 | 03-04> Up/Down Status | Up/Down | 1 Bit | 1.8 up/down | CRT |
| 39 | <Output B2 | 03-04> Closing Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 40 | <Output B2 | 03-04> Shutter Status | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 40 | <Output A4 | 04> Logic | Logic | 1 Bit | 1.1 switch | CW |
| 40 | <Output A4 | 04> Lock | Lock | 1 Bit | 1.1 switch | CW |
| 40 | <Output A4 | 04> Status | Open/Close | 1 Bit | 1.1 switch | CRT |
| 41 | <Output A4 | 04> PWM Status % | PWM % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 41 | <Output B2 | 03-04> Louvre Status | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 41 | <Output A4 | 04> Counter Reset | Off/On | 1 Bit | 1.15 reset | CW |
| 42 | <Output A4 | 04> Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 42 | <Output B2 | 03-04> Rising Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 43 | <Output A4 | 04> Counter | Counter | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 43 | <Output A4 | 04> Counter | Counter | 4 Bytes | 14.56 power (W) | CRT |
| 43 | <Output A4 | 04> Counter | Counter | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 43 | <Output A4 | 04> Counter | Counter | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 43 | <Output A4 | 04> Counter | Counter | 2 Bytes | 7.7 time (h) | CRT |
| 43 | <Output A4 | 04> Counter | Counter | 2 Bytes | 9.24 power (kW) | CRT |
| 43 | <Output B2 | 03-04> Lowering Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 43 | <Output B2 | 03-04> Enable Speed | Off/On | 1 Bit | 1.1 switch | CW |
| 44 | <Input 1> RGB | 3 Bytes | 3 Bytes | 232.600 RGB value 3x(0..255) | CRT |
| 44 | <Temperature 1> Actual Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 44 | <Input 1> Red | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 44 | <Input 1> Closure Action | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 44 | <Input 1> Closure Action | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 44 | <Input 1> Closure Action | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 44 | <Input 1> Closure - Opening Action | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 44 | <Input 1> Closure - Opening Action | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 44 | <Input 1> Closure - Opening Action | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 44 | <Input 1> Short - Long Closure | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 44 | <Input 1> Short - Long Closure | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 44 | <Input 1> Short - Long Closure | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 44 | <Input 1> Recall/Learn Scene | Scene | 1 Byte | 18.1 scene control | CRT |
| 44 | <Input 1> Sequence Command A 0-255 | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 44 | <Input 1> Sequence Command A 0-100% | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 44 | <Input 1> Sequence Command A HVAC Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 44 | <Input 1> Sequence Command A 0-255-Toggle | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 44 | <Input 1> Sequence Command A 0-100%-Toggle | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 44 | <Input 1> Sequence Command A HVAC Mode-Toggle | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 44 | <Input 1> Closure Action | Off/On | 1 Bit | 1.1 switch | CRWT |
| 44 | <Input 1> Closure - Opening Action | Off/On | 1 Bit | 1.1 switch | CRWT |
| 44 | <Input 1> Short - Long Closure | Off/On | 1 Bit | 1.1 switch | CRWT |
| 44 | <Input 1> Dimming On/Off | Off/On | 1 Bit | 1.1 switch | CRWT |
| 44 | <Input 1> Object A | Off/On | 1 Bit | 1.1 switch | CRT |
| 44 | <Input 1> Shutter - Up/Down | Up/Down | 1 Bit | 1.8 up/down | CRWT |
| 44 | <Input 1> Sequence Command A Off/On | Off/On | 1 Bit | 1.1 switch | CRT |
| 44 | <Input 1> Sequence Command A Off/On-Toggle | Off/On | 1 Bit | 1.1 switch | CRT |
| 44 | <Input 1> Make Up Room | Off/On | 1 Bit | 1.1 switch | CRT |
| 44 | <LED 1> Command | Off/On | 1 Bit | 1.1 switch | CW |
| 45 | <Temperature 1> KNX Probe Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 45 | <Input 1> Green | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 45 | <Input 1> Long Closure | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 45 | <Input 1> Long Closure | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 45 | <Input 1> Long Closure | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 45 | <Input 1> Opening Action | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 45 | <Input 1> Opening Action | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 45 | <Input 1> Opening Action | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 45 | <Input 1> Sequence Command B 0-255 | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 45 | <Input 1> Sequence Command B 0-100% | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 45 | <Input 1> Sequence Command B HVAC Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 45 | <Input 1> Sequence Command B 0-255-Toggle | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 45 | <Input 1> Sequence Command B 0-100%-Toggle | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 45 | <Input 1> Sequence Command B HVAC Mode-Toggle | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 45 | <Input 1> Loop Value Output | Loop Value Output | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 45 | <Input 1> Dimming Control | Brighter/Darker | 4 Bit | 3.7 dimming control | CRT |
| 45 | <Input 1> Long Closure | Off/On | 1 Bit | 1.1 switch | CRWT |
| 45 | <Input 1> Opening Action | Off/On | 1 Bit | 1.1 switch | CRWT |
| 45 | <Input 1> Object B | Off/On | 1 Bit | 1.1 switch | CRT |
| 45 | <Input 1> Shutter - Step/Stop | Step/Stop | 1 Bit | 1.7 step | CRT |
| 45 | <Input 1> Sequence Command B Off/On | Off/On | 1 Bit | 1.1 switch | CRT |
| 45 | <Input 1> Sequence Command B Off/On-Toggle | Off/On | 1 Bit | 1.1 switch | CRT |
| 45 | <Input 1> Send Learn Scene Trigger | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 45 | <Input 1> Do Not Disturb | Off/On | 1 Bit | 1.1 switch | CRT |
| 46 | <Input 1> Additional Object RGB | 3 Bytes | 3 Bytes | 232.600 RGB value 3x(0..255) | CRT |
| 46 | <Input 1> Blue | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 46 | <Input 1> Sequence Command C 0-255 | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 46 | <Input 1> Sequence Command C 0-100% | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 46 | <Input 1> Sequence Command C HVAC Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 46 | <Input 1> Sequence Command C 0-255-Toggle | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 46 | <Input 1> Sequence Command C 0-100%-Toggle | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 46 | <Input 1> Sequence Command C HVAC Mode-Toggle | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 46 | <Input 1> Loop Value Feedback | Loop Value Feedback | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 46 | <Input 1> Sequence Command C Off/On | Off/On | 1 Bit | 1.1 switch | CRT |
| 46 | <Input 1> Sequence Command C Off/On-Toggle | Off/On | 1 Bit | 1.1 switch | CRT |
| 46 | <Input 1> Feedback | Off/On | 1 Bit | 1.1 switch | CW |
| 46 | <Input 1> Feedback | Up/Down | 1 Bit | 1.8 up/down | CW |
| 46 | <Input 1> Object C | Off/On | 1 Bit | 1.1 switch | CRT |
| 46 | <T.Sensor 1> Enable Input | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 46 | <Thermostat 1> Heat/Cool Mode | Heat/Cool | 1 Bit | 1.100 heating/cooling | CW |
| 46 | <Thermostat 1> Heat/Cool Mode | Heat/Cool | 1 Bit | 1.100 heating/cooling | CRT |
| 47 | <T.Sensor 1> Setpoint Upper | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 47 | <Input 1> Enable Input | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 47 | <Thermostat 1> Window Contact | Close/Open | 1 Bit | 1.19 window/door | CW |
| 48 | <T.Sensor 1> Telegram Upper | Off/On | 1 Bit | 1.1 switch | CRT |
| 48 | <Thermostat 1> Comfort Mode | Off/On | 1 Bit | 1.1 switch | CW |
| 49 | <T.Sensor 1> Setpoint Lower | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 49 | <Thermostat 1> HVAC Mode | Comf/Standby/Eco/B.protection | 1 Byte | 20.102 HVAC mode | CW |
| 50 | <Thermostat 1> Actual Setpoint | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 50 | <T.Sensor 1> Telegram Lower | Off/On | 1 Bit | 1.1 switch | CRT |
| 51 | <Thermostat 1> Setpoint Adjustment | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 51 | <Thermostat 1> Setpoint Adjustment | Value °C | 1 Bit | 1.7 step | CW |
| 52 | <Thermostat 1> Base Setpoint | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 52 | <Thermostat 1> SP Economy Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 52 | <Thermostat 1> SP Economy | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 53 | <Thermostat 1> SP Standby Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 53 | <Thermostat 1> SP Standby | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 54 | <Thermostat 1> SP Comfort Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 54 | <Thermostat 1> SP Comfort | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 55 | <Thermostat 1> SP Economy Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 56 | <Thermostat 1> SP Standby Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 57 | <Thermostat 1> SP Comfort Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 58 | <Thermostat 1> Heating | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 58 | <Thermostat 1> Heating | Off/On | 1 Bit | 1.1 switch | CRT |
| 58 | <Fan Coil 1> Heating/Cooling Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 58 | <Fan Coil 1> Heating Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 59 | <Thermostat 1> Cooling | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 59 | <Thermostat 1> Cooling | Off/On | 1 Bit | 1.1 switch | CRT |
| 59 | <Fan Coil 1> Cooling Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 60 | <Thermostat 1> 0-100% 2nd Stage Heating | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 60 | <Thermostat 1> Off/On 2nd Stage Heating | Off/On | 1 Bit | 1.1 switch | CRT |
| 61 | <Thermostat 1> 0-100% 2nd Stage Cooling | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 61 | <Thermostat 1> Off/On 2nd Stage Cooling | Off/On | 1 Bit | 1.1 switch | CRT |
| 62 | <Fan Coil 1> Continuous Control % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 62 | <Fan Coil 1> Speed 1 | Off/On | 1 Bit | 1.1 switch | CRT |
| 63 | <Fan Coil 1> Speed 2 | Off/On | 1 Bit | 1.1 switch | CRT |
| 64 | <Fan Coil 1> Speed 3 | Off/On | 1 Bit | 1.1 switch | CRT |
| 65 | <Fan Coil 1> Set Man/Auto Mode | Manual (0) / Auto (1) | 1 Bit | 1.1 switch | CW |
| 66 | <Fan Coil 1> Force Speed Control in Man Mode | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 66 | <Fan Coil 1> Force Value in Man Mode Speed 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 67 | <Fan Coil 1> Force Value in Man Mode Speed 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 68 | <Fan Coil 1> Force Value in Man Mode Speed 3 | Off/On | 1 Bit | 1.1 switch | CW |
| 69 | <Thermostat 1> OFF Thermostat | Off/On | 1 Bit | 1.1 switch | CRWT |
| 70 | <Fan Coil 1> Ventilation Off/On | Off/On | 1 Bit | 1.1 switch | CW |
| 71 | <Additional Valve 1> Percentage | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 71 | <Additional Valve 1> Valve 6 Ways | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 71 | <Additional Valve 1> PWM | Off/On | 1 Bit | 1.1 switch | CRT |
| 72 | <Input 2> RGB | 3 Bytes | 3 Bytes | 232.600 RGB value 3x(0..255) | CRT |
| 72 | <Temperature 2> Actual Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 72 | <Input 2> Red | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 72 | <Input 2> Closure Action | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 72 | <Input 2> Closure Action | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 72 | <Input 2> Closure Action | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 72 | <Input 2> Closure - Opening Action | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 72 | <Input 2> Closure - Opening Action | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 72 | <Input 2> Closure - Opening Action | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 72 | <Input 2> Short - Long Closure | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 72 | <Input 2> Short - Long Closure | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 72 | <Input 2> Short - Long Closure | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 72 | <Input 2> Recall/Learn Scene | Scene | 1 Byte | 18.1 scene control | CRT |
| 72 | <Input 2> Sequence Command A 0-255 | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 72 | <Input 2> Sequence Command A 0-100% | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 72 | <Input 2> Sequence Command A HVAC Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 72 | <Input 2> Sequence Command A 0-255-Toggle | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 72 | <Input 2> Sequence Command A 0-100%-Toggle | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 72 | <Input 2> Sequence Command A HVAC Mode-Toggle | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 72 | <Input 2> Closure Action | Off/On | 1 Bit | 1.1 switch | CRWT |
| 72 | <Input 2> Closure - Opening Action | Off/On | 1 Bit | 1.1 switch | CRWT |
| 72 | <Input 2> Short - Long Closure | Off/On | 1 Bit | 1.1 switch | CRWT |
| 72 | <Input 2> Dimming On/Off | Off/On | 1 Bit | 1.1 switch | CRWT |
| 72 | <Input 2> Object A | Off/On | 1 Bit | 1.1 switch | CRT |
| 72 | <Input 2> Shutter - Up/Down | Up/Down | 1 Bit | 1.8 up/down | CRWT |
| 72 | <Input 2> Sequence Command A Off/On | Off/On | 1 Bit | 1.1 switch | CRT |
| 72 | <Input 2> Sequence Command A Off/On-Toggle | Off/On | 1 Bit | 1.1 switch | CRT |
| 72 | <Input 2> Make Up Room | Off/On | 1 Bit | 1.1 switch | CRT |
| 72 | <LED 2> Command | Off/On | 1 Bit | 1.1 switch | CW |
| 73 | <Temperature 2> KNX Probe Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 73 | <Input 2> Green | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 73 | <Input 2> Long Closure | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 73 | <Input 2> Long Closure | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 73 | <Input 2> Long Closure | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 73 | <Input 2> Opening Action | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 73 | <Input 2> Opening Action | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 73 | <Input 2> Opening Action | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 73 | <Input 2> Sequence Command B 0-255 | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 73 | <Input 2> Sequence Command B 0-100% | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 73 | <Input 2> Sequence Command B HVAC Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 73 | <Input 2> Sequence Command B 0-255-Toggle | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 73 | <Input 2> Sequence Command B 0-100%-Toggle | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 73 | <Input 2> Sequence Command B HVAC Mode-Toggle | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 73 | <Input 2> Loop Value Output | Loop Value Output | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 73 | <Input 2> Dimming Control | Brighter/Darker | 4 Bit | 3.7 dimming control | CRT |
| 73 | <Input 2> Long Closure | Off/On | 1 Bit | 1.1 switch | CRWT |
| 73 | <Input 2> Opening Action | Off/On | 1 Bit | 1.1 switch | CRWT |
| 73 | <Input 2> Object B | Off/On | 1 Bit | 1.1 switch | CRT |
| 73 | <Input 2> Shutter - Step/Stop | Step/Stop | 1 Bit | 1.7 step | CRT |
| 73 | <Input 2> Sequence Command B Off/On | Off/On | 1 Bit | 1.1 switch | CRT |
| 73 | <Input 2> Sequence Command B Off/On-Toggle | Off/On | 1 Bit | 1.1 switch | CRT |
| 73 | <Input 2> Send Learn Scene Trigger | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 73 | <Input 2> Do Not Disturb | Off/On | 1 Bit | 1.1 switch | CRT |
| 74 | <Input 2> Additional Object RGB | 3 Bytes | 3 Bytes | 232.600 RGB value 3x(0..255) | CRT |
| 74 | <Input 2> Blue | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 74 | <Input 2> Sequence Command C 0-255 | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 74 | <Input 2> Sequence Command C 0-100% | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 74 | <Input 2> Sequence Command C HVAC Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 74 | <Input 2> Sequence Command C 0-255-Toggle | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 74 | <Input 2> Sequence Command C 0-100%-Toggle | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 74 | <Input 2> Sequence Command C HVAC Mode-Toggle | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 74 | <Input 2> Loop Value Feedback | Loop Value Feedback | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 74 | <Input 2> Sequence Command C Off/On | Off/On | 1 Bit | 1.1 switch | CRT |
| 74 | <Input 2> Sequence Command C Off/On-Toggle | Off/On | 1 Bit | 1.1 switch | CRT |
| 74 | <Input 2> Feedback | Off/On | 1 Bit | 1.1 switch | CW |
| 74 | <Input 2> Feedback | Up/Down | 1 Bit | 1.8 up/down | CW |
| 74 | <Input 2> Object C | Off/On | 1 Bit | 1.1 switch | CRT |
| 74 | <T.Sensor 2> Enable Input | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 74 | <Thermostat 2> Heat/Cool Mode | Heat/Cool | 1 Bit | 1.100 heating/cooling | CW |
| 74 | <Thermostat 2> Heat/Cool Mode | Heat/Cool | 1 Bit | 1.100 heating/cooling | CRT |
| 75 | <T.Sensor 2> Setpoint Upper | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 75 | <Input 2> Enable Input | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 75 | <Thermostat 2> Window Contact | Close/Open | 1 Bit | 1.19 window/door | CW |
| 76 | <T.Sensor 2> Telegram Upper | Off/On | 1 Bit | 1.1 switch | CRT |
| 76 | <Thermostat 2> Comfort Mode | Off/On | 1 Bit | 1.1 switch | CW |
| 77 | <T.Sensor 2> Setpoint Lower | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 77 | <Thermostat 2> HVAC Mode | Comf/Standby/Eco/B.protection | 1 Byte | 20.102 HVAC mode | CW |
| 78 | <Thermostat 2> Actual Setpoint | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 78 | <T.Sensor 2> Telegram Lower | Off/On | 1 Bit | 1.1 switch | CRT |
| 79 | <Thermostat 2> Setpoint Adjustment | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 79 | <Thermostat 2> Setpoint Adjustment | Value °C | 1 Bit | 1.7 step | CW |
| 80 | <Thermostat 2> Base Setpoint | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 80 | <Thermostat 2> SP Economy Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 80 | <Thermostat 2> SP Economy | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 81 | <Thermostat 2> SP Standby Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 81 | <Thermostat 2> SP Standby | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 82 | <Thermostat 2> SP Comfort Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 82 | <Thermostat 2> SP Comfort | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 83 | <Thermostat 2> SP Economy Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 84 | <Thermostat 2> SP Standby Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 85 | <Thermostat 2> SP Comfort Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 86 | <Thermostat 2> Heating | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 86 | <Thermostat 2> Heating | Off/On | 1 Bit | 1.1 switch | CRT |
| 86 | <Fan Coil 2> Heating/Cooling Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 86 | <Fan Coil 2> Heating Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 87 | <Thermostat 2> Cooling | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 87 | <Thermostat 2> Cooling | Off/On | 1 Bit | 1.1 switch | CRT |
| 87 | <Fan Coil 2> Cooling Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 88 | <Thermostat 2> 0-100% 2nd Stage Heating | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 88 | <Thermostat 2> Off/On 2nd Stage Heating | Off/On | 1 Bit | 1.1 switch | CRT |
| 89 | <Thermostat 2> 0-100% 2nd Stage Cooling | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 89 | <Thermostat 2> Off/On 2nd Stage Cooling | Off/On | 1 Bit | 1.1 switch | CRT |
| 90 | <Fan Coil 2> Continuous Control % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 90 | <Fan Coil 2> Speed 1 | Off/On | 1 Bit | 1.1 switch | CRT |
| 91 | <Fan Coil 2> Speed 2 | Off/On | 1 Bit | 1.1 switch | CRT |
| 92 | <Fan Coil 2> Speed 3 | Off/On | 1 Bit | 1.1 switch | CRT |
| 93 | <Fan Coil 2> Set Man/Auto Mode | Manual (0) / Auto (1) | 1 Bit | 1.1 switch | CW |
| 94 | <Fan Coil 2> Force Speed Control in Man Mode | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 94 | <Fan Coil 2> Force Value in Man Mode Speed 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 95 | <Fan Coil 2> Force Value in Man Mode Speed 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 96 | <Fan Coil 2> Force Value in Man Mode Speed 3 | Off/On | 1 Bit | 1.1 switch | CW |
| 97 | <Thermostat 2> OFF Thermostat | Off/On | 1 Bit | 1.1 switch | CRWT |
| 98 | <Fan Coil 2> Ventilation Off/On | Off/On | 1 Bit | 1.1 switch | CW |
| 99 | <Additional Valve 2> Percentage | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 99 | <Additional Valve 2> Valve 6 Ways | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 99 | <Additional Valve 2> PWM | Off/On | 1 Bit | 1.1 switch | CRT |
| 100 | <Input 3> RGB | 3 Bytes | 3 Bytes | 232.600 RGB value 3x(0..255) | CRT |
| 100 | <Temperature 3> Actual Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 100 | <Input 3> Red | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 100 | <Input 3> Closure Action | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 100 | <Input 3> Closure Action | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 100 | <Input 3> Closure Action | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 100 | <Input 3> Closure - Opening Action | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 100 | <Input 3> Closure - Opening Action | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 100 | <Input 3> Closure - Opening Action | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 100 | <Input 3> Short - Long Closure | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 100 | <Input 3> Short - Long Closure | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 100 | <Input 3> Short - Long Closure | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 100 | <Input 3> Recall/Learn Scene | Scene | 1 Byte | 18.1 scene control | CRT |
| 100 | <Input 3> Sequence Command A 0-255 | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 100 | <Input 3> Sequence Command A 0-100% | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 100 | <Input 3> Sequence Command A HVAC Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 100 | <Input 3> Sequence Command A 0-255-Toggle | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 100 | <Input 3> Sequence Command A 0-100%-Toggle | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 100 | <Input 3> Sequence Command A HVAC Mode-Toggle | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 100 | <Input 3> Closure Action | Off/On | 1 Bit | 1.1 switch | CRWT |
| 100 | <Input 3> Closure - Opening Action | Off/On | 1 Bit | 1.1 switch | CRWT |
| 100 | <Input 3> Short - Long Closure | Off/On | 1 Bit | 1.1 switch | CRWT |
| 100 | <Input 3> Dimming On/Off | Off/On | 1 Bit | 1.1 switch | CRWT |
| 100 | <Input 3> Object A | Off/On | 1 Bit | 1.1 switch | CRT |
| 100 | <Input 3> Shutter - Up/Down | Up/Down | 1 Bit | 1.8 up/down | CRWT |
| 100 | <Input 3> Sequence Command A Off/On | Off/On | 1 Bit | 1.1 switch | CRT |
| 100 | <Input 3> Sequence Command A Off/On-Toggle | Off/On | 1 Bit | 1.1 switch | CRT |
| 100 | <Input 3> Make Up Room | Off/On | 1 Bit | 1.1 switch | CRT |
| 100 | <LED 3> Command | Off/On | 1 Bit | 1.1 switch | CW |
| 101 | <Temperature 3> KNX Probe Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 101 | <Input 3> Green | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 101 | <Input 3> Long Closure | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 101 | <Input 3> Long Closure | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 101 | <Input 3> Long Closure | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 101 | <Input 3> Opening Action | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 101 | <Input 3> Opening Action | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 101 | <Input 3> Opening Action | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 101 | <Input 3> Sequence Command B 0-255 | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 101 | <Input 3> Sequence Command B 0-100% | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 101 | <Input 3> Sequence Command B HVAC Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 101 | <Input 3> Sequence Command B 0-255-Toggle | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 101 | <Input 3> Sequence Command B 0-100%-Toggle | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 101 | <Input 3> Sequence Command B HVAC Mode-Toggle | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 101 | <Input 3> Loop Value Output | Loop Value Output | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 101 | <Input 3> Dimming Control | Brighter/Darker | 4 Bit | 3.7 dimming control | CRT |
| 101 | <Input 3> Long Closure | Off/On | 1 Bit | 1.1 switch | CRWT |
| 101 | <Input 3> Opening Action | Off/On | 1 Bit | 1.1 switch | CRWT |
| 101 | <Input 3> Object B | Off/On | 1 Bit | 1.1 switch | CRT |
| 101 | <Input 3> Shutter - Step/Stop | Step/Stop | 1 Bit | 1.7 step | CRT |
| 101 | <Input 3> Sequence Command B Off/On | Off/On | 1 Bit | 1.1 switch | CRT |
| 101 | <Input 3> Sequence Command B Off/On-Toggle | Off/On | 1 Bit | 1.1 switch | CRT |
| 101 | <Input 3> Send Learn Scene Trigger | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 101 | <Input 3> Do Not Disturb | Off/On | 1 Bit | 1.1 switch | CRT |
| 102 | <Input 3> Additional Object RGB | 3 Bytes | 3 Bytes | 232.600 RGB value 3x(0..255) | CRT |
| 102 | <Input 3> Blue | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 102 | <Input 3> Sequence Command C 0-255 | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 102 | <Input 3> Sequence Command C 0-100% | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 102 | <Input 3> Sequence Command C HVAC Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 102 | <Input 3> Sequence Command C 0-255-Toggle | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 102 | <Input 3> Sequence Command C 0-100%-Toggle | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 102 | <Input 3> Sequence Command C HVAC Mode-Toggle | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 102 | <Input 3> Loop Value Feedback | Loop Value Feedback | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 102 | <Input 3> Sequence Command C Off/On | Off/On | 1 Bit | 1.1 switch | CRT |
| 102 | <Input 3> Sequence Command C Off/On-Toggle | Off/On | 1 Bit | 1.1 switch | CRT |
| 102 | <Input 3> Feedback | Off/On | 1 Bit | 1.1 switch | CW |
| 102 | <Input 3> Feedback | Up/Down | 1 Bit | 1.8 up/down | CW |
| 102 | <Input 3> Object C | Off/On | 1 Bit | 1.1 switch | CRT |
| 102 | <T.Sensor 3> Enable Input | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 102 | <Thermostat 3> Heat/Cool Mode | Heat/Cool | 1 Bit | 1.100 heating/cooling | CW |
| 102 | <Thermostat 3> Heat/Cool Mode | Heat/Cool | 1 Bit | 1.100 heating/cooling | CRT |
| 103 | <T.Sensor 3> Setpoint Upper | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 103 | <Input 3> Enable Input | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 103 | <Thermostat 3> Window Contact | Close/Open | 1 Bit | 1.19 window/door | CW |
| 104 | <T.Sensor 3> Telegram Upper | Off/On | 1 Bit | 1.1 switch | CRT |
| 104 | <Thermostat 3> Comfort Mode | Off/On | 1 Bit | 1.1 switch | CW |
| 105 | <T.Sensor 3> Setpoint Lower | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 105 | <Thermostat 3> HVAC Mode | Comf/Standby/Eco/B.protection | 1 Byte | 20.102 HVAC mode | CW |
| 106 | <Thermostat 3> Actual Setpoint | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 106 | <T.Sensor 3> Telegram Lower | Off/On | 1 Bit | 1.1 switch | CRT |
| 107 | <Thermostat 3> Setpoint Adjustment | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 107 | <Thermostat 3> Setpoint Adjustment | Value °C | 1 Bit | 1.7 step | CW |
| 108 | <Thermostat 3> Base Setpoint | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 108 | <Thermostat 3> SP Economy Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 108 | <Thermostat 3> SP Economy | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 109 | <Thermostat 3> SP Standby Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 109 | <Thermostat 3> SP Standby | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 110 | <Thermostat 3> SP Comfort Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 110 | <Thermostat 3> SP Comfort | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 111 | <Thermostat 3> SP Economy Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 112 | <Thermostat 3> SP Standby Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 113 | <Thermostat 3> SP Comfort Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 114 | <Thermostat 3> Heating | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 114 | <Thermostat 3> Heating | Off/On | 1 Bit | 1.1 switch | CRT |
| 114 | <Fan Coil 3> Heating/Cooling Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 114 | <Fan Coil 3> Heating Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 115 | <Thermostat 3> Cooling | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 115 | <Thermostat 3> Cooling | Off/On | 1 Bit | 1.1 switch | CRT |
| 115 | <Fan Coil 3> Cooling Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 116 | <Thermostat 3> 0-100% 2nd Stage Heating | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 116 | <Thermostat 3> Off/On 2nd Stage Heating | Off/On | 1 Bit | 1.1 switch | CRT |
| 117 | <Thermostat 3> 0-100% 2nd Stage Cooling | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 117 | <Thermostat 3> Off/On 2nd Stage Cooling | Off/On | 1 Bit | 1.1 switch | CRT |
| 118 | <Fan Coil 3> Continuous Control % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 118 | <Fan Coil 3> Speed 1 | Off/On | 1 Bit | 1.1 switch | CRT |
| 119 | <Fan Coil 3> Speed 2 | Off/On | 1 Bit | 1.1 switch | CRT |
| 120 | <Fan Coil 3> Speed 3 | Off/On | 1 Bit | 1.1 switch | CRT |
| 121 | <Fan Coil 3> Set Man/Auto Mode | Manual (0) / Auto (1) | 1 Bit | 1.1 switch | CW |
| 122 | <Fan Coil 3> Force Speed Control in Man Mode | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 122 | <Fan Coil 3> Force Value in Man Mode Speed 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 123 | <Fan Coil 3> Force Value in Man Mode Speed 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 124 | <Fan Coil 3> Force Value in Man Mode Speed 3 | Off/On | 1 Bit | 1.1 switch | CW |
| 125 | <Thermostat 3> OFF Thermostat | Off/On | 1 Bit | 1.1 switch | CRWT |
| 126 | <Fan Coil 3> Ventilation Off/On | Off/On | 1 Bit | 1.1 switch | CW |
| 127 | <Additional Valve 3> Percentage | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 127 | <Additional Valve 3> Valve 6 Ways | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 127 | <Additional Valve 3> PWM | Off/On | 1 Bit | 1.1 switch | CRT |
| 128 | <Input 4> RGB | 3 Bytes | 3 Bytes | 232.600 RGB value 3x(0..255) | CRT |
| 128 | <Temperature 4> Actual Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 128 | <Input 4> Red | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 128 | <Input 4> Closure Action | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 128 | <Input 4> Closure Action | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | <Input 4> Closure Action | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 128 | <Input 4> Closure - Opening Action | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 128 | <Input 4> Closure - Opening Action | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | <Input 4> Closure - Opening Action | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 128 | <Input 4> Short - Long Closure | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 128 | <Input 4> Short - Long Closure | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | <Input 4> Short - Long Closure | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 128 | <Input 4> Recall/Learn Scene | Scene | 1 Byte | 18.1 scene control | CRT |
| 128 | <Input 4> Sequence Command A 0-255 | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 128 | <Input 4> Sequence Command A 0-100% | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | <Input 4> Sequence Command A HVAC Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 128 | <Input 4> Sequence Command A 0-255-Toggle | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 128 | <Input 4> Sequence Command A 0-100%-Toggle | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | <Input 4> Sequence Command A HVAC Mode-Toggle | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 128 | <Input 4> Closure Action | Off/On | 1 Bit | 1.1 switch | CRWT |
| 128 | <Input 4> Closure - Opening Action | Off/On | 1 Bit | 1.1 switch | CRWT |
| 128 | <Input 4> Short - Long Closure | Off/On | 1 Bit | 1.1 switch | CRWT |
| 128 | <Input 4> Dimming On/Off | Off/On | 1 Bit | 1.1 switch | CRWT |
| 128 | <Input 4> Object A | Off/On | 1 Bit | 1.1 switch | CRT |
| 128 | <Input 4> Shutter - Up/Down | Up/Down | 1 Bit | 1.8 up/down | CRWT |
| 128 | <Input 4> Sequence Command A Off/On | Off/On | 1 Bit | 1.1 switch | CRT |
| 128 | <Input 4> Sequence Command A Off/On-Toggle | Off/On | 1 Bit | 1.1 switch | CRT |
| 128 | <Input 4> Make Up Room | Off/On | 1 Bit | 1.1 switch | CRT |
| 128 | <LED 4> Command | Off/On | 1 Bit | 1.1 switch | CW |
| 129 | <Temperature 4> KNX Probe Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 129 | <Input 4> Green | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 129 | <Input 4> Long Closure | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 129 | <Input 4> Long Closure | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 129 | <Input 4> Long Closure | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 129 | <Input 4> Opening Action | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 129 | <Input 4> Opening Action | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 129 | <Input 4> Opening Action | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 129 | <Input 4> Sequence Command B 0-255 | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 129 | <Input 4> Sequence Command B 0-100% | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 129 | <Input 4> Sequence Command B HVAC Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 129 | <Input 4> Sequence Command B 0-255-Toggle | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 129 | <Input 4> Sequence Command B 0-100%-Toggle | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 129 | <Input 4> Sequence Command B HVAC Mode-Toggle | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 129 | <Input 4> Loop Value Output | Loop Value Output | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 129 | <Input 4> Dimming Control | Brighter/Darker | 4 Bit | 3.7 dimming control | CRT |
| 129 | <Input 4> Long Closure | Off/On | 1 Bit | 1.1 switch | CRWT |
| 129 | <Input 4> Opening Action | Off/On | 1 Bit | 1.1 switch | CRWT |
| 129 | <Input 4> Object B | Off/On | 1 Bit | 1.1 switch | CRT |
| 129 | <Input 4> Shutter - Step/Stop | Step/Stop | 1 Bit | 1.7 step | CRT |
| 129 | <Input 4> Sequence Command B Off/On | Off/On | 1 Bit | 1.1 switch | CRT |
| 129 | <Input 4> Sequence Command B Off/On-Toggle | Off/On | 1 Bit | 1.1 switch | CRT |
| 129 | <Input 4> Send Learn Scene Trigger | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 129 | <Input 4> Do Not Disturb | Off/On | 1 Bit | 1.1 switch | CRT |
| 130 | <Input 4> Additional Object RGB | 3 Bytes | 3 Bytes | 232.600 RGB value 3x(0..255) | CRT |
| 130 | <Input 4> Blue | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 130 | <Input 4> Sequence Command C 0-255 | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 130 | <Input 4> Sequence Command C 0-100% | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 130 | <Input 4> Sequence Command C HVAC Mode | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 130 | <Input 4> Sequence Command C 0-255-Toggle | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 130 | <Input 4> Sequence Command C 0-100%-Toggle | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 130 | <Input 4> Sequence Command C HVAC Mode-Toggle | HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 130 | <Input 4> Loop Value Feedback | Loop Value Feedback | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 130 | <Input 4> Sequence Command C Off/On | Off/On | 1 Bit | 1.1 switch | CRT |
| 130 | <Input 4> Sequence Command C Off/On-Toggle | Off/On | 1 Bit | 1.1 switch | CRT |
| 130 | <Input 4> Feedback | Off/On | 1 Bit | 1.1 switch | CW |
| 130 | <Input 4> Feedback | Up/Down | 1 Bit | 1.8 up/down | CW |
| 130 | <Input 4> Object C | Off/On | 1 Bit | 1.1 switch | CRT |
| 130 | <T.Sensor 4> Enable Input | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 130 | <Thermostat 4> Heat/Cool Mode | Heat/Cool | 1 Bit | 1.100 heating/cooling | CW |
| 130 | <Thermostat 4> Heat/Cool Mode | Heat/Cool | 1 Bit | 1.100 heating/cooling | CRT |
| 131 | <T.Sensor 4> Setpoint Upper | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 131 | <Input 4> Enable Input | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 131 | <Thermostat 4> Window Contact | Close/Open | 1 Bit | 1.19 window/door | CW |
| 132 | <T.Sensor 4> Telegram Upper | Off/On | 1 Bit | 1.1 switch | CRT |
| 132 | <Thermostat 4> Comfort Mode | Off/On | 1 Bit | 1.1 switch | CW |
| 133 | <T.Sensor 4> Setpoint Lower | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 133 | <Thermostat 4> HVAC Mode | Comf/Standby/Eco/B.protection | 1 Byte | 20.102 HVAC mode | CW |
| 134 | <Thermostat 4> Actual Setpoint | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 134 | <T.Sensor 4> Telegram Lower | Off/On | 1 Bit | 1.1 switch | CRT |
| 135 | <Thermostat 4> Setpoint Adjustment | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 135 | <Thermostat 4> Setpoint Adjustment | Value °C | 1 Bit | 1.7 step | CW |
| 136 | <Thermostat 4> Base Setpoint | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 136 | <Thermostat 4> SP Economy Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 136 | <Thermostat 4> SP Economy | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 137 | <Thermostat 4> SP Standby Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 137 | <Thermostat 4> SP Standby | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 138 | <Thermostat 4> SP Comfort Heating | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 138 | <Thermostat 4> SP Comfort | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 139 | <Thermostat 4> SP Economy Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 140 | <Thermostat 4> SP Standby Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 141 | <Thermostat 4> SP Comfort Cooling | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 142 | <Thermostat 4> Heating | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 142 | <Thermostat 4> Heating | Off/On | 1 Bit | 1.1 switch | CRT |
| 142 | <Fan Coil 4> Heating/Cooling Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 142 | <Fan Coil 4> Heating Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 143 | <Thermostat 4> Cooling | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 143 | <Thermostat 4> Cooling | Off/On | 1 Bit | 1.1 switch | CRT |
| 143 | <Fan Coil 4> Cooling Valve | Off/On | 1 Bit | 1.1 switch | CRT |
| 144 | <Thermostat 4> 0-100% 2nd Stage Heating | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 144 | <Thermostat 4> Off/On 2nd Stage Heating | Off/On | 1 Bit | 1.1 switch | CRT |
| 145 | <Thermostat 4> 0-100% 2nd Stage Cooling | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 145 | <Thermostat 4> Off/On 2nd Stage Cooling | Off/On | 1 Bit | 1.1 switch | CRT |
| 146 | <Fan Coil 4> Continuous Control % | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 146 | <Fan Coil 4> Speed 1 | Off/On | 1 Bit | 1.1 switch | CRT |
| 147 | <Fan Coil 4> Speed 2 | Off/On | 1 Bit | 1.1 switch | CRT |
| 148 | <Fan Coil 4> Speed 3 | Off/On | 1 Bit | 1.1 switch | CRT |
| 149 | <Fan Coil 4> Set Man/Auto Mode | Manual (0) / Auto (1) | 1 Bit | 1.1 switch | CW |
| 150 | <Fan Coil 4> Force Speed Control in Man Mode | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 150 | <Fan Coil 4> Force Value in Man Mode Speed 1 | Off/On | 1 Bit | 1.1 switch | CW |
| 151 | <Fan Coil 4> Force Value in Man Mode Speed 2 | Off/On | 1 Bit | 1.1 switch | CW |
| 152 | <Fan Coil 4> Force Value in Man Mode Speed 3 | Off/On | 1 Bit | 1.1 switch | CW |
| 153 | <Thermostat 4> OFF Thermostat | Off/On | 1 Bit | 1.1 switch | CRWT |
| 154 | <Fan Coil 4> Ventilation Off/On | Off/On | 1 Bit | 1.1 switch | CW |
| 155 | <Additional Valve 4> Percentage | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 155 | <Additional Valve 4> Valve 6 Ways | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 155 | <Additional Valve 4> PWM | Off/On | 1 Bit | 1.1 switch | CRT |