KNX Database
Core Smart Home 0000010001 Mitsubishi Electric AC Gateway

Mitsubishi Electric AC Gateway 0000010001

Core Smart Home · Order number 0000010001 · AC Gateways

Mitsubishi Electric AC Gateway

Download .knxprod CoreMEACInt_V3 0.1 · 113 KB

Product

ManufacturerCore Smart Home
Product nameMitsubishi Electric AC Gateway
Order number0000010001
Product textCore_MEACInt_V3
HardwareCore_MEACInt_V3
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2022-04-21
Languagesen-US
Catalog entryM-0228_H-022800010001-0_HP-F023-01-2387_CI-0000010001-1
Fingerprint2387
SHA-2564766e282e1046c693a0d80e93ddf0daa3ec2c4cf6242e61a2013b234186083a2
First seen2026-11-25
Markets59 markets

Application program: CoreMEACInt_V3 0.1

Application number$F023
Version0.1
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters27
Group objects63
Group objects (63)
NoNameFunctionSizeDPTFlags
1Control_On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRWU
2Status_On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
3Control_Setpoint_Temperature [DPT_9.001 - 2byte](°C)2 Bytes9.1 temperature (°C)CRWU
4Status_Setpoint_Temperature [DPT_9.001 - 2byte](°C)2 Bytes9.1 temperature (°C)CRT
5Control_Mode [DPT_20.105 -1byte]0-Aut;1-Heat;3-Coo;9-Fan;14-Dry1 Byte20.105 HVAC control modeCRWU
6Status_Mode [DPT_20.105 -1byte]0-Aut;1-Heat;3-Coo;9-Fan;14-Dry1 Byte20.105 HVAC control modeCRT
7Control_Fan_Speed / 2 Speeds [DPT_5.100 - 1byte]Speed Values;1,21 Byte5.100 fan stage (0..255)CRWU
7Control_Fan_Speed / 3 Speeds [DPT_5.100 - 1byte]Speed Values;1,2,31 Byte5.100 fan stage (0..255)CRWU
7Control_Fan_Speed / 4 Speeds [DPT_5.100 - 1byte]Speed Values;1,2,3,41 Byte5.100 fan stage (0..255)CRWU
7Control_Fan_Speed / 2 Speeds [DPT_5.001 -1byte]Threshold:75%1 Byte5.1 percentage (0..100%)CRWU
7Control_Fan_Speed / 3 Speeds [DPT_5.001 -1byte]Threshold:50%,83%1 Byte5.1 percentage (0..100%)CRWU
7Control_Fan_Speed / 4 Speeds [DPT_5.001 -1byte]Threshold:38%,63%,88%1 Byte5.1 percentage (0..100%)CRWU
7Control_Fan_Speed / 2 Speeds [DPT_5.100 - 1byte]Speed Values;0,1,21 Byte5.100 fan stage (0..255)CRWU
7Control_Fan_Speed / 3 Speeds [DPT_5.100 - 1byte]Speed Values;0,1,2,31 Byte5.100 fan stage (0..255)CRWU
7Control_Fan_Speed / 4 Speeds [DPT_5.100 - 1byte]Speed Values;0,1,2,3,41 Byte5.100 fan stage (0..255)CRWU
7Control_Fan_Speed / 2 Speeds [DPT_5.001 -1byte]0-Auto; Threshold:75%1 Byte5.1 percentage (0..100%)CRWU
7Control_Fan_Speed / 3 Speeds [DPT_5.001 -1byte]0-Auto; Threshold:50%,83%1 Byte5.1 percentage (0..100%)CRWU
7Control_Fan_Speed / 4 Speeds [DPT_5.001 -1byte]0-Auto; Threshold:38%,63%,88%1 Byte5.1 percentage (0..100%)CRWU
8Status_Fan_Speed / 2 Speeds [DPT_5.100 - 1byte]Speed Values;1,21 Byte5.100 fan stage (0..255)CRT
8Status_Fan_Speed / 3 Speeds [DPT_5.100 - 1byte]Speed Values;1,2,31 Byte5.100 fan stage (0..255)CRT
8Status_Fan_Speed / 4 Speeds [DPT_5.100 - 1byte]Speed Values;1,2,3,41 Byte5.100 fan stage (0..255)CRT
8Status_Fan_Speed / 2 Speeds [DPT_5.001 -1byte]50%,100%1 Byte5.1 percentage (0..100%)CRT
8Status_Fan_Speed / 3 Speeds [DPT_5.001 -1byte]33%,67%,100%1 Byte5.1 percentage (0..100%)CRT
8Status_Fan_Speed / 4 Speeds [DPT_5.001 -1byte]25%,50%,75%,100%1 Byte5.1 percentage (0..100%)CRT
8Status_Fan_Speed / 2 Speeds [DPT_5.100 - 1byte]Speed Values;0,1,21 Byte5.100 fan stage (0..255)CRT
8Status_Fan_Speed / 3 Speeds [DPT_5.100 - 1byte]Speed Values;0,1,2,31 Byte5.100 fan stage (0..255)CRT
8Status_Fan_Speed / 4 Speeds [DPT_5.100 - 1byte]Speed Values;0,1,2,3,41 Byte5.100 fan stage (0..255)CRT
8Status_Fan_Speed / 2 Speeds [DPT_5.001 -1byte]0-Auto; 50%,100%1 Byte5.1 percentage (0..100%)CRT
8Status_Fan_Speed / 3 Speeds [DPT_5.001 -1byte]0-Auto; 33%,67%,100%1 Byte5.1 percentage (0..100%)CRT
8Status_Fan_Speed / 4 Speeds [DPT_5.001 -1byte]0-Auto; 25%,50%,75%,100%1 Byte5.1 percentage (0..100%)CRT
9Control_Vanes Up-Down [DPT_5.010 - 1byte]1-Pos1;2-Pos2;3-Pos3;4-Pos4;5-Pos5;6-Swng1 Byte5.10 counter pulses (0..255)CRWU
10Status_Vanes Up-Down [DPT_5.010 - 1byte]1-Pos1;2-Pos2;3-Pos3;4-Pos4;5-Pos5;6-Swng1 Byte5.10 counter pulses (0..255)CRT
11Control_Vanes Left-Right [DPT_5.010 - 1byte]1-<<;2-<;3-||;4->;5->>;6-<>;7-~1 Byte5.10 counter pulses (0..255)CRWU
12Status_Vanes Left-Right [DPT_5.010 - 1byte]1-<<;2-<;3-||;4->;5->>;6-<>;7-~1 Byte5.10 counter pulses (0..255)CRT
13Control_AC_Return_Temp [DPT_9.001 - 2byte](°C)2 Bytes9.1 temperature (°C)CRWU
14Status_AC_Return_Temp [DPT_9.001 - 2byte](°C)2 Bytes9.1 temperature (°C)CRT
15Status_Error_Code [2byte]0-No Error / Any other see man.2 BytesCRT
16Control_Mode_Cool/Heat [DPT_1.100 - 1bit]0-Cool;1-Heat1 Bit1.100 cooling/heatingCRWU
17Status_Mode_Cool/Heat [DPT_1.100 - 1bit]0-Cool;1-Heat1 Bit1.100 cooling/heatingCRT
20Input 1 [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
21Input 2 [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
22Control_Mode_Auto [DPT_1.002 - 1bit]1-Set AUTO mode1 Bit1.2 booleanCRWU
23Status_Mode_Auto [DPT_1.002 - 1bit]1-AUTO mode is active1 Bit1.2 booleanCRT
24Control_Mode_Heat [DPT_1.002 - 1bit]1-Set HEAT mode1 Bit1.2 booleanCRWU
25Status_Mode_Heat [DPT_1.002 - 1bit]1-HEAT mode is active1 Bit1.2 booleanCRT
26Control_Mode_Cool [DPT_1.002 - 1bit]1-Set COOL mode1 Bit1.2 booleanCRWU
27Status_Mode_Cool [DPT_1.002 - 1bit]1-COOL mode is active1 Bit1.2 booleanCRT
28Control_Mode_Fan [DPT_1.002 - 1bit]1-Set FAN mode1 Bit1.2 booleanCRWU
29Status_Mode_Fan [DPT_1.002 - 1bit]1-FAN mode is active1 Bit1.2 booleanCRT
30Control_Mode_Dry [DPT_1.002 - 1bit]1-Set DRY mode1 Bit1.2 booleanCRWU
31Status_Mode_Dry [DPT_1.002 - 1bit]1-DRY mode is active1 Bit1.2 booleanCRT
32Control_Fan_Speed_Manual/Auto [DPT_1.002 - 1bit]0-Manual;1-Auto1 Bit1.2 booleanCRWU
33Status_Fan_Speed_Manual/Auto [DPT_1.002 - 1bit]0-Manual;1-Auto1 Bit1.2 booleanCRT
34Control_Fan_Speed_1 [DPT_1.002 - 1bit]1-Set Fan Speed 11 Bit1.2 booleanCRWU
35Status_Fan_Speed_1 [DPT_1.002 - 1bit]1-Fan Speed 11 Bit1.2 booleanCRT
36Control_Fan_Speed_2 [DPT_1.002 - 1bit]1-Set Fan Speed 21 Bit1.2 booleanCRWU
37Status_Fan_Speed_2 [DPT_1.002 - 1bit]1-Fan Speed 21 Bit1.2 booleanCRT
38Control_Fan_Speed_3 [DPT_1.002 - 1bit]1-Set Fan Speed 31 Bit1.2 booleanCRWU
39Status_Fan_Speed_3 [DPT_1.002 - 1bit]1-Fan Speed 31 Bit1.2 booleanCRT
40Control_Fan_Speed_4 [DPT_1.002 - 1bit]1-Set Fan Speed 41 Bit1.2 booleanCRWU
41Status_Fan_Speed_4 [DPT_1.002 - 1bit]1-Fan Speed 41 Bit1.2 booleanCRT
42Control_Fan_Speed +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCRWU
42Control_Fan_Speed -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 Bit1.7 stepCRWU
Parameters (27)
ParameterTypeDefault
Alive BeaconlistNo
Alive Beacon Timer(ms)unsignedInt 500…100003000
Digital Input 1 Contact TypelistNO
Digital Input 2 Contact TypelistNO
Enable Use of Digital Input 1listNo
Enable Use of Digital Input 2listNo
Control from remote control disablelistNo
Enable Object "Error Code [2Byte]"listNo
Fan Speed DPT Object TypelistEnumerated [DPT 5.100]
Available Fan Speeds in Indoor UnitunsignedInt 2…43
Enable use of Bit-type Fan Speed objects (Control&Status)listNo
Enable Fan Speed Manual/Auto objects (Control&Status)listNo
Fan is accessible in Indoor unitlistYes
Enable Mode Cool/Heat objects (Control&Status)listNo
Enable Mode Bit-type objects (Control&Status)listNo
Indoor unit has Fan modelistYes
Ambient temperature is provided from KNXlistNo
Enable limits on Setpoint Temp.listNo
Lower limit(°C)unsignedInt 16…3116
Setpoint Temp. scalelist1°C
Upper limit(°C)unsignedInt 16…3030
Enable Up/Down Vanes ControllistNo
Enable Left/Right Vanes ControllistNo
Indoor Unit has AUTO Fan SpeedlistNo
Fan Speed +/- Object DPT TypelistUp/Down [DPT 1.008]
Enable +/- objects for Fan SpeedlistNo
For more Information, User Manual & Latest Database Entrytextwww.core.com.tr

Version history

ApplicationApp noFingerprintFirst seenSizeFile
CoreMEACInt_V3 0.1 latest$F02323872026-11-25113 KBDownload

About this file

This is the official ETS product database for the Core Smart Home Mitsubishi Electric AC Gateway (0000010001), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.