4-channel RLC+LED Dimmer REKNT004
Dinuy · Order number REKNT004 · KNX-TP Devices › Actuators › Dimming Actuators
Download .knxprod REKNT004 0.2 · 102 KB
Product
| Manufacturer | Dinuy |
|---|---|
| Product name | 4-channel RLC+LED Dimmer |
| Order number | REKNT004 |
| Hardware | Modulo TP para caja 5 modulos |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Certified · 2017-11-30 |
| Languages | es-ES, de-DE, en-US |
| Catalog entry | M-009A_H-009AREKNT004-0_HP-00C0-02-E0BC_CI-REKNT004-1 |
| Fingerprint | E0BC |
| SHA-256 | 27005505f72cb65d076f853e67e9f1f69cb8172ee7f78384ae26465a324508f5 |
| First seen | 2026-11-25 |
| Markets | 68 markets |
Application program: REKNT004 0.2
| Application number | $00C0 |
|---|---|
| Version | 0.2 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 369 |
| Group objects | 71 |
Group objects (71)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | [Ch1] Switch Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 1 | [Ch1] Relative Control Input | Dimming control | 4 Bit | 3.7 dimming control | CW |
| 2 | [Ch1] Absolute Dimming Input | Dimming value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 3 | [Ch1] Timer Start/Stop Input | 1 = Start, 0 = Stop | 1 Bit | 1.1 switch | CW |
| 4 | [Ch1] Forced Input | Forced control | 2 Bit | 2.3 enable control | CW |
| 5 | [Ch1] Scene Number Input | Scene Number control | 1 Byte | 18.1 scene control | CW |
| 6 | [Ch1] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CRT |
| 7 | [Ch1] Actual Dimming Value Feedback | Dimming value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | [Ch1] Dimming Speed (from 1% to 100%) | Dimming Speed | 1 Byte | 5.1 percentage (0..100%) | CW |
| 9 | [Ch1] Overload Alarm | 1 = Alarm; 0 = No Alarm | 1 Bit | 1.5 alarm | CRWTUI |
| 10 | [Ch1] Disable Channel | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 11 | libre | libre | 1 Bit | 1.5 alarm | CW |
| 12 | libre | libre | 1 Bit | 1.5 alarm | CW |
| 13 | libre | libre | 1 Bit | 1.3 enable | CW |
| 14 | [Ch1] free future use | free future use | 1 Bit | 1.1 switch | CW |
| 15 | [Ch1] free future use | free future use | 1 Bit | 1.3 enable | CW |
| 16 | [Ch2] Switch Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 17 | [Ch2] Relative Control Input | Dimming control | 4 Bit | 3.7 dimming control | CW |
| 18 | [Ch2] Absolute Dimming Input | Dimming value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 19 | [Ch2] Timer Start/Stop Input | 1 = Start, 0 = Stop | 1 Bit | 1.1 switch | CW |
| 20 | [Ch2] Forced Input | Forced control | 2 Bit | 2.3 enable control | CW |
| 21 | [Ch2] Scene Number Input | Scene Number control | 1 Byte | 18.1 scene control | CW |
| 22 | [Ch2] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CRT |
| 23 | [Ch2] Actual Dimming Value Feedback | Dimming value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 24 | [Ch2] Dimming Speed (from 1% to 100%) | Dimming Speed | 1 Byte | 5.1 percentage (0..100%) | CW |
| 25 | [Ch2] Overload Alarm | 1 = Alarm; 0 = No Alarm | 1 Bit | 1.5 alarm | CW |
| 26 | [Ch2] Disable Channel | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 27 | libre | libre | 1 Bit | 1.5 alarm | CW |
| 28 | libre | libre | 1 Bit | 1.5 alarm | CW |
| 29 | libre | libre | 1 Bit | 1.3 enable | CW |
| 32 | [Ch3] Switch Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 33 | [Ch3] Relative Control Input | Dimming control | 4 Bit | 3.7 dimming control | CW |
| 34 | [Ch3] Absolute Dimming Input | Dimming value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 35 | [Ch3] Timer Start/Stop Input | 1 = Start, 0 = Stop | 1 Bit | 1.1 switch | CW |
| 36 | [Ch3] Forced Input | Forced control | 2 Bit | 2.3 enable control | CW |
| 37 | [Ch3] Scene Number Input | Scene Number control | 1 Byte | 18.1 scene control | CW |
| 38 | [Ch3] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CRT |
| 39 | [Ch3] Actual Dimming Value Feedback | Dimming value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 40 | [Ch3] Dimming Speed (from 1% to 100%) | Dimming Speed | 1 Byte | 5.1 percentage (0..100%) | CW |
| 41 | [Ch3] Overload Alarm | 1 = Alarm; 0 = No Alarm | 1 Bit | 1.5 alarm | CW |
| 42 | [Ch3] Disable Channel | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 43 | libre | libre | 1 Bit | 1.5 alarm | CW |
| 44 | libre | libre | 1 Bit | 1.5 alarm | CW |
| 45 | libre | libre | 1 Bit | 1.3 enable | CW |
| 48 | [Ch4] Switch Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 49 | [Ch4] Relative Control Input | Dimming control | 4 Bit | 3.7 dimming control | CW |
| 50 | [Ch4] Absolute Dimming Input | Dimming value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 51 | [Ch4] Timer Start/Stop Input | 1 = Start, 0 = Stop | 1 Bit | 1.1 switch | CW |
| 52 | [Ch4] Forced Input | Forced control | 2 Bit | 2.3 enable control | CW |
| 53 | [Ch4] Scene Number Input | Scene Number control | 1 Byte | 18.1 scene control | CW |
| 54 | [Ch4] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CRT |
| 55 | [Ch4] Actual Dimming Value Feedback | Dimming value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 56 | [Ch4] Dimming Speed (from 1% to 100%) | Dimming Speed | 1 Byte | 5.1 percentage (0..100%) | CW |
| 57 | [Ch4] Overload Alarm | 1 = Alarm; 0 = No Alarm | 1 Bit | 1.5 alarm | CW |
| 58 | [Ch4] Disable Channel | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 59 | libre | libre | 1 Bit | 1.5 alarm | CW |
| 60 | libre | libre | 1 Bit | 1.5 alarm | CW |
| 61 | libre | libre | 1 Bit | 1.3 enable | CW |
| 64 | Sequence 1 | 1 = Start; 0 = Stop | 1 Bit | 1.1 switch | CW |
| 65 | Sequence 2 | 1 = Start; 0 = Stop | 1 Bit | 1.1 switch | CW |
| 66 | Sequence 3 | 1 = Start; 0 = Stop | 1 Bit | 1.1 switch | CW |
| 67 | Sequence 4 | 1 = Start; 0 = Stop | 1 Bit | 1.1 switch | CW |
| 68 | Sequence 5 | 1 = Start; 0 = Stop | 1 Bit | 1.1 switch | CW |
| 69 | Sequence 1 Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CRWTI |
| 70 | Sequence 2 Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CRWTI |
| 71 | Sequence 3 Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CRWTI |
| 72 | Sequence 4 Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CRWTI |
| 73 | Sequence 5 Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CRWTI |
| 74 | Dimmer Temperature | Temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 75 | High Temperature Alarm | 1 = High Temperature | 1 Bit | 1.5 alarm | CR |
| 76 | Critical Temperature Alarm | 1 = Critical Temperature | 1 Bit | 1.5 alarm | CR |
Parameters (52)
| Parameter | Type | Default |
|---|---|---|
| Timer Time Delay (sec) | list | 60 |
| Pre-warning in Timer function (sec) | list | 0 |
| Minimum Brightness (%) | unsignedInt 3…96 | 3 |
| Maximum Brightness (%) | unsignedInt 0…100 | 99 |
| Soft Turn-On Time (x 0,1sec) | unsignedInt 1…65535 | 1 |
| Soft Turn-Off Time (x 0,1sec) | unsignedInt 1…65535 | 3 |
| Switch-On Mode | list | Switch-On at Last brightness |
| Switch-On Brightness Value (%) | unsignedInt 0…100 | 3 |
| Action after power supply failure | list | Switch-On |
| Brightness after power supply failure (%) | unsignedInt 0…100 | 100 |
| Switch-On ramp time (sec) | unsignedInt 1…65535 | 1 |
| ON time (sec) | unsignedInt 1…65535 | 1 |
| Switch-Off ramp time (sec) | unsignedInt 1…65535 | 1 |
| OFF time (sec) | unsignedInt 1…65535 | 1 |
| Number of Scenes attended | list | All Scenes |
| Scene Number 1 | list | Scene 1 |
| Scene Number 2 | list | Scene 2 |
| Scene Number 3 | list | Scene 3 |
| Scene Number 4 | list | Scene 4 |
| Scene Number 5 | list | Scene 5 |
| Scene 1 Brightness (%) | unsignedInt 0…100 | 100 |
| Scene 2 Brightness (%) | unsignedInt 0…100 | 100 |
| Scene 3 Brightness (%) | unsignedInt 0…100 | 100 |
| Scene 4 Brightness (%) | unsignedInt 0…100 | 100 |
| Scene 5 Brightness (%) | unsignedInt 0…100 | 100 |
| Dimming Speed (from 0% to 100% x 0,1sec) | unsignedInt 1…4864 | 20 |
| Behavior on incoming Dimming Value | list | Go right away |
| OFF value (%) | unsignedInt 0…100 | 2 |
| ETS_UPDATE | unsignedInt 0…255 | 16 |
| Switch-On mode | list | Switch-On at Last brightness |
| Scene Number 3 | list | Scene 1 |
| Enable Sequence 1 | list | No |
| Enable Sequence 2 | list | No |
| Enable Sequence 3 | list | No |
| Enable Sequence 4 | list | No |
| Enable Sequence 5 | list | No |
| Do this Sequence | list | Once |
| Number of Steps | list | One Step |
| Channel 1 | unsignedInt 0…100 | 100 |
| Channel 2 | unsignedInt 0…100 | 100 |
| Channel 3 | unsignedInt 0…100 | 100 |
| Channel 4 | unsignedInt 0…100 | 100 |
| Step Time (x 0,1sec) | unsignedInt 1…65535 | 100 |
| Operating Mode | list | 4-channel Dimmer |
| Dimming type | list | Leading-edge |
| Ripple Filter State | list | Filter Deactivated |
| Action after power supply failure | list | Switch-Off |
| Action after power supply failure | list | Sequence 1 |
| Dimming type Channel 1 | list | Leading-edge |
| Dimming type Channel 2 | list | Leading-edge |
| Dimming type Channel 3 | list | Leading-edge |
| Dimming type Channel 4 | list | Leading-edge |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| REKNT004 0.2 latest | $00C0 | E0BC | 2026-11-25 | 102 KB | Download |
About this file
This is the official ETS product database for the Dinuy 4-channel RLC+LED Dimmer (REKNT004), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Dinuy
- KNX IP Interface Secure CO KNT IPI CO KNT IPI
- KNX IP Router Secure CO KNT IPR CO KNT IPR
- KNX Line Coupler Secure CO KNT LC1 CO KNT LC1
- KNX IP Router Secure CO KNX IPR CO KNX IPR
- KNX Line Coupler Secure CO KNX LC2 CO KNX LC2
- Coin-/Token-operated Timer CT KNT XXX
- Movement Detector DM KNT XXX
- 4-INPUT/OUTPUT BINARY INTERFACE EM KNT 001
- 4-FOLD ANALOG/BINARY INTERFACE EM KNT 002
- 8-channel Binary Input EM KNT 003
- 2-/4-/8- Input/Output Analog/Binary Interface EM KNX 0XX
- FA KNT 001 FA KNT 001