RDF/A x.1 RTR fan coil with display, SM 2CDG 006 138 R001x

ABB AG - STOTZ-KONTAKT · Order number 2CDG 006 138 R001x · Heating, Ventilation and Air Conditioning › Thermostats

Download .knxprod FanCoil Display Operate Control/1.2 1.2 · 120 KB

Product

ManufacturerABB AG - STOTZ-KONTAKT
Product nameRDF/A x.1 RTR fan coil with display, SM
Order number2CDG 006 138 R001x
Hardware6138 RTR FanCoil
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationUnregistered
Languagesen-US, de-DE, fr-FR
Catalog entryM-0002_H-07.2F6138-1_HP-6138-12-7B91-O0007_CI-2CDG.20006.20138.20R001x-1
Fingerprint7B91
SHA-256376c337024a20c7056d977dd02ecf4f046709577182878061a2469ecad5385c3
First seen2026-11-25
Markets59 markets

Application program: FanCoil Display Operate Control/1.2 1.2

Application number$6138
Version1.2
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Parameters216
Group objects66
Group objects (66)
NoNameFunctionSizeDPTFlags
0In OperationGeneral1 BitCT
0GeneralIn Operation1 BitCT
1GeneralUnit On/Off1 BitCRWT
2GeneralSwitch °C/°F display unit1 BitCRW
3GeneralIllumination On/Off1 BitCW
4ControlFrost/heat protection1 BitCRW
5ControlActivate night mode1 BitCRW
6ControlUser absent1 BitCRWT
7ControlOperating mode switchover1 ByteCRWT
8ControlOperating mode switchover requ1 ByteCRW
9Temperature sensorSend actual value2 BytesCRT
10Temperature recordingInput current exterior tempera2 BytesCW
11Temperature recordingInput exterior temperature2 BytesCW
12ControlCurrent setpoint cooling2 BytesCRWT
13ControlCurrent setpoint heating2 BytesCRWT
14ControlBase setpoint2 BytesCRW
15ControlHeating setpoint comfort2 BytesCRW
16ControlHeating setpoint standby2 BytesCRW
17ControlHeating setpoint night mode2 BytesCRW
18ControlSetpoint frost protection2 BytesCRW
19ControlCooling setpoint comfort2 BytesCRW
20ControlCooling setpoint standby2 BytesCRW
21ControlCooling setpoint night mode2 BytesCRW
22ControlSetpoint heat protection2 BytesCRW
23ControlReset of local operation1 BitCW
24Control valueControl value heating1 ByteCRT
24Control valueControl value heating1 BitCRT
24Control valueControl value heat/cool1 BitCRT
24Control valueControl value heat/cool1 ByteCRT
24Control valueControl value heating1 ByteCW
24Control valueControl value heating1 BitCW
24Control valueControl value heat/cool1 BitCW
24Control valueControl value heat/cool1 ByteCW
25Control valueControl value cooling1 ByteCRT
25Control valueControl value cooling1 BitCRT
25Control valueControl value cooling1 ByteCW
25Control valueControl value cooling1 BitCW
26Control valueContr. value add. heat. stage1 BitCRT
26Control valueContr. value add. heat. stage1 ByteCRT
27Control valueContr. value add. cool. stage1 BitCRT
27Control valueContr. value add. cool. stage1 ByteCRT
28Control valueStatus heat requirement1 BitCRT
28Control valueStatus heat requirement1 BitCW
29Control valueStatus cooling requirement1 BitCRT
29Control valueStatus cooling requirement1 BitCW
30Heat/CoolHeat/cool switchover1 BitCRWT
30Heat/CoolHeat/cool switchover1 BitCW
31Fan automatic / manualManual On/Off1 BitCRWT
31Fan automatic / manualAutomatic On/Off1 BitCRWT
32Fan manualFan stage manual 1 byte1 ByteCRWT
33Status FanCoil operationStatus operating state of FanC1 ByteCW
34Fan manualSwitch FanCoil level 11 BitCRWT
35Fan manualSwitch FanCoil level 21 BitCRWT
36Fan manualSwitch FanCoil level 31 BitCRWT
37Actuator monitoringReceive in operation1 BitCW
39Dew-point monitoringSignal dew point1 BitCW
40Monitoring of condensate tankSignal condensate tank1 BitCW
41Alarm temperatureReport failure of current temp1 BitCRT
42Alarm temperatureReport failure of ext. temp.1 BitCRT
43Status byteStatus byte RHCC status2 BytesCRT
44Status byteStatus byte HVAC status1 ByteCRT
45ControlSummer compensation active1 BitCRT
46ControlWinter compensation active1 BitCRT
47Status FanCoil operationStatus stage 11 BitCW
48Status FanCoil operationStatus stage 21 BitCW
49Status FanCoil operationStatus stage 31 BitCW
Parameters (102)
ParameterTypeDefault
Send "In operation" objectlistNo
Send cycle time in s [1...65.535]unsignedInt 1…6553560
Enable switchover of temperature display via button °C/°FlistYes, standard °C
Display during normal operationlistAbsolute setpoint temperature
Display in adjusting modelistAbsolute setpoint temperature
Display heat/cool is activelistWhen requesting heating or cooling
Display illuminationlist5 seconds recovery time
Operating mode switchoverlist1 Byte (2 x DPT_HVAC mode)
Enable switchover of comfort/standby via button On/OfflistNo
Operation mode after resetlistComfort operation
Offset for room temp. meas. (measured value change by (-128..127)x0.1 KsignedInt -128…1270
Send actual value if change is larger thanlistInactive
Send actual value cyclically (0 - inactive, min)unsignedInt 0…600
Measurement of room temperaturelistInterior
Weighting interior / exteriorlist50 % / 50 %
Monitoring temperature measurementlistNo
Control value at temp. measuring errorlistFinal value
Monitoring time exterior temperature (0 - inactive, min)unsignedInt 0…6010
Offset for ext. temp. meas. (measured value change by (-128..127)x0.1 KsignedInt -128…1270
Operating mode of unitlistNormal operation with control function
Used control functionslistHeat and cool
Switchover between heating and coolinglistAutomatic
Additional heating stage activelistNo
Additional cooling stage activelistNo
Condensate alarm activelistNo
Dew-point alarm activelistNo
Operation mode after resetlistHeating
Number of output channelslist2 channels (four-pipe system) for heat / cool
Status send heat requirementlistNo
Cycle time heating control value sending (0 - inactive, min)unsignedInt 0…600
Control modelistFanCoil
Hysteresislist1,0 K
Invert heatinglistNo
Control parameterlistAcc. to installation type
Type of heating systemlistSplit unit (4 K / 90 min)
Proportional range (Xp)list4,0 K
Readjust time (Tn)list90 min
Minimum control valuelist0%
Maximum control valuelist100%
Control value larger when sending changelist0%
Readjust timelist90 min
Cycle time PWM control value (min)unsignedInt 1…6015
PWM cycle is 0% up to control valuelist10%
PWM cycle is 100 % up to control valuelist90%
Status send cooling requirementlistNo
Cycle time cooling control value sending (0 - inactive, min)unsignedInt 0…600
Invert coolinglistNo
Type of cooling systemlistSplit unit (blower convector 4 K / 90 min)
Type of control valuelistSwitching (1 Bit)
Invert control valuelistNo
Hysteresis (one-sided)list1,0 K
Cycle time for sending of control value (0 - inactive, min)unsignedInt 0…600
Interval of additional level (value change by (0..127)x0.1 KunsignedInt 0…12730
Setpoint larger when sending changelistInactive
Cyclic sending of setpoint (0 - inactive, min)unsignedInt 0…600
Cycle time sending of setpoint (0 - inactive, min)unsignedInt 0…600
Select base setpointlistDependent setpoints
Reference base setpointlistSetpoint heating
Manual setpoint adjustment at reset of change from night / to nightlistYes
Manual setpoint adjustmentlistActive
Maximum manual setpoint increaseunsignedInt 0…103
Maximum manual setpoint reductionunsignedInt 0…103
Object reset manual setpoint adjustment activelistNo
When receiving base setpointlistRetain manual setpoint adjustment
Range manual setpoint adjustmentlist0,5 K
Long press of button to enable change of setpoint heating / coolinglistNo
Heating setpoint comfort modelist21,0 °C
Heating setpoint standby modelist19,0 °C
Heating setpoint night modelist15,0 °C
Cooling setpoint comfort modelist23,0 °C
Cooling setpoint standby modelist25,0 °C
Cooling setpoint night modelist27,0 °C
Setpoint frost protectionlist7 °C
Setpoint heat protectionlistCooling disabled
Minimum distance between heating setpoint and cooling setpointlist2,0 K
Heating setpoint reduction standbylist2,0 K
Heating setpoint reduction night operationlist4,0 K
Cooling setpoint increase standbylist2,0 K
Cooling setpoint increase night modelist4,0 K
Number of fan levelslist3 levels
Manual operation of fan stage is signaled to the actuator vialistObject "Automatic ON/OFF"
Object manual fan stage send hat has the following codelist1-Byte object as counting value 0-3
Evaluate status byte fan stagelistNo
Evaluate status byte operationlistNo
Send cycle time of actuator in s [1...65.535]unsignedInt 1…65535120
Stage of fan after resetlistAutomatic
Stage limit in night modelistNo limit
Automatic return from manual adjustment (0 - inactive, min)unsignedInt 0…600
Return inactive a fan stage off and automatic return not 0listYes
Threshold value stage 1unsignedInt 1…10010
Threshold value stage 2unsignedInt 1…10040
Threshold value stage 3unsignedInt 1…10070
Summer compensation activelistNo
Summer compensation lower exterior temp. valuelist20 °C
Summer compensation upper exterior temp. valuelist32 °C
Summer compensation lower setpoint offsetlist0 K
Summer compensation upper setpoint offsetlist4 K
Winter compensation activelistNo
Winter compensation lower exterior temp. valuelist0 °C
Winter compensation upper exterior temp. valuelist10 °C
Winter compensation lower setpoint offsetlist4 K
Winter compensation upper setpoint offsetlist0 K

Version history

ApplicationApp noFingerprintFirst seenSizeFile
FanCoil Display Operate Control/1.2 1.2 latest$61387B912026-11-25120 KBDownload

About this file

This is the official ETS product database for the ABB AG - STOTZ-KONTAKT RDF/A x.1 RTR fan coil with display, SM (2CDG 006 138 R001x), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.