| 1 | Control_On/Off [DPT_1.001 - 1bit] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRWU |
| 2 | Status_On/Off [DPT_1.001 - 1bit] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 3 | Control_Setpoint_Temperature [DPT_9.001 - 2byte] | (°C) | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 4 | Status_Setpoint_Temperature [DPT_9.001 - 2byte] | (°C) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 5 | Control_Mode [DPT_20.105 - 1byte] | 0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry | 1 Byte | 20.105 HVAC control mode | CRWU |
| 5 | Control_Mode [DPT_20.105 - 1byte] | 0-Auto; 1-Heat; 3-Cool; 14-Dry | 1 Byte | 20.105 HVAC control mode | CRWU |
| 6 | Status_Mode [DPT_20.105 - 1byte] | 0-Auto; 1-Heat; 3-Cool; 9-Fan; 14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 6 | Status_Mode [DPT_20.105 - 1byte] | 0-Auto; 1-Heat; 3-Cool; 14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 7 | Control_Fan_Speed / 3 Speeds [DPT_5.100 - 1byte] | Speed Values: 1,2,3 | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 7 | Control_Fan_Speed / 3 Speeds [DPT_5.001 - 1byte] | Threshold: 50%,83% | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 7 | Control_Fan_Speed / 3 Speeds [DPT_5.100 - 1byte] | Speed Values: 0,1,2,3 | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 7 | Control_Fan_Speed / 3 Speeds [DPT_5.001 - 1byte] | 0-Auto; Threshold: 50%,83% | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 8 | Status_Fan_Speed / 3 Speeds [DPT_5.100 - 1byte] | Speed Values: 1,2,3 | 1 Byte | 5.100 fan stage (0..255) | CRT |
| 8 | Status_Fan_Speed / 3 Speeds [DPT_5.001 - 1byte] | 33%,67%,100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | Status_Fan_Speed / 3 Speeds [DPT_5.100 - 1byte] | Speed Values: 0,1,2,3 | 1 Byte | 5.100 fan stage (0..255) | CRT |
| 8 | Status_Fan_Speed / 3 Speeds [DPT_5.001 - 1byte] | 0-Auto; 33%,67%,100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 9 | Control_Vanes_Up-Down [DPT_5.010 - 1byte] | 0-Swing Off; 1-Swing On | 1 Byte | 5.10 counter pulses (0..255) | CRWU |
| 10 | Status_Vanes_Up-Down [DPT_5.010 - 1byte] | 0-Swing Off; 1-Swing On | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 11 | Control_AC_Return_Temp [DPT_9.001 - 2byte] | (°C) | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 12 | Status_AC_Return_Temp [DPT_9.001 - 2byte] | (°C) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 13 | Status_Error_Code [2byte] | 0-No Error / Any other see man. | 2 Bytes | | CRT |
| 14 | Control_Mode_Cool/Heat [DPT_1.100 - 1bit] | 0-Cool; 1-Heat | 1 Bit | 1.100 cooling/heating | CRWU |
| 14 | Control_Mode_Heat/Cool [DPT_1.100 - 1bit] | 0-Heat; 1-Cool | 1 Bit | 1.100 cooling/heating | CRWU |
| 15 | Status_Mode_Cool/Heat [DPT_1.100 - 1bit] | 0-Cool; 1-Heat | 1 Bit | 1.100 cooling/heating | CRT |
| 15 | Status_Mode_Heat/Cool [DPT_1.100 - 1bit] | 0-Heat; 1-Cool | 1 Bit | 1.100 cooling/heating | CRT |
| 16 | Input_1 [DPT_1.001 -1bit] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 17 | Input_2 [DPT_1.001 -1bit] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 18 | Control_Mode_Auto [DPT_1.002 - 1bit] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CRWU |
| 19 | Status_Mode_Auto [DPT_1.002 - 1bit] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 20 | Control_Mode_Heat [DPT_1.002 - 1bit] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CRWU |
| 21 | Status_Mode_Heat [DPT_1.002 - 1bit] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 22 | Control_Mode_Cool [DPT_1.002 - 1bit] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CRWU |
| 23 | Status_Mode_Cool [DPT_1.002 - 1bit] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 24 | Control_Mode_Fan [DPT_1.002 - 1bit] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CRWU |
| 25 | Status_Mode_Fan [DPT_1.002 - 1bit] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 26 | Control_Mode_Dry [DPT_1.002 - 1bit] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CRWU |
| 27 | Status_Mode_Dry [DPT_1.002 - 1bit] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 28 | Control_Fan_Speed_Manual/Auto [DPT_1.002 -1bit] | 0-Manual; 1-Auto | 1 Bit | 1.2 boolean | CRWU |
| 29 | Status_Fan_Speed_Manual/Auto [DPT_1.002 -1bit] | 0-Manual; 1-Auto | 1 Bit | 1.2 boolean | CRT |
| 30 | Control_Fan_Speed_1 [DPT_1.002 - 1bit] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CRWU |
| 31 | Status_Fan_Speed_1 [DPT_1.002 - 1bit] | 1-Fan Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 32 | Control_Fan_Speed_2 [DPT_1.002 - 1bit] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CRWU |
| 33 | Status_Fan_Speed_2 [DPT_1.002 - 1bit] | 1-Fan Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 34 | Control_Fan_Speed_3 [DPT_1.002 - 1bit] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CRWU |
| 35 | Status_Fan_Speed_3 [DPT_1.002 - 1bit] | 1-Fan Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 36 | Control_Turbo_Mode[DPT_1.002 - 1bit] | 0-Turbo Off; 1-Turbo On | 1 Bit | 1.2 boolean | CRWU |
| 37 | Status_Turbo_Mode[DPT_1.002 - 1bit] | 0-Turbo Off; 1-Turbo On | 1 Bit | 1.2 boolean | CRT |
| 38 | Control_Windfree [DPT_1.002 - 1bit] | 0-Windfree Off; 1-Windfree On | 1 Bit | 1.2 boolean | CRWU |
| 39 | Status_Windfree [DPT_1.002 - 1bit] | 0-Windfree Off; 1-Windfree On | 1 Bit | 1.2 boolean | CRT |
| 40 | Control_Fan_Speed -/+ [DPT_1.007 - 1bit] | 0-Decrease; 1-Increase | 1 Bit | 1.7 step | CRWU |
| 40 | Control_Fan_Speed +/- [DPT_1.008 - 1bit] | 0-Up; 1-Down | 1 Bit | 1.8 up/down | CRWU |
| 41 | Error_Code/Alarm [DPT_1.005 - 1bit] | 0-No Error | 1 Bit | 1.5 alarm | CRT |
| 42 | Control_Vanes_Up/Down_Swing [DPT_1.002 - 1bit] | 0-Swing Off; 1-Swing On | 1 Bit | 1.2 boolean | CRWU |
| 43 | Status_Vanes_Up/Down_Swing [DPT_1.002 - 1bit] | 0-Swing Off; 1-Swing On | 1 Bit | 1.2 boolean | CRT |