| 1 | [In1] Disable Input | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 1 | [In1] Disable Temperature Functionality | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 2 | [In1] Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 2 | [In1] Stop / Step | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CT |
| 2 | [In1] Bit value on press | Bit value | 1 Bit | 1.11 state | CT |
| 2 | [In1] 2 Bits value on press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 2 | [In1] Scene Control 8 Bits | Scene Control | 1 Byte | 18.1 scene control | CT |
| 2 | [In1] 2 Bytes signed value on press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 2 | [In1] 2 Bytes floating value on press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 2 | [In1] Byte value on press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 2 | [In1] 4 Bytes value on press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 2 | [In1] Temperature value Output | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 2 | [In1] Counter direction | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 2 | [In1] Scene 1 Bit | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.11 state | CT |
| 2 | [In1] 2 Bytes value on press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 3 | [In1] Long Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 3 | [In1] Reset Counter | 0 = No action, 1 = Reset | 1 Bit | 1.15 reset | CW |
| 3 | [In1] Switch 2 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 3 | [In1] Save Scene | 0 = No action, 1 = Save Scene | 1 Bit | 1.3 enable | CW |
| 3 | [In1] 4 Bytes value on Long press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 3 | [In1] 2 Bytes floating value on Long press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 3 | [In1] 2 Bytes signed value on Long press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 3 | [In1] Bit value on Long press | Bit value | 1 Bit | 1.11 state | CT |
| 3 | [In1] 2 Bits value on Long press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 3 | [In1] Sensor not connected | 0 = Sensor Ok, 1 = Sensor not connected | 1 Bit | 1.11 state | CT |
| 3 | [In1] Byte value on Long press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 3 | [In1] 2 Bytes value on Long press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 3 | [In1] Dimming Control | Dimming Control | 4 Bit | 3.7 dimming control | CT |
| 3 | [In1] Move | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 4 | [In1] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 4 | [In1] Request Counter | 1 = Trigger | 1 Bit | 1.17 trigger | CW |
| 4 | [In1] Over-Heating Output | 1 = Over-Heating, 0 = No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 4 | [In1] Switch 3 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 5 | [In1] Long Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 5 | [In1] Counter 32 Bits | Counter (0-4.294.967.295) | 4 Bytes | 13.1 counter pulses (signed) | CT |
| 5 | [In1] Over-Cooling Output | 1 = Over-Cooling, 0 = No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 5 | [In1] Counter 8 Bits | Counter (0-255) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 5 | [In1] Counter 16 Bits | Counter (0-65535) | 2 Bytes | 7.1 pulses | CT |
| 5 | [In1] Switch 4 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 6 | [In1] Switch 5 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 7 | [In1] Increase/Decrease | 0 = Increase, 1 = Decrease | 1 Bit | 1.8 up/down | CW |
| 7 | [In1] Save Scene | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.3 enable | CT |
| 8 | [In2] Disable Input | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 8 | [In2] Disable Temperature Functionality | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 9 | [In2] Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 9 | [In2] 4 Bytes value on press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 9 | [In2] 2 Bytes signed value on press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 9 | [In2] Temperature value Output | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 9 | [In2] Stop / Step | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CT |
| 9 | [In2] 2 Bits value on press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 9 | [In2] 2 Bytes value on press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 9 | [In2] Bit value on press | Bit value | 1 Bit | 1.11 state | CT |
| 9 | [In2] Counter direction | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 9 | [In2] Byte value on press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 9 | [In2] 2 Bytes floating value on press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 9 | [In2] Scene 1 Bit | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.11 state | CT |
| 9 | [In2] Scene Control 8 Bits | Scene Control | 1 Byte | 18.1 scene control | CT |
| 10 | [In2] Long Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 10 | [In2] Save Scene | 0 = No action, 1 = Save Scene | 1 Bit | 1.3 enable | CW |
| 10 | [In2] Switch 2 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 10 | [In2] Bit value on Long press | Bit value | 1 Bit | 1.11 state | CT |
| 10 | [In2] Reset Counter | 0 = No action, 1 = Reset | 1 Bit | 1.15 reset | CW |
| 10 | [In2] Move | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 10 | [In2] 2 Bytes floating value on Long press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 10 | [In2] 2 Bytes signed value on Long press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 10 | [In2] 4 Bytes value on Long press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 10 | [In2] 2 Bits value on Long press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 10 | [In2] Sensor not connected Output | 0 = Sensor Ok, 1 = Sensor not connected | 1 Bit | 1.11 state | CT |
| 10 | [In2] Byte value on Long press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 10 | [In2] 2 Bytes value on Long press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 10 | [In2] Dimming Control | Dimming Control | 4 Bit | 3.7 dimming control | CT |
| 11 | [In2] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 11 | [In2] Switch 3 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 11 | [In2] Request Counter | 1 = Trigger | 1 Bit | 1.17 trigger | CW |
| 11 | [In2] Over-Heating Output | 1 = Over-Heating, 0 = No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 12 | [In2] Long Switch Feeback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 12 | [In2] Counter 16 Bits | Counter (0-65535) | 2 Bytes | 7.1 pulses | CT |
| 12 | [In2] Switch 4 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 12 | [In2] Over-Cooling Output | 1 = Over-Cooling, 0 = No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 12 | [In2] Counter 8 Bits | Counter (0-255) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 12 | [In2] Counter 32 Bits | Counter (0-4.294.967.295) | 4 Bytes | 13.1 counter pulses (signed) | CT |
| 13 | [In2] Switch 5 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 14 | [In2] Save Scene | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.3 enable | CT |
| 14 | [In2] Increase/Decrease | 0 = Increase, 1 = Decrease | 1 Bit | 1.8 up/down | CW |
| 15 | [In3] Disable Input | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 15 | [In3] Disable Temperature Functionality | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 16 | [In3] Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 16 | [In3] Scene Control 8 Bits | Scene Control | 1 Byte | 18.1 scene control | CT |
| 16 | [In3] Temperature value Output | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 16 | [In3] 2 Bytes floating value on press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 16 | [In3] Byte value on press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 16 | [In3] Counter direction | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 16 | [In3] Bit value on press | Bit value | 1 Bit | 1.11 state | CT |
| 16 | [In3] 2 Bytes value on press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 16 | [In3] 2 Bits value on press | 2 Bits value | 2 Bit | 2.1 switch control | T |
| 16 | [In3] Stop / Step | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CT |
| 16 | [In3] 2 Bytes signed value on press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 16 | [In3] Scene 1 Bit | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.11 state | CT |
| 16 | [In3] 4 Bytes value on press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 17 | [In3] 2 Bytes floating value on Long press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 17 | [In3] Switch 2 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 17 | [In3] 2 Bytes signed value on Long press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 17 | [In3] Save Scene | 0 = No action, 1 = Save Scene | 1 Bit | 1.3 enable | CW |
| 17 | [In3] Move | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 17 | [In3] Reset Counter | 0 = No action, 1 = Reset | 1 Bit | 1.15 reset | CW |
| 17 | [In3] 2 Bits value on Long press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 17 | [In3] Sensor not connected Output | 0 = Sensor Ok, 1 = Sensor not connected | 1 Bit | 1.11 state | CT |
| 17 | [In3] Byte value on Long press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 17 | [In3] 2 Bytes value on Long press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 17 | [In3] Dimming Control | Dimming Control | 4 Bit | 3.7 dimming control | CT |
| 17 | [In3] Switch Long | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 17 | [In3] Bit value on Long press | Bit value | 1 Bit | 1.11 state | CT |
| 17 | [In3] 4 Bytes value on Long press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 18 | [In3] Request Counter | 1 = Trigger | 1 Bit | 1.17 trigger | CW |
| 18 | [In3] Over-Heating Output | 1 = Over-Heating, 0 = No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 18 | [In3] Switch 3 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 18 | [In3] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 19 | [In3] Switch 4 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 19 | [In3] Over-Cooling Output | 1 = Over-Cooling, 0 = No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 19 | [In3] Counter 8 Bits | Counter (0-255) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 19 | [In3] Counter 32 Bits | Counter (0-4.294.967.295) | 4 Bytes | 13.1 counter pulses (signed) | CT |
| 19 | [In3] Long Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 19 | [In3] Counter 16 Bits | Counter (0-65535) | 2 Bytes | 7.1 pulses | CT |
| 20 | [In3] Switch 5 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 21 | [In3] Increase/Decrease | 0 = Increase, 1 = Decrease | 1 Bit | 1.8 up/down | CW |
| 21 | [In3] Save Scene | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.3 enable | CT |
| 22 | [In4] Disable Input | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 22 | [In4] Disable Temperature Functionality | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 23 | [In4] Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 23 | [In4] 2 Bytes floating value on press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 23 | [In4] Scene 1 Bit | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.11 state | CT |
| 23 | [In4] Counter direction | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 23 | [In4] 4 Bytes value on press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 23 | [In4] Temperature value Output | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 23 | [In4] 2 Bytes value on press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 23 | [In4] 2 Bits value on press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 23 | [In4] Stop / Step | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CT |
| 23 | [In4] 2 Bytes signed value on press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 23 | [In4] Bit value on press | Bit value | 1 Bit | 1.11 state | CT |
| 23 | [In4] Byte value on press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 23 | [In4] Scene Control 8 Bits | Scene Control | 1 Byte | 18.1 scene control | CT |
| 24 | [In4] 4 Bytes value on Long press | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 24 | [In4] 2 Bytes floating value on Long press | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 24 | [In4] Move | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 24 | [In4] 2 Bytes signed value on Long press | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 24 | [In4] Reset Counter | 0 = No action, 1 = Reset | 1 Bit | 1.15 reset | CW |
| 24 | [In4] 2 Bits value on Long press | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 24 | [In4] Sensor not connected Output | 0 = Sensor Ok, 1 = Sensor not connected | 1 Bit | 1.11 state | CT |
| 24 | [In4] Byte value on Long press | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 24 | [In4] 2 Bytes value on Long press | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 24 | [In4] Dimming Control | Dimming Control | 4 Bit | 3.7 dimming control | CT |
| 24 | [In4] Long Switch | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 24 | [In4] Bit value on Long press | Bit value | 1 Bit | 1.11 state | CT |
| 24 | [In4] Switch 2 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 24 | [In4] Save Scene | 0 = No action, 1 = Save Scene | 1 Bit | 1.3 enable | CW |
| 25 | [In4] Switch 3 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 25 | [In4] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 25 | [In4] Over-Heating Output | 1 = Over-Heating, 0 = No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 25 | [In4] Request Counter | 1 = Trigger | 1 Bit | 1.17 trigger | CW |
| 26 | [In4] Counter 32 Bits | Counter (0-4.294.967.295) | 4 Bytes | 13.1 counter pulses (signed) | CT |
| 26 | [In4] Over-Cooling Output | 1 = Over-Cooling, 0 = No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 26 | [In4] Counter 8 Bits | Counter (0-255) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 26 | [In4] Long Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 26 | [In4] Switch 4 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 26 | [In4] Counter 16 Bits | Counter (0-65535) | 2 Bytes | 7.1 pulses | CT |
| 27 | [In4] Switch 5 | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 28 | [In4] Save Scene | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.3 enable | CT |
| 28 | [In4] Increase/Decrease | 0 = Increase, 1 = Decrease | 1 Bit | 1.8 up/down | CW |
| 30 | [Out1] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 31 | [Out1] Switch On/Off | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 32 | [Out1] Forced positioning 1 Bit | 1 = Forced, 0 = Not Forced | 1 Bit | 1.1 switch | CW |
| 32 | [Out1] Forced positioning 2 Bits | 2 Bits value | 2 Bit | 2.1 switch control | CW |
| 34 | [Out1] Change Threshold value | 1 Byte value | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 34 | [Out1] Change Threshold value | 2 Bytes value | 2 Bytes | 7.1 pulses | CW |
| 35 | [Out1] Threshold Input | 1 Byte value | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 35 | [Out1] Threshold Input | 2 Bytes value | 2 Bytes | 7.1 pulses | CW |
| 37 | [Out1] Logical connection 1 | 1 = True, 0 = False | 1 Bit | 1.2 boolean | CW |
| 38 | [Out1] Logical connection 2 | 1 = True, 0 = False | 1 Bit | 1.2 boolean | CW |
| 39 | [Out1] Scene | Scene Control | 1 Byte | 18.1 scene control | CW |
| 40 | [Out1] Set Preset 1/2 | Telegram 0 --> Set Preset 1, Telegram 1 --> Set Preset 2 | 1 Bit | 1.1 switch | CW |
| 41 | [Out1] Call Preset 1/2 | Telegram 0 --> Call Preset 1, Telegram 1 --> Call Preset 2 | 1 Bit | 1.3 enable | CW |
| 42 | [Out1] Time Switch | 1 = Timer On | 1 Bit | 1.10 start/stop | CW |
| 43 | [Out1] Staircase lighting Pre-warning | 1 = Pre-warning, 0 = No Pre-warning | 1 Bit | 1.1 switch | CT |
| 44 | [Out1] Length of staircase light (sec) | 2 Bytes value | 2 Bytes | 7.5 time (s) | CW |
| 45 | [Out1] Permanent ON | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 46 | [Out1] Disable Time Function | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 50 | [Out2] Switch Feedback | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 51 | [Out2] Switch On/Off | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 52 | [Out2] Forced positioning 1-Bit | 1 = Forced, 0 = Not Forced | 1 Bit | 1.1 switch | CW |
| 52 | [Out2] Forced positioning 2 Bits | 2 Bits value | 2 Bit | 2.1 switch control | CW |
| 54 | [Out2] Change Threshold value | 1 Byte value | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 54 | [Out2] Change Threshold value | 2 Bytes value | 2 Bytes | 7.1 pulses | CW |
| 55 | [Out2] Threshold Input | 1 Byte value | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 55 | [Out2] Threshold Input | 2 Bytes value | 2 Bytes | 7.1 pulses | CW |
| 57 | [Out2] Logical connection 1 | 1 = True, 0 = False | 1 Bit | 1.2 boolean | CW |
| 58 | [Out2] Logical connection 2 | 1 = True, 0 = False | 1 Bit | 1.2 boolean | CW |
| 59 | [Out2] Scene | Scene Control | 1 Byte | 18.1 scene control | CW |
| 60 | [Out2] Set Preset 1/2 | Telegram 0 --> Set Preset 1, Telegram 1 --> Set Preset 2 | 1 Bit | 1.1 switch | CW |
| 61 | [Out2] Call Preset 1/2 | Telegram 0 --> Call Preset 1, Telegram 1 --> Call Preset 2 | 1 Bit | 1.3 enable | CW |
| 62 | [Out2] Time Switch | 1 = Timer On | 1 Bit | 1.10 start/stop | CW |
| 63 | [Out2] Stairca lighting Pre-warning | 1 = Pre-warning, 0 = No pre-warning | 1 Bit | 1.1 switch | CT |
| 64 | [Out2] Length of staircase light (sec) | 2 Bytes value | 2 Bytes | 7.5 time (s) | CW |
| 65 | [Out2] Permanent ON | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 66 | [Out2] Disable Time Function | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 70 | [Out] Blind Move Up/Down | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 70 | [Out] Roller Move Up/Down | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 70 | [Out] Louver Move Up/Down | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 71 | [Out] Blind Stop / Step Up/Down | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CW |
| 71 | [Out] Roller Stop / Step Up/Down | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CW |
| 71 | [Out] Louver Stop / Step Up/Down | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CW |
| 72 | [Out] Forced Input | 2 Bits control | 2 Bit | 2.1 switch control | CW |
| 73 | [Out] Wind Alarm 1 | 1 = Alarm, 0 = No Alarm | 1 Bit | 1.5 alarm | CW |
| 74 | [Out] Wind Alarm 2 | 1 = Alarm, 0 = No Alarm | 1 Bit | 1.5 alarm | CW |
| 75 | [Out] Wind Alarm 3 | 1 = Alarm, 0 = No Alarm | 1 Bit | 1.5 alarm | CW |
| 76 | [Out] Rain Alarm | 1 = Alarm, 0 = No Alarm | 1 Bit | 1.5 alarm | CW |
| 77 | [Out] Frost Alarm | 1 = Alarm, 0 = No Alarm | 1 Bit | 1.5 alarm | CW |
| 78 | [Out] Scene Input | Scene Control | 1 Byte | 18.1 scene control | CW |
| 79 | [Out] Movement Feedback | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 80 | [Out] Blind position Input | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 80 | [Out] Louver position Input | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 80 | [Out] Roller position Input | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 81 | [Out] Slats position Input | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 82 | [Out] Blind position Feedback | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 82 | [Out] Roller position Feedback | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 82 | [Out] Louver position Feedback | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 83 | [Out] Slats position Feedback | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 84 | [Out] Lux level Input | Lux value | 2 Bytes | 9.4 lux (Lux) | CW |
| 84 | [Out] Sun Protection Input | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 85 | [Out] Sun Protection position Input | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 90 | [T1] On/Off Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 91 | [T1] On/Off Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 92 | [T1] Set-point Feedback | Current Set-point | 2 Bytes | 9.1 temperature (°C) | CT |
| 93 | [T1] Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 93 | [T1] Comfort Set-point Input | Comfort Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 94 | [T1] Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 94 | [T1] Output | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 94 | [T1] Heating Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 94 | [T1] Heating Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 94 | [T1] Heating Output | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 94 | [T1] Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 95 | [T1] Cooling Output | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 95 | [T1] Cooling Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 95 | [T1] Cooling Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 96 | [T1] Temperature Sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 97 | [T1] Temperature Sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 98 | [T1] Special mode Feedback | 2 Bytes mode Feedback | 2 Bytes | 22.101 RHCC status | CT |
| 99 | [T1] Special mode Input 1 Byte | 1 Byte mode HVAC | 1 Byte | 20.102 HVAC mode | CW |
| 100 | [T1] Special mode Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 101 | [T1] Special mode Stand-by | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 102 | [T1] Special mode Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 103 | [T1] Special mode Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 104 | [T1] Heating or Cooling mode Status | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CT |
| 105 | [T1] Heating or Cooling mode | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CW |
| 106 | [T1] Window Alarm 1 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 107 | [T1] Window Alarm 2 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 108 | [T1] Window Alarm 3 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 109 | [T1] Window Alarm 4 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 110 | [T2] On/Off Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 111 | [T2] On/Off Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 112 | [T2] Set-point Feedback | Current Set-point | 2 Bytes | 9.1 temperature (°C) | CT |
| 113 | [T2] Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 113 | [T2] Comfort Set-point Input | Comfort Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 114 | [T2] Heating Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 114 | [T2] Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 114 | [T2] Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 114 | [T2] Output | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 114 | [T2] Heating Output | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 114 | [T2] Heating Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 115 | [T2] Cooling Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 115 | [T2] Cooling Output | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 115 | [T2] Cooling Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 116 | [T2] Temperature sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 117 | [T2] Temperature sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 118 | [T2] Special mode Feedback | 2 Bytes mode Feedback | 2 Bytes | 22.101 RHCC status | CT |
| 119 | [T2] Special mode Input 1 Byte | 1 Byte mode HVAC | 1 Byte | 20.102 HVAC mode | CW |
| 120 | [T2] Special mode Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 121 | [T2] Special mode Stand-by | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 122 | [T2] Special mode Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 123 | [T2] Special mode Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 124 | [T2] Heating or Cooling mode Status | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CT |
| 125 | [T2] Heating or Cooling mode | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CW |
| 126 | [T2] Window Alarm 1 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 127 | [T2] Window Alarm 2 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 128 | [T2] Window Alarm 3 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 129 | [T2] Window Alarm 4 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 130 | [T3] On/Off Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 131 | [T3] On/Off Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 132 | [T3] Set-point Feedback | Current Set-point | 2 Bytes | 9.1 temperature (°C) | CT |
| 133 | [T3] Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 133 | [T3] Comfort set-point Input | Comfort Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 134 | [T3] Heating Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 134 | [T3] Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 134 | [T3] Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 134 | [T3] Output | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 134 | [T3] Heating Output | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 134 | [T3] Heating Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 135 | [T3] Cooling Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 135 | [T3] Cooling Output | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 135 | [T3] Cooling Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 136 | [T3] Temperature Sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 137 | [T3] Temperature Sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 138 | [T3] Special mode Feedback | 2 Bytes mode Feedback | 2 Bytes | 22.101 RHCC status | CT |
| 139 | [T3] Special mode Input 1 byte | 1 Byte mode HVAC | 1 Byte | 20.102 HVAC mode | CW |
| 140 | [T3] Special mode Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 141 | [T3] Special mode Stand-by | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 142 | [T3] Special mode Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 143 | [T3] Special mode Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 144 | [T3] Heating or Cooling mode Status | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CT |
| 145 | [T3] Heating or Cooling mode | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CW |
| 146 | [T3] Window Alarm 1 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 147 | [T3] Window Alarm 2 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 148 | [T3] Window Alarm 3 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 149 | [T3] Window Alarm 4 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 150 | [T4] On/Off Feedback | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 151 | [T4] On/Off Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 152 | [T4] Set-point Feedback | Current Set-point | 2 Bytes | 9.1 temperature (°C) | CT |
| 153 | [T4] Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 153 | [T4] Comfort set-point Input | Comfort Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 154 | [T4] Heating Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 154 | [T4] Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 154 | [T4] Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 154 | [T4] Output | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 154 | [T4] Heating Output | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 154 | [T4] Heating Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 155 | [T4] Cooling Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 155 | [T4] Cooling Output | Output (2-point with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 155 | [T4] Cooling Output | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 156 | [T4] Temperature Sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 157 | [T4] Temperature Sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 158 | [T4] Special mode Feedback | 2 Bytes mode Feedback | 2 Bytes | 22.101 RHCC status | CT |
| 159 | [T4] Special mode Input 1 Byte | 1 Byte mode HVAC | 1 Byte | 20.102 HVAC mode | CW |
| 160 | [T4] Special mode Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 161 | [T4] Special mode Stand-by | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 162 | [T4] Special mode Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 163 | [T4] Special mode Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 164 | [T4] Heating or Cooling mode Status | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CT |
| 165 | [T4] Heating or Cooling mode | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CW |
| 166 | [T4] Window Alarm 1 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 167 | [T4] Window Alarm 2 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 168 | [T4] Window Alarm 3 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 169 | [T4] Window Alarm 4 Input | 0=No Alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |