| 1 | Central - General: | In operation | 1 Bit | 1.2 boolean | CRT |
| 2 | Central - General: | Request status values | 1 Bit | 1.17 trigger | CW |
| 3 | Central - General: | Reset valve output fault | 1 Bit | 1.17 trigger | CW |
| 4 | Central - General: | Status Fault supply voltage | 1 Bit | 1.5 alarm | CRT |
| 5 | Central - General: | Summer/winter mode | 1 Bit | 1.2 boolean | CW |
| 6 | Central - Date/time: | Set time | 3 Bytes | 10.1 time of day | CW |
| 7 | Central - Date/time: | Set date | 3 Bytes | 11.1 date | CW |
| 8 | Central - Date/time: | Set date/time | 8 Bytes | 19.1 date time | CW |
| 9 | Central - Date/time: | Request date/time | 1 Bit | 1.17 trigger | CW |
| 10 | Central - Service: | Activate service | 2 Bit | 2.1 switch control | CW |
| 11 | Central - Service: | Status Service | 1 Bit | 1.2 boolean | CRT |
| 12 | Central - Pump control: {{0}} | External pump control 1 | 1 Bit | 1.1 switch | CW |
| 13 | Central - Pump control: {{0}} | Pump on/off 1 | 1 Bit | 1.1 switch | CRT |
| 14 | Central - Pump control: {{0}} | External pump control 2 | 1 Bit | 1.1 switch | CW |
| 15 | Central - Pump control: {{0}} | Pump on/off 2 | 1 Bit | 1.1 switch | CRT |
| 16 | Central - Maximum control value: | Maximum external control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 17 | Central - Maximum control value: | Status Maximum control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 18 | Central - Manual operation: | Status Manual operation | 1 Bit | 1.11 state | CRT |
| 19 | Central - Manual operation: | Enable/block manual operation | 1 Bit | 1.3 enable | CW |
| 20 | Central - Manual operation: | Deactivate manual operation | 1 Bit | 1.17 trigger | CW |
| 21 | Logic/threshold 1 - Logic: {{0}} | Connection A | 1 Bit | 1.2 boolean | CWTU |
| 21 | Logic/threshold 1 - Logic: {{0}} | Connection A | 1 Bit | 1.1 switch | CWTU |
| 21 | Logic/threshold 1 - Threshold: {{0}} | Threshold input | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 21 | Logic/threshold 1 - Threshold: {{0}} | Threshold input | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 21 | Logic/threshold 1 - Threshold: {{0}} | Threshold input | 2 Bytes | 7.1 pulses | CWTU |
| 21 | Logic/threshold 1 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 21 | Logic/threshold 1 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.4 lux (Lux) | CWTU |
| 21 | Logic/threshold 1 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.5 speed (m/s) | CWTU |
| 21 | Logic/threshold 1 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.21 current (mA) | CWTU |
| 21 | Logic/threshold 1 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.19 electric current (A) | CWTU |
| 21 | Logic/threshold 1 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.56 power (W) | CWTU |
| 21 | Logic/threshold 1 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.24 power (kW) | CWTU |
| 21 | Logic/threshold 1 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 21 | Logic/threshold 1 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 22 | Logic/threshold 1 - Logic: {{0}} | Connection B | 1 Bit | 1.2 boolean | CWTU |
| 22 | Logic/threshold 1 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 22 | Logic/threshold 1 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 22 | Logic/threshold 1 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 7.1 pulses | CW |
| 22 | Logic/threshold 1 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 22 | Logic/threshold 1 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 22 | Logic/threshold 1 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 22 | Logic/threshold 1 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.21 current (mA) | CW |
| 22 | Logic/threshold 1 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 22 | Logic/threshold 1 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.56 power (W) | CW |
| 22 | Logic/threshold 1 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.24 power (kW) | CW |
| 22 | Logic/threshold 1 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 22 | Logic/threshold 1 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 23 | Logic/threshold 1 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 23 | Logic/threshold 1 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 23 | Logic/threshold 1 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 7.1 pulses | CW |
| 23 | Logic/threshold 1 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 23 | Logic/threshold 1 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 23 | Logic/threshold 1 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 23 | Logic/threshold 1 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.21 current (mA) | CW |
| 23 | Logic/threshold 1 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 23 | Logic/threshold 1 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.56 power (W) | CW |
| 23 | Logic/threshold 1 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.24 power (kW) | CW |
| 23 | Logic/threshold 1 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 23 | Logic/threshold 1 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 24 | Logic/threshold 1 - Logic: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 24 | Logic/threshold 1 - Logic: {{0}} | Status Result | 1 Bit | 1.1 switch | CRT |
| 24 | Logic/threshold 1 - Threshold: {{0}} | Status Input value between thresholds | 1 Bit | 1.2 boolean | CRT |
| 25 | Logic/threshold 1 - Threshold: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 26 | Logic/threshold 2 - Logic: {{0}} | Connection A | 1 Bit | 1.2 boolean | CWTU |
| 26 | Logic/threshold 2 - Logic: {{0}} | Connection A | 1 Bit | 1.1 switch | CWTU |
| 26 | Logic/threshold 2 - Threshold: {{0}} | Threshold input | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 26 | Logic/threshold 2 - Threshold: {{0}} | Threshold input | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 26 | Logic/threshold 2 - Threshold: {{0}} | Threshold input | 2 Bytes | 7.1 pulses | CWTU |
| 26 | Logic/threshold 2 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 26 | Logic/threshold 2 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.4 lux (Lux) | CWTU |
| 26 | Logic/threshold 2 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.5 speed (m/s) | CWTU |
| 26 | Logic/threshold 2 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.21 current (mA) | CWTU |
| 26 | Logic/threshold 2 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.19 electric current (A) | CWTU |
| 26 | Logic/threshold 2 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.56 power (W) | CWTU |
| 26 | Logic/threshold 2 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.24 power (kW) | CWTU |
| 26 | Logic/threshold 2 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 26 | Logic/threshold 2 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 27 | Logic/threshold 2 - Logic: {{0}} | Connection B | 1 Bit | 1.2 boolean | CWTU |
| 27 | Logic/threshold 2 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 27 | Logic/threshold 2 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 27 | Logic/threshold 2 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 7.1 pulses | CW |
| 27 | Logic/threshold 2 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 27 | Logic/threshold 2 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 27 | Logic/threshold 2 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 27 | Logic/threshold 2 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.21 current (mA) | CW |
| 27 | Logic/threshold 2 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 27 | Logic/threshold 2 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.56 power (W) | CW |
| 27 | Logic/threshold 2 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.24 power (kW) | CW |
| 27 | Logic/threshold 2 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 27 | Logic/threshold 2 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 28 | Logic/threshold 2 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 28 | Logic/threshold 2 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 28 | Logic/threshold 2 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 7.1 pulses | CW |
| 28 | Logic/threshold 2 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 28 | Logic/threshold 2 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 28 | Logic/threshold 2 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 28 | Logic/threshold 2 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.21 current (mA) | CW |
| 28 | Logic/threshold 2 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 28 | Logic/threshold 2 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.56 power (W) | CW |
| 28 | Logic/threshold 2 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.24 power (kW) | CW |
| 28 | Logic/threshold 2 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 28 | Logic/threshold 2 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 29 | Logic/threshold 2 - Logic: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 29 | Logic/threshold 2 - Logic: {{0}} | Status Result | 1 Bit | 1.1 switch | CRT |
| 29 | Logic/threshold 2 - Threshold: {{0}} | Status Input value between thresholds | 1 Bit | 1.2 boolean | CRT |
| 30 | Logic/threshold 2 - Threshold: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 31 | Logic/threshold 3 - Logic: {{0}} | Connection A | 1 Bit | 1.2 boolean | CWTU |
| 31 | Logic/threshold 3 - Logic: {{0}} | Connection A | 1 Bit | 1.1 switch | CWTU |
| 31 | Logic/threshold 3 - Threshold: {{0}} | Threshold input | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 31 | Logic/threshold 3 - Threshold: {{0}} | Threshold input | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 31 | Logic/threshold 3 - Threshold: {{0}} | Threshold input | 2 Bytes | 7.1 pulses | CWTU |
| 31 | Logic/threshold 3 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 31 | Logic/threshold 3 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.4 lux (Lux) | CWTU |
| 31 | Logic/threshold 3 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.5 speed (m/s) | CWTU |
| 31 | Logic/threshold 3 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.21 current (mA) | CWTU |
| 31 | Logic/threshold 3 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.19 electric current (A) | CWTU |
| 31 | Logic/threshold 3 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.56 power (W) | CWTU |
| 31 | Logic/threshold 3 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.24 power (kW) | CWTU |
| 31 | Logic/threshold 3 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 31 | Logic/threshold 3 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 32 | Logic/threshold 3 - Logic: {{0}} | Connection B | 1 Bit | 1.2 boolean | CWTU |
| 32 | Logic/threshold 3 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 32 | Logic/threshold 3 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 32 | Logic/threshold 3 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 7.1 pulses | CW |
| 32 | Logic/threshold 3 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 32 | Logic/threshold 3 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 32 | Logic/threshold 3 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 32 | Logic/threshold 3 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.21 current (mA) | CW |
| 32 | Logic/threshold 3 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 32 | Logic/threshold 3 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.56 power (W) | CW |
| 32 | Logic/threshold 3 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.24 power (kW) | CW |
| 32 | Logic/threshold 3 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 32 | Logic/threshold 3 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 33 | Logic/threshold 3 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 33 | Logic/threshold 3 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 33 | Logic/threshold 3 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 7.1 pulses | CW |
| 33 | Logic/threshold 3 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 33 | Logic/threshold 3 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 33 | Logic/threshold 3 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 33 | Logic/threshold 3 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.21 current (mA) | CW |
| 33 | Logic/threshold 3 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 33 | Logic/threshold 3 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.56 power (W) | CW |
| 33 | Logic/threshold 3 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.24 power (kW) | CW |
| 33 | Logic/threshold 3 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 33 | Logic/threshold 3 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 34 | Logic/threshold 3 - Logic: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 34 | Logic/threshold 3 - Logic: {{0}} | Status Result | 1 Bit | 1.1 switch | CRT |
| 34 | Logic/threshold 3 - Threshold: {{0}} | Status Input value between thresholds | 1 Bit | 1.2 boolean | CRT |
| 35 | Logic/threshold 3 - Threshold: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 36 | Logic/threshold 4 - Logic: {{0}} | Connection A | 1 Bit | 1.2 boolean | CWTU |
| 36 | Logic/threshold 4 - Logic: {{0}} | Connection A | 1 Bit | 1.1 switch | CWTU |
| 36 | Logic/threshold 4 - Threshold: {{0}} | Threshold input | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 36 | Logic/threshold 4 - Threshold: {{0}} | Threshold input | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 36 | Logic/threshold 4 - Threshold: {{0}} | Threshold input | 2 Bytes | 7.1 pulses | CWTU |
| 36 | Logic/threshold 4 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 36 | Logic/threshold 4 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.4 lux (Lux) | CWTU |
| 36 | Logic/threshold 4 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.5 speed (m/s) | CWTU |
| 36 | Logic/threshold 4 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.21 current (mA) | CWTU |
| 36 | Logic/threshold 4 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.19 electric current (A) | CWTU |
| 36 | Logic/threshold 4 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.56 power (W) | CWTU |
| 36 | Logic/threshold 4 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.24 power (kW) | CWTU |
| 36 | Logic/threshold 4 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 36 | Logic/threshold 4 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 37 | Logic/threshold 4 - Logic: {{0}} | Connection B | 1 Bit | 1.2 boolean | CWTU |
| 37 | Logic/threshold 4 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 37 | Logic/threshold 4 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 37 | Logic/threshold 4 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 7.1 pulses | CW |
| 37 | Logic/threshold 4 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 37 | Logic/threshold 4 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 37 | Logic/threshold 4 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 37 | Logic/threshold 4 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.21 current (mA) | CW |
| 37 | Logic/threshold 4 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 37 | Logic/threshold 4 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.56 power (W) | CW |
| 37 | Logic/threshold 4 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.24 power (kW) | CW |
| 37 | Logic/threshold 4 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 37 | Logic/threshold 4 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 38 | Logic/threshold 4 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 38 | Logic/threshold 4 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 38 | Logic/threshold 4 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 7.1 pulses | CW |
| 38 | Logic/threshold 4 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 38 | Logic/threshold 4 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 38 | Logic/threshold 4 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 38 | Logic/threshold 4 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.21 current (mA) | CW |
| 38 | Logic/threshold 4 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 38 | Logic/threshold 4 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.56 power (W) | CW |
| 38 | Logic/threshold 4 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.24 power (kW) | CW |
| 38 | Logic/threshold 4 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 38 | Logic/threshold 4 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 39 | Logic/threshold 4 - Logic: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 39 | Logic/threshold 4 - Logic: {{0}} | Status Result | 1 Bit | 1.1 switch | CRT |
| 39 | Logic/threshold 4 - Threshold: {{0}} | Status Input value between thresholds | 1 Bit | 1.2 boolean | CRT |
| 40 | Logic/threshold 4 - Threshold: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 41 | Logic/threshold 5 - Logic: {{0}} | Connection A | 1 Bit | 1.2 boolean | CWTU |
| 41 | Logic/threshold 5 - Logic: {{0}} | Connection A | 1 Bit | 1.1 switch | CWTU |
| 41 | Logic/threshold 5 - Threshold: {{0}} | Threshold input | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 41 | Logic/threshold 5 - Threshold: {{0}} | Threshold input | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 41 | Logic/threshold 5 - Threshold: {{0}} | Threshold input | 2 Bytes | 7.1 pulses | CWTU |
| 41 | Logic/threshold 5 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 41 | Logic/threshold 5 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.4 lux (Lux) | CWTU |
| 41 | Logic/threshold 5 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.5 speed (m/s) | CWTU |
| 41 | Logic/threshold 5 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.21 current (mA) | CWTU |
| 41 | Logic/threshold 5 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.19 electric current (A) | CWTU |
| 41 | Logic/threshold 5 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.56 power (W) | CWTU |
| 41 | Logic/threshold 5 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.24 power (kW) | CWTU |
| 41 | Logic/threshold 5 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 41 | Logic/threshold 5 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 42 | Logic/threshold 5 - Logic: {{0}} | Connection B | 1 Bit | 1.2 boolean | CWTU |
| 42 | Logic/threshold 5 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 42 | Logic/threshold 5 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 42 | Logic/threshold 5 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 7.1 pulses | CW |
| 42 | Logic/threshold 5 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 42 | Logic/threshold 5 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 42 | Logic/threshold 5 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 42 | Logic/threshold 5 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.21 current (mA) | CW |
| 42 | Logic/threshold 5 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 42 | Logic/threshold 5 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.56 power (W) | CW |
| 42 | Logic/threshold 5 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.24 power (kW) | CW |
| 42 | Logic/threshold 5 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 42 | Logic/threshold 5 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 43 | Logic/threshold 5 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 43 | Logic/threshold 5 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 43 | Logic/threshold 5 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 7.1 pulses | CW |
| 43 | Logic/threshold 5 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 43 | Logic/threshold 5 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 43 | Logic/threshold 5 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 43 | Logic/threshold 5 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.21 current (mA) | CW |
| 43 | Logic/threshold 5 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 43 | Logic/threshold 5 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.56 power (W) | CW |
| 43 | Logic/threshold 5 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.24 power (kW) | CW |
| 43 | Logic/threshold 5 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 43 | Logic/threshold 5 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 44 | Logic/threshold 5 - Logic: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 44 | Logic/threshold 5 - Logic: {{0}} | Status Result | 1 Bit | 1.1 switch | CRT |
| 44 | Logic/threshold 5 - Threshold: {{0}} | Status Input value between thresholds | 1 Bit | 1.2 boolean | CRT |
| 45 | Logic/threshold 5 - Threshold: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 46 | Logic/threshold 6 - Logic: {{0}} | Connection A | 1 Bit | 1.2 boolean | CWTU |
| 46 | Logic/threshold 6 - Logic: {{0}} | Connection A | 1 Bit | 1.1 switch | CWTU |
| 46 | Logic/threshold 6 - Threshold: {{0}} | Threshold input | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 46 | Logic/threshold 6 - Threshold: {{0}} | Threshold input | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 46 | Logic/threshold 6 - Threshold: {{0}} | Threshold input | 2 Bytes | 7.1 pulses | CWTU |
| 46 | Logic/threshold 6 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 46 | Logic/threshold 6 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.4 lux (Lux) | CWTU |
| 46 | Logic/threshold 6 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.5 speed (m/s) | CWTU |
| 46 | Logic/threshold 6 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.21 current (mA) | CWTU |
| 46 | Logic/threshold 6 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.19 electric current (A) | CWTU |
| 46 | Logic/threshold 6 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.56 power (W) | CWTU |
| 46 | Logic/threshold 6 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.24 power (kW) | CWTU |
| 46 | Logic/threshold 6 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 46 | Logic/threshold 6 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 47 | Logic/threshold 6 - Logic: {{0}} | Connection B | 1 Bit | 1.2 boolean | CWTU |
| 47 | Logic/threshold 6 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 47 | Logic/threshold 6 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 47 | Logic/threshold 6 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 7.1 pulses | CW |
| 47 | Logic/threshold 6 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 47 | Logic/threshold 6 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 47 | Logic/threshold 6 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 47 | Logic/threshold 6 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.21 current (mA) | CW |
| 47 | Logic/threshold 6 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 47 | Logic/threshold 6 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.56 power (W) | CW |
| 47 | Logic/threshold 6 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.24 power (kW) | CW |
| 47 | Logic/threshold 6 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 47 | Logic/threshold 6 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 48 | Logic/threshold 6 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 48 | Logic/threshold 6 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 48 | Logic/threshold 6 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 7.1 pulses | CW |
| 48 | Logic/threshold 6 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 48 | Logic/threshold 6 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 48 | Logic/threshold 6 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 48 | Logic/threshold 6 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.21 current (mA) | CW |
| 48 | Logic/threshold 6 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 48 | Logic/threshold 6 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.56 power (W) | CW |
| 48 | Logic/threshold 6 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.24 power (kW) | CW |
| 48 | Logic/threshold 6 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 48 | Logic/threshold 6 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 49 | Logic/threshold 6 - Logic: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 49 | Logic/threshold 6 - Logic: {{0}} | Status Result | 1 Bit | 1.1 switch | CRT |
| 49 | Logic/threshold 6 - Threshold: {{0}} | Status Input value between thresholds | 1 Bit | 1.2 boolean | CRT |
| 50 | Logic/threshold 6 - Threshold: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 51 | Logic/threshold 7 - Logic: {{0}} | Connection A | 1 Bit | 1.2 boolean | CWTU |
| 51 | Logic/threshold 7 - Logic: {{0}} | Connection A | 1 Bit | 1.1 switch | CWTU |
| 51 | Logic/threshold 7 - Threshold: {{0}} | Threshold input | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 51 | Logic/threshold 7 - Threshold: {{0}} | Threshold input | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 51 | Logic/threshold 7 - Threshold: {{0}} | Threshold input | 2 Bytes | 7.1 pulses | CWTU |
| 51 | Logic/threshold 7 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 51 | Logic/threshold 7 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.4 lux (Lux) | CWTU |
| 51 | Logic/threshold 7 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.5 speed (m/s) | CWTU |
| 51 | Logic/threshold 7 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.21 current (mA) | CWTU |
| 51 | Logic/threshold 7 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.19 electric current (A) | CWTU |
| 51 | Logic/threshold 7 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.56 power (W) | CWTU |
| 51 | Logic/threshold 7 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.24 power (kW) | CWTU |
| 51 | Logic/threshold 7 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 51 | Logic/threshold 7 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 52 | Logic/threshold 7 - Logic: {{0}} | Connection B | 1 Bit | 1.2 boolean | CWTU |
| 52 | Logic/threshold 7 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 52 | Logic/threshold 7 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 52 | Logic/threshold 7 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 7.1 pulses | CW |
| 52 | Logic/threshold 7 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 52 | Logic/threshold 7 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 52 | Logic/threshold 7 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 52 | Logic/threshold 7 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.21 current (mA) | CW |
| 52 | Logic/threshold 7 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 52 | Logic/threshold 7 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.56 power (W) | CW |
| 52 | Logic/threshold 7 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.24 power (kW) | CW |
| 52 | Logic/threshold 7 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 52 | Logic/threshold 7 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 53 | Logic/threshold 7 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 53 | Logic/threshold 7 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 53 | Logic/threshold 7 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 7.1 pulses | CW |
| 53 | Logic/threshold 7 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 53 | Logic/threshold 7 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 53 | Logic/threshold 7 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 53 | Logic/threshold 7 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.21 current (mA) | CW |
| 53 | Logic/threshold 7 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 53 | Logic/threshold 7 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.56 power (W) | CW |
| 53 | Logic/threshold 7 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.24 power (kW) | CW |
| 53 | Logic/threshold 7 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 53 | Logic/threshold 7 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 54 | Logic/threshold 7 - Logic: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 54 | Logic/threshold 7 - Logic: {{0}} | Status Result | 1 Bit | 1.1 switch | CRT |
| 54 | Logic/threshold 7 - Threshold: {{0}} | Status Input value between thresholds | 1 Bit | 1.2 boolean | CRT |
| 55 | Logic/threshold 7 - Threshold: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 56 | Logic/threshold 8 - Logic: {{0}} | Connection A | 1 Bit | 1.2 boolean | CWTU |
| 56 | Logic/threshold 8 - Logic: {{0}} | Connection A | 1 Bit | 1.1 switch | CWTU |
| 56 | Logic/threshold 8 - Threshold: {{0}} | Threshold input | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 56 | Logic/threshold 8 - Threshold: {{0}} | Threshold input | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 56 | Logic/threshold 8 - Threshold: {{0}} | Threshold input | 2 Bytes | 7.1 pulses | CWTU |
| 56 | Logic/threshold 8 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 56 | Logic/threshold 8 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.4 lux (Lux) | CWTU |
| 56 | Logic/threshold 8 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.5 speed (m/s) | CWTU |
| 56 | Logic/threshold 8 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.21 current (mA) | CWTU |
| 56 | Logic/threshold 8 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.19 electric current (A) | CWTU |
| 56 | Logic/threshold 8 - Threshold: {{0}} | Threshold input | 4 Bytes | 14.56 power (W) | CWTU |
| 56 | Logic/threshold 8 - Threshold: {{0}} | Threshold input | 2 Bytes | 9.24 power (kW) | CWTU |
| 56 | Logic/threshold 8 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 56 | Logic/threshold 8 - Threshold: {{0}} | Threshold input | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 57 | Logic/threshold 8 - Logic: {{0}} | Connection B | 1 Bit | 1.2 boolean | CWTU |
| 57 | Logic/threshold 8 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 57 | Logic/threshold 8 - Threshold: {{0}} | Change upper threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 57 | Logic/threshold 8 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 7.1 pulses | CW |
| 57 | Logic/threshold 8 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 57 | Logic/threshold 8 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 57 | Logic/threshold 8 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 57 | Logic/threshold 8 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.21 current (mA) | CW |
| 57 | Logic/threshold 8 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 57 | Logic/threshold 8 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 14.56 power (W) | CW |
| 57 | Logic/threshold 8 - Threshold: {{0}} | Change upper threshold | 2 Bytes | 9.24 power (kW) | CW |
| 57 | Logic/threshold 8 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 57 | Logic/threshold 8 - Threshold: {{0}} | Change upper threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 58 | Logic/threshold 8 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.1 percentage (0..100%) | CW |
| 58 | Logic/threshold 8 - Threshold: {{0}} | Change lower threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 58 | Logic/threshold 8 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 7.1 pulses | CW |
| 58 | Logic/threshold 8 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.1 temperature (°C) | CW |
| 58 | Logic/threshold 8 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.4 lux (Lux) | CW |
| 58 | Logic/threshold 8 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.5 speed (m/s) | CW |
| 58 | Logic/threshold 8 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.21 current (mA) | CW |
| 58 | Logic/threshold 8 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.19 electric current (A) | CW |
| 58 | Logic/threshold 8 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 14.56 power (W) | CW |
| 58 | Logic/threshold 8 - Threshold: {{0}} | Change lower threshold | 2 Bytes | 9.24 power (kW) | CW |
| 58 | Logic/threshold 8 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.10 active energy (Wh) | CW |
| 58 | Logic/threshold 8 - Threshold: {{0}} | Change lower threshold | 4 Bytes | 13.13 active energy (kWh) | CW |
| 59 | Logic/threshold 8 - Logic: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 59 | Logic/threshold 8 - Logic: {{0}} | Status Result | 1 Bit | 1.1 switch | CRT |
| 59 | Logic/threshold 8 - Threshold: {{0}} | Status Input value between thresholds | 1 Bit | 1.2 boolean | CRT |
| 60 | Logic/threshold 8 - Threshold: {{0}} | Status Result | 1 Bit | 1.2 boolean | CRT |
| 61 | Output A - Valve: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 61 | Output A - Valve: {{0}} | Control value | 1 Bit | 1.1 switch | CW |
| 62 | Output A - Valve: {{0}} | Status Control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 62 | Output A - Valve: {{0}} | Status Control value | 1 Bit | 1.2 boolean | CRT |
| 63 | Output A - Valve: {{0}} | Status byte | 2 Bytes | 22.102 combined status HVA | CRT |
| 64 | Output A - Valve: {{0}} | Status Valve purge | 1 Bit | 1.2 boolean | CRT |
| 65 | Output A - Valve: {{0}} | Activate valve purge | 1 Bit | 1.17 trigger | CW |
| 66 | Output A - Valve: {{0}} | Override control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 66 | Output A - Valve: {{0}} | Override control value | 1 Bit | 1.1 switch | CW |
| 67 | Output A - Valve: {{0}} | Activate/block control value override | 1 Bit | 1.3 enable | CW |
| 68 | Output A - Valve: {{0}} | Status Safety mode | 1 Bit | 1.5 alarm | CRT |
| 68 | Output A - Valve: {{0}} | Safety mode | 1 Bit | 1.5 alarm | CRT |
| 69 | Output A - Valve: {{0}} | Forced operation, 1 bit | 1 Bit | 1.3 enable | CW |
| 70 | Output A - Valve: {{0}} | Forced operation, 2 bit | 2 Bit | 2.1 switch control | CW |
| 71 | Output A - Valve: {{0}} | Status Fault valve | 1 Bit | 1.5 alarm | CRT |
| 72 | Output B - Valve: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 72 | Output B - Valve: {{0}} | Control value | 1 Bit | 1.1 switch | CW |
| 73 | Output B - Valve: {{0}} | Status Control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 73 | Output B - Valve: {{0}} | Status Control value | 1 Bit | 1.2 boolean | CRT |
| 74 | Output B - Valve: {{0}} | Status byte | 2 Bytes | 22.102 combined status HVA | CRT |
| 75 | Output B - Valve: {{0}} | Status Valve purge | 1 Bit | 1.2 boolean | CRT |
| 76 | Output B - Valve: {{0}} | Activate valve purge | 1 Bit | 1.17 trigger | CW |
| 77 | Output B - Valve: {{0}} | Override control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 77 | Output B - Valve: {{0}} | Override control value | 1 Bit | 1.1 switch | CW |
| 78 | Output B - Valve: {{0}} | Activate/block control value override | 1 Bit | 1.3 enable | CW |
| 79 | Output B - Valve: {{0}} | Status Safety mode | 1 Bit | 1.5 alarm | CRT |
| 79 | Output B - Valve: {{0}} | Safety mode | 1 Bit | 1.5 alarm | CRT |
| 80 | Output B - Valve: {{0}} | Forced operation, 1 bit | 1 Bit | 1.3 enable | CW |
| 81 | Output B - Valve: {{0}} | Forced operation, 2 bit | 2 Bit | 2.1 switch control | CW |
| 82 | Output B - Valve: {{0}} | Status Fault valve | 1 Bit | 1.5 alarm | CRT |
| 83 | Output C - Valve: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 83 | Output C - Valve: {{0}} | Control value | 1 Bit | 1.1 switch | CW |
| 84 | Output C - Valve: {{0}} | Status Control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Output C - Valve: {{0}} | Status Control value | 1 Bit | 1.2 boolean | CRT |
| 85 | Output C - Valve: {{0}} | Status byte | 2 Bytes | 22.102 combined status HVA | CRT |
| 86 | Output C - Valve: {{0}} | Status Valve purge | 1 Bit | 1.2 boolean | CRT |
| 87 | Output C - Valve: {{0}} | Activate valve purge | 1 Bit | 1.17 trigger | CW |
| 88 | Output C - Valve: {{0}} | Override control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 88 | Output C - Valve: {{0}} | Override control value | 1 Bit | 1.1 switch | CW |
| 89 | Output C - Valve: {{0}} | Activate/block control value override | 1 Bit | 1.3 enable | CW |
| 90 | Output C - Valve: {{0}} | Status Safety mode | 1 Bit | 1.5 alarm | CRT |
| 90 | Output C - Valve: {{0}} | Safety mode | 1 Bit | 1.5 alarm | CRT |
| 91 | Output C - Valve: {{0}} | Forced operation, 1 bit | 1 Bit | 1.3 enable | CW |
| 92 | Output C - Valve: {{0}} | Forced operation, 2 bit | 2 Bit | 2.1 switch control | CW |
| 93 | Output C - Valve: {{0}} | Status Fault valve | 1 Bit | 1.5 alarm | CRT |
| 94 | Output D - Valve: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 94 | Output D - Valve: {{0}} | Control value | 1 Bit | 1.1 switch | CW |
| 95 | Output D - Valve: {{0}} | Status Control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 95 | Output D - Valve: {{0}} | Status Control value | 1 Bit | 1.2 boolean | CRT |
| 96 | Output D - Valve: {{0}} | Status byte | 2 Bytes | 22.102 combined status HVA | CRT |
| 97 | Output D - Valve: {{0}} | Status Valve purge | 1 Bit | 1.2 boolean | CRT |
| 98 | Output D - Valve: {{0}} | Activate valve purge | 1 Bit | 1.17 trigger | CW |
| 99 | Output D - Valve: {{0}} | Override control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 99 | Output D - Valve: {{0}} | Override control value | 1 Bit | 1.1 switch | CW |
| 100 | Output D - Valve: {{0}} | Activate/block control value override | 1 Bit | 1.3 enable | CW |
| 101 | Output D - Valve: {{0}} | Status Safety mode | 1 Bit | 1.5 alarm | CRT |
| 101 | Output D - Valve: {{0}} | Safety mode | 1 Bit | 1.5 alarm | CRT |
| 102 | Output D - Valve: {{0}} | Forced operation, 1 bit | 1 Bit | 1.3 enable | CW |
| 103 | Output D - Valve: {{0}} | Forced operation, 2 bit | 2 Bit | 2.1 switch control | CW |
| 104 | Output D - Valve: {{0}} | Status Fault valve | 1 Bit | 1.5 alarm | CRT |
| 105 | Output E - Valve: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 105 | Output E - Valve: {{0}} | Control value | 1 Bit | 1.1 switch | CW |
| 106 | Output E - Valve: {{0}} | Status Control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 106 | Output E - Valve: {{0}} | Status Control value | 1 Bit | 1.2 boolean | CRT |
| 107 | Output E - Valve: {{0}} | Status byte | 2 Bytes | 22.102 combined status HVA | CRT |
| 108 | Output E - Valve: {{0}} | Status Valve purge | 1 Bit | 1.2 boolean | CRT |
| 109 | Output E - Valve: {{0}} | Activate valve purge | 1 Bit | 1.17 trigger | CW |
| 110 | Output E - Valve: {{0}} | Override control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 110 | Output E - Valve: {{0}} | Override control value | 1 Bit | 1.1 switch | CW |
| 111 | Output E - Valve: {{0}} | Activate/block control value override | 1 Bit | 1.3 enable | CW |
| 112 | Output E - Valve: {{0}} | Status Safety mode | 1 Bit | 1.5 alarm | CRT |
| 112 | Output E - Valve: {{0}} | Safety mode | 1 Bit | 1.5 alarm | CRT |
| 113 | Output E - Valve: {{0}} | Forced operation, 1 bit | 1 Bit | 1.3 enable | CW |
| 114 | Output E - Valve: {{0}} | Forced operation, 2 bit | 2 Bit | 2.1 switch control | CW |
| 115 | Output E - Valve: {{0}} | Status Fault valve | 1 Bit | 1.5 alarm | CRT |
| 116 | Output F - Valve: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 116 | Output F - Valve: {{0}} | Control value | 1 Bit | 1.1 switch | CW |
| 117 | Output F - Valve: {{0}} | Status Control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 117 | Output F - Valve: {{0}} | Status Control value | 1 Bit | 1.2 boolean | CRT |
| 118 | Output F - Valve: {{0}} | Status byte | 2 Bytes | 22.102 combined status HVA | CRT |
| 119 | Output F - Valve: {{0}} | Status Valve purge | 1 Bit | 1.2 boolean | CRT |
| 120 | Output F - Valve: {{0}} | Activate valve purge | 1 Bit | 1.17 trigger | CW |
| 121 | Output F - Valve: {{0}} | Override control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 121 | Output F - Valve: {{0}} | Override control value | 1 Bit | 1.1 switch | CW |
| 122 | Output F - Valve: {{0}} | Activate/block control value override | 1 Bit | 1.3 enable | CW |
| 123 | Output F - Valve: {{0}} | Status Safety mode | 1 Bit | 1.5 alarm | CRT |
| 123 | Output F - Valve: {{0}} | Safety mode | 1 Bit | 1.5 alarm | CRT |
| 124 | Output F - Valve: {{0}} | Forced operation, 1 bit | 1 Bit | 1.3 enable | CW |
| 125 | Output F - Valve: {{0}} | Forced operation, 2 bit | 2 Bit | 2.1 switch control | CW |
| 126 | Output F - Valve: {{0}} | Status Fault valve | 1 Bit | 1.5 alarm | CRT |
| 127 | RTC 1 - Room temperature controller: {{0}} | Control value basic-stage heating | 1 Byte | 5.1 percentage (0..100%) | CT |
| 127 | RTC 1 - Room temperature controller: {{0}} | Basic-stage heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 128 | RTC 1 - Room temperature controller: {{0}} | Control value additional-stage heating | 1 Byte | 5.1 percentage (0..100%) | CT |
| 128 | RTC 1 - Room temperature controller: {{0}} | Control value additional-stage heating | 1 Bit | 1.1 switch | CT |
| 129 | RTC 1 - Room temperature controller: {{0}} | Control value basic-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 129 | RTC 1 - Room temperature controller: {{0}} | Additional-stage heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 130 | RTC 1 - Room temperature controller: {{0}} | Control value additional-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 130 | RTC 1 - Room temperature controller: {{0}} | Control value additional-stage cooling | 1 Bit | 1.1 switch | CT |
| 131 | RTC 1 - Room temperature controller: {{0}} | Valve actuator status HVA heating | 2 Bytes | 22.102 combined status HVA | CWU |
| 132 | RTC 1 - Room temperature controller: {{0}} | Valve actuator status HVA additional-stage heating | 2 Bytes | 22.102 combined status HVA | CWU |
| 133 | RTC 1 - Room temperature controller: {{0}} | Valve actuator status HVA cooling | 2 Bytes | 22.102 combined status HVA | CWU |
| 134 | RTC 1 - Room temperature controller: {{0}} | Valve actuator status HVA additional-stage cooling | 2 Bytes | 22.102 combined status HVA | CWU |
| 135 | RTC 1 - Room temperature controller: {{0}} | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 135 | RTC 1 - Room temperature controller: {{0}} | Actual temperature weighted | 2 Bytes | 9.1 temperature (°C) | CRT |
| 136 | RTC 1 - Room temperature controller: {{0}} | External actual temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 137 | RTC 1 - Room temperature controller: {{0}} | Local actual temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 138 | RTC 1 - Room temperature controller: {{0}} | Temperature comparison | 2 Bytes | 9.1 temperature (°C) | CW |
| 139 | RTC 1 - Room temperature controller: {{0}} | Fault: actual temperature | 1 Bit | 1.5 alarm | CRT |
| 140 | RTC 1 - Room temperature controller: {{0}} | Current setpoint (main/secondary) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 141 | RTC 1 - Room temperature controller: {{0}} | Request setpoint adjustment (main/secondary) | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 142 | RTC 1 - Room temperature controller: {{0}} | Confirm setpoint adjustment (main/secondary) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 143 | RTC 1 - Room temperature controller: {{0}} | Reset setpoint adjustment | 1 Bit | 1.15 reset | CWU |
| 144 | RTC 1 - Room temperature controller: {{0}} | Current heating setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 145 | RTC 1 - Room temperature controller: {{0}} | Current cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 146 | RTC 1 - Room temperature controller: {{0}} | Heating setpoints | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CWTU |
| 147 | RTC 1 - Room temperature controller: {{0}} | Cooling setpoints | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CWTU |
| 148 | RTC 1 - Room temperature controller: {{0}} | Heating setpoint status | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CT |
| 149 | RTC 1 - Room temperature controller: {{0}} | Cooling setpoint status | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CT |
| 150 | RTC 1 - Room temperature controller: {{0}} | Comfort heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 150 | RTC 1 - Room temperature controller: {{0}} | Base setpoint Comfort heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 151 | RTC 1 - Room temperature controller: {{0}} | Standby heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 152 | RTC 1 - Room temperature controller: {{0}} | Economy heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 153 | RTC 1 - Room temperature controller: {{0}} | Building Protection heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 154 | RTC 1 - Room temperature controller: {{0}} | Comfort cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 154 | RTC 1 - Room temperature controller: {{0}} | Base setpoint Comfort cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 155 | RTC 1 - Room temperature controller: {{0}} | Standby cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 156 | RTC 1 - Room temperature controller: {{0}} | Economy cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 157 | RTC 1 - Room temperature controller: {{0}} | Building Protection cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 158 | RTC 1 - Room temperature controller: {{0}} | Operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CWTU |
| 159 | RTC 1 - Room temperature controller: {{0}} | Status Operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CT |
| 160 | RTC 1 - Room temperature controller: {{0}} | Operating mode override | 1 Byte | 20.102 HVAC mode | CWTU |
| 161 | RTC 1 - Room temperature controller: {{0}} | Status Operating mode override | 1 Byte | 20.102 HVAC mode | CT |
| 162 | RTC 1 - Room temperature controller: {{0}} | Current operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CRT |
| 163 | RTC 1 - Room temperature controller: {{0}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 164 | RTC 1 - Room temperature controller: {{0}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 165 | RTC 1 - Room temperature controller: {{0}} | Presence button | 1 Bit | 1.18 occupancy | CWU |
| 165 | RTC 1 - Room temperature controller: {{0}} | Comfort extension | 1 Bit | 1.18 occupancy | CWU |
| 166 | RTC 1 - Room temperature controller: {{0}} | Comfort extension status | 1 Bit | 1.18 occupancy | CT |
| 167 | RTC 1 - Room temperature controller: {{0}} | Dew point alarm | 1 Bit | 1.5 alarm | CWTU |
| 168 | RTC 1 - Room temperature controller: {{0}} | Outside temperature for summer compensation | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 169 | RTC 1 - Room temperature controller: {{0}} | Summer compensation active | 1 Bit | 1.2 boolean | CT |
| 170 | RTC 1 - Room temperature controller: {{0}} | Status RTSM Controller (main/secondary) | 1 Byte | 21.107 combined status RTSM | CRT |
| 171 | RTC 1 - Room temperature controller: {{0}} | Status RTC Controller (main/secondary) | 2 Bytes | 22.103 combined status RTC | CRT |
| 172 | RTC 1 - Room temperature controller: {{0}} | Status RHCC controller | 2 Bytes | 22.101 RHCC status | CRT |
| 173 | RTC 1 - Room temperature controller: {{0}} | Unit changeover | 1 Bit | 1.1 switch | CWTU |
| 174 | RTC 1 - Room temperature controller: {{0}} | Heating active | 1 Bit | 1.11 state | CT |
| 175 | RTC 1 - Room temperature controller: {{0}} | Cooling active | 1 Bit | 1.11 state | CT |
| 176 | RTC 1 - Room temperature controller: {{0}} | Heating/cooling changeover (main/secondary) | 1 Bit | 1.100 cooling/heating | CWTU |
| 177 | RTC 1 - Room temperature controller: {{0}} | Status Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CT |
| 178 | RTC 1 - Room temperature controller: {{0}} | Block/enable heating | 1 Bit | 1.3 enable | CWTU |
| 179 | RTC 1 - Room temperature controller: {{0}} | Block/enable cooling | 1 Bit | 1.3 enable | CWTU |
| 180 | RTC 1 - Room temperature controller: {{0}} | Block/enable heating stages separately | 1 Byte | 20.116 enable H/C stage | CWTU |
| 181 | RTC 1 - Room temperature controller: {{0}} | Block/enable cooling stages separately | 1 Byte | 20.116 enable H/C stage | CWTU |
| 182 | RTC 1 - Room temperature controller: {{0}} | Controller synchronization output | 1 Byte | 20.105 HVAC control mode | CRT |
| 183 | RTC 1 - Room temperature controller: {{0}} | Controller synchronization input | 1 Byte | 20.105 HVAC control mode | CWTU |
| 184 | RTC 1 - Room temperature controller: {{0}} | Basic-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 185 | RTC 1 - Room temperature controller: {{0}} | Additional-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 186 | RTC 1 - Room temperature controller: {{0}} | Basic-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 187 | RTC 1 - Room temperature controller: {{0}} | Additional-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 188 | RTC 1 - Room temperature controller: {{0}} | Activate floor heating | 1 Bit | 1.11 state | CWTU |
| 189 | RTC 1 - Room temperature controller: {{0}} | Floor heating basic-stage heating | 2 Bytes | 9.1 temperature (°C) | CWU |
| 190 | RTC 1 - Room temperature controller: {{0}} | Floor heating additional-stage heating | 2 Bytes | 9.1 temperature (°C) | CWU |
| 191 | RTC 1 - Room temperature controller: {{0}} | Basic load | 1 Bit | 1.11 state | CWTU |
| 192 | RTC 1 - Room temperature controller: {{0}} | Boost | 1 Bit | 1.11 state | CWTU |
| 193 | RTC 1 - Room temperature controller: {{0}} | Scene | 1 Byte | 18.1 scene control | CWU |
| 194 | RTC 1 - Room temperature controller: {{0}} | Solar power surplus | 1 Bit | 1.11 state | CWTU |
| 195 | RTC 1 - Room temperature controller: {{0}} | Request master/slave synchronization | 14 Bytes | 16.1 Character String (ISO 8859-1) | CWU |
| 196 | RTC 1 - Room temperature controller: {{0}} | Confirm master/slave synchronization | 14 Bytes | 16.1 Character String (ISO 8859-1) | CT |
| 197 | RTC 1 - Room temperature controller: {{0}} | Fan manual | 1 Bit | 1.2 boolean | CWTU |
| 198 | RTC 1 - Room temperature controller: {{0}} | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 199 | RTC 1 - Room temperature controller: {{0}} | Fan manual status | 1 Bit | 1.2 boolean | CT |
| 199 | RTC 1 - Room temperature controller: {{0}} | Fan manual (heating) status | 1 Bit | 1.2 boolean | CT |
| 200 | RTC 1 - Room temperature controller: {{0}} | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CT |
| 200 | RTC 1 - Room temperature controller: {{0}} | Fan speed (Heating) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 201 | RTC 1 - Room temperature controller: {{0}} | Fan speed 1 | 1 Bit | 1.1 switch | CT |
| 201 | RTC 1 - Room temperature controller: {{0}} | Fan speed 1 (Heating) | 1 Bit | 1.1 switch | CT |
| 202 | RTC 1 - Room temperature controller: {{0}} | Fan speed 2 | 1 Bit | 1.1 switch | CT |
| 202 | RTC 1 - Room temperature controller: {{0}} | Fan speed 2 (Heating) | 1 Bit | 1.1 switch | CT |
| 203 | RTC 1 - Room temperature controller: {{0}} | Fan speed 3 | 1 Bit | 1.1 switch | CT |
| 203 | RTC 1 - Room temperature controller: {{0}} | Fan speed 3 (heating) | 1 Bit | 1.1 switch | CT |
| 204 | RTC 1 - Room temperature controller: {{0}} | Fan speed 4 | 1 Bit | 1.1 switch | CT |
| 204 | RTC 1 - Room temperature controller: {{0}} | Fan speed 4 (heating) | 1 Bit | 1.1 switch | CT |
| 205 | RTC 1 - Room temperature controller: {{0}} | Fan speed 5 | 1 Bit | 1.1 switch | CT |
| 205 | RTC 1 - Room temperature controller: {{0}} | Fan speed 5 (heating) | 1 Bit | 1.1 switch | CT |
| 206 | RTC 1 - Room temperature controller: {{0}} | Fan manual (Cooling) status | 1 Bit | 1.2 boolean | CT |
| 207 | RTC 1 - Room temperature controller: {{0}} | Fan speed (Cooling) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 208 | RTC 1 - Room temperature controller: {{0}} | Fan speed 1 (Cooling) | 1 Bit | 1.1 switch | CT |
| 209 | RTC 1 - Room temperature controller: {{0}} | Fan speed 2 (Cooling) | 1 Bit | 1.1 switch | CT |
| 210 | RTC 1 - Room temperature controller: {{0}} | Fan speed 3 (Cooling) | 1 Bit | 1.1 switch | CT |
| 211 | RTC 1 - Room temperature controller: {{0}} | Fan speed 4 (Cooling) | 1 Bit | 1.1 switch | CT |
| 212 | RTC 1 - Room temperature controller: {{0}} | Fan speed 5 (Cooling) | 1 Bit | 1.1 switch | CT |
| 213 | RTC 1 - Room temperature controller: {{0}} | Current fan speed | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 214 | RTC 1 - Room temperature controller: {{0}} | Current fan speed Cooling | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 215 | RTC 1 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA | 1 Byte | 21.1 general status | CT |
| 215 | RTC 1 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA Kühlen | 1 Byte | 21.1 general status | CT |
| 216 | RTC 1 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA Heizen | 1 Byte | 21.1 general status | CT |
| 217 | RTC 2 - Room temperature controller: {{0}} | Control value basic-stage heating | 1 Byte | 5.1 percentage (0..100%) | CT |
| 217 | RTC 2 - Room temperature controller: {{0}} | Basic-stage heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 218 | RTC 2 - Room temperature controller: {{0}} | Control value additional-stage heating | 1 Byte | 5.1 percentage (0..100%) | CT |
| 218 | RTC 2 - Room temperature controller: {{0}} | Control value additional-stage heating | 1 Bit | 1.1 switch | CT |
| 219 | RTC 2 - Room temperature controller: {{0}} | Control value basic-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 219 | RTC 2 - Room temperature controller: {{0}} | Additional-stage heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 220 | RTC 2 - Room temperature controller: {{0}} | Control value additional-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 220 | RTC 2 - Room temperature controller: {{0}} | Control value additional-stage cooling | 1 Bit | 1.1 switch | CT |
| 221 | RTC 2 - Room temperature controller: {{0}} | Valve actuator status HVA heating | 2 Bytes | 22.102 combined status HVA | CWU |
| 222 | RTC 2 - Room temperature controller: {{0}} | Valve actuator status HVA additional-stage heating | 2 Bytes | 22.102 combined status HVA | CWU |
| 223 | RTC 2 - Room temperature controller: {{0}} | Valve actuator status HVA cooling | 2 Bytes | 22.102 combined status HVA | CWU |
| 224 | RTC 2 - Room temperature controller: {{0}} | Valve actuator status HVA additional-stage cooling | 2 Bytes | 22.102 combined status HVA | CWU |
| 225 | RTC 2 - Room temperature controller: {{0}} | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 225 | RTC 2 - Room temperature controller: {{0}} | Actual temperature weighted | 2 Bytes | 9.1 temperature (°C) | CRT |
| 226 | RTC 2 - Room temperature controller: {{0}} | External actual temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 227 | RTC 2 - Room temperature controller: {{0}} | Local actual temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 228 | RTC 2 - Room temperature controller: {{0}} | Temperature comparison | 2 Bytes | 9.1 temperature (°C) | CW |
| 229 | RTC 2 - Room temperature controller: {{0}} | Fault: actual temperature | 1 Bit | 1.5 alarm | CRT |
| 230 | RTC 2 - Room temperature controller: {{0}} | Current setpoint (main/secondary) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 231 | RTC 2 - Room temperature controller: {{0}} | Request setpoint adjustment (main/secondary) | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 232 | RTC 2 - Room temperature controller: {{0}} | Confirm setpoint adjustment (main/secondary) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 233 | RTC 2 - Room temperature controller: {{0}} | Reset setpoint adjustment | 1 Bit | 1.15 reset | CWU |
| 234 | RTC 2 - Room temperature controller: {{0}} | Current heating setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 235 | RTC 2 - Room temperature controller: {{0}} | Current cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 236 | RTC 2 - Room temperature controller: {{0}} | Heating setpoints | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CWTU |
| 237 | RTC 2 - Room temperature controller: {{0}} | Cooling setpoints | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CWTU |
| 238 | RTC 2 - Room temperature controller: {{0}} | Heating setpoint status | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CT |
| 239 | RTC 2 - Room temperature controller: {{0}} | Cooling setpoint status | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CT |
| 240 | RTC 2 - Room temperature controller: {{0}} | Comfort heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 240 | RTC 2 - Room temperature controller: {{0}} | Base setpoint Comfort heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 241 | RTC 2 - Room temperature controller: {{0}} | Standby heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 242 | RTC 2 - Room temperature controller: {{0}} | Economy heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 243 | RTC 2 - Room temperature controller: {{0}} | Building Protection heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 244 | RTC 2 - Room temperature controller: {{0}} | Comfort cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 244 | RTC 2 - Room temperature controller: {{0}} | Base setpoint Comfort cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 245 | RTC 2 - Room temperature controller: {{0}} | Standby cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 246 | RTC 2 - Room temperature controller: {{0}} | Economy cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 247 | RTC 2 - Room temperature controller: {{0}} | Building Protection cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 248 | RTC 2 - Room temperature controller: {{0}} | Operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CWTU |
| 249 | RTC 2 - Room temperature controller: {{0}} | Status Operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CT |
| 250 | RTC 2 - Room temperature controller: {{0}} | Operating mode override | 1 Byte | 20.102 HVAC mode | CWTU |
| 251 | RTC 2 - Room temperature controller: {{0}} | Status Operating mode override | 1 Byte | 20.102 HVAC mode | CT |
| 252 | RTC 2 - Room temperature controller: {{0}} | Current operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CRT |
| 253 | RTC 2 - Room temperature controller: {{0}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 254 | RTC 2 - Room temperature controller: {{0}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 255 | RTC 2 - Room temperature controller: {{0}} | Presence button | 1 Bit | 1.18 occupancy | CWU |
| 255 | RTC 2 - Room temperature controller: {{0}} | Comfort extension | 1 Bit | 1.18 occupancy | CWU |
| 256 | RTC 2 - Room temperature controller: {{0}} | Comfort extension status | 1 Bit | 1.18 occupancy | CT |
| 257 | RTC 2 - Room temperature controller: {{0}} | Dew point alarm | 1 Bit | 1.5 alarm | CWTU |
| 258 | RTC 2 - Room temperature controller: {{0}} | Outside temperature for summer compensation | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 259 | RTC 2 - Room temperature controller: {{0}} | Summer compensation active | 1 Bit | 1.2 boolean | CT |
| 260 | RTC 2 - Room temperature controller: {{0}} | Status RTSM Controller (main/secondary) | 1 Byte | 21.107 combined status RTSM | CRT |
| 261 | RTC 2 - Room temperature controller: {{0}} | Status RTC Controller (main/secondary) | 2 Bytes | 22.103 combined status RTC | CRT |
| 262 | RTC 2 - Room temperature controller: {{0}} | Status RHCC controller | 2 Bytes | 22.101 RHCC status | CRT |
| 263 | RTC 2 - Room temperature controller: {{0}} | Unit changeover | 1 Bit | 1.1 switch | CWTU |
| 264 | RTC 2 - Room temperature controller: {{0}} | Heating active | 1 Bit | 1.11 state | CT |
| 265 | RTC 2 - Room temperature controller: {{0}} | Cooling active | 1 Bit | 1.11 state | CT |
| 266 | RTC 2 - Room temperature controller: {{0}} | Heating/cooling changeover (main/secondary) | 1 Bit | 1.100 cooling/heating | CWTU |
| 267 | RTC 2 - Room temperature controller: {{0}} | Status Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CT |
| 268 | RTC 2 - Room temperature controller: {{0}} | Block/enable heating | 1 Bit | 1.3 enable | CWTU |
| 269 | RTC 2 - Room temperature controller: {{0}} | Block/enable cooling | 1 Bit | 1.3 enable | CWTU |
| 270 | RTC 2 - Room temperature controller: {{0}} | Block/enable heating stages separately | 1 Byte | 20.116 enable H/C stage | CWTU |
| 271 | RTC 2 - Room temperature controller: {{0}} | Block/enable cooling stages separately | 1 Byte | 20.116 enable H/C stage | CWTU |
| 272 | RTC 2 - Room temperature controller: {{0}} | Controller synchronization output | 1 Byte | 20.105 HVAC control mode | CRT |
| 273 | RTC 2 - Room temperature controller: {{0}} | Controller synchronization input | 1 Byte | 20.105 HVAC control mode | CWTU |
| 274 | RTC 2 - Room temperature controller: {{0}} | Basic-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 275 | RTC 2 - Room temperature controller: {{0}} | Additional-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 276 | RTC 2 - Room temperature controller: {{0}} | Basic-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 277 | RTC 2 - Room temperature controller: {{0}} | Additional-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 278 | RTC 2 - Room temperature controller: {{0}} | Activate floor heating | 1 Bit | 1.11 state | CWTU |
| 279 | RTC 2 - Room temperature controller: {{0}} | Floor heating basic-stage heating | 2 Bytes | 9.1 temperature (°C) | CWU |
| 280 | RTC 2 - Room temperature controller: {{0}} | Floor heating additional-stage heating | 2 Bytes | 9.1 temperature (°C) | CWU |
| 281 | RTC 2 - Room temperature controller: {{0}} | Basic load | 1 Bit | 1.11 state | CWTU |
| 282 | RTC 2 - Room temperature controller: {{0}} | Boost | 1 Bit | 1.11 state | CWTU |
| 283 | RTC 2 - Room temperature controller: {{0}} | Scene | 1 Byte | 18.1 scene control | CWU |
| 284 | RTC 2 - Room temperature controller: {{0}} | Solar power surplus | 1 Bit | 1.11 state | CWTU |
| 285 | RTC 2 - Room temperature controller: {{0}} | Request master/slave synchronization | 14 Bytes | 16.1 Character String (ISO 8859-1) | CWU |
| 286 | RTC 2 - Room temperature controller: {{0}} | Confirm master/slave synchronization | 14 Bytes | 16.1 Character String (ISO 8859-1) | CT |
| 287 | RTC 2 - Room temperature controller: {{0}} | Fan manual | 1 Bit | 1.2 boolean | CWTU |
| 288 | RTC 2 - Room temperature controller: {{0}} | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 289 | RTC 2 - Room temperature controller: {{0}} | Fan manual status | 1 Bit | 1.2 boolean | CT |
| 289 | RTC 2 - Room temperature controller: {{0}} | Fan manual (heating) status | 1 Bit | 1.2 boolean | CT |
| 290 | RTC 2 - Room temperature controller: {{0}} | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CT |
| 290 | RTC 2 - Room temperature controller: {{0}} | Fan speed (Heating) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 291 | RTC 2 - Room temperature controller: {{0}} | Fan speed 1 | 1 Bit | 1.1 switch | CT |
| 291 | RTC 2 - Room temperature controller: {{0}} | Fan speed 1 (Heating) | 1 Bit | 1.1 switch | CT |
| 292 | RTC 2 - Room temperature controller: {{0}} | Fan speed 2 | 1 Bit | 1.1 switch | CT |
| 292 | RTC 2 - Room temperature controller: {{0}} | Fan speed 2 (Heating) | 1 Bit | 1.1 switch | CT |
| 293 | RTC 2 - Room temperature controller: {{0}} | Fan speed 3 | 1 Bit | 1.1 switch | CT |
| 293 | RTC 2 - Room temperature controller: {{0}} | Fan speed 3 (heating) | 1 Bit | 1.1 switch | CT |
| 294 | RTC 2 - Room temperature controller: {{0}} | Fan speed 4 | 1 Bit | 1.1 switch | CT |
| 294 | RTC 2 - Room temperature controller: {{0}} | Fan speed 4 (heating) | 1 Bit | 1.1 switch | CT |
| 295 | RTC 2 - Room temperature controller: {{0}} | Fan speed 5 | 1 Bit | 1.1 switch | CT |
| 295 | RTC 2 - Room temperature controller: {{0}} | Fan speed 5 (heating) | 1 Bit | 1.1 switch | CT |
| 296 | RTC 2 - Room temperature controller: {{0}} | Fan manual (Cooling) status | 1 Bit | 1.2 boolean | CT |
| 297 | RTC 2 - Room temperature controller: {{0}} | Fan speed (Cooling) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 298 | RTC 2 - Room temperature controller: {{0}} | Fan speed 1 (Cooling) | 1 Bit | 1.1 switch | CT |
| 299 | RTC 2 - Room temperature controller: {{0}} | Fan speed 2 (Cooling) | 1 Bit | 1.1 switch | CT |
| 300 | RTC 2 - Room temperature controller: {{0}} | Fan speed 3 (Cooling) | 1 Bit | 1.1 switch | CT |
| 301 | RTC 2 - Room temperature controller: {{0}} | Fan speed 4 (Cooling) | 1 Bit | 1.1 switch | CT |
| 302 | RTC 2 - Room temperature controller: {{0}} | Fan speed 5 (Cooling) | 1 Bit | 1.1 switch | CT |
| 303 | RTC 2 - Room temperature controller: {{0}} | Current fan speed | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 304 | RTC 2 - Room temperature controller: {{0}} | Current fan speed Cooling | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 305 | RTC 2 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA | 1 Byte | 21.1 general status | CT |
| 305 | RTC 2 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA Kühlen | 1 Byte | 21.1 general status | CT |
| 306 | RTC 2 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA Heizen | 1 Byte | 21.1 general status | CT |
| 307 | RTC 3 - Room temperature controller: {{0}} | Control value basic-stage heating | 1 Byte | 5.1 percentage (0..100%) | CT |
| 307 | RTC 3 - Room temperature controller: {{0}} | Basic-stage heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 308 | RTC 3 - Room temperature controller: {{0}} | Control value additional-stage heating | 1 Byte | 5.1 percentage (0..100%) | CT |
| 308 | RTC 3 - Room temperature controller: {{0}} | Control value additional-stage heating | 1 Bit | 1.1 switch | CT |
| 309 | RTC 3 - Room temperature controller: {{0}} | Control value basic-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 309 | RTC 3 - Room temperature controller: {{0}} | Additional-stage heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 310 | RTC 3 - Room temperature controller: {{0}} | Control value additional-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 310 | RTC 3 - Room temperature controller: {{0}} | Control value additional-stage cooling | 1 Bit | 1.1 switch | CT |
| 311 | RTC 3 - Room temperature controller: {{0}} | Valve actuator status HVA heating | 2 Bytes | 22.102 combined status HVA | CWU |
| 312 | RTC 3 - Room temperature controller: {{0}} | Valve actuator status HVA additional-stage heating | 2 Bytes | 22.102 combined status HVA | CWU |
| 313 | RTC 3 - Room temperature controller: {{0}} | Valve actuator status HVA cooling | 2 Bytes | 22.102 combined status HVA | CWU |
| 314 | RTC 3 - Room temperature controller: {{0}} | Valve actuator status HVA additional-stage cooling | 2 Bytes | 22.102 combined status HVA | CWU |
| 315 | RTC 3 - Room temperature controller: {{0}} | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 315 | RTC 3 - Room temperature controller: {{0}} | Actual temperature weighted | 2 Bytes | 9.1 temperature (°C) | CRT |
| 316 | RTC 3 - Room temperature controller: {{0}} | External actual temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 317 | RTC 3 - Room temperature controller: {{0}} | Local actual temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 318 | RTC 3 - Room temperature controller: {{0}} | Temperature comparison | 2 Bytes | 9.1 temperature (°C) | CW |
| 319 | RTC 3 - Room temperature controller: {{0}} | Fault: actual temperature | 1 Bit | 1.5 alarm | CRT |
| 320 | RTC 3 - Room temperature controller: {{0}} | Current setpoint (main/secondary) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 321 | RTC 3 - Room temperature controller: {{0}} | Request setpoint adjustment (main/secondary) | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 322 | RTC 3 - Room temperature controller: {{0}} | Confirm setpoint adjustment (main/secondary) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 323 | RTC 3 - Room temperature controller: {{0}} | Reset setpoint adjustment | 1 Bit | 1.15 reset | CWU |
| 324 | RTC 3 - Room temperature controller: {{0}} | Current heating setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 325 | RTC 3 - Room temperature controller: {{0}} | Current cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 326 | RTC 3 - Room temperature controller: {{0}} | Heating setpoints | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CWTU |
| 327 | RTC 3 - Room temperature controller: {{0}} | Cooling setpoints | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CWTU |
| 328 | RTC 3 - Room temperature controller: {{0}} | Heating setpoint status | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CT |
| 329 | RTC 3 - Room temperature controller: {{0}} | Cooling setpoint status | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CT |
| 330 | RTC 3 - Room temperature controller: {{0}} | Comfort heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 330 | RTC 3 - Room temperature controller: {{0}} | Base setpoint Comfort heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 331 | RTC 3 - Room temperature controller: {{0}} | Standby heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 332 | RTC 3 - Room temperature controller: {{0}} | Economy heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 333 | RTC 3 - Room temperature controller: {{0}} | Building Protection heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 334 | RTC 3 - Room temperature controller: {{0}} | Comfort cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 334 | RTC 3 - Room temperature controller: {{0}} | Base setpoint Comfort cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 335 | RTC 3 - Room temperature controller: {{0}} | Standby cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 336 | RTC 3 - Room temperature controller: {{0}} | Economy cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 337 | RTC 3 - Room temperature controller: {{0}} | Building Protection cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 338 | RTC 3 - Room temperature controller: {{0}} | Operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CWTU |
| 339 | RTC 3 - Room temperature controller: {{0}} | Status Operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CT |
| 340 | RTC 3 - Room temperature controller: {{0}} | Operating mode override | 1 Byte | 20.102 HVAC mode | CWTU |
| 341 | RTC 3 - Room temperature controller: {{0}} | Status Operating mode override | 1 Byte | 20.102 HVAC mode | CT |
| 342 | RTC 3 - Room temperature controller: {{0}} | Current operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CRT |
| 343 | RTC 3 - Room temperature controller: {{0}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 344 | RTC 3 - Room temperature controller: {{0}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 345 | RTC 3 - Room temperature controller: {{0}} | Presence button | 1 Bit | 1.18 occupancy | CWU |
| 345 | RTC 3 - Room temperature controller: {{0}} | Comfort extension | 1 Bit | 1.18 occupancy | CWU |
| 346 | RTC 3 - Room temperature controller: {{0}} | Comfort extension status | 1 Bit | 1.18 occupancy | CT |
| 347 | RTC 3 - Room temperature controller: {{0}} | Dew point alarm | 1 Bit | 1.5 alarm | CWTU |
| 348 | RTC 3 - Room temperature controller: {{0}} | Outside temperature for summer compensation | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 349 | RTC 3 - Room temperature controller: {{0}} | Summer compensation active | 1 Bit | 1.2 boolean | CT |
| 350 | RTC 3 - Room temperature controller: {{0}} | Status RTSM Controller (main/secondary) | 1 Byte | 21.107 combined status RTSM | CRT |
| 351 | RTC 3 - Room temperature controller: {{0}} | Status RTC Controller (main/secondary) | 2 Bytes | 22.103 combined status RTC | CRT |
| 352 | RTC 3 - Room temperature controller: {{0}} | Status RHCC controller | 2 Bytes | 22.101 RHCC status | CRT |
| 353 | RTC 3 - Room temperature controller: {{0}} | Unit changeover | 1 Bit | 1.1 switch | CWTU |
| 354 | RTC 3 - Room temperature controller: {{0}} | Heating active | 1 Bit | 1.11 state | CT |
| 355 | RTC 3 - Room temperature controller: {{0}} | Cooling active | 1 Bit | 1.11 state | CT |
| 356 | RTC 3 - Room temperature controller: {{0}} | Heating/cooling changeover (main/secondary) | 1 Bit | 1.100 cooling/heating | CWTU |
| 357 | RTC 3 - Room temperature controller: {{0}} | Status Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CT |
| 358 | RTC 3 - Room temperature controller: {{0}} | Block/enable heating | 1 Bit | 1.3 enable | CWTU |
| 359 | RTC 3 - Room temperature controller: {{0}} | Block/enable cooling | 1 Bit | 1.3 enable | CWTU |
| 360 | RTC 3 - Room temperature controller: {{0}} | Block/enable heating stages separately | 1 Byte | 20.116 enable H/C stage | CWTU |
| 361 | RTC 3 - Room temperature controller: {{0}} | Block/enable cooling stages separately | 1 Byte | 20.116 enable H/C stage | CWTU |
| 362 | RTC 3 - Room temperature controller: {{0}} | Controller synchronization output | 1 Byte | 20.105 HVAC control mode | CRT |
| 363 | RTC 3 - Room temperature controller: {{0}} | Controller synchronization input | 1 Byte | 20.105 HVAC control mode | CWTU |
| 364 | RTC 3 - Room temperature controller: {{0}} | Basic-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 365 | RTC 3 - Room temperature controller: {{0}} | Additional-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 366 | RTC 3 - Room temperature controller: {{0}} | Basic-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 367 | RTC 3 - Room temperature controller: {{0}} | Additional-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 368 | RTC 3 - Room temperature controller: {{0}} | Activate floor heating | 1 Bit | 1.11 state | CWTU |
| 369 | RTC 3 - Room temperature controller: {{0}} | Floor heating basic-stage heating | 2 Bytes | 9.1 temperature (°C) | CWU |
| 370 | RTC 3 - Room temperature controller: {{0}} | Floor heating additional-stage heating | 2 Bytes | 9.1 temperature (°C) | CWU |
| 371 | RTC 3 - Room temperature controller: {{0}} | Basic load | 1 Bit | 1.11 state | CWTU |
| 372 | RTC 3 - Room temperature controller: {{0}} | Boost | 1 Bit | 1.11 state | CWTU |
| 373 | RTC 3 - Room temperature controller: {{0}} | Scene | 1 Byte | 18.1 scene control | CWU |
| 374 | RTC 3 - Room temperature controller: {{0}} | Solar power surplus | 1 Bit | 1.11 state | CWTU |
| 375 | RTC 3 - Room temperature controller: {{0}} | Request master/slave synchronization | 14 Bytes | 16.1 Character String (ISO 8859-1) | CWU |
| 376 | RTC 3 - Room temperature controller: {{0}} | Confirm master/slave synchronization | 14 Bytes | 16.1 Character String (ISO 8859-1) | CT |
| 377 | RTC 3 - Room temperature controller: {{0}} | Fan manual | 1 Bit | 1.2 boolean | CWTU |
| 378 | RTC 3 - Room temperature controller: {{0}} | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 379 | RTC 3 - Room temperature controller: {{0}} | Fan manual status | 1 Bit | 1.2 boolean | CT |
| 379 | RTC 3 - Room temperature controller: {{0}} | Fan manual (heating) status | 1 Bit | 1.2 boolean | CT |
| 380 | RTC 3 - Room temperature controller: {{0}} | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CT |
| 380 | RTC 3 - Room temperature controller: {{0}} | Fan speed (Heating) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 381 | RTC 3 - Room temperature controller: {{0}} | Fan speed 1 | 1 Bit | 1.1 switch | CT |
| 381 | RTC 3 - Room temperature controller: {{0}} | Fan speed 1 (Heating) | 1 Bit | 1.1 switch | CT |
| 382 | RTC 3 - Room temperature controller: {{0}} | Fan speed 2 | 1 Bit | 1.1 switch | CT |
| 382 | RTC 3 - Room temperature controller: {{0}} | Fan speed 2 (Heating) | 1 Bit | 1.1 switch | CT |
| 383 | RTC 3 - Room temperature controller: {{0}} | Fan speed 3 | 1 Bit | 1.1 switch | CT |
| 383 | RTC 3 - Room temperature controller: {{0}} | Fan speed 3 (heating) | 1 Bit | 1.1 switch | CT |
| 384 | RTC 3 - Room temperature controller: {{0}} | Fan speed 4 | 1 Bit | 1.1 switch | CT |
| 384 | RTC 3 - Room temperature controller: {{0}} | Fan speed 4 (heating) | 1 Bit | 1.1 switch | CT |
| 385 | RTC 3 - Room temperature controller: {{0}} | Fan speed 5 | 1 Bit | 1.1 switch | CT |
| 385 | RTC 3 - Room temperature controller: {{0}} | Fan speed 5 (heating) | 1 Bit | 1.1 switch | CT |
| 386 | RTC 3 - Room temperature controller: {{0}} | Fan manual (Cooling) status | 1 Bit | 1.2 boolean | CT |
| 387 | RTC 3 - Room temperature controller: {{0}} | Fan speed (Cooling) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 388 | RTC 3 - Room temperature controller: {{0}} | Fan speed 1 (Cooling) | 1 Bit | 1.1 switch | CT |
| 389 | RTC 3 - Room temperature controller: {{0}} | Fan speed 2 (Cooling) | 1 Bit | 1.1 switch | CT |
| 390 | RTC 3 - Room temperature controller: {{0}} | Fan speed 3 (Cooling) | 1 Bit | 1.1 switch | CT |
| 391 | RTC 3 - Room temperature controller: {{0}} | Fan speed 4 (Cooling) | 1 Bit | 1.1 switch | CT |
| 392 | RTC 3 - Room temperature controller: {{0}} | Fan speed 5 (Cooling) | 1 Bit | 1.1 switch | CT |
| 393 | RTC 3 - Room temperature controller: {{0}} | Current fan speed | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 394 | RTC 3 - Room temperature controller: {{0}} | Current fan speed Cooling | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 395 | RTC 3 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA | 1 Byte | 21.1 general status | CT |
| 395 | RTC 3 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA Kühlen | 1 Byte | 21.1 general status | CT |
| 396 | RTC 3 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA Heizen | 1 Byte | 21.1 general status | CT |
| 397 | RTC 4 - Room temperature controller: {{0}} | Control value basic-stage heating | 1 Byte | 5.1 percentage (0..100%) | CT |
| 397 | RTC 4 - Room temperature controller: {{0}} | Basic-stage heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 398 | RTC 4 - Room temperature controller: {{0}} | Control value additional-stage heating | 1 Byte | 5.1 percentage (0..100%) | CT |
| 398 | RTC 4 - Room temperature controller: {{0}} | Control value additional-stage heating | 1 Bit | 1.1 switch | CT |
| 399 | RTC 4 - Room temperature controller: {{0}} | Control value basic-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 399 | RTC 4 - Room temperature controller: {{0}} | Additional-stage heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 400 | RTC 4 - Room temperature controller: {{0}} | Control value additional-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 400 | RTC 4 - Room temperature controller: {{0}} | Control value additional-stage cooling | 1 Bit | 1.1 switch | CT |
| 401 | RTC 4 - Room temperature controller: {{0}} | Valve actuator status HVA heating | 2 Bytes | 22.102 combined status HVA | CWU |
| 402 | RTC 4 - Room temperature controller: {{0}} | Valve actuator status HVA additional-stage heating | 2 Bytes | 22.102 combined status HVA | CWU |
| 403 | RTC 4 - Room temperature controller: {{0}} | Valve actuator status HVA cooling | 2 Bytes | 22.102 combined status HVA | CWU |
| 404 | RTC 4 - Room temperature controller: {{0}} | Valve actuator status HVA additional-stage cooling | 2 Bytes | 22.102 combined status HVA | CWU |
| 405 | RTC 4 - Room temperature controller: {{0}} | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 405 | RTC 4 - Room temperature controller: {{0}} | Actual temperature weighted | 2 Bytes | 9.1 temperature (°C) | CRT |
| 406 | RTC 4 - Room temperature controller: {{0}} | External actual temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 407 | RTC 4 - Room temperature controller: {{0}} | Local actual temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 408 | RTC 4 - Room temperature controller: {{0}} | Temperature comparison | 2 Bytes | 9.1 temperature (°C) | CW |
| 409 | RTC 4 - Room temperature controller: {{0}} | Fault: actual temperature | 1 Bit | 1.5 alarm | CRT |
| 410 | RTC 4 - Room temperature controller: {{0}} | Current setpoint (main/secondary) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 411 | RTC 4 - Room temperature controller: {{0}} | Request setpoint adjustment (main/secondary) | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 412 | RTC 4 - Room temperature controller: {{0}} | Confirm setpoint adjustment (main/secondary) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 413 | RTC 4 - Room temperature controller: {{0}} | Reset setpoint adjustment | 1 Bit | 1.15 reset | CWU |
| 414 | RTC 4 - Room temperature controller: {{0}} | Current heating setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 415 | RTC 4 - Room temperature controller: {{0}} | Current cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 416 | RTC 4 - Room temperature controller: {{0}} | Heating setpoints | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CWTU |
| 417 | RTC 4 - Room temperature controller: {{0}} | Cooling setpoints | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CWTU |
| 418 | RTC 4 - Room temperature controller: {{0}} | Heating setpoint status | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CT |
| 419 | RTC 4 - Room temperature controller: {{0}} | Cooling setpoint status | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CT |
| 420 | RTC 4 - Room temperature controller: {{0}} | Comfort heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 420 | RTC 4 - Room temperature controller: {{0}} | Base setpoint Comfort heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 421 | RTC 4 - Room temperature controller: {{0}} | Standby heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 422 | RTC 4 - Room temperature controller: {{0}} | Economy heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 423 | RTC 4 - Room temperature controller: {{0}} | Building Protection heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 424 | RTC 4 - Room temperature controller: {{0}} | Comfort cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 424 | RTC 4 - Room temperature controller: {{0}} | Base setpoint Comfort cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 425 | RTC 4 - Room temperature controller: {{0}} | Standby cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 426 | RTC 4 - Room temperature controller: {{0}} | Economy cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 427 | RTC 4 - Room temperature controller: {{0}} | Building Protection cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 428 | RTC 4 - Room temperature controller: {{0}} | Operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CWTU |
| 429 | RTC 4 - Room temperature controller: {{0}} | Status Operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CT |
| 430 | RTC 4 - Room temperature controller: {{0}} | Operating mode override | 1 Byte | 20.102 HVAC mode | CWTU |
| 431 | RTC 4 - Room temperature controller: {{0}} | Status Operating mode override | 1 Byte | 20.102 HVAC mode | CT |
| 432 | RTC 4 - Room temperature controller: {{0}} | Current operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CRT |
| 433 | RTC 4 - Room temperature controller: {{0}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 434 | RTC 4 - Room temperature controller: {{0}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 435 | RTC 4 - Room temperature controller: {{0}} | Presence button | 1 Bit | 1.18 occupancy | CWU |
| 435 | RTC 4 - Room temperature controller: {{0}} | Comfort extension | 1 Bit | 1.18 occupancy | CWU |
| 436 | RTC 4 - Room temperature controller: {{0}} | Comfort extension status | 1 Bit | 1.18 occupancy | CT |
| 437 | RTC 4 - Room temperature controller: {{0}} | Dew point alarm | 1 Bit | 1.5 alarm | CWTU |
| 438 | RTC 4 - Room temperature controller: {{0}} | Outside temperature for summer compensation | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 439 | RTC 4 - Room temperature controller: {{0}} | Summer compensation active | 1 Bit | 1.2 boolean | CT |
| 440 | RTC 4 - Room temperature controller: {{0}} | Status RTSM Controller (main/secondary) | 1 Byte | 21.107 combined status RTSM | CRT |
| 441 | RTC 4 - Room temperature controller: {{0}} | Status RTC Controller (main/secondary) | 2 Bytes | 22.103 combined status RTC | CRT |
| 442 | RTC 4 - Room temperature controller: {{0}} | Status RHCC controller | 2 Bytes | 22.101 RHCC status | CRT |
| 443 | RTC 4 - Room temperature controller: {{0}} | Unit changeover | 1 Bit | 1.1 switch | CWTU |
| 444 | RTC 4 - Room temperature controller: {{0}} | Heating active | 1 Bit | 1.11 state | CT |
| 445 | RTC 4 - Room temperature controller: {{0}} | Cooling active | 1 Bit | 1.11 state | CT |
| 446 | RTC 4 - Room temperature controller: {{0}} | Heating/cooling changeover (main/secondary) | 1 Bit | 1.100 cooling/heating | CWTU |
| 447 | RTC 4 - Room temperature controller: {{0}} | Status Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CT |
| 448 | RTC 4 - Room temperature controller: {{0}} | Block/enable heating | 1 Bit | 1.3 enable | CWTU |
| 449 | RTC 4 - Room temperature controller: {{0}} | Block/enable cooling | 1 Bit | 1.3 enable | CWTU |
| 450 | RTC 4 - Room temperature controller: {{0}} | Block/enable heating stages separately | 1 Byte | 20.116 enable H/C stage | CWTU |
| 451 | RTC 4 - Room temperature controller: {{0}} | Block/enable cooling stages separately | 1 Byte | 20.116 enable H/C stage | CWTU |
| 452 | RTC 4 - Room temperature controller: {{0}} | Controller synchronization output | 1 Byte | 20.105 HVAC control mode | CRT |
| 453 | RTC 4 - Room temperature controller: {{0}} | Controller synchronization input | 1 Byte | 20.105 HVAC control mode | CWTU |
| 454 | RTC 4 - Room temperature controller: {{0}} | Basic-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 455 | RTC 4 - Room temperature controller: {{0}} | Additional-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 456 | RTC 4 - Room temperature controller: {{0}} | Basic-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 457 | RTC 4 - Room temperature controller: {{0}} | Additional-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 458 | RTC 4 - Room temperature controller: {{0}} | Activate floor heating | 1 Bit | 1.11 state | CWTU |
| 459 | RTC 4 - Room temperature controller: {{0}} | Floor heating basic-stage heating | 2 Bytes | 9.1 temperature (°C) | CWU |
| 460 | RTC 4 - Room temperature controller: {{0}} | Floor heating additional-stage heating | 2 Bytes | 9.1 temperature (°C) | CWU |
| 461 | RTC 4 - Room temperature controller: {{0}} | Basic load | 1 Bit | 1.11 state | CWTU |
| 462 | RTC 4 - Room temperature controller: {{0}} | Boost | 1 Bit | 1.11 state | CWTU |
| 463 | RTC 4 - Room temperature controller: {{0}} | Scene | 1 Byte | 18.1 scene control | CWU |
| 464 | RTC 4 - Room temperature controller: {{0}} | Solar power surplus | 1 Bit | 1.11 state | CWTU |
| 465 | RTC 4 - Room temperature controller: {{0}} | Request master/slave synchronization | 14 Bytes | 16.1 Character String (ISO 8859-1) | CWU |
| 466 | RTC 4 - Room temperature controller: {{0}} | Confirm master/slave synchronization | 14 Bytes | 16.1 Character String (ISO 8859-1) | CT |
| 467 | RTC 4 - Room temperature controller: {{0}} | Fan manual | 1 Bit | 1.2 boolean | CWTU |
| 468 | RTC 4 - Room temperature controller: {{0}} | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 469 | RTC 4 - Room temperature controller: {{0}} | Fan manual status | 1 Bit | 1.2 boolean | CT |
| 469 | RTC 4 - Room temperature controller: {{0}} | Fan manual (heating) status | 1 Bit | 1.2 boolean | CT |
| 470 | RTC 4 - Room temperature controller: {{0}} | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CT |
| 470 | RTC 4 - Room temperature controller: {{0}} | Fan speed (Heating) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 471 | RTC 4 - Room temperature controller: {{0}} | Fan speed 1 | 1 Bit | 1.1 switch | CT |
| 471 | RTC 4 - Room temperature controller: {{0}} | Fan speed 1 (Heating) | 1 Bit | 1.1 switch | CT |
| 472 | RTC 4 - Room temperature controller: {{0}} | Fan speed 2 | 1 Bit | 1.1 switch | CT |
| 472 | RTC 4 - Room temperature controller: {{0}} | Fan speed 2 (Heating) | 1 Bit | 1.1 switch | CT |
| 473 | RTC 4 - Room temperature controller: {{0}} | Fan speed 3 | 1 Bit | 1.1 switch | CT |
| 473 | RTC 4 - Room temperature controller: {{0}} | Fan speed 3 (heating) | 1 Bit | 1.1 switch | CT |
| 474 | RTC 4 - Room temperature controller: {{0}} | Fan speed 4 | 1 Bit | 1.1 switch | CT |
| 474 | RTC 4 - Room temperature controller: {{0}} | Fan speed 4 (heating) | 1 Bit | 1.1 switch | CT |
| 475 | RTC 4 - Room temperature controller: {{0}} | Fan speed 5 | 1 Bit | 1.1 switch | CT |
| 475 | RTC 4 - Room temperature controller: {{0}} | Fan speed 5 (heating) | 1 Bit | 1.1 switch | CT |
| 476 | RTC 4 - Room temperature controller: {{0}} | Fan manual (Cooling) status | 1 Bit | 1.2 boolean | CT |
| 477 | RTC 4 - Room temperature controller: {{0}} | Fan speed (Cooling) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 478 | RTC 4 - Room temperature controller: {{0}} | Fan speed 1 (Cooling) | 1 Bit | 1.1 switch | CT |
| 479 | RTC 4 - Room temperature controller: {{0}} | Fan speed 2 (Cooling) | 1 Bit | 1.1 switch | CT |
| 480 | RTC 4 - Room temperature controller: {{0}} | Fan speed 3 (Cooling) | 1 Bit | 1.1 switch | CT |
| 481 | RTC 4 - Room temperature controller: {{0}} | Fan speed 4 (Cooling) | 1 Bit | 1.1 switch | CT |
| 482 | RTC 4 - Room temperature controller: {{0}} | Fan speed 5 (Cooling) | 1 Bit | 1.1 switch | CT |
| 483 | RTC 4 - Room temperature controller: {{0}} | Current fan speed | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 484 | RTC 4 - Room temperature controller: {{0}} | Current fan speed Cooling | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 485 | RTC 4 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA | 1 Byte | 21.1 general status | CT |
| 485 | RTC 4 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA Kühlen | 1 Byte | 21.1 general status | CT |
| 486 | RTC 4 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA Heizen | 1 Byte | 21.1 general status | CT |
| 487 | RTC 5 - Room temperature controller: {{0}} | Control value basic-stage heating | 1 Byte | 5.1 percentage (0..100%) | CT |
| 487 | RTC 5 - Room temperature controller: {{0}} | Basic-stage heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 488 | RTC 5 - Room temperature controller: {{0}} | Control value additional-stage heating | 1 Byte | 5.1 percentage (0..100%) | CT |
| 488 | RTC 5 - Room temperature controller: {{0}} | Control value additional-stage heating | 1 Bit | 1.1 switch | CT |
| 489 | RTC 5 - Room temperature controller: {{0}} | Control value basic-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 489 | RTC 5 - Room temperature controller: {{0}} | Additional-stage heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 490 | RTC 5 - Room temperature controller: {{0}} | Control value additional-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 490 | RTC 5 - Room temperature controller: {{0}} | Control value additional-stage cooling | 1 Bit | 1.1 switch | CT |
| 491 | RTC 5 - Room temperature controller: {{0}} | Valve actuator status HVA heating | 2 Bytes | 22.102 combined status HVA | CWU |
| 492 | RTC 5 - Room temperature controller: {{0}} | Valve actuator status HVA additional-stage heating | 2 Bytes | 22.102 combined status HVA | CWU |
| 493 | RTC 5 - Room temperature controller: {{0}} | Valve actuator status HVA cooling | 2 Bytes | 22.102 combined status HVA | CWU |
| 494 | RTC 5 - Room temperature controller: {{0}} | Valve actuator status HVA additional-stage cooling | 2 Bytes | 22.102 combined status HVA | CWU |
| 495 | RTC 5 - Room temperature controller: {{0}} | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 495 | RTC 5 - Room temperature controller: {{0}} | Actual temperature weighted | 2 Bytes | 9.1 temperature (°C) | CRT |
| 496 | RTC 5 - Room temperature controller: {{0}} | External actual temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 497 | RTC 5 - Room temperature controller: {{0}} | Local actual temperature | 2 Bytes | 9.1 temperature (°C) | CT |
| 498 | RTC 5 - Room temperature controller: {{0}} | Temperature comparison | 2 Bytes | 9.1 temperature (°C) | CW |
| 499 | RTC 5 - Room temperature controller: {{0}} | Fault: actual temperature | 1 Bit | 1.5 alarm | CRT |
| 500 | RTC 5 - Room temperature controller: {{0}} | Current setpoint (main/secondary) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 501 | RTC 5 - Room temperature controller: {{0}} | Request setpoint adjustment (main/secondary) | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 502 | RTC 5 - Room temperature controller: {{0}} | Confirm setpoint adjustment (main/secondary) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 503 | RTC 5 - Room temperature controller: {{0}} | Reset setpoint adjustment | 1 Bit | 1.15 reset | CWU |
| 504 | RTC 5 - Room temperature controller: {{0}} | Current heating setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 505 | RTC 5 - Room temperature controller: {{0}} | Current cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 506 | RTC 5 - Room temperature controller: {{0}} | Heating setpoints | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CWTU |
| 507 | RTC 5 - Room temperature controller: {{0}} | Cooling setpoints | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CWTU |
| 508 | RTC 5 - Room temperature controller: {{0}} | Heating setpoint status | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CT |
| 509 | RTC 5 - Room temperature controller: {{0}} | Cooling setpoint status | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CT |
| 510 | RTC 5 - Room temperature controller: {{0}} | Comfort heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 510 | RTC 5 - Room temperature controller: {{0}} | Base setpoint Comfort heating | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 511 | RTC 5 - Room temperature controller: {{0}} | Standby heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 512 | RTC 5 - Room temperature controller: {{0}} | Economy heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 513 | RTC 5 - Room temperature controller: {{0}} | Building Protection heating setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 514 | RTC 5 - Room temperature controller: {{0}} | Comfort cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 514 | RTC 5 - Room temperature controller: {{0}} | Base setpoint Comfort cooling | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 515 | RTC 5 - Room temperature controller: {{0}} | Standby cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 516 | RTC 5 - Room temperature controller: {{0}} | Economy cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 517 | RTC 5 - Room temperature controller: {{0}} | Building Protection cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 518 | RTC 5 - Room temperature controller: {{0}} | Operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CWTU |
| 519 | RTC 5 - Room temperature controller: {{0}} | Status Operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CT |
| 520 | RTC 5 - Room temperature controller: {{0}} | Operating mode override | 1 Byte | 20.102 HVAC mode | CWTU |
| 521 | RTC 5 - Room temperature controller: {{0}} | Status Operating mode override | 1 Byte | 20.102 HVAC mode | CT |
| 522 | RTC 5 - Room temperature controller: {{0}} | Current operating mode (main/secondary) | 1 Byte | 20.102 HVAC mode | CRT |
| 523 | RTC 5 - Room temperature controller: {{0}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 524 | RTC 5 - Room temperature controller: {{0}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 525 | RTC 5 - Room temperature controller: {{0}} | Presence button | 1 Bit | 1.18 occupancy | CWU |
| 525 | RTC 5 - Room temperature controller: {{0}} | Comfort extension | 1 Bit | 1.18 occupancy | CWU |
| 526 | RTC 5 - Room temperature controller: {{0}} | Comfort extension status | 1 Bit | 1.18 occupancy | CT |
| 527 | RTC 5 - Room temperature controller: {{0}} | Dew point alarm | 1 Bit | 1.5 alarm | CWTU |
| 528 | RTC 5 - Room temperature controller: {{0}} | Outside temperature for summer compensation | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 529 | RTC 5 - Room temperature controller: {{0}} | Summer compensation active | 1 Bit | 1.2 boolean | CT |
| 530 | RTC 5 - Room temperature controller: {{0}} | Status RTSM Controller (main/secondary) | 1 Byte | 21.107 combined status RTSM | CRT |
| 531 | RTC 5 - Room temperature controller: {{0}} | Status RTC Controller (main/secondary) | 2 Bytes | 22.103 combined status RTC | CRT |
| 532 | RTC 5 - Room temperature controller: {{0}} | Status RHCC controller | 2 Bytes | 22.101 RHCC status | CRT |
| 533 | RTC 5 - Room temperature controller: {{0}} | Unit changeover | 1 Bit | 1.1 switch | CWTU |
| 534 | RTC 5 - Room temperature controller: {{0}} | Heating active | 1 Bit | 1.11 state | CT |
| 535 | RTC 5 - Room temperature controller: {{0}} | Cooling active | 1 Bit | 1.11 state | CT |
| 536 | RTC 5 - Room temperature controller: {{0}} | Heating/cooling changeover (main/secondary) | 1 Bit | 1.100 cooling/heating | CWTU |
| 537 | RTC 5 - Room temperature controller: {{0}} | Status Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CT |
| 538 | RTC 5 - Room temperature controller: {{0}} | Block/enable heating | 1 Bit | 1.3 enable | CWTU |
| 539 | RTC 5 - Room temperature controller: {{0}} | Block/enable cooling | 1 Bit | 1.3 enable | CWTU |
| 540 | RTC 5 - Room temperature controller: {{0}} | Block/enable heating stages separately | 1 Byte | 20.116 enable H/C stage | CWTU |
| 541 | RTC 5 - Room temperature controller: {{0}} | Block/enable cooling stages separately | 1 Byte | 20.116 enable H/C stage | CWTU |
| 542 | RTC 5 - Room temperature controller: {{0}} | Controller synchronization output | 1 Byte | 20.105 HVAC control mode | CRT |
| 543 | RTC 5 - Room temperature controller: {{0}} | Controller synchronization input | 1 Byte | 20.105 HVAC control mode | CWTU |
| 544 | RTC 5 - Room temperature controller: {{0}} | Basic-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 545 | RTC 5 - Room temperature controller: {{0}} | Additional-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 546 | RTC 5 - Room temperature controller: {{0}} | Basic-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 547 | RTC 5 - Room temperature controller: {{0}} | Additional-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 548 | RTC 5 - Room temperature controller: {{0}} | Activate floor heating | 1 Bit | 1.11 state | CWTU |
| 549 | RTC 5 - Room temperature controller: {{0}} | Floor heating basic-stage heating | 2 Bytes | 9.1 temperature (°C) | CWU |
| 550 | RTC 5 - Room temperature controller: {{0}} | Floor heating additional-stage heating | 2 Bytes | 9.1 temperature (°C) | CWU |
| 551 | RTC 5 - Room temperature controller: {{0}} | Basic load | 1 Bit | 1.11 state | CWTU |
| 552 | RTC 5 - Room temperature controller: {{0}} | Boost | 1 Bit | 1.11 state | CWTU |
| 553 | RTC 5 - Room temperature controller: {{0}} | Scene | 1 Byte | 18.1 scene control | CWU |
| 554 | RTC 5 - Room temperature controller: {{0}} | Solar power surplus | 1 Bit | 1.11 state | CWTU |
| 555 | RTC 5 - Room temperature controller: {{0}} | Request master/slave synchronization | 14 Bytes | 16.1 Character String (ISO 8859-1) | CWU |
| 556 | RTC 5 - Room temperature controller: {{0}} | Confirm master/slave synchronization | 14 Bytes | 16.1 Character String (ISO 8859-1) | CT |
| 557 | RTC 5 - Room temperature controller: {{0}} | Fan manual | 1 Bit | 1.2 boolean | CWTU |
| 558 | RTC 5 - Room temperature controller: {{0}} | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 559 | RTC 5 - Room temperature controller: {{0}} | Fan manual status | 1 Bit | 1.2 boolean | CT |
| 559 | RTC 5 - Room temperature controller: {{0}} | Fan manual (heating) status | 1 Bit | 1.2 boolean | CT |
| 560 | RTC 5 - Room temperature controller: {{0}} | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CT |
| 560 | RTC 5 - Room temperature controller: {{0}} | Fan speed (Heating) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 561 | RTC 5 - Room temperature controller: {{0}} | Fan speed 1 | 1 Bit | 1.1 switch | CT |
| 561 | RTC 5 - Room temperature controller: {{0}} | Fan speed 1 (Heating) | 1 Bit | 1.1 switch | CT |
| 562 | RTC 5 - Room temperature controller: {{0}} | Fan speed 2 | 1 Bit | 1.1 switch | CT |
| 562 | RTC 5 - Room temperature controller: {{0}} | Fan speed 2 (Heating) | 1 Bit | 1.1 switch | CT |
| 563 | RTC 5 - Room temperature controller: {{0}} | Fan speed 3 | 1 Bit | 1.1 switch | CT |
| 563 | RTC 5 - Room temperature controller: {{0}} | Fan speed 3 (heating) | 1 Bit | 1.1 switch | CT |
| 564 | RTC 5 - Room temperature controller: {{0}} | Fan speed 4 | 1 Bit | 1.1 switch | CT |
| 564 | RTC 5 - Room temperature controller: {{0}} | Fan speed 4 (heating) | 1 Bit | 1.1 switch | CT |
| 565 | RTC 5 - Room temperature controller: {{0}} | Fan speed 5 | 1 Bit | 1.1 switch | CT |
| 565 | RTC 5 - Room temperature controller: {{0}} | Fan speed 5 (heating) | 1 Bit | 1.1 switch | CT |
| 566 | RTC 5 - Room temperature controller: {{0}} | Fan manual (Cooling) status | 1 Bit | 1.2 boolean | CT |
| 567 | RTC 5 - Room temperature controller: {{0}} | Fan speed (Cooling) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 568 | RTC 5 - Room temperature controller: {{0}} | Fan speed 1 (Cooling) | 1 Bit | 1.1 switch | CT |
| 569 | RTC 5 - Room temperature controller: {{0}} | Fan speed 2 (Cooling) | 1 Bit | 1.1 switch | CT |
| 570 | RTC 5 - Room temperature controller: {{0}} | Fan speed 3 (Cooling) | 1 Bit | 1.1 switch | CT |
| 571 | RTC 5 - Room temperature controller: {{0}} | Fan speed 4 (Cooling) | 1 Bit | 1.1 switch | CT |
| 572 | RTC 5 - Room temperature controller: {{0}} | Fan speed 5 (Cooling) | 1 Bit | 1.1 switch | CT |
| 573 | RTC 5 - Room temperature controller: {{0}} | Current fan speed | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 574 | RTC 5 - Room temperature controller: {{0}} | Current fan speed Cooling | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 575 | RTC 5 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA | 1 Byte | 21.1 general status | CT |
| 575 | RTC 5 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA Kühlen | 1 Byte | 21.1 general status | CT |
| 576 | RTC 5 - Room temperature controller: {{0}} | Fancoil-Aktor-Status FA Heizen | 1 Byte | 21.1 general status | CT |
| 577 | RTC 6 - Room temperature controller: {{0}} | Control value basic-stage heating | 1 Byte | 5.1 percentage (0..100%) | CT |
| 577 | RTC 6 - Room temperature controller: {{0}} | Basic-stage heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 578 | RTC 6 - Room temperature controller: {{0}} | Control value additional-stage heating | 1 Byte | 5.1 percentage (0..100%) | CT |
| 578 | RTC 6 - Room temperature controller: {{0}} | Control value additional-stage heating | 1 Bit | 1.1 switch | CT |
| 579 | RTC 6 - Room temperature controller: {{0}} | Control value basic-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 579 | RTC 6 - Room temperature controller: {{0}} | Additional-stage heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 580 | RTC 6 - Room temperature controller: {{0}} | Control value additional-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CT |
| 580 | RTC 6 - Room temperature controller: {{0}} | Control value additional-stage cooling | 1 Bit | 1.1 switch | CT |
| 581 | RTC 6 - Room temperature controller: {{0}} | Valve actuator status HVA heating | 2 Bytes | 22.102 combined status HVA | CWU |
| 582 | RTC 6 - Room temperature controller: {{0}} | Valve actuator status HVA additional-stage heating | 2 Bytes | 22.102 combined status HVA | CWU |
| 583 | RTC 6 - Room temperature controller: {{0}} | Valve actuator status HVA cooling | 2 Bytes | 22.102 combined status HVA | CWU |
| 584 | RTC 6 - Room temperature controller: {{0}} | Valve actuator status HVA additional-stage cooling | 2 Bytes | 22.102 combined status HVA | CWU |
| 585 | RTC 6 - Room temperature controller: {{0}} | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 585 | RTC 6 - Room temperature controller: {{0}} | Actual temperature weighted | 2 Bytes | 9.1 temperature (°C) | CRT |
| 586 | RTC 6 - Room temperature controller: {{0}} | External actual temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 587 | RTC 6 - Room temperature controller: {{0}} | Local actual temperature | 2 Bytes | 9.1 temperature (°C) | CT |