ABB AG - STOTZ-KONTAKT 2CDG 120 061 R0011 VAA/A6.24.2 Floor heating-Controller,6-fold

VAA/A6.24.2 Floor heating-Controller,6-fold 2CDG 120 061 R0011

ABB AG - STOTZ-KONTAKT · Order number 2CDG 120 061 R0011 · Heating, Ventilation and Air Conditioning › Valve Drive Actuators

Floor heating-Controller, 6-fold/1.0a

Download .knxprod Floor heating-Controller, 6-fold/1.0a 1.0 · 112 KB

Product

ManufacturerABB AG - STOTZ-KONTAKT
Product nameVAA/A6.24.2 Floor heating-Controller,6-fold
Order number2CDG 120 061 R0011
HardwareHMT 6 S
MediumTwisted Pair
Bus current (mA)7.5
Rail mountedYes
Width (mm)290
RegistrationRegistered · 2018-09-05
Languagesen-US, de-DE
Catalog entryM-0002_H-4900373-1-O0048_HP-490A-10-33AA-O0048_CI-2CDG.20120.20061.20R0011-1
Fingerprint33AA
SHA-25668a24496ff72175996af90c264634c96093867be503bd2cc7155b2c032f9d427
First seen2026-11-25
Markets59 markets

Application program: Floor heating-Controller, 6-fold/1.0a 1.0

Application number$490A
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version4.0
Parameters418
Group objects129
Group objects (129)
NoNameFunctionSizeDPTFlags
1Channel H1Base setpoint value2 Bytes9.1 temperature (°C)CRW
1Channel H1Switching actuating value1 Bit1.1 switchCRWU
1Channel H1Continuous actuating value1 Byte5.1 percentage (0..100%)CRWU
2Channel H1Manual set point offset2 Bytes9.2 temperature difference (K)CRW
3Channel H1Actual value2 Bytes9.1 temperature (°C)CRWU
4Channel H1Operating mode preset1 Byte20.102 HVAC modeCRW
4Channel H1Current actuating value1 Byte5.1 percentage (0..100%)CRTU
5Channel H1Presence1 Bit1.18 occupancyCRW
6Channel H1Window position1 Bit1.19 window/doorCRW
7Channel H1Current operating mode1 Byte20.102 HVAC modeCRT
8Channel H1Heating actuating value1 Byte5.1 percentage (0..100%)CRT
8Channel H1Heat & cool actuating values1 Byte5.1 percentage (0..100%)CRT
9Channel H1Cooling actuating value1 Byte5.1 percentage (0..100%)CRT
10Channel H1Heating = 0, Cooling = 11 Bit1.1 switchCRWU
10Channel H1Heating = 1, Cooling = 01 Bit1.100 heating/coolingCRWU
11Channel H1Current setpoint value2 Bytes9.1 temperature (°C)CRWT
12Channel H1Report actuating value failure1 Bit1.5 alarmCRTU
12Channel H1Report actual value failure1 Bit1.5 alarmCRTU
13Channel H1Forced operation mode1 Bit1.3 enableCRWU
14Channel H1Overcurr./short circuit1 Bit1.5 alarmCRTU
21Channel H2Continuous actuating value1 Byte5.1 percentage (0..100%)CRWU
21Channel H2Switching actuating value1 Bit1.1 switchCRWU
21Channel H2Base setpoint2 Bytes9.1 temperature (°C)CRW
22Channel H2Manual setpoint offset2 Bytes9.2 temperature difference (K)CRW
23Channel H2Actual value2 Bytes9.1 temperature (°C)CRWU
24Channel H2Current actuating value1 Byte5.1 percentage (0..100%)CRTU
24Channel H2Operating mode preset1 Byte20.102 HVAC modeCRW
25Channel H2Presence1 Bit1.18 occupancyCRW
26Channel H2Window setting1 Bit1.19 window/doorCRW
27Channel H2Current operating mode1 Byte20.102 HVAC modeCRT
28Channel H2Heating actuating value1 Byte5.1 percentage (0..100%)CRT
28Channel H2Heating and cooling actuating value1 Byte5.1 percentage (0..100%)CRT
29Channel H2Cooling actuating value1 Byte5.1 percentage (0..100%)CRT
30Channel H2Heating = 0, cooling = 11 Bit1.1 switchCRWU
30Channel H2Heating = 1, cooling = 01 Bit1.100 heating/coolingCRWU
31Channel H2Current setpoint2 Bytes9.1 temperature (°C)CRWT
32Channel H2Report actuating value failure1 Bit1.5 alarmCRTU
32Channel H2Report actual value failure1 Bit1.5 alarmCRTU
33Channel H2Forced operation1 Bit1.3 enableCRWU
34Channel H2Overcurrent/short circuit1 Bit1.5 alarmCRTU
41Channel H3Continuous actuating value1 Byte5.1 percentage (0..100%)CRWU
41Channel H3Switching actuating value1 Bit1.1 switchCRWU
41Channel H3Base setpoint2 Bytes9.1 temperature (°C)CRW
42Channel H3Manual setpoint offset2 Bytes9.2 temperature difference (K)CRW
43Channel H3Actual value2 Bytes9.1 temperature (°C)CRWU
44Channel H3Current actuating value1 Byte5.1 percentage (0..100%)CRTU
44Channel H3Operating mode preset1 Byte20.102 HVAC modeCRW
45Channel H3Presence1 Bit1.18 occupancyCRW
46Channel H3Window setting1 Bit1.19 window/doorCRW
47Channel H3Current operating mode1 Byte20.102 HVAC modeCRT
48Channel H3Heating actuating value1 Byte5.1 percentage (0..100%)CRT
48Channel H3Heating and cooling actuating value1 Byte5.1 percentage (0..100%)CRT
49Channel H3Cooling actuating value1 Byte5.1 percentage (0..100%)CRT
50Channel H3Heating = 0, cooling = 11 Bit1.1 switchCRWU
50Channel H3Heating = 1, cooling = 01 Bit1.100 heating/coolingCRWU
51Channel H3Current setpoint2 Bytes9.1 temperature (°C)CRWT
52Channel H3Report actuating value failure1 Bit1.5 alarmCRTU
52Channel H3Report actual value failure1 Bit1.5 alarmCRTU
53Channel H3Forced operation1 Bit1.3 enableCRWU
54Channel H3Overcurrent/short circuit1 Bit1.5 alarmCRTU
61Channel H4Continuous actuating value1 Byte5.1 percentage (0..100%)CRWU
61Channel H4Switching actuating value1 Bit1.1 switchCRWU
61Channel H4Base setpoint2 Bytes9.1 temperature (°C)CRW
62Channel H4Manual setpoint offset2 Bytes9.2 temperature difference (K)CRW
63Channel H4Actual value2 Bytes9.1 temperature (°C)CRWU
64Channel H4Current actuating value1 Byte5.1 percentage (0..100%)CRTU
64Channel H4Operating mode preset1 Byte20.102 HVAC modeCRW
65Channel H4Presence1 Bit1.18 occupancyCRW
66Channel H4Window setting1 Bit1.19 window/doorCRW
67Channel H4Current operating mode1 Byte20.102 HVAC modeCRT
68Channel H4Heating actuating value1 Byte5.1 percentage (0..100%)CRT
68Channel H4Heating and cooling actuating value1 Byte5.1 percentage (0..100%)CRT
69Channel H4Cooling actuating value1 Byte5.1 percentage (0..100%)CRT
70Channel H4Heating = 0, cooling = 11 Bit1.1 switchCRWU
70Channel H4Heating = 1, cooling = 01 Bit1.100 heating/coolingCRWU
71Channel H4Current setpoint2 Bytes9.1 temperature (°C)CRWT
72Channel H4Report actuating value failure1 Bit1.5 alarmCRTU
72Channel H4Report actual value failure1 Bit1.5 alarmCRTU
73Channel H4Forced operation1 Bit1.3 enableCRWU
74Channel H4Overcurrent/short circuit1 Bit1.5 alarmCRTU
81Channel H5Continuous actuating value1 Byte5.1 percentage (0..100%)CRWU
81Channel H5Switching actuating value1 Bit1.1 switchCRWU
81Channel H5Base setpoint2 Bytes9.1 temperature (°C)CRW
82Channel H5Manual setpoint offset2 Bytes9.2 temperature difference (K)CRW
83Channel H5Actual value2 Bytes9.1 temperature (°C)CRWU
84Channel H5Current actuating value1 Byte5.1 percentage (0..100%)CRTU
84Channel H5Operating mode preset1 Byte20.102 HVAC modeCRW
85Channel H5Presence1 Bit1.18 occupancyCRW
86Channel H5Window setting1 Bit1.19 window/doorCRW
87Channel H5Current operating mode1 Byte20.102 HVAC modeCRT
88Channel H5Heating actuating value1 Byte5.1 percentage (0..100%)CRT
88Channel H5Heating and cooling actuating value1 Byte5.1 percentage (0..100%)CRT
89Channel H5Cooling actuating value1 Byte5.1 percentage (0..100%)CRT
90Channel H5Heating = 0, cooling = 11 Bit1.1 switchCRWU
90Channel H5Heating = 1, cooling = 01 Bit1.100 heating/coolingCRWU
91Channel H5Current setpoint2 Bytes9.1 temperature (°C)CRWT
92Channel H5Report actuating value failure1 Bit1.5 alarmCRTU
92Channel H5Report actual value failure1 Bit1.5 alarmCRTU
93Channel H5Forced operation1 Bit1.3 enableCRWU
94Channel H5Overcurrent/short circuit1 Bit1.5 alarmCRTU
101Channel H6Continuous actuating value1 Byte5.1 percentage (0..100%)CRWU
101Channel H6Switching actuating value1 Bit1.1 switchCRWU
101Channel H6Base setpoint2 Bytes9.1 temperature (°C)CRW
102Channel H6Manual setpoint offset2 Bytes9.2 temperature difference (K)CRW
103Channel H6Actual value2 Bytes9.1 temperature (°C)CRWU
104Channel H6Current actuating value1 Byte5.1 percentage (0..100%)CRTU
104Channel H6Operating mode preset1 Byte20.102 HVAC modeCRW
105Channel H6Presence1 Bit1.18 occupancyCRW
106Channel H6Window setting1 Bit1.19 window/doorCRW
107Channel H6Current operating mode1 Byte20.102 HVAC modeCRT
108Channel H6Heating actuating value1 Byte5.1 percentage (0..100%)CRT
108Channel H6Heating and cooling actuating value1 Byte5.1 percentage (0..100%)CRT
109Channel H6Cooling actuating value1 Byte5.1 percentage (0..100%)CRT
110Channel H6Heating = 0, cooling = 11 Bit1.1 switchCRWU
110Channel H6Heating = 1, cooling = 01 Bit1.100 heating/coolingCRWU
111Channel H6Current setpoint2 Bytes9.1 temperature (°C)CRWT
112Channel H6Report actuating value failure1 Bit1.5 alarmCRTU
112Channel H6Report actual value failure1 Bit1.5 alarmCRTU
113Channel H6Forced operation1 Bit1.3 enableCRWU
114Channel H6Overcurrent/short circuit1 Bit1.5 alarmCRTU
241H1 - H6Summer mode ON/OFF1 Bit1.3 enableCRWU
242H1 - H6Highest actuating value1 Byte5.1 percentage (0..100%)CRWTU
244H1 - H6Pump ON/OFF1 Bit1.1 switchCRTU
245H1 - H6Pump relay status1 Bit1.1 switchCRTU
246H1 - H6Outside temperature2 Bytes9.1 temperature (°C)CRWU
247H1 - H6Outside temperature failure1 Bit1.5 alarmCRTU
248H1 - H6Manual1 Bit1.1 switchCRWTU
249Version of bus coupling unitSend14 Bytes16.1 Character String (ISO 8859-1)CRTU
250Firmware versionSend14 Bytes16.1 Character String (ISO 8859-1)CRTU
Parameters (105)
ParameterTypeDefault
Channel functionlistHeating actuator
Type of actuating valuelistContinuous..
Include in summer modelistno
Activate valve protectionlistyes
Valve protection disable telegramlist1 = Block (standard)
Monitoring actuating valuelistno
Execute valve protectionlistAlways
Monitor actual valuelistno
-listMinutes
Activate compulsory functionlistno
Type of valve controllistswitch output
Actuator direction of operationlistStandard: 1 = Open valve
Output voltage at 0%list0 V
Output voltage at 100%list10 V
Output voltage at 100%list0 V
Output voltage at 0%list10 V
Switchover between heating and coolinglistautomatic
Channel processes actuating value forlistHeating
Output of the cooling actuating valuelistOn separate object
Minimum actuating valuelist0%
Maximum actuating valuelist90%
Send heating actuating value in cycleslistWith change of 5 %
Take channel into account for highest actuating valuelistyes
Send current actuating value in cycleslistNot cyclical, only in the event of change
Actuating value when value violates the min./max. actuating valuelist0 = 0%, otherwise use set actuating values
Send current actuating valuelistWith change of 5 %
Control pumplistvia relay
Actuation cycle time (PWM period)list10 min
Controlliststandard
Control functions usedlistOnly heating control
Operating mode after resetlistStandby
Type of presence sensorlistPresence detector
Comfort extension by presence buttons in night modelist2 hours
Sends the current operating mode in cycleslistNot cyclical, only in the event of change
System typelistRadiator heating system
Send heating actuating value in cycleslistNot cyclical, only in the event of change
Setting the control parameterslistVia installation type
Proportional band of heating controllist2 K
Integrated time of heating controllist10 h
Base setpoint value after loading the applicationlist21 °C
Minimum valid base setpoint valuelist10 °C
Maximum valid base setpoint valuelist32 °C
Reduction in standby mode (during heating)list1,5 K
Reduction in night mode (during heating)list5 K
Setpoint value for frost protection operation (during heating)list5 °C
Maximum valid setpoint offsetlist+/- 5 K
Setpoint offset applieslistIn comfort, standby and night mode
Current setpoint value in comfort modelistSends actual value (heating < > cooling)
Send current setpoint value in cycleslistNot cyclical, only in the event of change
Proportional band of the cooling controllist4 K
Integrated time of the cooling controllist180 min.
System typelistCooling surface
Send cooling actuating valuelistWith change of 5 %
Sends the cooling actuating value in cycleslistNot cyclical, only in the event of change
Format object heating/coolinglistDPT100 (Heating= 1 / Cooling=0)
Dead zone between heating and coolinglist2 K
Increase in standby mode (during cooling)list1,5 K
Increase in night mode (during cooling)list5 K
Setpoint value for heat protection mode (during cooling)list42 °C i.e. no real heat protection
Actuating value for emergency program islistFixed
Emergency program active when outside temperature belowlist10 °C
Max. actuating value in emergency programlist40%
Fixed emergency program with failure of outside temperaturelist20%
Fixed emergency program in winter modelist20%
Actuating value in the forced operation modelist0%
Forced telegramlist1 = Force (standard)
TypelistHMT 6 S..
Monitoring timelist30 min.
Status of monitoringlistReport only in the event of malfunction
Send status in cycleslistno
Cycle timelistEvery 30 min.
Only switch on relay if at least (only for switch output)listone input actuating value is > 0 %
Switch-off delaylist10 min
Send relay status cyclicallylistno, only in the event of change
Switch on telegram only if at least (only for switch output)listone input actuating value is > 0 %
Send pump control in cycleslistno, only in the event of change
Function of manual push buttonlistvalid until reset via object
Manual operation of channelslistenabled
Send highest actuating value (If continuous actuating value used)listonly if own actuating value is greater
Monitor actuating valuelistno
Sends heating actuating valuelistWith change of 5 %
Actuating value when value violates the min./max. actuating valuelist0 = 0%, otherwise use set actuating values
Comfort extension by presence button in night modelist2 hours
Sends the current operating mode in cycleslistNot cyclical, only in the event of change
Installation typelistRadiator heating system
Sends heating actuating value in cycleslistNot cyclical, only in the event of change
Proportional band of heating controllerlist2 K
Integrated time of heating controllerlist10 h
Base setpoint after loading the applicationlist21 °C
Minimum valid base setpointlist10 °C
Maximum valid base setpointlist32 °C
Reduction in standby mode (during heating)list1,5 K
Setpoint for frost protection mode (during heating)list5 °C
Current setpoint in comfort modelistSends actual value (heating < > cooling)
Send current setpoint in cycleslistNot cyclical, only in the event of change
Proportional band of the cooling controllerlist4 K
Integrated time of the cooling controllerlist180 min.
Installation typelistCooling surface
Sends cooling actuating valuelistWith change of 5 %
Sends cooling actuating value in cycleslistNot cyclical, only in the event of change
Increase in standby mode (during cooling)list1,5 K
Setpoint for heat protection mode (during cooling)list42 °C i.e. no real heat protection
Emergency program active when outside temperature belowlist10 °C
Fixed emergency program at failure of outside temperaturelist20%
Actuating value in the forced operationlist0%

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Floor heating-Controller, 6-fold/1.0a 1.0 latest$490A33AA2026-11-25112 KBDownload

About this file

This is the official ETS product database for the ABB AG - STOTZ-KONTAKT VAA/A6.24.2 Floor heating-Controller,6-fold (2CDG 120 061 R0011), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.