| 0 | Switch Actuator A | Switch | 1 Bit | 1.1 switch | CRWU |
| 0 | Shutter / Blind A-B | Up Down | 1 Bit | 1.8 up/down | CRWU |
| 0 | Heating Actuator A | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 0 | Shutter / Blind DC A-B-C-D | Up Down | 1 Bit | 1.8 up/down | CRWU |
| 0 | 2 Pipes Fan Coil A-B-C-D | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 0 | 4 Pipes Fan Coil A-B-C-D-E | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 0 | Heating Actuator A | Switch | 1 Bit | 1.1 switch | CRWU |
| 1 | Switch Actuator A | Status | 1 Bit | 1.11 state | CRWT |
| 1 | Shutter / Blind A-B | Status | 1 Bit | 1.11 state | CRWT |
| 1 | Shutter / Blind DC A-B-C-D | Status | 1 Bit | 1.11 state | CRWT |
| 1 | 2 Pipes Fan Coil A-B-C-D | Cooling Value | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 1 | 4 Pipes Fan Coil A-B-C-D-E | Cooling Value | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 1 | Heating Actuator A | Status | 1 Bit | 1.11 state | CRWT |
| 2 | Switch Actuator A | Timer | 1 Bit | 1.1 switch | CRWTU |
| 2 | Shutter / Blind A-B | Position Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 2 | Shutter / Blind DC A-B-C-D | Position Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 2 | 2 Pipes Fan Coil A-B-C-D | Mode Change Cooling / Heating | 1 Bit | 1.100 cooling/heating | CRWTU |
| 2 | 4 Pipes Fan Coil A-B-C-D-E | Mode Change Cooling / Heating | 1 Bit | 1.100 cooling/heating | CRWTU |
| 3 | Switch Actuator A | Hours Counter | 4 Bytes | 13.100 time lag (s) | CRWTU |
| 4 | Switch Actuator A | Reset Counter | 1 Bit | 1.2 boolean | CRWTU |
| 5 | Switch Actuator A | Counter Setpointed | 1 Bit | 1.2 boolean | CRWTU |
| 6 | Switch Actuator A | Blinking | 1 Bit | 1.1 switch | CRWU |
| 6 | Shutter / Blind A-B | Sun Alarm | 1 Bit | 1.5 alarm | CRWU |
| 6 | Shutter / Blind DC A-B-C-D | Sun Alarm | 1 Bit | 1.5 alarm | CRWU |
| 6 | 2 Pipes Fan Coil A-B-C-D | Fan Control Mode [0: Manual / 1: Automatic] | 1 Bit | 1.1 switch | CRWU |
| 6 | 4 Pipes Fan Coil A-B-C-D-E | Fan Control Mode [0: Manual / 1: Automatic] | 1 Bit | 1.1 switch | CRWU |
| 7 | Switch Actuator A | Locking | 1 Bit | 1.3 enable | CRWU |
| 7 | Shutter / Blind A-B | Locking | 1 Bit | 1.3 enable | CRWU |
| 7 | Heating Actuator A | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 7 | Shutter / Blind DC A-B-C-D | Locking | 1 Bit | 1.3 enable | CRWU |
| 7 | 2 Pipes Fan Coil A-B-C-D | Disabling | 1 Bit | 1.1 switch | CRWU |
| 7 | 4 Pipes Fan Coil A-B-C-D-E | Disabling | 1 Bit | 1.1 switch | CRWU |
| 8 | Switch Actuator A | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 8 | Shutter / Blind A-B | Rain Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 8 | Heating Actuator A | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 8 | Shutter / Blind DC A-B-C-D | Rain Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 8 | 2 Pipes Fan Coil A-B-C-D | Fan Controller + / - | 1 Bit | 1.7 step | CRWTU |
| 8 | 4 Pipes Fan Coil A-B-C-D-E | Fan Controller + / - | 1 Bit | 1.7 step | CRWTU |
| 9 | Switch Actuator A | Scene | 1 Byte | 18.1 scene control | CRWU |
| 9 | Shutter / Blind A-B | Scene | 1 Byte | 18.1 scene control | CRWU |
| 9 | 2 Pipes Fan Coil A-B-C-D | Fan Controller 1 Byte | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 9 | 4 Pipes Fan Coil A-B-C-D-E | Fan Controller 1 Byte | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 9 | Shutter / Blind DC A-B-C-D | Scene | 1 Byte | 18.1 scene control | CRWU |
| 9 | 2 Pipes Fan Coil A-B-C-D | Fan Controller 1 Byte | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 9 | 4 Pipes Fan Coil A-B-C-D-E | Fan Controller 1 Byte | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 10 | Shutter / Blind A-B | Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 10 | Switch Actuator B | Switch | 1 Bit | 1.1 switch | CRWU |
| 10 | Heating Actuator B | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 10 | Shutter / Blind DC A-B-C-D | Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 10 | Heating Actuator B | Switch | 1 Bit | 1.1 switch | CRWU |
| 11 | Switch Actuator B | Status | 1 Bit | 1.11 state | CRWT |
| 11 | Shutter / Blind A-B | Stop / Step | 1 Bit | 1.7 step | CRWT |
| 11 | Shutter / Blind DC A-B-C-D | Stop / Step | 1 Bit | 1.7 step | CRWT |
| 11 | 2 Pipes Fan Coil A-B-C-D | Airing Level | 1 Byte | 5.100 fan stage (0..255) | CRWT |
| 11 | 4 Pipes Fan Coil A-B-C-D-E | Airing Level | 1 Byte | 5.100 fan stage (0..255) | CRWT |
| 11 | 2 Pipes Fan Coil A-B-C-D | Airing Fan Controller + / - | 1 Bit | 1.7 step | CRWT |
| 11 | 4 Pipes Fan Coil A-B-C-D-E | Airing Fan Controller + / - | 1 Bit | 1.7 step | CRWT |
| 11 | Heating Actuator B | Status | 1 Bit | 1.11 state | CRWT |
| 11 | 2 Pipes Fan Coil A-B-C-D | Airing Level | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 11 | 4 Pipes Fan Coil A-B-C-D-E | Airing Level | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 12 | Switch Actuator B | Timer | 1 Bit | 1.1 switch | CRWTU |
| 12 | Shutter / Blind A-B | Wind Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 12 | Shutter / Blind DC A-B-C-D | Wind Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 12 | 2 Pipes Fan Coil A-B-C-D | Active Valve Status | 1 Bit | 1.11 state | CRWTU |
| 12 | 4 Pipes Fan Coil A-B-C-D-E | Active Valve Status | 1 Bit | 1.11 state | CRWTU |
| 13 | Switch Actuator B | Locking | 1 Bit | 1.3 enable | CRWU |
| 13 | Shutter / Blind A-B | Slat Angle Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 13 | Heating Actuator B | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 13 | Shutter / Blind DC A-B-C-D | Slat Angle Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 13 | 2 Pipes Fan Coil A-B-C-D | Active Fan Level Status | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 13 | 4 Pipes Fan Coil A-B-C-D-E | Active Fan Level Status | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 13 | 4 Pipes Fan Coil A-B-C-D-E | Active Fan Level Status | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 13 | 2 Pipes Fan Coil A-B-C-D | Active Fan Level Status | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 14 | Switch Actuator B | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 14 | Shutter / Blind A-B | Slat Angle Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 14 | Heating Actuator B | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 14 | Shutter / Blind DC A-B-C-D | Slat Angle Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 14 | 2 Pipes Fan Coil A-B-C-D | Status for Fan Level 1 | 1 Bit | 1.11 state | CRWTU |
| 14 | 4 Pipes Fan Coil A-B-C-D-E | Status for Fan Level 1 | 1 Bit | 1.11 state | CRWTU |
| 15 | Shutter / Blind A-B | Frost Alarm | 1 Bit | 1.5 alarm | CRWU |
| 15 | Switch Actuator B | Scene | 1 Byte | 18.1 scene control | CRWU |
| 15 | Shutter / Blind DC A-B-C-D | Frost Alarm | 1 Bit | 1.5 alarm | CRWU |
| 15 | 2 Pipes Fan Coil A-B-C-D | Status for Fan Level 2 | 1 Bit | 1.11 state | CRWU |
| 15 | 4 Pipes Fan Coil A-B-C-D-E | Status for Fan Level 2 | 1 Bit | 1.11 state | CRWU |
| 16 | Switch Actuator C | Switch | 1 Bit | 1.1 switch | CRWU |
| 16 | Shutter / Blind C-D | Up Down | 1 Bit | 1.8 up/down | CRWU |
| 16 | Heating Actuator C | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 16 | 2 Pipes Fan Coil A-B-C-D | Status for Fan Level 3 | 1 Bit | 1.11 state | CRWU |
| 16 | 4 Pipes Fan Coil A-B-C-D-E | Status for Fan Level 3 | 1 Bit | 1.11 state | CRWU |
| 16 | Heating Actuator C | Switch | 1 Bit | 1.1 switch | CRWU |
| 17 | Switch Actuator C | Status | 1 Bit | 1.11 state | CRWT |
| 17 | Shutter / Blind C-D | Status | 1 Bit | 1.11 state | CRWT |
| 17 | 2 Pipes Fan Coil A-B-C-D | Fan Control Mode Status [0: Manual / 1: Automatic] | 1 Bit | 1.11 state | CRWT |
| 17 | 4 Pipes Fan Coil A-B-C-D-E | Fan Control Mode Status [0: Manual / 1: Automatic] | 1 Bit | 1.11 state | CRWT |
| 17 | Heating Actuator C | Status | 1 Bit | 1.11 state | CRWT |
| 18 | Switch Actuator C | Timer | 1 Bit | 1.1 switch | CRWTU |
| 18 | Shutter / Blind C-D | Position Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 19 | Switch Actuator C | Hours Counter | 4 Bytes | 13.100 time lag (s) | CRWTU |
| 20 | Switch Actuator C | Reset Counter | 1 Bit | 1.2 boolean | CRWTU |
| 21 | Switch Actuator C | Counter Setpointed | 1 Bit | 1.2 boolean | CRWTU |
| 22 | Switch Actuator C | Blinking | 1 Bit | 1.1 switch | CRWU |
| 22 | Shutter / Blind C-D | Sun Alarm | 1 Bit | 1.5 alarm | CRWU |
| 23 | Switch Actuator C | Locking | 1 Bit | 1.3 enable | CRWU |
| 23 | Shutter / Blind C-D | Locking | 1 Bit | 1.3 enable | CRWU |
| 23 | Heating Actuator C | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 24 | Switch Actuator C | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 24 | Shutter / Blind C-D | Rain Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 24 | Heating Actuator C | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 25 | Switch Actuator C | Scene | 1 Byte | 18.1 scene control | CRWU |
| 25 | Shutter / Blind C-D | Scene | 1 Byte | 18.1 scene control | CRWU |
| 26 | Shutter / Blind C-D | Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 26 | Switch Actuator D | Switch | 1 Bit | 1.1 switch | CRWU |
| 26 | Heating Actuator D | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 26 | Heating Actuator D | Switch | 1 Bit | 1.1 switch | CRWU |
| 26 | 2 Pipes Fan Coil A-B-C-D | Control Fan Level 1 | 1 Bit | 1.3 enable | CRWTU |
| 26 | 4 Pipes Fan Coil A-B-C-D-E | Control Fan Level 1 | 1 Bit | 1.3 enable | CRWTU |
| 27 | Switch Actuator D | Status | 1 Bit | 1.11 state | CRWT |
| 27 | Shutter / Blind C-D | Stop / Step | 1 Bit | 1.7 step | CRWT |
| 27 | Heating Actuator D | Status | 1 Bit | 1.11 state | CRWT |
| 27 | 2 Pipes Fan Coil A-B-C-D | Control Fan Level 2 | 1 Bit | 1.3 enable | CRWTU |
| 27 | 4 Pipes Fan Coil A-B-C-D-E | Control Fan Level 2 | 1 Bit | 1.3 enable | CRWTU |
| 28 | Switch Actuator D | Timer | 1 Bit | 1.1 switch | CRWTU |
| 28 | Shutter / Blind C-D | Wind Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 28 | 2 Pipes Fan Coil A-B-C-D | Control Fan Level 3 | 1 Bit | 1.3 enable | CRWTU |
| 28 | 4 Pipes Fan Coil A-B-C-D-E | Control Fan Level 3 | 1 Bit | 1.3 enable | CRWTU |
| 29 | Switch Actuator D | Locking | 1 Bit | 1.3 enable | CRWU |
| 29 | Shutter / Blind C-D | Slat Angle Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 29 | Heating Actuator D | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 30 | Switch Actuator D | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 30 | Shutter / Blind C-D | Slat Angle Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 30 | Heating Actuator D | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 31 | Shutter / Blind C-D | Frost Alarm | 1 Bit | 1.5 alarm | CRWU |
| 31 | Switch Actuator D | Scene | 1 Byte | 18.1 scene control | CRWU |
| 31 | 2 Pipes Fan Coil A-B-C-D | Mode Change Cooling / Heating Status | 1 Bit | 1.100 cooling/heating | CRWU |
| 32 | Switch Actuator E | Switch | 1 Bit | 1.1 switch | CRWU |
| 32 | Shutter / Blind E-F | Up Down | 1 Bit | 1.8 up/down | CRWU |
| 32 | Heating Actuator E | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 32 | Shutter / Blind DC E-F-G-H | Up Down | 1 Bit | 1.8 up/down | CRWU |
| 32 | 2 Pipes Fan Coil E-F-G-H | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 32 | Heating Actuator E | Switch | 1 Bit | 1.1 switch | CRWU |
| 33 | Switch Actuator E | Status | 1 Bit | 1.11 state | CRWT |
| 33 | Shutter / Blind E-F | Status | 1 Bit | 1.11 state | CRWT |
| 33 | Shutter / Blind DC E-F-G-H | Status | 1 Bit | 1.11 state | CRWT |
| 33 | 2 Pipes Fan Coil E-F-G-H | Cooling Value | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 33 | Heating Actuator E | Status | 1 Bit | 1.11 state | CRWT |
| 34 | Switch Actuator E | Timer | 1 Bit | 1.1 switch | CRWTU |
| 34 | Shutter / Blind E-F | Position Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 34 | Shutter / Blind DC E-F-G-H | Position Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 34 | 2 Pipes Fan Coil E-F-G-H | Mode Change Cooling / Heating | 1 Bit | 1.100 cooling/heating | CRWTU |
| 35 | Switch Actuator E | Blinking | 1 Bit | 1.1 switch | CRWU |
| 35 | Shutter / Blind E-F | Sun Alarm | 1 Bit | 1.5 alarm | CRWU |
| 35 | Shutter / Blind DC E-F-G-H | Sun Alarm | 1 Bit | 1.5 alarm | CRWU |
| 35 | 2 Pipes Fan Coil E-F-G-H | Fan Control Mode [0: Manual / 1: Automatic] | 1 Bit | 1.1 switch | CRWU |
| 36 | Switch Actuator E | Locking | 1 Bit | 1.3 enable | CRWU |
| 36 | Shutter / Blind E-F | Locking | 1 Bit | 1.3 enable | CRWU |
| 36 | Heating Actuator E | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 36 | Shutter / Blind DC E-F-G-H | Locking | 1 Bit | 1.3 enable | CRWU |
| 36 | 2 Pipes Fan Coil E-F-G-H | Disabling | 1 Bit | 1.1 switch | CRWU |
| 37 | Switch Actuator E | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 37 | Shutter / Blind E-F | Rain Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 37 | Heating Actuator E | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 37 | Shutter / Blind DC E-F-G-H | Rain Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 37 | 2 Pipes Fan Coil E-F-G-H | Fan Controller + / - | 1 Bit | 1.7 step | CRWTU |
| 38 | Switch Actuator E | Scene | 1 Byte | 18.1 scene control | CRWU |
| 38 | Shutter / Blind E-F | Scene | 1 Byte | 18.1 scene control | CRWU |
| 38 | 2 Pipes Fan Coil E-F-G-H | Fan Controller 1 Byte | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 38 | Shutter / Blind DC E-F-G-H | Scene | 1 Byte | 18.1 scene control | CRWU |
| 38 | 4 Pipes Fan Coil A-B-C-D-E | Mode Change Cooling / Heating Status | 1 Bit | 1.100 cooling/heating | CRWU |
| 38 | 2 Pipes Fan Coil E-F-G-H | Fan Controller 1 Byte | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 39 | Shutter / Blind E-F | Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 39 | Switch Actuator F | Switch | 1 Bit | 1.1 switch | CRWU |
| 39 | Heating Actuator F | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 39 | Shutter / Blind DC E-F-G-H | Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 39 | Heating Actuator F | Switch | 1 Bit | 1.1 switch | CRWU |
| 40 | Switch Actuator F | Status | 1 Bit | 1.11 state | CRWT |
| 40 | Shutter / Blind E-F | Stop / Step | 1 Bit | 1.7 step | CRWT |
| 40 | Shutter / Blind DC E-F-G-H | Stop / Step | 1 Bit | 1.7 step | CRWT |
| 40 | 2 Pipes Fan Coil E-F-G-H | Airing Level | 1 Byte | 5.100 fan stage (0..255) | CRWT |
| 40 | 2 Pipes Fan Coil E-F-G-H | Airing Fan Controller + / - | 1 Bit | 1.7 step | CRWT |
| 40 | Heating Actuator F | Status | 1 Bit | 1.11 state | CRWT |
| 40 | 2 Pipes Fan Coil E-F-G-H | Airing Level | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 41 | Switch Actuator F | Timer | 1 Bit | 1.1 switch | CRWTU |
| 41 | Shutter / Blind E-F | Wind Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 41 | Shutter / Blind DC E-F-G-H | Wind Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 41 | 2 Pipes Fan Coil E-F-G-H | Active Valve Status | 1 Bit | 1.11 state | CRWTU |
| 42 | Switch Actuator F | Locking | 1 Bit | 1.3 enable | CRWU |
| 42 | Shutter / Blind E-F | Slat Angle Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 42 | Heating Actuator F | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 42 | Shutter / Blind DC E-F-G-H | Slat Angle Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 42 | 2 Pipes Fan Coil E-F-G-H | Active Fan Level Status | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 42 | 2 Pipes Fan Coil E-F-G-H | Active Fan Level Status | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 43 | Switch Actuator F | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 43 | Shutter / Blind E-F | Slat Angle Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 43 | Heating Actuator F | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 43 | Shutter / Blind DC E-F-G-H | Slat Angle Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 43 | 2 Pipes Fan Coil E-F-G-H | Status for Fan Level 1 | 1 Bit | 1.11 state | CRWTU |
| 44 | Shutter / Blind E-F | Frost Alarm | 1 Bit | 1.5 alarm | CRWU |
| 44 | Switch Actuator F | Scene | 1 Byte | 18.1 scene control | CRWU |
| 44 | Shutter / Blind DC E-F-G-H | Frost Alarm | 1 Bit | 1.5 alarm | CRWU |
| 44 | 2 Pipes Fan Coil E-F-G-H | Status for Fan Level 2 | 1 Bit | 1.11 state | CRWU |
| 45 | Switch Actuator G | Switch | 1 Bit | 1.1 switch | CRWU |
| 45 | Heating Actuator G | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 45 | Shutter / Blind G-H | Up Down | 1 Bit | 1.8 up/down | CRWU |
| 45 | 2 Pipes Fan Coil E-F-G-H | Status for Fan Level 3 | 1 Bit | 1.11 state | CRWU |
| 45 | Heating Actuator G | Switch | 1 Bit | 1.1 switch | CRWU |
| 46 | Switch Actuator G | Status | 1 Bit | 1.11 state | CRWT |
| 46 | Shutter / Blind G-H | Status | 1 Bit | 1.11 state | CRWT |
| 46 | 2 Pipes Fan Coil E-F-G-H | Fan Control Mode Status [0: Manual / 1: Automatic] | 1 Bit | 1.11 state | CRWT |
| 46 | Heating Actuator G | Status | 1 Bit | 1.11 state | CRWT |
| 47 | Switch Actuator G | Timer | 1 Bit | 1.1 switch | CRWTU |
| 47 | Shutter / Blind G-H | Position Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 48 | Switch Actuator G | Blinking | 1 Bit | 1.1 switch | CRWU |
| 48 | Shutter / Blind G-H | Sun Alarm | 1 Bit | 1.5 alarm | CRWU |
| 49 | Switch Actuator G | Locking | 1 Bit | 1.3 enable | CRWU |
| 49 | Heating Actuator G | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 49 | Shutter / Blind G-H | Locking | 1 Bit | 1.3 enable | CRWU |
| 50 | Switch Actuator G | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 50 | Heating Actuator G | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 50 | Shutter / Blind G-H | Rain Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 51 | Switch Actuator G | Scene | 1 Byte | 18.1 scene control | CRWU |
| 51 | Shutter / Blind G-H | Scene | 1 Byte | 18.1 scene control | CRWU |
| 52 | Switch Actuator H | Switch | 1 Bit | 1.1 switch | CRWU |
| 52 | Heating Actuator H | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 52 | Shutter / Blind G-H | Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 52 | Heating Actuator H | Switch | 1 Bit | 1.1 switch | CRWU |
| 52 | 2 Pipes Fan Coil E-F-G-H | Control Fan Level 1 | 1 Bit | 1.3 enable | CRWTU |
| 53 | Switch Actuator H | Status | 1 Bit | 1.11 state | CRWT |
| 53 | Shutter / Blind G-H | Stop / Step | 1 Bit | 1.7 step | CRWT |
| 53 | Heating Actuator H | Status | 1 Bit | 1.11 state | CRWT |
| 53 | 2 Pipes Fan Coil E-F-G-H | Control Fan Level 2 | 1 Bit | 1.3 enable | CRWTU |
| 54 | Switch Actuator H | Timer | 1 Bit | 1.1 switch | CRWTU |
| 54 | Shutter / Blind G-H | Wind Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 54 | 2 Pipes Fan Coil E-F-G-H | Control Fan Level 3 | 1 Bit | 1.3 enable | CRWTU |
| 55 | Switch Actuator H | Locking | 1 Bit | 1.3 enable | CRWU |
| 55 | Heating Actuator H | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 55 | Shutter / Blind G-H | Slat Angle Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 56 | Switch Actuator H | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 56 | Heating Actuator H | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 56 | Shutter / Blind G-H | Slat Angle Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 57 | Switch Actuator H | Scene | 1 Byte | 18.1 scene control | CRWU |
| 57 | Shutter / Blind G-H | Frost Alarm | 1 Bit | 1.5 alarm | CRWU |
| 57 | 2 Pipes Fan Coil E-F-G-H | Mode Change Cooling / Heating Status | 1 Bit | 1.100 cooling/heating | CRWU |
| 58 | Switch Actuator I | Switch | 1 Bit | 1.1 switch | CRWU |
| 58 | Heating Actuator I | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 58 | Shutter / Blind I-J | Up Down | 1 Bit | 1.8 up/down | CRWU |
| 58 | Shutter / Blind DC I-J-K-L | Up Down | 1 Bit | 1.8 up/down | CRWU |
| 58 | 2 Pipes Fan Coil I-J-K-L | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 58 | Heating Actuator I | Switch | 1 Bit | 1.1 switch | CRWU |
| 58 | 4 Pipes Fan Coil I-J-K-L-M | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 59 | Switch Actuator I | Status | 1 Bit | 1.11 state | CRWT |
| 59 | Shutter / Blind I-J | Status | 1 Bit | 1.11 state | CRWT |
| 59 | Shutter / Blind DC I-J-K-L | Status | 1 Bit | 1.11 state | CRWT |
| 59 | 2 Pipes Fan Coil I-J-K-L | Cooling Value | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 59 | Heating Actuator I | Status | 1 Bit | 1.11 state | CRWT |
| 59 | 4 Pipes Fan Coil I-J-K-L-M | Cooling Value | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 60 | Switch Actuator I | Timer | 1 Bit | 1.1 switch | CRWTU |
| 60 | Shutter / Blind I-J | Position Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 60 | Shutter / Blind DC I-J-K-L | Position Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 60 | 2 Pipes Fan Coil I-J-K-L | Mode Change Cooling / Heating | 1 Bit | 1.100 cooling/heating | CRWTU |
| 60 | 4 Pipes Fan Coil I-J-K-L-M | Mode Change Cooling / Heating | 1 Bit | 1.100 cooling/heating | CRWTU |
| 61 | Switch Actuator I | Blinking | 1 Bit | 1.1 switch | CRWU |
| 61 | Shutter / Blind I-J | Sun Alarm | 1 Bit | 1.5 alarm | CRWU |
| 61 | Shutter / Blind DC I-J-K-L | Sun Alarm | 1 Bit | 1.5 alarm | CRWU |
| 61 | 2 Pipes Fan Coil I-J-K-L | Fan Control Mode [0: Manual / 1: Automatic] | 1 Bit | 1.1 switch | CRWU |
| 61 | 4 Pipes Fan Coil I-J-K-L-M | Fan Control Mode [0: Manual / 1: Automatic] | 1 Bit | 1.1 switch | CRWU |
| 62 | Switch Actuator I | Locking | 1 Bit | 1.3 enable | CRWU |
| 62 | Heating Actuator I | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 62 | Shutter / Blind I-J | Locking | 1 Bit | 1.3 enable | CRWU |
| 62 | Shutter / Blind DC I-J-K-L | Locking | 1 Bit | 1.3 enable | CRWU |
| 62 | 2 Pipes Fan Coil I-J-K-L | Disabling | 1 Bit | 1.1 switch | CRWU |
| 62 | 4 Pipes Fan Coil I-J-K-L-M | Disabling | 1 Bit | 1.1 switch | CRWU |
| 63 | Switch Actuator I | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 63 | Heating Actuator I | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 63 | Shutter / Blind I-J | Rain Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 63 | Shutter / Blind DC I-J-K-L | Rain Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 63 | 2 Pipes Fan Coil I-J-K-L | Fan Controller + / - | 1 Bit | 1.7 step | CRWTU |
| 63 | 4 Pipes Fan Coil I-J-K-L-M | Fan Controller + / - | 1 Bit | 1.7 step | CRWTU |
| 64 | Switch Actuator I | Scene | 1 Byte | 18.1 scene control | CRWU |
| 64 | Shutter / Blind I-J | Scene | 1 Byte | 18.1 scene control | CRWU |
| 64 | 2 Pipes Fan Coil I-J-K-L | Fan Controller 1 Byte | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 64 | Shutter / Blind DC I-J-K-L | Scene | 1 Byte | 18.1 scene control | CRWU |
| 64 | 4 Pipes Fan Coil I-J-K-L-M | Fan Controller 1 Byte | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 64 | 4 Pipes Fan Coil I-J-K-L-M | Fan Controller 1 Byte | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 64 | 2 Pipes Fan Coil I-J-K-L | Fan Controller 1 Byte | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 65 | Switch Actuator J | Switch | 1 Bit | 1.1 switch | CRWU |
| 65 | Heating Actuator J | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 65 | Shutter / Blind I-J | Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 65 | Shutter / Blind DC I-J-K-L | Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 65 | Heating Actuator J | Switch | 1 Bit | 1.1 switch | CRWU |
| 66 | Switch Actuator J | Status | 1 Bit | 1.11 state | CRWT |
| 66 | Shutter / Blind I-J | Stop / Step | 1 Bit | 1.7 step | CRWT |
| 66 | Shutter / Blind DC I-J-K-L | Stop / Step | 1 Bit | 1.7 step | CRWT |
| 66 | 2 Pipes Fan Coil I-J-K-L | Airing Level | 1 Byte | 5.100 fan stage (0..255) | CRWT |
| 66 | 2 Pipes Fan Coil I-J-K-L | Airing Fan Controller + / - | 1 Bit | 1.7 step | CRWT |
| 66 | Heating Actuator J | Status | 1 Bit | 1.11 state | CRWT |
| 66 | 4 Pipes Fan Coil I-J-K-L-M | Airing Fan Controller + / - | 1 Bit | 1.7 step | CRWT |
| 66 | 4 Pipes Fan Coil I-J-K-L-M | Airing Level | 1 Byte | 5.100 fan stage (0..255) | CRWT |
| 66 | 2 Pipes Fan Coil I-J-K-L | Airing Level | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 66 | 4 Pipes Fan Coil I-J-K-L-M | Airing Level | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 67 | Switch Actuator J | Timer | 1 Bit | 1.1 switch | CRWTU |
| 67 | Shutter / Blind I-J | Wind Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 67 | Shutter / Blind DC I-J-K-L | Wind Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 67 | 2 Pipes Fan Coil I-J-K-L | Active Valve Status | 1 Bit | 1.11 state | CRWTU |
| 67 | 4 Pipes Fan Coil I-J-K-L-M | Active Valve Status | 1 Bit | 1.11 state | CRWTU |
| 68 | Switch Actuator J | Locking | 1 Bit | 1.3 enable | CRWU |
| 68 | Heating Actuator J | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 68 | Shutter / Blind I-J | Slat Angle Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 68 | Shutter / Blind DC I-J-K-L | Slat Angle Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 68 | 2 Pipes Fan Coil I-J-K-L | Active Fan Level Status | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 68 | 4 Pipes Fan Coil I-J-K-L-M | Active Fan Level Status | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 68 | 2 Pipes Fan Coil I-J-K-L | Active Fan Level Status | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 68 | 4 Pipes Fan Coil I-J-K-L-M | Active Fan Level Status | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 69 | Switch Actuator J | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 69 | Heating Actuator J | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 69 | Shutter / Blind I-J | Slat Angle Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 69 | Shutter / Blind DC I-J-K-L | Slat Angle Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 69 | 2 Pipes Fan Coil I-J-K-L | Status for Fan Level 1 | 1 Bit | 1.11 state | CRWTU |
| 69 | 4 Pipes Fan Coil I-J-K-L-M | Status for Fan Level 1 | 1 Bit | 1.11 state | CRWTU |
| 70 | Switch Actuator J | Scene | 1 Byte | 18.1 scene control | CRWU |
| 70 | Shutter / Blind I-J | Frost Alarm | 1 Bit | 1.5 alarm | CRWU |
| 70 | Shutter / Blind DC I-J-K-L | Frost Alarm | 1 Bit | 1.5 alarm | CRWU |
| 70 | 2 Pipes Fan Coil I-J-K-L | Status for Fan Level 2 | 1 Bit | 1.11 state | CRWU |
| 70 | 4 Pipes Fan Coil I-J-K-L-M | Status for Fan Level 2 | 1 Bit | 1.11 state | CRWU |
| 71 | Switch Actuator K | Switch | 1 Bit | 1.1 switch | CRWU |
| 71 | Heating Actuator K | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 71 | Shutter / Blind K-L | Up Down | 1 Bit | 1.8 up/down | CRWU |
| 71 | 2 Pipes Fan Coil I-J-K-L | Status for Fan Level 3 | 1 Bit | 1.11 state | CRWU |
| 71 | Heating Actuator K | Switch | 1 Bit | 1.1 switch | CRWU |
| 71 | 4 Pipes Fan Coil I-J-K-L-M | Status for Fan Level 3 | 1 Bit | 1.11 state | CRWU |
| 72 | Switch Actuator K | Status | 1 Bit | 1.11 state | CRWT |
| 72 | Shutter / Blind K-L | Status | 1 Bit | 1.11 state | CRWT |
| 72 | 2 Pipes Fan Coil I-J-K-L | Fan Control Mode Status [0: Manual / 1: Automatic] | 1 Bit | 1.11 state | CRWT |
| 72 | Heating Actuator K | Status | 1 Bit | 1.11 state | CRWT |
| 72 | 4 Pipes Fan Coil I-J-K-L-M | Fan Control Mode Status [0: Manual / 1: Automatic] | 1 Bit | 1.11 state | CRWT |
| 73 | Switch Actuator K | Timer | 1 Bit | 1.1 switch | CRWTU |
| 73 | Shutter / Blind K-L | Position Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 74 | Switch Actuator K | Blinking | 1 Bit | 1.1 switch | CRWU |
| 74 | Shutter / Blind K-L | Sun Alarm | 1 Bit | 1.5 alarm | CRWU |
| 75 | Switch Actuator K | Locking | 1 Bit | 1.3 enable | CRWU |
| 75 | Heating Actuator K | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 75 | Shutter / Blind K-L | Locking | 1 Bit | 1.3 enable | CRWU |
| 76 | Heating Actuator K | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 76 | Switch Actuator K | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 76 | Shutter / Blind K-L | Rain Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 77 | Switch Actuator K | Scene | 1 Byte | 18.1 scene control | CRWU |
| 77 | Shutter / Blind K-L | Scene | 1 Byte | 18.1 scene control | CRWU |
| 78 | Switch Actuator L | Switch | 1 Bit | 1.1 switch | CRWU |
| 78 | Heating Actuator L | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 78 | Shutter / Blind K-L | Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 78 | Heating Actuator L | Switch | 1 Bit | 1.1 switch | CRWU |
| 78 | 2 Pipes Fan Coil I-J-K-L | Control Fan Level 1 | 1 Bit | 1.3 enable | CRWTU |
| 78 | 4 Pipes Fan Coil I-J-K-L-M | Control Fan Level 1 | 1 Bit | 1.3 enable | CRWTU |
| 79 | Switch Actuator L | Status | 1 Bit | 1.11 state | CRWT |
| 79 | Shutter / Blind K-L | Stop / Step | 1 Bit | 1.7 step | CRWT |
| 79 | Heating Actuator L | Status | 1 Bit | 1.11 state | CRWT |
| 79 | 2 Pipes Fan Coil I-J-K-L | Control Fan Level 2 | 1 Bit | 1.3 enable | CRWTU |
| 79 | 4 Pipes Fan Coil I-J-K-L-M | Control Fan Level 2 | 1 Bit | 1.3 enable | CRWTU |
| 80 | Switch Actuator L | Timer | 1 Bit | 1.1 switch | CRWTU |
| 80 | Shutter / Blind K-L | Wind Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 80 | 2 Pipes Fan Coil I-J-K-L | Control Fan Level 3 | 1 Bit | 1.3 enable | CRWTU |
| 80 | 4 Pipes Fan Coil I-J-K-L-M | Control Fan Level 3 | 1 Bit | 1.3 enable | CRWTU |
| 81 | Switch Actuator L | Locking | 1 Bit | 1.3 enable | CRWU |
| 81 | Heating Actuator L | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 81 | Shutter / Blind K-L | Slat Angle Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 82 | Heating Actuator L | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 82 | Switch Actuator L | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 82 | Shutter / Blind K-L | Slat Angle Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 83 | Switch Actuator L | Scene | 1 Byte | 18.1 scene control | CRWU |
| 83 | Shutter / Blind K-L | Frost Alarm | 1 Bit | 1.5 alarm | CRWU |
| 83 | 2 Pipes Fan Coil I-J-K-L | Mode Change Cooling / Heating Status | 1 Bit | 1.100 cooling/heating | CRWU |
| 84 | Switch Actuator M | Switch | 1 Bit | 1.1 switch | CRWU |
| 84 | Heating Actuator M | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 84 | Shutter / Blind M-N | Up Down | 1 Bit | 1.8 up/down | CRWU |
| 84 | Shutter / Blind DC M-N-O-P | Up Down | 1 Bit | 1.8 up/down | CRWU |
| 84 | 2 Pipes Fan Coil M-N-O-P | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 84 | Heating Actuator M | Switch | 1 Bit | 1.1 switch | CRWU |
| 85 | Switch Actuator M | Status | 1 Bit | 1.11 state | CRWT |
| 85 | Shutter / Blind M-N | Status | 1 Bit | 1.11 state | CRWT |
| 85 | Shutter / Blind DC M-N-O-P | Status | 1 Bit | 1.11 state | CRWT |
| 85 | 2 Pipes Fan Coil M-N-O-P | Cooling Value | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 85 | Heating Actuator M | Status | 1 Bit | 1.11 state | CRWT |
| 86 | Switch Actuator M | Timer | 1 Bit | 1.1 switch | CRWTU |
| 86 | Shutter / Blind M-N | Position Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 86 | Shutter / Blind DC M-N-O-P | Position Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 86 | 2 Pipes Fan Coil M-N-O-P | Mode Change Cooling / Heating | 1 Bit | 1.100 cooling/heating | CRWTU |
| 87 | Switch Actuator M | Blinking | 1 Bit | 1.1 switch | CRWU |
| 87 | Shutter / Blind M-N | Sun Alarm | 1 Bit | 1.5 alarm | CRWU |
| 87 | Shutter / Blind DC M-N-O-P | Sun Alarm | 1 Bit | 1.5 alarm | CRWU |
| 87 | 2 Pipes Fan Coil M-N-O-P | Fan Control Mode [0: Manual / 1: Automatic] | 1 Bit | 1.1 switch | CRWU |
| 88 | Switch Actuator M | Locking | 1 Bit | 1.3 enable | CRWU |
| 88 | Heating Actuator M | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 88 | Shutter / Blind M-N | Locking | 1 Bit | 1.3 enable | CRWU |
| 88 | Shutter / Blind DC M-N-O-P | Locking | 1 Bit | 1.3 enable | CRWU |
| 88 | 2 Pipes Fan Coil M-N-O-P | Disabling | 1 Bit | 1.1 switch | CRWU |
| 89 | Heating Actuator M | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 89 | Switch Actuator M | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 89 | Shutter / Blind M-N | Rain Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 89 | Shutter / Blind DC M-N-O-P | Rain Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 89 | 2 Pipes Fan Coil M-N-O-P | Fan Controller + / - | 1 Bit | 1.7 step | CRWTU |
| 90 | Switch Actuator M | Scene | 1 Byte | 18.1 scene control | CRWU |
| 90 | Shutter / Blind M-N | Scene | 1 Byte | 18.1 scene control | CRWU |
| 90 | 2 Pipes Fan Coil M-N-O-P | Fan Controller 1 Byte | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 90 | Shutter / Blind DC M-N-O-P | Scene | 1 Byte | 18.1 scene control | CRWU |
| 90 | 4 Pipes Fan Coil I-J-K-L-M | Mode Change Cooling / Heating Status | 1 Bit | 1.100 cooling/heating | CRWU |
| 90 | 2 Pipes Fan Coil M-N-O-P | Fan Controller 1 Byte | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 91 | Switch Actuator N | Switch | 1 Bit | 1.1 switch | CRWU |
| 91 | Heating Actuator N | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 91 | Shutter / Blind M-N | Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 91 | Shutter / Blind DC M-N-O-P | Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 91 | Heating Actuator N | Switch | 1 Bit | 1.1 switch | CRWU |
| 92 | Switch Actuator N | Status | 1 Bit | 1.11 state | CRWT |
| 92 | Shutter / Blind M-N | Stop / Step | 1 Bit | 1.7 step | CRWT |
| 92 | Shutter / Blind DC M-N-O-P | Stop / Step | 1 Bit | 1.7 step | CRWT |
| 92 | 2 Pipes Fan Coil M-N-O-P | Airing Level | 1 Byte | 5.100 fan stage (0..255) | CRWT |
| 92 | 2 Pipes Fan Coil M-N-O-P | Airing Fan Controller + / - | 1 Bit | 1.7 step | CRWT |
| 92 | Heating Actuator N | Status | 1 Bit | 1.11 state | CRWT |
| 92 | 2 Pipes Fan Coil M-N-O-P | Airing Level | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 93 | Switch Actuator N | Timer | 1 Bit | 1.1 switch | CRWTU |
| 93 | Shutter / Blind M-N | Wind Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 93 | Shutter / Blind DC M-N-O-P | Wind Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 93 | 2 Pipes Fan Coil M-N-O-P | Active Valve Status | 1 Bit | 1.11 state | CRWTU |
| 94 | Switch Actuator N | Locking | 1 Bit | 1.3 enable | CRWU |
| 94 | Heating Actuator N | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 94 | Shutter / Blind M-N | Slat Angle Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 94 | Shutter / Blind DC M-N-O-P | Slat Angle Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 94 | 2 Pipes Fan Coil M-N-O-P | Active Fan Level Status | 1 Byte | 5.100 fan stage (0..255) | CRWU |
| 94 | 2 Pipes Fan Coil M-N-O-P | Active Fan Level Status | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 95 | Heating Actuator N | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 95 | Switch Actuator N | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 95 | Shutter / Blind M-N | Slat Angle Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 95 | Shutter / Blind DC M-N-O-P | Slat Angle Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 95 | 2 Pipes Fan Coil M-N-O-P | Status for Fan Level 1 | 1 Bit | 1.11 state | CRWTU |
| 96 | Switch Actuator N | Scene | 1 Byte | 18.1 scene control | CRWU |
| 96 | Shutter / Blind M-N | Frost Alarm | 1 Bit | 1.5 alarm | CRWU |
| 96 | Shutter / Blind DC M-N-O-P | Frost Alarm | 1 Bit | 1.5 alarm | CRWU |
| 96 | 2 Pipes Fan Coil M-N-O-P | Status for Fan Level 2 | 1 Bit | 1.11 state | CRWU |
| 97 | Switch Actuator O | Switch | 1 Bit | 1.1 switch | CRWU |
| 97 | Heating Actuator O | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 97 | Shutter / Blind O-P | Up Down | 1 Bit | 1.8 up/down | CRWU |
| 97 | 2 Pipes Fan Coil M-N-O-P | Status for Fan Level 3 | 1 Bit | 1.11 state | CRWU |
| 97 | Heating Actuator O | Switch | 1 Bit | 1.1 switch | CRWU |
| 98 | Switch Actuator O | Status | 1 Bit | 1.11 state | CRWT |
| 98 | Shutter / Blind O-P | Status | 1 Bit | 1.11 state | CRWT |
| 98 | 2 Pipes Fan Coil M-N-O-P | Fan Control Mode Status [0: Manual / 1: Automatic] | 1 Bit | 1.11 state | CRWT |
| 98 | Heating Actuator O | Status | 1 Bit | 1.11 state | CRWT |
| 99 | Switch Actuator O | Timer | 1 Bit | 1.1 switch | CRWTU |
| 99 | Shutter / Blind O-P | Position Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 100 | Switch Actuator O | Blinking | 1 Bit | 1.1 switch | CRWU |
| 100 | Shutter / Blind O-P | Sun Alarm | 1 Bit | 1.5 alarm | CRWU |
| 101 | Switch Actuator O | Locking | 1 Bit | 1.3 enable | CRWU |
| 101 | Heating Actuator O | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 101 | Shutter / Blind O-P | Locking | 1 Bit | 1.3 enable | CRWU |
| 102 | Heating Actuator O | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 102 | Switch Actuator O | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 102 | Shutter / Blind O-P | Rain Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 103 | Switch Actuator O | Scene | 1 Byte | 18.1 scene control | CRWU |
| 103 | Shutter / Blind O-P | Scene | 1 Byte | 18.1 scene control | CRWU |
| 104 | Switch Actuator P | Switch | 1 Bit | 1.1 switch | CRWU |
| 104 | Heating Actuator P | Heating Value | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 104 | Shutter / Blind O-P | Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 104 | Heating Actuator P | Switch | 1 Bit | 1.1 switch | CRWU |
| 104 | 2 Pipes Fan Coil M-N-O-P | Control Fan Level 1 | 1 Bit | 1.3 enable | CRWTU |
| 105 | Switch Actuator P | Status | 1 Bit | 1.11 state | CRWT |
| 105 | Shutter / Blind O-P | Stop / Step | 1 Bit | 1.7 step | CRWT |
| 105 | Heating Actuator P | Status | 1 Bit | 1.11 state | CRWT |
| 105 | 2 Pipes Fan Coil M-N-O-P | Control Fan Level 2 | 1 Bit | 1.3 enable | CRWTU |
| 106 | Switch Actuator P | Timer | 1 Bit | 1.1 switch | CRWTU |
| 106 | Shutter / Blind O-P | Wind Alarm | 1 Bit | 1.5 alarm | CRWTU |
| 106 | 2 Pipes Fan Coil M-N-O-P | Control Fan Level 3 | 1 Bit | 1.3 enable | CRWTU |
| 107 | Switch Actuator P | Locking | 1 Bit | 1.3 enable | CRWU |
| 107 | Heating Actuator P | Forced Position | 1 Bit | 1.1 switch | CRWU |
| 107 | Shutter / Blind O-P | Slat Angle Position | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 108 | Heating Actuator P | Mode Change Winter / Summer | 1 Bit | 1.1 switch | CRWTU |
| 108 | Switch Actuator P | Logic Input | 1 Bit | 1.2 boolean | CRWTU |
| 108 | Shutter / Blind O-P | Slat Angle Status | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 109 | Switch Actuator P | Scene | 1 Byte | 18.1 scene control | CRWU |
| 109 | Shutter / Blind O-P | Frost Alarm | 1 Bit | 1.5 alarm | CRWU |
| 109 | 2 Pipes Fan Coil M-N-O-P | Mode Change Cooling / Heating Status | 1 Bit | 1.100 cooling/heating | CRWU |
| 162 | Input 1 | On Off | 1 Bit | 1.1 switch | CRT |
| 162 | Input 1 | Up Down | 1 Bit | 1.8 up/down | CRT |
| 162 | Input 1 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 162 | Input 1 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 162 | Input 1 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 162 | Input 1 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 162 | Input 1 | Value 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 162 | Input 1 | Scene | 1 Byte | 18.1 scene control | RW |
| 162 | Input 1 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 162 | Input 1 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 162 | Input 1 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRWTU |
| 162 | Input 1 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CRWTU |
| 162 | Input 1 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CRWTU |
| 162 | Input 1 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 162 | Input 1 | Step Count Scene | 1 Byte | 18.1 scene control | CRWTU |
| 162 | Input 1 | Short Press On | 1 Bit | 1.1 switch | CRT |
| 162 | Input 1 | Short Press Off | 1 Bit | 1.1 switch | CRT |
| 162 | Input 1 | Short Press On Off | 1 Bit | 1.1 switch | CRT |
| 162 | Input 1 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 162 | Input 1 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 162 | Input 1 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 162 | Input 1 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 162 | Input 1 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 163 | Input 1 | Dimming | 4 Bit | 3.7 dimming control | CRT |
| 163 | Input 1 | Stop / Step | 1 Bit | 1.7 step | CRT |
| 163 | Input 1 | Long Press On | 1 Bit | 1.1 switch | CRT |
| 163 | Input 1 | Long Press Off | 1 Bit | 1.1 switch | CRT |
| 163 | Input 1 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 163 | Input 1 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 163 | Input 1 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 163 | Input 1 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 163 | Input 1 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 163 | Input 1 | Long Press On Off | 1 Bit | 1.1 switch | CRT |
| 164 | Input 1 | Status | 1 Bit | 1.11 state | CRWU |
| 164 | Input 1 | Short Press Status | 1 Bit | 1.11 state | CRWU |
| 165 | Input 1 | Long Press Status | 1 Bit | 1.11 state | CRWU |
| 166 | Input 1 | Locking | 1 Bit | 1.3 enable | CRWU |
| 167 | Input 2 | On Off | 1 Bit | 1.1 switch | CRT |
| 167 | Input 2 | Up Down | 1 Bit | 1.8 up/down | CRT |
| 167 | Input 2 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 167 | Input 2 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 167 | Input 2 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 167 | Input 2 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 167 | Input 2 | Value 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 167 | Input 2 | Scene | 1 Byte | 18.1 scene control | RW |
| 167 | Input 2 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 167 | Input 2 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 167 | Input 2 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRWTU |
| 167 | Input 2 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CRWTU |
| 167 | Input 2 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CRWTU |
| 167 | Input 2 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 167 | Input 2 | Step Count Scene | 1 Byte | 18.1 scene control | CRWTU |
| 167 | Input 2 | Short Press On | 1 Bit | 1.1 switch | CRT |
| 167 | Input 2 | Short Press Off | 1 Bit | 1.1 switch | CRT |
| 167 | Input 2 | Short Press On Off | 1 Bit | 1.1 switch | CRT |
| 167 | Input 2 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 167 | Input 2 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 167 | Input 2 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 167 | Input 2 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 167 | Input 2 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 168 | Input 2 | Dimming | 4 Bit | 3.7 dimming control | CRT |
| 168 | Input 2 | Stop / Step | 1 Bit | 1.7 step | CRT |
| 168 | Input 2 | Long Press On | 1 Bit | 1.1 switch | CRT |
| 168 | Input 2 | Long Press Off | 1 Bit | 1.1 switch | CRT |
| 168 | Input 2 | Long Press On Off | 1 Bit | 1.1 switch | CRT |
| 168 | Input 2 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 168 | Input 2 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 168 | Input 2 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 168 | Input 2 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 168 | Input 2 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 169 | Input 2 | Status | 1 Bit | 1.11 state | CRWU |
| 169 | Input 2 | Short Press Status | 1 Bit | 1.11 state | CRWU |
| 170 | Input 2 | Long Press Status | 1 Bit | 1.11 state | CRWU |
| 171 | Input 2 | Locking | 1 Bit | 1.3 enable | CRWU |
| 172 | Input 3 | On Off | 1 Bit | 1.1 switch | CRT |
| 172 | Input 3 | Up Down | 1 Bit | 1.8 up/down | CRT |
| 172 | Input 3 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 172 | Input 3 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 172 | Input 3 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 172 | Input 3 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 172 | Input 3 | Value 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 172 | Input 3 | Scene | 1 Byte | 18.1 scene control | RW |
| 172 | Input 3 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 172 | Input 3 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 172 | Input 3 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRWTU |
| 172 | Input 3 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CRWTU |
| 172 | Input 3 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CRWTU |
| 172 | Input 3 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 172 | Input 3 | Step Count Scene | 1 Byte | 18.1 scene control | CRWTU |
| 172 | Input 3 | Short Press On | 1 Bit | 1.1 switch | CRT |
| 172 | Input 3 | Short Press Off | 1 Bit | 1.1 switch | CRT |
| 172 | Input 3 | Short Press On Off | 1 Bit | 1.1 switch | CRT |
| 172 | Input 3 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 172 | Input 3 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 172 | Input 3 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 172 | Input 3 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 172 | Input 3 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 173 | Input 3 | Dimming | 4 Bit | 3.7 dimming control | CRT |
| 173 | Input 3 | Stop / Step | 1 Bit | 1.7 step | CRT |
| 173 | Input 3 | Long Press On | 1 Bit | 1.1 switch | CRT |
| 173 | Input 3 | Long Press Off | 1 Bit | 1.1 switch | CRT |
| 173 | Input 3 | Long Press On Off | 1 Bit | 1.1 switch | CRT |
| 173 | Input 3 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 173 | Input 3 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 173 | Input 3 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 173 | Input 3 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 173 | Input 3 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 174 | Input 3 | Status | 1 Bit | 1.11 state | CRWU |
| 174 | Input 3 | Short Press Status | 1 Bit | 1.11 state | CRWTU |
| 175 | Input 3 | Long Press Status | 1 Bit | 1.11 state | CRWU |
| 176 | Input 3 | Locking | 1 Bit | 1.3 enable | CRWU |
| 177 | Input 4 | On Off | 1 Bit | 1.1 switch | CRT |
| 177 | Input 4 | Up Down | 1 Bit | 1.8 up/down | CRT |
| 177 | Input 4 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 177 | Input 4 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 177 | Input 4 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 177 | Input 4 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 177 | Input 4 | Value 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 177 | Input 4 | Scene | 1 Byte | 18.1 scene control | RW |
| 177 | Input 4 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 177 | Input 4 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 177 | Input 4 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRWTU |
| 177 | Input 4 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CRWTU |
| 177 | Input 4 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CRWTU |
| 177 | Input 4 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 177 | Input 4 | Step Count Scene | 1 Byte | 18.1 scene control | CRWTU |
| 177 | Input 4 | Short Press On | 1 Bit | 1.1 switch | CRT |
| 177 | Input 4 | Short Press Off | 1 Bit | 1.1 switch | CRT |
| 177 | Input 4 | Short Press On Off | 1 Bit | 1.1 switch | CRT |
| 177 | Input 4 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 177 | Input 4 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 177 | Input 4 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 177 | Input 4 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 177 | Input 4 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 178 | Input 4 | Dimming | 4 Bit | 3.7 dimming control | CRT |
| 178 | Input 4 | Stop / Step | 1 Bit | 1.7 step | CRT |
| 178 | Input 4 | Long Press On | 1 Bit | 1.1 switch | CRT |
| 178 | Input 4 | Long Press Off | 1 Bit | 1.1 switch | CRT |
| 178 | Input 4 | Long Press On Off | 1 Bit | 1.1 switch | CRT |
| 178 | Input 4 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 178 | Input 4 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 178 | Input 4 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 178 | Input 4 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 178 | Input 4 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 179 | Input 4 | Status | 1 Bit | 1.11 state | CRWU |
| 179 | Input 4 | Short Press Status | 1 Bit | 1.11 state | CRWTU |
| 180 | Input 4 | Long Press Status | 1 Bit | 1.11 state | CRWU |
| 181 | Input 4 | Locking | 1 Bit | 1.3 enable | CRWU |
| 182 | Input 5 | On Off | 1 Bit | 1.1 switch | CRT |
| 182 | Input 5 | Up Down | 1 Bit | 1.8 up/down | CRT |
| 182 | Input 5 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 182 | Input 5 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 182 | Input 5 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 182 | Input 5 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 182 | Input 5 | Value 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 182 | Input 5 | Scene | 1 Byte | 18.1 scene control | RW |
| 182 | Input 5 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 182 | Input 5 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 182 | Input 5 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRWTU |
| 182 | Input 5 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CRWTU |
| 182 | Input 5 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CRWTU |
| 182 | Input 5 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 182 | Input 5 | Step Count Scene | 1 Byte | 18.1 scene control | CRWTU |
| 182 | Input 5 | Short Press On | 1 Bit | 1.1 switch | CRT |
| 182 | Input 5 | Short Press Off | 1 Bit | 1.1 switch | CRT |
| 182 | Input 5 | Short Press On Off | 1 Bit | 1.1 switch | CRT |
| 182 | Input 5 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 182 | Input 5 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 182 | Input 5 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 182 | Input 5 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 182 | Input 5 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 183 | Input 5 | Dimming | 4 Bit | 3.7 dimming control | CRT |
| 183 | Input 5 | Stop / Step | 1 Bit | 1.7 step | CRT |
| 183 | Input 5 | Long Press On | 1 Bit | 1.1 switch | CRT |
| 183 | Input 5 | Long Press Off | 1 Bit | 1.1 switch | CRT |
| 183 | Input 5 | Long Press On Off | 1 Bit | 1.1 switch | CRT |
| 183 | Input 5 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 183 | Input 5 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 183 | Input 5 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 183 | Input 5 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 183 | Input 5 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 184 | Input 5 | Status | 1 Bit | 1.11 state | CRWU |
| 184 | Input 5 | Short Press Status | 1 Bit | 1.11 state | CRWTU |
| 185 | Input 5 | Long Press Status | 1 Bit | 1.11 state | CRWU |
| 186 | Input 5 | Locking | 1 Bit | 1.3 enable | CRWU |
| 187 | Input 6 | On Off | 1 Bit | 1.1 switch | CRT |
| 187 | Input 6 | Up Down | 1 Bit | 1.8 up/down | CRT |
| 187 | Input 6 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 187 | Input 6 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 187 | Input 6 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 187 | Input 6 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 187 | Input 6 | Value 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 187 | Input 6 | Scene | 1 Byte | 18.1 scene control | RW |
| 187 | Input 6 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 187 | Input 6 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 187 | Input 6 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRWTU |
| 187 | Input 6 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CRWTU |
| 187 | Input 6 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CRWTU |
| 187 | Input 6 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 187 | Input 6 | Step Count Scene | 1 Byte | 18.1 scene control | CRWTU |
| 187 | Input 6 | Short Press On | 1 Bit | 1.1 switch | CRT |
| 187 | Input 6 | Short Press Off | 1 Bit | 1.1 switch | CRT |
| 187 | Input 6 | Short Press On Off | 1 Bit | 1.1 switch | CRT |
| 187 | Input 6 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 187 | Input 6 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 187 | Input 6 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 187 | Input 6 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 187 | Input 6 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 188 | Input 6 | Dimming | 4 Bit | 3.7 dimming control | CRT |
| 188 | Input 6 | Stop / Step | 1 Bit | 1.7 step | CRT |
| 188 | Input 6 | Long Press On | 1 Bit | 1.1 switch | CRT |
| 188 | Input 6 | Long Press Off | 1 Bit | 1.1 switch | CRT |
| 188 | Input 6 | Long Press On Off | 1 Bit | 1.1 switch | CRT |
| 188 | Input 6 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 188 | Input 6 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 188 | Input 6 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 188 | Input 6 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 188 | Input 6 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 189 | Input 6 | Status | 1 Bit | 1.11 state | CRWU |
| 189 | Input 6 | Short Press Status | 1 Bit | 1.11 state | CRWTU |
| 190 | Input 6 | Long Press Status | 1 Bit | 1.11 state | CRWU |
| 191 | Input 6 | Locking | 1 Bit | 1.3 enable | CRWU |
| 192 | Input 7 | On Off | 1 Bit | 1.1 switch | CRT |
| 192 | Input 7 | Up Down | 1 Bit | 1.8 up/down | CRT |
| 192 | Input 7 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 192 | Input 7 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 192 | Input 7 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 192 | Input 7 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 192 | Input 7 | Value 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 192 | Input 7 | Scene | 1 Byte | 18.1 scene control | RW |
| 192 | Input 7 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 192 | Input 7 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 192 | Input 7 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRWTU |
| 192 | Input 7 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CRWTU |
| 192 | Input 7 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CRWTU |
| 192 | Input 7 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 192 | Input 7 | Step Count Scene | 1 Byte | 18.1 scene control | CRWTU |
| 192 | Input 7 | Short Press On | 1 Bit | 1.1 switch | CRT |
| 192 | Input 7 | Short Press Off | 1 Bit | 1.1 switch | CRT |
| 192 | Input 7 | Short Press On Off | 1 Bit | 1.1 switch | CRT |
| 192 | Input 7 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 192 | Input 7 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 192 | Input 7 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 192 | Input 7 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 192 | Input 7 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 193 | Input 7 | Dimming | 4 Bit | 3.7 dimming control | CRT |
| 193 | Input 7 | Stop / Step | 1 Bit | 1.7 step | CRT |
| 193 | Input 7 | Long Press On | 1 Bit | 1.1 switch | CRT |
| 193 | Input 7 | Long Press Off | 1 Bit | 1.1 switch | CRT |
| 193 | Input 7 | Long Press On Off | 1 Bit | 1.1 switch | CRT |
| 193 | Input 7 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 193 | Input 7 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 193 | Input 7 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 193 | Input 7 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 193 | Input 7 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 194 | Input 7 | Status | 1 Bit | 1.11 state | CRWU |
| 194 | Input 7 | Short Press Status | 1 Bit | 1.11 state | CRWTU |
| 195 | Input 7 | Long Press Status | 1 Bit | 1.11 state | CRWU |
| 196 | Input 7 | Locking | 1 Bit | 1.3 enable | CRWU |
| 197 | Input 8 | On Off | 1 Bit | 1.1 switch | CRT |
| 197 | Input 8 | Up Down | 1 Bit | 1.8 up/down | CRT |
| 197 | Input 8 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 197 | Input 8 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 197 | Input 8 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 197 | Input 8 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 197 | Input 8 | Value 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 197 | Input 8 | Scene | 1 Byte | 18.1 scene control | RW |
| 197 | Input 8 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 197 | Input 8 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 197 | Input 8 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRWTU |
| 197 | Input 8 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CRWTU |
| 197 | Input 8 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CRWTU |
| 197 | Input 8 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 197 | Input 8 | Step Count Scene | 1 Byte | 18.1 scene control | CRWTU |
| 197 | Input 8 | Short Press On | 1 Bit | 1.1 switch | CRT |
| 197 | Input 8 | Short Press Off | 1 Bit | 1.1 switch | CRT |
| 197 | Input 8 | Short Press On Off | 1 Bit | 1.1 switch | CRT |
| 197 | Input 8 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 197 | Input 8 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 197 | Input 8 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 197 | Input 8 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 197 | Input 8 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 198 | Input 8 | Dimming | 4 Bit | 3.7 dimming control | CRT |
| 198 | Input 8 | Stop / Step | 1 Bit | 1.7 step | CRT |
| 198 | Input 8 | Long Press On | 1 Bit | 1.1 switch | CRT |
| 198 | Input 8 | Long Press Off | 1 Bit | 1.1 switch | CRT |
| 198 | Input 8 | Long Press On Off | 1 Bit | 1.1 switch | CRT |
| 198 | Input 8 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 198 | Input 8 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 198 | Input 8 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 198 | Input 8 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 198 | Input 8 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 199 | Input 8 | Status | 1 Bit | 1.11 state | CRWU |
| 199 | Input 8 | Short Press Status | 1 Bit | 1.11 state | CRWTU |
| 200 | Input 8 | Long Press Status | 1 Bit | 1.11 state | CRWU |
| 201 | Input 8 | Locking | 1 Bit | 1.3 enable | CRWU |
| 202 | Input 9 | On Off | 1 Bit | 1.1 switch | CRT |
| 202 | Input 9 | Up Down | 1 Bit | 1.8 up/down | CRT |
| 202 | Input 9 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 202 | Input 9 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 202 | Input 9 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 202 | Input 9 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 202 | Input 9 | Value 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 202 | Input 9 | Scene | 1 Byte | 18.1 scene control | RW |
| 202 | Input 9 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 202 | Input 9 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 202 | Input 9 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRWTU |
| 202 | Input 9 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CRWTU |
| 202 | Input 9 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CRWTU |
| 202 | Input 9 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 202 | Input 9 | Step Count Scene | 1 Byte | 18.1 scene control | CRWTU |
| 202 | Input 9 | Short Press On | 1 Bit | 1.1 switch | CRT |
| 202 | Input 9 | Short Press Off | 1 Bit | 1.1 switch | CRT |
| 202 | Input 9 | Short Press On Off | 1 Bit | 1.1 switch | CRT |
| 202 | Input 9 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 202 | Input 9 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 202 | Input 9 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 202 | Input 9 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 202 | Input 9 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 203 | Input 9 | Dimming | 4 Bit | 3.7 dimming control | CRT |
| 203 | Input 9 | Stop / Step | 1 Bit | 1.7 step | CRT |
| 203 | Input 9 | Long Press On | 1 Bit | 1.1 switch | CRT |
| 203 | Input 9 | Long Press Off | 1 Bit | 1.1 switch | CRT |
| 203 | Input 9 | Long Press On Off | 1 Bit | 1.1 switch | CRT |
| 203 | Input 9 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 203 | Input 9 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 203 | Input 9 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 203 | Input 9 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 203 | Input 9 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 204 | Input 9 | Status | 1 Bit | 1.11 state | CRWU |
| 204 | Input 9 | Short Press Status | 1 Bit | 1.11 state | CRWTU |
| 205 | Input 9 | Long Press Status | 1 Bit | 1.11 state | CRWU |
| 206 | Input 9 | Locking | 1 Bit | 1.3 enable | CRWU |
| 207 | Input 10 | On Off | 1 Bit | 1.1 switch | CRT |
| 207 | Input 10 | Up Down | 1 Bit | 1.8 up/down | CRT |
| 207 | Input 10 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 207 | Input 10 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 207 | Input 10 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 207 | Input 10 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 207 | Input 10 | Value 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 207 | Input 10 | Scene | 1 Byte | 18.1 scene control | RW |
| 207 | Input 10 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 207 | Input 10 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 207 | Input 10 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRWTU |
| 207 | Input 10 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CRWTU |
| 207 | Input 10 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CRWTU |
| 207 | Input 10 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 207 | Input 10 | Step Count Scene | 1 Byte | 18.1 scene control | CRWTU |
| 207 | Input 10 | Short Press On | 1 Bit | 1.1 switch | CRT |
| 207 | Input 10 | Short Press Off | 1 Bit | 1.1 switch | CRT |
| 207 | Input 10 | Short Press On Off | 1 Bit | 1.1 switch | CRT |
| 207 | Input 10 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 207 | Input 10 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 207 | Input 10 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 207 | Input 10 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 207 | Input 10 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 208 | Input 10 | Dimming | 4 Bit | 3.7 dimming control | CRT |
| 208 | Input 10 | Stop / Step | 1 Bit | 1.7 step | CRT |
| 208 | Input 10 | Long Press On | 1 Bit | 1.1 switch | CRT |
| 208 | Input 10 | Long Press Off | 1 Bit | 1.1 switch | CRT |
| 208 | Input 10 | Long Press On Off | 1 Bit | 1.1 switch | CRT |
| 208 | Input 10 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 208 | Input 10 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 208 | Input 10 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 208 | Input 10 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 208 | Input 10 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 209 | Input 10 | Status | 1 Bit | 1.11 state | CRWU |
| 209 | Input 10 | Short Press Status | 1 Bit | 1.11 state | CRWTU |
| 210 | Input 10 | Long Press Status | 1 Bit | 1.11 state | CRWU |
| 211 | Input 10 | Locking | 1 Bit | 1.3 enable | CRWU |
| 212 | Input 11 | On Off | 1 Bit | 1.1 switch | CRT |
| 212 | Input 11 | Up Down | 1 Bit | 1.8 up/down | CRT |
| 212 | Input 11 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 212 | Input 11 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 212 | Input 11 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 212 | Input 11 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 212 | Input 11 | Value 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 212 | Input 11 | Scene | 1 Byte | 18.1 scene control | RW |
| 212 | Input 11 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 212 | Input 11 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 212 | Input 11 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRWTU |
| 212 | Input 11 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CRWTU |
| 212 | Input 11 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CRWTU |
| 212 | Input 11 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 212 | Input 11 | Step Count Scene | 1 Byte | 18.1 scene control | CRWTU |
| 212 | Input 11 | Short Press On | 1 Bit | 1.1 switch | CRT |
| 212 | Input 11 | Short Press Off | 1 Bit | 1.1 switch | CRT |
| 212 | Input 11 | Short Press On Off | 1 Bit | 1.1 switch | CRT |
| 212 | Input 11 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 212 | Input 11 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 212 | Input 11 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 212 | Input 11 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 212 | Input 11 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 213 | Input 11 | Dimming | 4 Bit | 3.7 dimming control | CRT |
| 213 | Input 11 | Stop / Step | 1 Bit | 1.7 step | CRT |
| 213 | Input 11 | Long Press On | 1 Bit | 1.1 switch | CRT |
| 213 | Input 11 | Long Press Off | 1 Bit | 1.1 switch | CRT |
| 213 | Input 11 | Long Press On Off | 1 Bit | 1.1 switch | CRT |
| 213 | Input 11 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 213 | Input 11 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 213 | Input 11 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 213 | Input 11 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 213 | Input 11 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 214 | Input 11 | Status | 1 Bit | 1.11 state | CRWU |
| 214 | Input 11 | Short Press Status | 1 Bit | 1.11 state | CRWTU |
| 215 | Input 11 | Long Press Status | 1 Bit | 1.11 state | CRWU |
| 216 | Input 11 | Locking | 1 Bit | 1.3 enable | CRWU |
| 217 | Input 12 | On Off | 1 Bit | 1.1 switch | CRT |
| 217 | Input 12 | Up Down | 1 Bit | 1.8 up/down | CRT |
| 217 | Input 12 | Value 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 217 | Input 12 | Value Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 217 | Input 12 | Value Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 217 | Input 12 | Value Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 217 | Input 12 | Value 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 217 | Input 12 | Scene | 1 Byte | 18.1 scene control | RW |
| 217 | Input 12 | Step Count Percentage | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 217 | Input 12 | Step Count Temperature °C | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 217 | Input 12 | Step Count Temperature °F | 2 Bytes | 9.27 temperature (°F) | CRWTU |
| 217 | Input 12 | Step Count Luminosity | 2 Bytes | 9.4 lux (Lux) | CRWTU |
| 217 | Input 12 | Step Count 2 Byte | 2 Bytes | 7.1 pulses | CRWTU |
| 217 | Input 12 | Step Count 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 217 | Input 12 | Step Count Scene | 1 Byte | 18.1 scene control | CRWTU |
| 217 | Input 12 | Short Press On | 1 Bit | 1.1 switch | CRT |
| 217 | Input 12 | Short Press Off | 1 Bit | 1.1 switch | CRT |
| 217 | Input 12 | Short Press On Off | 1 Bit | 1.1 switch | CRT |
| 217 | Input 12 | Short Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 217 | Input 12 | Short Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 217 | Input 12 | Short Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 217 | Input 12 | Short Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 217 | Input 12 | Short Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 218 | Input 12 | Dimming | 4 Bit | 3.7 dimming control | CRT |
| 218 | Input 12 | Stop / Step | 1 Bit | 1.7 step | CRT |
| 218 | Input 12 | Long Press On | 1 Bit | 1.1 switch | CRT |
| 218 | Input 12 | Long Press Off | 1 Bit | 1.1 switch | CRT |
| 218 | Input 12 | Long Press On Off | 1 Bit | 1.1 switch | CRT |
| 218 | Input 12 | Long Press Percentage | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 218 | Input 12 | Long Press Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 218 | Input 12 | Long Press Luminosity | 2 Bytes | 9.4 lux (Lux) | CRT |
| 218 | Input 12 | Long Press 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 218 | Input 12 | Long Press 2 Byte | 2 Bytes | 7.1 pulses | CRT |
| 219 | Input 12 | Status | 1 Bit | 1.11 state | CRWU |
| 219 | Input 12 | Short Press Status | 1 Bit | 1.11 state | CRWTU |
| 220 | Input 12 | Long Press Status | 1 Bit | 1.11 state | CRWU |
| 221 | Input 12 | Locking | 1 Bit | 1.3 enable | CRWU |
| 222 | Converter 1 | Input 1 Bit | 1 Bit | 1.1 switch | CRWU |
| 222 | Converter 1 | Input 2 Bit | 2 Bit | 2.1 switch control | CRWU |
| 222 | Converter 1 | Input 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWU |
| 222 | Converter 1 | Input 2 Byte | 2 Bytes | 7.1 pulses | CRWU |
| 223 | Converter 1 | Output 1 Bit | 1 Bit | 1.1 switch | CRU |
| 223 | Converter 1 | Output 2 Bit | 2 Bit | 2.1 switch control | CRU |
| 223 | Converter 1 | Output 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRU |
| 223 | Converter 1 | Output 2 Byte | 2 Bytes | 7.1 pulses | CRU |
| 224 | Converter 2 | Input 1 Bit | 1 Bit | 1.1 switch | CRWU |
| 224 | Converter 2 | Input 2 Bit | 2 Bit | 2.1 switch control | CRWU |
| 224 | Converter 2 | Input 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWU |
| 224 | Converter 2 | Input 2 Byte | 2 Bytes | 7.1 pulses | CRWU |
| 225 | Converter 2 | Output 1 Bit | 1 Bit | 1.1 switch | CRU |
| 225 | Converter 2 | Output 2 Bit | 2 Bit | 2.1 switch control | CRU |
| 225 | Converter 2 | Output 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRU |
| 225 | Converter 2 | Output 2 Byte | 2 Bytes | 7.1 pulses | CRU |
| 226 | Converter 3 | Input 1 Bit | 1 Bit | 1.1 switch | CRWU |
| 226 | Converter 3 | Input 2 Bit | 2 Bit | 2.1 switch control | CRWU |
| 226 | Converter 3 | Input 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWU |
| 226 | Converter 3 | Input 2 Byte | 2 Bytes | 7.1 pulses | CRWU |
| 227 | Converter 3 | Output 1 Bit | 1 Bit | 1.1 switch | CRU |
| 227 | Converter 3 | Output 2 Bit | 2 Bit | 2.1 switch control | CRU |
| 227 | Converter 3 | Output 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRU |
| 227 | Converter 3 | Output 2 Byte | 2 Bytes | 7.1 pulses | CRU |
| 228 | Converter 4 | Input 1 Bit | 1 Bit | 1.1 switch | CRWU |
| 228 | Converter 4 | Input 2 Bit | 2 Bit | 2.1 switch control | CRWU |
| 228 | Converter 4 | Input 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRWU |
| 228 | Converter 4 | Imput 2 Byte | 2 Bytes | 7.1 pulses | CRWU |
| 229 | Converter 4 | Output 1 Bit | 1 Bit | 1.1 switch | CRU |
| 229 | Converter 4 | Output 2 Bit | 2 Bit | 2.1 switch control | CRU |
| 229 | Converter 4 | Output 1 Byte | 1 Byte | 5.10 counter pulses (0..255) | CRU |
| 229 | Converter 4 | Output 2 Byte | 2 Bytes | 7.1 pulses | CRU |
| 230 | Logic Input 1 | Input Gate 1 | 1 Bit | 1.2 boolean | CRWU |
| 231 | Logic Input 1 | Input Gate 2 | 1 Bit | 1.2 boolean | CRWU |
| 232 | Logic Input 1 | Input Gate 3 | 1 Bit | 1.2 boolean | CRWU |
| 233 | Logic Input 1 | Input Gate 4 | 1 Bit | 1.2 boolean | CRWU |
| 234 | Logic Output 1 | Output Result | 1 Bit | 1.2 boolean | CRWU |
| 235 | Logic Input 2 | Input Gate 1 | 1 Bit | 1.2 boolean | CRWU |
| 236 | Logic Input 2 | Input Gate 2 | 1 Bit | 1.2 boolean | CRWU |
| 237 | Logic Input 2 | Input Gate 3 | 1 Bit | 1.2 boolean | CRWU |
| 238 | Logic Input 2 | Input Gate 4 | 1 Bit | 1.2 boolean | CRWU |
| 239 | Logic Output 2 | Output Result | 1 Bit | 1.2 boolean | CRWU |
| 240 | Logic Input 3 | Input Gate 1 | 1 Bit | 1.2 boolean | CRWU |
| 241 | Logic Input 3 | Input Gate 2 | 1 Bit | 1.2 boolean | CRWU |
| 242 | Logic Input 3 | Input Gate 3 | 1 Bit | 1.2 boolean | CRWU |
| 243 | Logic Input 3 | Input Gate 4 | 1 Bit | 1.2 boolean | CRWU |
| 244 | Logic Output 3 | Output Result | 1 Bit | 1.2 boolean | CRWU |
| 245 | Logic Input 4 | Input Gate 1 | 1 Bit | 1.2 boolean | CRWU |
| 246 | Logic Input 4 | Input Gate 2 | 1 Bit | 1.2 boolean | CRWU |
| 247 | Logic Input 4 | Input Gate 3 | 1 Bit | 1.2 boolean | CRWU |
| 248 | Logic Input 4 | Input Gate 4 | 1 Bit | 1.2 boolean | CRWU |
| 249 | Logic Output 4 | Output Result | 1 Bit | 1.2 boolean | CRWU |
| 250 | FTR-MSA1612.1.1 | Device Notification | 1 Bit | 1.2 boolean | CRT |
| 251 | FTR-MSA1612.1.1 | Device Buttons Active | 1 Bit | 1.3 enable | CRTU |
| 252 | FTR-MSA1612.1.1 | Device LEDs Active | 1 Bit | 1.3 enable | CRWT |