| 1 | Central - General: | In operation | 1 Bit | 1.2 boolean | CT |
| 2 | Central - General: | Request status values | 1 Bit | 1.17 trigger | CWU |
| 3 | Central - Date/time: | Set time | 3 Bytes | 10.1 time of day | CWU |
| 3 | Central - Date/time: | Set date/time | 8 Bytes | 19.1 date time | CWU |
| 4 | Central - Date/time: | Set date | 3 Bytes | 11.1 date | CWU |
| 5 | Central - Date/time: | Poll time | 1 Bit | 1.17 trigger | CT |
| 10 | Central - General: | DCA configuration access is active | 1 Bit | 1.2 boolean | CRT |
| 11 | Central - General: | MP-Bus voltage failure | 1 Bit | 1.5 alarm | CRT |
| 12 | Central - General: | Communication error | 1 Bit | 1.5 alarm | CRT |
| 13 | Central - General: | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 14 | Central - General: | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 15 | Central - General: | MP-Bus device error | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 16 | Channel 1 - Air VAV compact controller: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 16 | Channel 1 - Air VAV compact controller: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 16 | Channel 1 - Air VAV compact controller: {{0}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 16 | Channel 1 - Air rotary/damper actuator: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 16 | Channel 1 - Air rotary/damper actuator: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 16 | Channel 1 - Air rotary/damper actuator: {{0}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 16 | Channel 1 - Water rotary actuator: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 16 | Channel 1 - Water rotary actuator: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 16 | Channel 1 - Water rotary actuator: {{0}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 16 | Channel 1 - VAV universal controller: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 16 | Channel 1 - Water 2-way valve: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 16 | Channel 1 - Thermal energy meter: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 16 | Channel 1 - Room control unit: {{0}} | Confirm room temperature setpoint (absolute) | 2 Bytes | 9.1 temperature (°C) | CWTUI |
| 16 | Channel 1 - Room control unit: {{0}} | Confirm room temperature setpoint (relative) | 2 Bytes | 9.2 temperature difference (K) | CWTUI |
| 17 | Channel 1 - Air VAV compact controller: {{0}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 17 | Channel 1 - Air rotary/damper actuator: {{0}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 17 | Channel 1 - Water rotary actuator: {{0}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 17 | Channel 1 - VAV universal controller: {{0}} | Override control | 1 Byte | | CWTUI |
| 17 | Channel 1 - Water 2-way valve: {{0}} | Setpoint absolute differential pressure | 4 Bytes | 14.58 pressure (Pa) | CWTUI |
| 17 | Channel 1 - Thermal energy meter: {{0}} | Setpoint absolute differential pressure | 4 Bytes | 14.58 pressure (Pa) | CWTUI |
| 17 | Channel 1 - Room control unit: {{0}} | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CWTUI |
| 18 | Channel 1 - Air VAV compact controller: {{0}} | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTUI |
| 18 | Channel 1 - Air rotary/damper actuator: {{0}} | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTUI |
| 18 | Channel 1 - Water rotary actuator: {{0}} | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTUI |
| 18 | Channel 1 - VAV universal controller: {{0}} | Start adjustment | 1 Bit | 1.17 trigger | CW |
| 18 | Channel 1 - Water 2-way valve: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 18 | Channel 1 - Thermal energy meter: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 18 | Channel 1 - Room control unit: {{0}} | Confirm fan speed | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 19 | Channel 1 - Air VAV compact controller: {{0}} | Activate heating | 1 Bit | 1.3 enable | CWTUI |
| 19 | Channel 1 - Air rotary/damper actuator: {{0}} | Activate heating | 1 Bit | 1.3 enable | CWTUI |
| 19 | Channel 1 - Water rotary actuator: {{0}} | Activate heating | 1 Bit | 1.3 enable | CWTUI |
| 19 | Channel 1 - VAV universal controller: {{0}} | Start synchronization | 1 Bit | 1.17 trigger | CW |
| 19 | Channel 1 - Water 2-way valve: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 19 | Channel 1 - Thermal energy meter: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 19 | Channel 1 - Room control unit: {{0}} | Request fan automatic mode | 1 Bit | 1.3 enable | CWTUI |
| 20 | Channel 1 - Air VAV compact controller: {{0}} | Activate cooling | 1 Bit | 1.3 enable | CWTUI |
| 20 | Channel 1 - Air rotary/damper actuator: {{0}} | Activate cooling | 1 Bit | 1.3 enable | CWTUI |
| 20 | Channel 1 - Water rotary actuator: {{0}} | Activate cooling | 1 Bit | 1.3 enable | CWTUI |
| 20 | Channel 1 - VAV universal controller: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 20 | Channel 1 - VAV universal controller: {{0}} | Minimum differential pressure | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 20 | Channel 1 - Water 2-way valve: {{0}} | Maximum power limit | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 20 | Channel 1 - Thermal energy meter: {{0}} | Maximum power limit | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 20 | Channel 1 - Room control unit: {{0}} | Display warning icon | 1 Bit | 1.3 enable | CWTUI |
| 21 | Channel 1 - Air VAV compact controller: {{0}} | Override control | 1 Byte | | CWTUI |
| 21 | Channel 1 - Air rotary/damper actuator: {{0}} | Override control | 1 Byte | | CWTUI |
| 21 | Channel 1 - Water rotary actuator: {{0}} | Override control | 1 Byte | | CWTUI |
| 21 | Channel 1 - VAV universal controller: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 21 | Channel 1 - VAV universal controller: {{0}} | Maximum differential pressure | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 21 | Channel 1 - Water 2-way valve: {{0}} | Activate Delta-T Manager | 1 Bit | 1.3 enable | CWTUI |
| 21 | Channel 1 - Thermal energy meter: {{0}} | Activate Delta-T Manager | 1 Bit | 1.3 enable | CWTUI |
| 21 | Channel 1 - Room control unit: {{0}} | Display window icon | 1 Bit | 1.3 enable | CWTUI |
| 22 | Channel 1 - Air VAV compact controller: {{0}} | Minimum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 22 | Channel 1 - Air VAV compact controller: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 22 | Channel 1 - Air rotary/damper actuator: {{0}} | Minimum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 22 | Channel 1 - Air rotary/damper actuator: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 22 | Channel 1 - Water rotary actuator: {{0}} | Minimum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 22 | Channel 1 - Water rotary actuator: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 22 | Channel 1 - VAV universal controller: {{0}} | Status Analog input signal | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 22 | Channel 1 - Water 2-way valve: {{0}} | Activate Delta-T Manager flow-dependent adjustment (scaling) | 1 Bit | 1.3 enable | CWTUI |
| 22 | Channel 1 - Thermal energy meter: {{0}} | Activate Delta-T Manager flow-dependent adjustment (scaling) | 1 Bit | 1.3 enable | CWTUI |
| 22 | Channel 1 - Room control unit: {{0}} | Status RTC controller | 2 Bytes | 22.103 combined status RTC | CWTUI |
| 23 | Channel 1 - Air VAV compact controller: {{0}} | Maximum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 23 | Channel 1 - Air VAV compact controller: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 23 | Channel 1 - Air rotary/damper actuator: {{0}} | Maximum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 23 | Channel 1 - Air rotary/damper actuator: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 23 | Channel 1 - Water rotary actuator: {{0}} | Maximum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 23 | Channel 1 - Water rotary actuator: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 23 | Channel 1 - VAV universal controller: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 23 | Channel 1 - Water 2-way valve: {{0}} | Setpoint Delta-T limitation | 2 Bytes | 9.2 temperature difference (K) | CWTUI |
| 23 | Channel 1 - Thermal energy meter: {{0}} | Setpoint Delta-T limitation | 2 Bytes | 9.2 temperature difference (K) | CWTUI |
| 23 | Channel 1 - Room control unit: {{0}} | Receive status Heating | 1 Bit | 1.3 enable | CWTUI |
| 24 | Channel 1 - Air VAV compact controller: {{0}} | Start test run | 1 Bit | 1.17 trigger | CW |
| 24 | Channel 1 - Air rotary/damper actuator: {{0}} | Start test run | 1 Bit | 1.17 trigger | CW |
| 24 | Channel 1 - Water rotary actuator: {{0}} | Start test run | 1 Bit | 1.17 trigger | CW |
| 24 | Channel 1 - VAV universal controller: {{0}} | Status Absolute position | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 24 | Channel 1 - Water 2-way valve: {{0}} | Setpoint absolute flow at Delta-T | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CWTUI |
| 24 | Channel 1 - Thermal energy meter: {{0}} | Setpoint absolute flow at Delta-T | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CWTUI |
| 24 | Channel 1 - Room control unit: {{0}} | Receive status Cooling | 1 Bit | 1.3 enable | CWTUI |
| 25 | Channel 1 - Air VAV compact controller: {{0}} | Start adjustment | 1 Bit | 1.17 trigger | CW |
| 25 | Channel 1 - Air rotary/damper actuator: {{0}} | Start adjustment | 1 Bit | 1.17 trigger | CW |
| 25 | Channel 1 - Water rotary actuator: {{0}} | Start adjustment | 1 Bit | 1.17 trigger | CW |
| 25 | Channel 1 - VAV universal controller: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 25 | Channel 1 - VAV universal controller: {{0}} | Status Minimum differential pressure | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 25 | Channel 1 - Water 2-way valve: {{0}} | Start synchronization | 1 Bit | 1.17 trigger | CW |
| 25 | Channel 1 - Thermal energy meter: {{0}} | Start synchronization | 1 Bit | 1.17 trigger | CW |
| 25 | Channel 1 - Room control unit: {{0}} | Confirm RTR operating mode | 1 Byte | 20.102 HVAC mode | CWTUI |
| 26 | Channel 1 - Air VAV compact controller: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 26 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 26 | Channel 1 - Water rotary actuator: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 26 | Channel 1 - VAV universal controller: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 26 | Channel 1 - VAV universal controller: {{0}} | Status Maximum differential pressure | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 26 | Channel 1 - Water 2-way valve: {{0}} | Override control | 1 Byte | | CWTUI |
| 26 | Channel 1 - Thermal energy meter: {{0}} | Override control | 1 Byte | | CWTUI |
| 26 | Channel 1 - Room control unit: {{0}} | Block local operation | 1 Bit | 1.3 enable | CWTUI |
| 27 | Channel 1 - Air VAV compact controller: {{0}} | Status Absolute position (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 27 | Channel 1 - Air VAV compact controller: {{0}} | Status Absolute position (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 27 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Absolute position (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 27 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Absolute position (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 27 | Channel 1 - Water rotary actuator: {{0}} | Status Absolute position (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 27 | Channel 1 - Water rotary actuator: {{0}} | Status Absolute position (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 27 | Channel 1 - VAV universal controller: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 27 | Channel 1 - Water 2-way valve: {{0}} | Status Analog input signal | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 27 | Channel 1 - Thermal energy meter: {{0}} | Status Analog input signal | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 27 | Channel 1 - Room control unit: {{0}} | Display Boost mode | 1 Bit | 1.1 switch | CWTUI |
| 28 | Channel 1 - Air VAV compact controller: {{0}} | Status Nominal range (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 28 | Channel 1 - Air VAV compact controller: {{0}} | Status Nominal range (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 28 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Nominal range (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 28 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Nominal range (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 28 | Channel 1 - Water rotary actuator: {{0}} | Status Nominal range (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 28 | Channel 1 - Water rotary actuator: {{0}} | Status Nominal range (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 28 | Channel 1 - VAV universal controller: {{0}} | Status Absolute flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 28 | Channel 1 - VAV universal controller: {{0}} | Status Absolute flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 28 | Channel 1 - Water 2-way valve: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 28 | Channel 1 - Thermal energy meter: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 28 | Channel 1 - Room control unit: {{0}} | Status Room temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 29 | Channel 1 - Air VAV compact controller: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 29 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 29 | Channel 1 - Water rotary actuator: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 29 | Channel 1 - VAV universal controller: {{0}} | Status Nominal flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 29 | Channel 1 - VAV universal controller: {{0}} | Status Nominal flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 29 | Channel 1 - Water 2-way valve: {{0}} | Status Absolute position | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 29 | Channel 1 - Thermal energy meter: {{0}} | Status Absolute position | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 29 | Channel 1 - Room control unit: {{0}} | Status Relative humidity | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 30 | Channel 1 - Air VAV compact controller: {{0}} | Status Absolute flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 30 | Channel 1 - Air VAV compact controller: {{0}} | Status Absolute flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 30 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Absolute flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 30 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Absolute flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 30 | Channel 1 - Water rotary actuator: {{0}} | Status Absolute flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 30 | Channel 1 - Water rotary actuator: {{0}} | Status Absolute flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 30 | Channel 1 - VAV universal controller: {{0}} | Status Relative differential pressure | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 30 | Channel 1 - Water 2-way valve: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 30 | Channel 1 - Water 2-way valve: {{0}} | Status Relative flow rate | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 30 | Channel 1 - Thermal energy meter: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 30 | Channel 1 - Thermal energy meter: {{0}} | Status Relative flow rate | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 30 | Channel 1 - Room control unit: {{0}} | CO2 value | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 31 | Channel 1 - Air VAV compact controller: {{0}} | Status Nominal flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 31 | Channel 1 - Air VAV compact controller: {{0}} | Status Nominal flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 31 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Nominal flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 31 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Nominal flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 31 | Channel 1 - Water rotary actuator: {{0}} | Status Nominal flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 31 | Channel 1 - Water rotary actuator: {{0}} | Status Nominal flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 31 | Channel 1 - VAV universal controller: {{0}} | Status Absolute differential pressure | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 31 | Channel 1 - Water 2-way valve: {{0}} | Status Absolute flow rate | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CRT |
| 31 | Channel 1 - Thermal energy meter: {{0}} | Status Absolute flow rate | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CRT |
| 31 | Channel 1 - Room control unit: {{0}} | Air quality OK | 1 Bit | 1.2 boolean | CRT |
| 32 | Channel 1 - Air VAV compact controller: {{0}} | Status Minimum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 32 | Channel 1 - Air VAV compact controller: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 32 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Minimum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 32 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 32 | Channel 1 - Water rotary actuator: {{0}} | Status Minimum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 32 | Channel 1 - Water rotary actuator: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 32 | Channel 1 - VAV universal controller: {{0}} | Status Nominal differential pressure | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 32 | Channel 1 - Water 2-way valve: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 32 | Channel 1 - Thermal energy meter: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 32 | Channel 1 - Room control unit: {{0}} | Air quality warning | 1 Bit | 1.2 boolean | CRT |
| 33 | Channel 1 - Air VAV compact controller: {{0}} | Status Maximum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 33 | Channel 1 - Air VAV compact controller: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 33 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Maximum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 33 | Channel 1 - Air rotary/damper actuator: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 33 | Channel 1 - Water rotary actuator: {{0}} | Status Maximum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 33 | Channel 1 - Water rotary actuator: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 33 | Channel 1 - VAV universal controller: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 33 | Channel 1 - VAV universal controller: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 33 | Channel 1 - VAV universal controller: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 33 | Channel 1 - VAV universal controller: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 33 | Channel 1 - VAV universal controller: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 33 | Channel 1 - VAV universal controller: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 33 | Channel 1 - VAV universal controller: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 33 | Channel 1 - VAV universal controller: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 33 | Channel 1 - VAV universal controller: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 33 | Channel 1 - Water 2-way valve: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 33 | Channel 1 - Thermal energy meter: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 33 | Channel 1 - Room control unit: {{0}} | Air quality alarm | 1 Bit | 1.2 boolean | CRT |
| 34 | Channel 1 - Air VAV compact controller: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 34 | Channel 1 - Air VAV compact controller: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 34 | Channel 1 - Air VAV compact controller: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 34 | Channel 1 - Air VAV compact controller: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 34 | Channel 1 - Air VAV compact controller: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 34 | Channel 1 - Air VAV compact controller: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 34 | Channel 1 - Air VAV compact controller: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 34 | Channel 1 - Air VAV compact controller: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 34 | Channel 1 - Air VAV compact controller: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 34 | Channel 1 - Air rotary/damper actuator: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 34 | Channel 1 - Air rotary/damper actuator: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 34 | Channel 1 - Air rotary/damper actuator: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 34 | Channel 1 - Air rotary/damper actuator: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 34 | Channel 1 - Air rotary/damper actuator: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 34 | Channel 1 - Air rotary/damper actuator: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 34 | Channel 1 - Air rotary/damper actuator: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 34 | Channel 1 - Air rotary/damper actuator: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 34 | Channel 1 - Air rotary/damper actuator: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 34 | Channel 1 - Water rotary actuator: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 34 | Channel 1 - Water rotary actuator: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 34 | Channel 1 - Water rotary actuator: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 34 | Channel 1 - Water rotary actuator: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 34 | Channel 1 - Water rotary actuator: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 34 | Channel 1 - Water rotary actuator: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 34 | Channel 1 - Water rotary actuator: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 34 | Channel 1 - Water rotary actuator: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 34 | Channel 1 - Water rotary actuator: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 34 | Channel 1 - VAV universal controller: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 34 | Channel 1 - Water 2-way valve: {{0}} | Status Nominal flow rate | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CRT |
| 34 | Channel 1 - Thermal energy meter: {{0}} | Status Nominal flow rate | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CRT |
| 34 | Channel 1 - Room control unit: {{0}} | Binary input | 1 Bit | 1.1 switch | CRT |
| 35 | Channel 1 - Air VAV compact controller: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 35 | Channel 1 - Air rotary/damper actuator: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 35 | Channel 1 - Water rotary actuator: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 35 | Channel 1 - VAV universal controller: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 35 | Channel 1 - Water 2-way valve: {{0}} | Status Relative power | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 35 | Channel 1 - Water 2-way valve: {{0}} | Status Relative power | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 35 | Channel 1 - Thermal energy meter: {{0}} | Status Relative power | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 35 | Channel 1 - Thermal energy meter: {{0}} | Status Relative power | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 35 | Channel 1 - Room control unit: {{0}} | Dew point temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 36 | Channel 1 - Air VAV compact controller: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 36 | Channel 1 - Air rotary/damper actuator: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 36 | Channel 1 - Water rotary actuator: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 36 | Channel 1 - VAV universal controller: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 36 | Channel 1 - Water 2-way valve: {{0}} | Status Absolute cooling power | 4 Bytes | 14.56 power (W) | CRT |
| 36 | Channel 1 - Thermal energy meter: {{0}} | Status Absolute cooling power | 4 Bytes | 14.56 power (W) | CRT |
| 36 | Channel 1 - Room control unit: {{0}} | Request room temperature setpoint (absolute) | 2 Bytes | 9.1 temperature (°C) | CT |
| 37 | Channel 1 - Air VAV compact controller: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 37 | Channel 1 - Air rotary/damper actuator: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 37 | Channel 1 - Water rotary actuator: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 37 | Channel 1 - VAV universal controller: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 37 | Channel 1 - Water 2-way valve: {{0}} | Status Absolute heating power | 4 Bytes | 14.56 power (W) | CRT |
| 37 | Channel 1 - Thermal energy meter: {{0}} | Status Absolute heating power | 4 Bytes | 14.56 power (W) | CRT |
| 37 | Channel 1 - Room control unit: {{0}} | Request room temperature setpoint (relative) | 2 Bytes | 9.2 temperature difference (K) | CT |
| 38 | Channel 1 - Air VAV compact controller: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 38 | Channel 1 - Air rotary/damper actuator: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 38 | Channel 1 - Water rotary actuator: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 38 | Channel 1 - VAV universal controller: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 38 | Channel 1 - Water 2-way valve: {{0}} | Status Maximum power limit | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 38 | Channel 1 - Thermal energy meter: {{0}} | Status Maximum power limit | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 38 | Channel 1 - Room control unit: {{0}} | Request fan speed | 1 Byte | 5.1 percentage (0..100%) | CT |
| 39 | Channel 1 - Air VAV compact controller: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 39 | Channel 1 - Air rotary/damper actuator: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 39 | Channel 1 - Water rotary actuator: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 39 | Channel 1 - VAV universal controller: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 39 | Channel 1 - Water 2-way valve: {{0}} | Status Nominal power | 4 Bytes | 14.56 power (W) | CRT |
| 39 | Channel 1 - Thermal energy meter: {{0}} | Status Nominal power | 4 Bytes | 14.56 power (W) | CRT |
| 39 | Channel 1 - Room control unit: {{0}} | Confirm fan automatic mode | 1 Bit | 1.3 enable | CT |
| 40 | Channel 1 - Air VAV compact controller: {{0}} | Reset service information | 1 Bit | 1.10 start/stop | CW |
| 40 | Channel 1 - Air rotary/damper actuator: {{0}} | Reset service information | 1 Bit | 1.10 start/stop | CW |
| 40 | Channel 1 - Water rotary actuator: {{0}} | Reset service information | 1 Bit | 1.10 start/stop | CW |
| 40 | Channel 1 - VAV universal controller: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 40 | Channel 1 - Water 2-way valve: {{0}} | Status Relative differential pressure | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 40 | Channel 1 - Room control unit: {{0}} | Request RTR operating mode | 1 Byte | 20.102 HVAC mode | CT |
| 41 | Channel 1 - Air VAV compact controller: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 41 | Channel 1 - Air rotary/damper actuator: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 41 | Channel 1 - Water rotary actuator: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 41 | Channel 1 - VAV universal controller: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 41 | Channel 1 - Water 2-way valve: {{0}} | Status Absolute differential pressure | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 41 | Channel 1 - Room control unit: {{0}} | Activate Boost mode | 1 Bit | 1.1 switch | CT |
| 42 | Channel 1 - Air VAV compact controller: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 42 | Channel 1 - Air rotary/damper actuator: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 42 | Channel 1 - Water rotary actuator: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 42 | Channel 1 - VAV universal controller: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 42 | Channel 1 - Water 2-way valve: {{0}} | Status Nominal differential pressure | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 42 | Channel 1 - Room control unit: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 43 | Channel 1 - Air VAV compact controller: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 43 | Channel 1 - Air rotary/damper actuator: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 43 | Channel 1 - Water rotary actuator: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 43 | Channel 1 - Water 2-way valve: {{0}} | Status Glycol concentration | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 43 | Channel 1 - Thermal energy meter: {{0}} | Status Glycol concentration | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 43 | Channel 1 - Room control unit: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 44 | Channel 1 - Air VAV compact controller: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 44 | Channel 1 - Air rotary/damper actuator: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 44 | Channel 1 - Water rotary actuator: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 44 | Channel 1 - Water 2-way valve: {{0}} | Certified meter | 1 Bit | 1.2 boolean | CRT |
| 44 | Channel 1 - Thermal energy meter: {{0}} | Certified meter | 1 Bit | 1.2 boolean | CRT |
| 44 | Channel 1 - Room control unit: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 45 | Channel 1 - Water 2-way valve: {{0}} | Status Accumulated volume | 4 Bytes | 14.76 volume (m³) | CRT |
| 45 | Channel 1 - Thermal energy meter: {{0}} | Status Accumulated volume | 4 Bytes | 14.76 volume (m³) | CRT |
| 45 | Channel 1 - Room control unit: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 46 | Channel 1 - Water 2-way valve: {{0}} | Status Total energy cooling | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 46 | Channel 1 - Thermal energy meter: {{0}} | Status Total energy cooling | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 46 | Channel 1 - Room control unit: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 47 | Channel 1 - Water 2-way valve: {{0}} | Status Total energy heating | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 47 | Channel 1 - Thermal energy meter: {{0}} | Status Total energy heating | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 48 | Channel 1 - Water 2-way valve: {{0}} | Energy meter serial number (upper digits) | 4 Bytes | | CRT |
| 48 | Channel 1 - Thermal energy meter: {{0}} | Energy meter serial number (upper digits) | 4 Bytes | | CRT |
| 49 | Channel 1 - Water 2-way valve: {{0}} | Energy meter serial number (lower digits) | 4 Bytes | | CRT |
| 49 | Channel 1 - Thermal energy meter: {{0}} | Energy meter serial number (lower digits) | 4 Bytes | | CRT |
| 50 | Channel 1 - Water 2-way valve: {{0}} | Status Delta temperature | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 50 | Channel 1 - Thermal energy meter: {{0}} | Status Delta temperature | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 51 | Channel 1 - Water 2-way valve: {{0}} | Status Delta-T Manager | 1 Bit | 1.2 boolean | CRT |
| 51 | Channel 1 - Thermal energy meter: {{0}} | Status Delta-T Manager | 1 Bit | 1.2 boolean | CRT |
| 52 | Channel 1 - Water 2-way valve: {{0}} | Status Delta-T Manager flow-dependent adjustment (scaling) | 1 Bit | 1.2 boolean | CRT |
| 52 | Channel 1 - Thermal energy meter: {{0}} | Status Delta-T Manager flow-dependent adjustment (scaling) | 1 Bit | 1.2 boolean | CRT |
| 53 | Channel 1 - Water 2-way valve: {{0}} | Temperature internal sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 53 | Channel 1 - Thermal energy meter: {{0}} | Temperature internal sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 54 | Channel 1 - Water 2-way valve: {{0}} | Temperature external sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 54 | Channel 1 - Thermal energy meter: {{0}} | Temperature external sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 55 | Channel 1 - Water 2-way valve: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 55 | Channel 1 - Water 2-way valve: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 55 | Channel 1 - Water 2-way valve: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 55 | Channel 1 - Water 2-way valve: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 55 | Channel 1 - Water 2-way valve: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 55 | Channel 1 - Water 2-way valve: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 55 | Channel 1 - Water 2-way valve: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 55 | Channel 1 - Water 2-way valve: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 55 | Channel 1 - Water 2-way valve: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 55 | Channel 1 - Thermal energy meter: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 55 | Channel 1 - Thermal energy meter: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 55 | Channel 1 - Thermal energy meter: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 55 | Channel 1 - Thermal energy meter: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 55 | Channel 1 - Thermal energy meter: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 55 | Channel 1 - Thermal energy meter: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 55 | Channel 1 - Thermal energy meter: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 55 | Channel 1 - Thermal energy meter: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 55 | Channel 1 - Thermal energy meter: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 56 | Channel 1 - Water 2-way valve: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 56 | Channel 1 - Thermal energy meter: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 57 | Channel 1 - Water 2-way valve: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 57 | Channel 1 - Thermal energy meter: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 58 | Channel 1 - Water 2-way valve: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 58 | Channel 1 - Thermal energy meter: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 59 | Channel 1 - Water 2-way valve: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 59 | Channel 1 - Thermal energy meter: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 60 | Channel 1 - Water 2-way valve: {{0}} | Sensor module must be replaced | 1 Bit | 1.5 alarm | CRT |
| 60 | Channel 1 - Thermal energy meter: {{0}} | Sensor module must be replaced | 1 Bit | 1.5 alarm | CRT |
| 61 | Channel 1 - Water 2-way valve: {{0}} | MP-Bus monitoring timed out | 1 Bit | 1.5 alarm | CRT |
| 61 | Channel 1 - Thermal energy meter: {{0}} | MP-Bus monitoring timed out | 1 Bit | 1.5 alarm | CRT |
| 62 | Channel 1 - Water 2-way valve: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 62 | Channel 1 - Thermal energy meter: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 63 | Channel 1 - Water 2-way valve: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 63 | Channel 1 - Thermal energy meter: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 64 | Channel 1 - Water 2-way valve: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 64 | Channel 1 - Thermal energy meter: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 65 | Channel 1 - Water 2-way valve: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 65 | Channel 1 - Thermal energy meter: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 66 | Channel 1 - Water 2-way valve: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 66 | Channel 1 - Thermal energy meter: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 67 | Channel 2 - Air VAV compact controller: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 67 | Channel 2 - Air VAV compact controller: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 67 | Channel 2 - Air VAV compact controller: {{0}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 67 | Channel 2 - Air rotary/damper actuator: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 67 | Channel 2 - Air rotary/damper actuator: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 67 | Channel 2 - Air rotary/damper actuator: {{0}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 67 | Channel 2 - Water rotary actuator: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 67 | Channel 2 - Water rotary actuator: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 67 | Channel 2 - Water rotary actuator: {{0}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 67 | Channel 2 - VAV universal controller: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 67 | Channel 2 - Water 2-way valve: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 67 | Channel 2 - Thermal energy meter: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 67 | Channel 2 - Room control unit: {{0}} | Confirm room temperature setpoint (absolute) | 2 Bytes | 9.1 temperature (°C) | CWTUI |
| 67 | Channel 2 - Room control unit: {{0}} | Confirm room temperature setpoint (relative) | 2 Bytes | 9.2 temperature difference (K) | CWTUI |
| 68 | Channel 2 - Air VAV compact controller: {{0}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 68 | Channel 2 - Air rotary/damper actuator: {{0}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 68 | Channel 2 - Water rotary actuator: {{0}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 68 | Channel 2 - VAV universal controller: {{0}} | Override control | 1 Byte | | CWTUI |
| 68 | Channel 2 - Water 2-way valve: {{0}} | Setpoint absolute differential pressure | 4 Bytes | 14.58 pressure (Pa) | CWTUI |
| 68 | Channel 2 - Thermal energy meter: {{0}} | Setpoint absolute differential pressure | 4 Bytes | 14.58 pressure (Pa) | CWTUI |
| 68 | Channel 2 - Room control unit: {{0}} | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CWTUI |
| 69 | Channel 2 - Air VAV compact controller: {{0}} | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTUI |
| 69 | Channel 2 - Air rotary/damper actuator: {{0}} | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTUI |
| 69 | Channel 2 - Water rotary actuator: {{0}} | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTUI |
| 69 | Channel 2 - VAV universal controller: {{0}} | Start adjustment | 1 Bit | 1.17 trigger | CW |
| 69 | Channel 2 - Water 2-way valve: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 69 | Channel 2 - Thermal energy meter: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 69 | Channel 2 - Room control unit: {{0}} | Confirm fan speed | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 70 | Channel 2 - Air VAV compact controller: {{0}} | Activate heating | 1 Bit | 1.3 enable | CWTUI |
| 70 | Channel 2 - Air rotary/damper actuator: {{0}} | Activate heating | 1 Bit | 1.3 enable | CWTUI |
| 70 | Channel 2 - Water rotary actuator: {{0}} | Activate heating | 1 Bit | 1.3 enable | CWTUI |
| 70 | Channel 2 - VAV universal controller: {{0}} | Start synchronization | 1 Bit | 1.17 trigger | CW |
| 70 | Channel 2 - Water 2-way valve: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 70 | Channel 2 - Thermal energy meter: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 70 | Channel 2 - Room control unit: {{0}} | Request fan automatic mode | 1 Bit | 1.3 enable | CWTUI |
| 71 | Channel 2 - Air VAV compact controller: {{0}} | Activate cooling | 1 Bit | 1.3 enable | CWTUI |
| 71 | Channel 2 - Air rotary/damper actuator: {{0}} | Activate cooling | 1 Bit | 1.3 enable | CWTUI |
| 71 | Channel 2 - Water rotary actuator: {{0}} | Activate cooling | 1 Bit | 1.3 enable | CWTUI |
| 71 | Channel 2 - VAV universal controller: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 71 | Channel 2 - VAV universal controller: {{0}} | Minimum differential pressure | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 71 | Channel 2 - Water 2-way valve: {{0}} | Maximum power limit | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 71 | Channel 2 - Thermal energy meter: {{0}} | Maximum power limit | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 71 | Channel 2 - Room control unit: {{0}} | Display warning icon | 1 Bit | 1.3 enable | CWTUI |
| 72 | Channel 2 - Air VAV compact controller: {{0}} | Override control | 1 Byte | | CWTUI |
| 72 | Channel 2 - Air rotary/damper actuator: {{0}} | Override control | 1 Byte | | CWTUI |
| 72 | Channel 2 - Water rotary actuator: {{0}} | Override control | 1 Byte | | CWTUI |
| 72 | Channel 2 - VAV universal controller: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 72 | Channel 2 - VAV universal controller: {{0}} | Maximum differential pressure | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 72 | Channel 2 - Water 2-way valve: {{0}} | Activate Delta-T Manager | 1 Bit | 1.3 enable | CWTUI |
| 72 | Channel 2 - Thermal energy meter: {{0}} | Activate Delta-T Manager | 1 Bit | 1.3 enable | CWTUI |
| 72 | Channel 2 - Room control unit: {{0}} | Display window icon | 1 Bit | 1.3 enable | CWTUI |
| 73 | Channel 2 - Air VAV compact controller: {{0}} | Minimum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 73 | Channel 2 - Air VAV compact controller: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 73 | Channel 2 - Air rotary/damper actuator: {{0}} | Minimum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 73 | Channel 2 - Air rotary/damper actuator: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 73 | Channel 2 - Water rotary actuator: {{0}} | Minimum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 73 | Channel 2 - Water rotary actuator: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 73 | Channel 2 - VAV universal controller: {{0}} | Status Analog input signal | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 73 | Channel 2 - Water 2-way valve: {{0}} | Activate Delta-T Manager flow-dependent adjustment (scaling) | 1 Bit | 1.3 enable | CWTUI |
| 73 | Channel 2 - Thermal energy meter: {{0}} | Activate Delta-T Manager flow-dependent adjustment (scaling) | 1 Bit | 1.3 enable | CWTUI |
| 73 | Channel 2 - Room control unit: {{0}} | Status RTC controller | 2 Bytes | 22.103 combined status RTC | CWTUI |
| 74 | Channel 2 - Air VAV compact controller: {{0}} | Maximum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 74 | Channel 2 - Air VAV compact controller: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 74 | Channel 2 - Air rotary/damper actuator: {{0}} | Maximum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 74 | Channel 2 - Air rotary/damper actuator: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 74 | Channel 2 - Water rotary actuator: {{0}} | Maximum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 74 | Channel 2 - Water rotary actuator: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 74 | Channel 2 - VAV universal controller: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 74 | Channel 2 - Water 2-way valve: {{0}} | Setpoint Delta-T limitation | 2 Bytes | 9.2 temperature difference (K) | CWTUI |
| 74 | Channel 2 - Thermal energy meter: {{0}} | Setpoint Delta-T limitation | 2 Bytes | 9.2 temperature difference (K) | CWTUI |
| 74 | Channel 2 - Room control unit: {{0}} | Receive status Heating | 1 Bit | 1.3 enable | CWTUI |
| 75 | Channel 2 - Air VAV compact controller: {{0}} | Start test run | 1 Bit | 1.17 trigger | CW |
| 75 | Channel 2 - Air rotary/damper actuator: {{0}} | Start test run | 1 Bit | 1.17 trigger | CW |
| 75 | Channel 2 - Water rotary actuator: {{0}} | Start test run | 1 Bit | 1.17 trigger | CW |
| 75 | Channel 2 - VAV universal controller: {{0}} | Status Absolute position | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 75 | Channel 2 - Water 2-way valve: {{0}} | Setpoint absolute flow at Delta-T | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CWTUI |
| 75 | Channel 2 - Thermal energy meter: {{0}} | Setpoint absolute flow at Delta-T | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CWTUI |
| 75 | Channel 2 - Room control unit: {{0}} | Receive status Cooling | 1 Bit | 1.3 enable | CWTUI |
| 76 | Channel 2 - Air VAV compact controller: {{0}} | Start adjustment | 1 Bit | 1.17 trigger | CW |
| 76 | Channel 2 - Air rotary/damper actuator: {{0}} | Start adjustment | 1 Bit | 1.17 trigger | CW |
| 76 | Channel 2 - Water rotary actuator: {{0}} | Start adjustment | 1 Bit | 1.17 trigger | CW |
| 76 | Channel 2 - VAV universal controller: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 76 | Channel 2 - VAV universal controller: {{0}} | Status Minimum differential pressure | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 76 | Channel 2 - Water 2-way valve: {{0}} | Start synchronization | 1 Bit | 1.17 trigger | CW |
| 76 | Channel 2 - Thermal energy meter: {{0}} | Start synchronization | 1 Bit | 1.17 trigger | CW |
| 76 | Channel 2 - Room control unit: {{0}} | Confirm RTR operating mode | 1 Byte | 20.102 HVAC mode | CWTUI |
| 77 | Channel 2 - Air VAV compact controller: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 77 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 77 | Channel 2 - Water rotary actuator: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 77 | Channel 2 - VAV universal controller: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 77 | Channel 2 - VAV universal controller: {{0}} | Status Maximum differential pressure | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 77 | Channel 2 - Water 2-way valve: {{0}} | Override control | 1 Byte | | CWTUI |
| 77 | Channel 2 - Thermal energy meter: {{0}} | Override control | 1 Byte | | CWTUI |
| 77 | Channel 2 - Room control unit: {{0}} | Block local operation | 1 Bit | 1.3 enable | CWTUI |
| 78 | Channel 2 - Air VAV compact controller: {{0}} | Status Absolute position (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 78 | Channel 2 - Air VAV compact controller: {{0}} | Status Absolute position (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 78 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Absolute position (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 78 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Absolute position (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 78 | Channel 2 - Water rotary actuator: {{0}} | Status Absolute position (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 78 | Channel 2 - Water rotary actuator: {{0}} | Status Absolute position (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 78 | Channel 2 - VAV universal controller: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 78 | Channel 2 - Water 2-way valve: {{0}} | Status Analog input signal | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 78 | Channel 2 - Thermal energy meter: {{0}} | Status Analog input signal | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 78 | Channel 2 - Room control unit: {{0}} | Display Boost mode | 1 Bit | 1.1 switch | CWTUI |
| 79 | Channel 2 - Air VAV compact controller: {{0}} | Status Nominal range (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 79 | Channel 2 - Air VAV compact controller: {{0}} | Status Nominal range (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 79 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Nominal range (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 79 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Nominal range (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 79 | Channel 2 - Water rotary actuator: {{0}} | Status Nominal range (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 79 | Channel 2 - Water rotary actuator: {{0}} | Status Nominal range (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 79 | Channel 2 - VAV universal controller: {{0}} | Status Absolute flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 79 | Channel 2 - VAV universal controller: {{0}} | Status Absolute flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 79 | Channel 2 - Water 2-way valve: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 79 | Channel 2 - Thermal energy meter: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 79 | Channel 2 - Room control unit: {{0}} | Status Room temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 80 | Channel 2 - Air VAV compact controller: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 80 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 80 | Channel 2 - Water rotary actuator: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 80 | Channel 2 - VAV universal controller: {{0}} | Status Nominal flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 80 | Channel 2 - VAV universal controller: {{0}} | Status Nominal flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 80 | Channel 2 - Water 2-way valve: {{0}} | Status Absolute position | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 80 | Channel 2 - Thermal energy meter: {{0}} | Status Absolute position | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 80 | Channel 2 - Room control unit: {{0}} | Status Relative humidity | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 81 | Channel 2 - Air VAV compact controller: {{0}} | Status Absolute flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 81 | Channel 2 - Air VAV compact controller: {{0}} | Status Absolute flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 81 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Absolute flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 81 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Absolute flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 81 | Channel 2 - Water rotary actuator: {{0}} | Status Absolute flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 81 | Channel 2 - Water rotary actuator: {{0}} | Status Absolute flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 81 | Channel 2 - VAV universal controller: {{0}} | Status Relative differential pressure | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 81 | Channel 2 - Water 2-way valve: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 81 | Channel 2 - Water 2-way valve: {{0}} | Status Relative flow rate | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 81 | Channel 2 - Thermal energy meter: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 81 | Channel 2 - Thermal energy meter: {{0}} | Status Relative flow rate | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 81 | Channel 2 - Room control unit: {{0}} | CO2 value | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 82 | Channel 2 - Air VAV compact controller: {{0}} | Status Nominal flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 82 | Channel 2 - Air VAV compact controller: {{0}} | Status Nominal flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 82 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Nominal flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 82 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Nominal flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 82 | Channel 2 - Water rotary actuator: {{0}} | Status Nominal flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 82 | Channel 2 - Water rotary actuator: {{0}} | Status Nominal flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 82 | Channel 2 - VAV universal controller: {{0}} | Status Absolute differential pressure | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 82 | Channel 2 - Water 2-way valve: {{0}} | Status Absolute flow rate | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CRT |
| 82 | Channel 2 - Thermal energy meter: {{0}} | Status Absolute flow rate | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CRT |
| 82 | Channel 2 - Room control unit: {{0}} | Air quality OK | 1 Bit | 1.2 boolean | CRT |
| 83 | Channel 2 - Air VAV compact controller: {{0}} | Status Minimum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 83 | Channel 2 - Air VAV compact controller: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 83 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Minimum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 83 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 83 | Channel 2 - Water rotary actuator: {{0}} | Status Minimum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 83 | Channel 2 - Water rotary actuator: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 83 | Channel 2 - VAV universal controller: {{0}} | Status Nominal differential pressure | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 83 | Channel 2 - Water 2-way valve: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 83 | Channel 2 - Thermal energy meter: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 83 | Channel 2 - Room control unit: {{0}} | Air quality warning | 1 Bit | 1.2 boolean | CRT |
| 84 | Channel 2 - Air VAV compact controller: {{0}} | Status Maximum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Channel 2 - Air VAV compact controller: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Maximum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Channel 2 - Air rotary/damper actuator: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Channel 2 - Water rotary actuator: {{0}} | Status Maximum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Channel 2 - Water rotary actuator: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Channel 2 - VAV universal controller: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 84 | Channel 2 - VAV universal controller: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Channel 2 - VAV universal controller: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 84 | Channel 2 - VAV universal controller: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 84 | Channel 2 - VAV universal controller: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 84 | Channel 2 - VAV universal controller: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 84 | Channel 2 - VAV universal controller: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Channel 2 - VAV universal controller: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 84 | Channel 2 - VAV universal controller: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 84 | Channel 2 - Water 2-way valve: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Channel 2 - Thermal energy meter: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Channel 2 - Room control unit: {{0}} | Air quality alarm | 1 Bit | 1.2 boolean | CRT |
| 85 | Channel 2 - Air VAV compact controller: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 85 | Channel 2 - Air VAV compact controller: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 85 | Channel 2 - Air VAV compact controller: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 85 | Channel 2 - Air VAV compact controller: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 85 | Channel 2 - Air VAV compact controller: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 85 | Channel 2 - Air VAV compact controller: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 85 | Channel 2 - Air VAV compact controller: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 85 | Channel 2 - Air VAV compact controller: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 85 | Channel 2 - Air VAV compact controller: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 85 | Channel 2 - Air rotary/damper actuator: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 85 | Channel 2 - Air rotary/damper actuator: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 85 | Channel 2 - Air rotary/damper actuator: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 85 | Channel 2 - Air rotary/damper actuator: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 85 | Channel 2 - Air rotary/damper actuator: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 85 | Channel 2 - Air rotary/damper actuator: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 85 | Channel 2 - Air rotary/damper actuator: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 85 | Channel 2 - Air rotary/damper actuator: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 85 | Channel 2 - Air rotary/damper actuator: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 85 | Channel 2 - Water rotary actuator: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 85 | Channel 2 - Water rotary actuator: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 85 | Channel 2 - Water rotary actuator: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 85 | Channel 2 - Water rotary actuator: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 85 | Channel 2 - Water rotary actuator: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 85 | Channel 2 - Water rotary actuator: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 85 | Channel 2 - Water rotary actuator: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 85 | Channel 2 - Water rotary actuator: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 85 | Channel 2 - Water rotary actuator: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 85 | Channel 2 - VAV universal controller: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 85 | Channel 2 - Water 2-way valve: {{0}} | Status Nominal flow rate | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CRT |
| 85 | Channel 2 - Thermal energy meter: {{0}} | Status Nominal flow rate | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CRT |
| 85 | Channel 2 - Room control unit: {{0}} | Binary input | 1 Bit | 1.1 switch | CRT |
| 86 | Channel 2 - Air VAV compact controller: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 86 | Channel 2 - Air rotary/damper actuator: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 86 | Channel 2 - Water rotary actuator: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 86 | Channel 2 - VAV universal controller: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 86 | Channel 2 - Water 2-way valve: {{0}} | Status Relative power | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 86 | Channel 2 - Water 2-way valve: {{0}} | Status Relative power | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 86 | Channel 2 - Thermal energy meter: {{0}} | Status Relative power | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 86 | Channel 2 - Thermal energy meter: {{0}} | Status Relative power | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 86 | Channel 2 - Room control unit: {{0}} | Dew point temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 87 | Channel 2 - Air VAV compact controller: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 87 | Channel 2 - Air rotary/damper actuator: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 87 | Channel 2 - Water rotary actuator: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 87 | Channel 2 - VAV universal controller: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 87 | Channel 2 - Water 2-way valve: {{0}} | Status Absolute cooling power | 4 Bytes | 14.56 power (W) | CRT |
| 87 | Channel 2 - Thermal energy meter: {{0}} | Status Absolute cooling power | 4 Bytes | 14.56 power (W) | CRT |
| 87 | Channel 2 - Room control unit: {{0}} | Request room temperature setpoint (absolute) | 2 Bytes | 9.1 temperature (°C) | CT |
| 88 | Channel 2 - Air VAV compact controller: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 88 | Channel 2 - Air rotary/damper actuator: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 88 | Channel 2 - Water rotary actuator: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 88 | Channel 2 - VAV universal controller: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 88 | Channel 2 - Water 2-way valve: {{0}} | Status Absolute heating power | 4 Bytes | 14.56 power (W) | CRT |
| 88 | Channel 2 - Thermal energy meter: {{0}} | Status Absolute heating power | 4 Bytes | 14.56 power (W) | CRT |
| 88 | Channel 2 - Room control unit: {{0}} | Request room temperature setpoint (relative) | 2 Bytes | 9.2 temperature difference (K) | CT |
| 89 | Channel 2 - Air VAV compact controller: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 89 | Channel 2 - Air rotary/damper actuator: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 89 | Channel 2 - Water rotary actuator: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 89 | Channel 2 - VAV universal controller: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 89 | Channel 2 - Water 2-way valve: {{0}} | Status Maximum power limit | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 89 | Channel 2 - Thermal energy meter: {{0}} | Status Maximum power limit | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 89 | Channel 2 - Room control unit: {{0}} | Request fan speed | 1 Byte | 5.1 percentage (0..100%) | CT |
| 90 | Channel 2 - Air VAV compact controller: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 90 | Channel 2 - Air rotary/damper actuator: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 90 | Channel 2 - Water rotary actuator: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 90 | Channel 2 - VAV universal controller: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 90 | Channel 2 - Water 2-way valve: {{0}} | Status Nominal power | 4 Bytes | 14.56 power (W) | CRT |
| 90 | Channel 2 - Thermal energy meter: {{0}} | Status Nominal power | 4 Bytes | 14.56 power (W) | CRT |
| 90 | Channel 2 - Room control unit: {{0}} | Confirm fan automatic mode | 1 Bit | 1.3 enable | CT |
| 91 | Channel 2 - Air VAV compact controller: {{0}} | Reset service information | 1 Bit | 1.10 start/stop | CW |
| 91 | Channel 2 - Air rotary/damper actuator: {{0}} | Reset service information | 1 Bit | 1.10 start/stop | CW |
| 91 | Channel 2 - Water rotary actuator: {{0}} | Reset service information | 1 Bit | 1.10 start/stop | CW |
| 91 | Channel 2 - VAV universal controller: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 91 | Channel 2 - Water 2-way valve: {{0}} | Status Relative differential pressure | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 91 | Channel 2 - Room control unit: {{0}} | Request RTR operating mode | 1 Byte | 20.102 HVAC mode | CT |
| 92 | Channel 2 - Air VAV compact controller: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 92 | Channel 2 - Air rotary/damper actuator: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 92 | Channel 2 - Water rotary actuator: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 92 | Channel 2 - VAV universal controller: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 92 | Channel 2 - Water 2-way valve: {{0}} | Status Absolute differential pressure | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 92 | Channel 2 - Room control unit: {{0}} | Activate Boost mode | 1 Bit | 1.1 switch | CT |
| 93 | Channel 2 - Air VAV compact controller: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 93 | Channel 2 - Air rotary/damper actuator: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 93 | Channel 2 - Water rotary actuator: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 93 | Channel 2 - VAV universal controller: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 93 | Channel 2 - Water 2-way valve: {{0}} | Status Nominal differential pressure | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 93 | Channel 2 - Room control unit: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 94 | Channel 2 - Air VAV compact controller: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 94 | Channel 2 - Air rotary/damper actuator: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 94 | Channel 2 - Water rotary actuator: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 94 | Channel 2 - Water 2-way valve: {{0}} | Status Glycol concentration | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 94 | Channel 2 - Thermal energy meter: {{0}} | Status Glycol concentration | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 94 | Channel 2 - Room control unit: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 95 | Channel 2 - Air VAV compact controller: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 95 | Channel 2 - Air rotary/damper actuator: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 95 | Channel 2 - Water rotary actuator: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 95 | Channel 2 - Water 2-way valve: {{0}} | Certified meter | 1 Bit | 1.2 boolean | CRT |
| 95 | Channel 2 - Thermal energy meter: {{0}} | Certified meter | 1 Bit | 1.2 boolean | CRT |
| 95 | Channel 2 - Room control unit: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 96 | Channel 2 - Water 2-way valve: {{0}} | Status Accumulated volume | 4 Bytes | 14.76 volume (m³) | CRT |
| 96 | Channel 2 - Thermal energy meter: {{0}} | Status Accumulated volume | 4 Bytes | 14.76 volume (m³) | CRT |
| 96 | Channel 2 - Room control unit: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 97 | Channel 2 - Water 2-way valve: {{0}} | Status Total energy cooling | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 97 | Channel 2 - Thermal energy meter: {{0}} | Status Total energy cooling | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 97 | Channel 2 - Room control unit: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 98 | Channel 2 - Water 2-way valve: {{0}} | Status Total energy heating | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 98 | Channel 2 - Thermal energy meter: {{0}} | Status Total energy heating | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 99 | Channel 2 - Water 2-way valve: {{0}} | Energy meter serial number (upper digits) | 4 Bytes | | CRT |
| 99 | Channel 2 - Thermal energy meter: {{0}} | Energy meter serial number (upper digits) | 4 Bytes | | CRT |
| 100 | Channel 2 - Water 2-way valve: {{0}} | Energy meter serial number (lower digits) | 4 Bytes | | CRT |
| 100 | Channel 2 - Thermal energy meter: {{0}} | Energy meter serial number (lower digits) | 4 Bytes | | CRT |
| 101 | Channel 2 - Water 2-way valve: {{0}} | Status Delta temperature | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 101 | Channel 2 - Thermal energy meter: {{0}} | Status Delta temperature | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 102 | Channel 2 - Water 2-way valve: {{0}} | Status Delta-T Manager | 1 Bit | 1.2 boolean | CRT |
| 102 | Channel 2 - Thermal energy meter: {{0}} | Status Delta-T Manager | 1 Bit | 1.2 boolean | CRT |
| 103 | Channel 2 - Water 2-way valve: {{0}} | Status Delta-T Manager flow-dependent adjustment (scaling) | 1 Bit | 1.2 boolean | CRT |
| 103 | Channel 2 - Thermal energy meter: {{0}} | Status Delta-T Manager flow-dependent adjustment (scaling) | 1 Bit | 1.2 boolean | CRT |
| 104 | Channel 2 - Water 2-way valve: {{0}} | Temperature internal sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 104 | Channel 2 - Thermal energy meter: {{0}} | Temperature internal sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 105 | Channel 2 - Water 2-way valve: {{0}} | Temperature external sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 105 | Channel 2 - Thermal energy meter: {{0}} | Temperature external sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 106 | Channel 2 - Water 2-way valve: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 106 | Channel 2 - Water 2-way valve: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 106 | Channel 2 - Water 2-way valve: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 106 | Channel 2 - Water 2-way valve: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 106 | Channel 2 - Water 2-way valve: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 106 | Channel 2 - Water 2-way valve: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 106 | Channel 2 - Water 2-way valve: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 106 | Channel 2 - Water 2-way valve: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 106 | Channel 2 - Water 2-way valve: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 106 | Channel 2 - Thermal energy meter: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 106 | Channel 2 - Thermal energy meter: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 106 | Channel 2 - Thermal energy meter: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 106 | Channel 2 - Thermal energy meter: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 106 | Channel 2 - Thermal energy meter: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 106 | Channel 2 - Thermal energy meter: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 106 | Channel 2 - Thermal energy meter: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 106 | Channel 2 - Thermal energy meter: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 106 | Channel 2 - Thermal energy meter: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 107 | Channel 2 - Water 2-way valve: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 107 | Channel 2 - Thermal energy meter: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 108 | Channel 2 - Water 2-way valve: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 108 | Channel 2 - Thermal energy meter: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 109 | Channel 2 - Water 2-way valve: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 109 | Channel 2 - Thermal energy meter: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 110 | Channel 2 - Water 2-way valve: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 110 | Channel 2 - Thermal energy meter: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 111 | Channel 2 - Water 2-way valve: {{0}} | Sensor module must be replaced | 1 Bit | 1.5 alarm | CRT |
| 111 | Channel 2 - Thermal energy meter: {{0}} | Sensor module must be replaced | 1 Bit | 1.5 alarm | CRT |
| 112 | Channel 2 - Water 2-way valve: {{0}} | MP-Bus monitoring timed out | 1 Bit | 1.5 alarm | CRT |
| 112 | Channel 2 - Thermal energy meter: {{0}} | MP-Bus monitoring timed out | 1 Bit | 1.5 alarm | CRT |
| 113 | Channel 2 - Water 2-way valve: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 113 | Channel 2 - Thermal energy meter: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 114 | Channel 2 - Water 2-way valve: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 114 | Channel 2 - Thermal energy meter: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 115 | Channel 2 - Water 2-way valve: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 115 | Channel 2 - Thermal energy meter: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 116 | Channel 2 - Water 2-way valve: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 116 | Channel 2 - Thermal energy meter: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 117 | Channel 2 - Water 2-way valve: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 117 | Channel 2 - Thermal energy meter: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 118 | Channel 3 - Air VAV compact controller: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 118 | Channel 3 - Air VAV compact controller: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 118 | Channel 3 - Air VAV compact controller: {{0}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 118 | Channel 3 - Air rotary/damper actuator: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 118 | Channel 3 - Air rotary/damper actuator: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 118 | Channel 3 - Air rotary/damper actuator: {{0}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 118 | Channel 3 - Water rotary actuator: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 118 | Channel 3 - Water rotary actuator: {{0}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 118 | Channel 3 - Water rotary actuator: {{0}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 118 | Channel 3 - VAV universal controller: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 118 | Channel 3 - Water 2-way valve: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 118 | Channel 3 - Thermal energy meter: {{0}} | Setpoint | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 118 | Channel 3 - Room control unit: {{0}} | Confirm room temperature setpoint (absolute) | 2 Bytes | 9.1 temperature (°C) | CWTUI |
| 118 | Channel 3 - Room control unit: {{0}} | Confirm room temperature setpoint (relative) | 2 Bytes | 9.2 temperature difference (K) | CWTUI |
| 119 | Channel 3 - Air VAV compact controller: {{0}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 119 | Channel 3 - Air rotary/damper actuator: {{0}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 119 | Channel 3 - Water rotary actuator: {{0}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 119 | Channel 3 - VAV universal controller: {{0}} | Override control | 1 Byte | | CWTUI |
| 119 | Channel 3 - Water 2-way valve: {{0}} | Setpoint absolute differential pressure | 4 Bytes | 14.58 pressure (Pa) | CWTUI |
| 119 | Channel 3 - Thermal energy meter: {{0}} | Setpoint absolute differential pressure | 4 Bytes | 14.58 pressure (Pa) | CWTUI |
| 119 | Channel 3 - Room control unit: {{0}} | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CWTUI |
| 120 | Channel 3 - Air VAV compact controller: {{0}} | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTUI |
| 120 | Channel 3 - Air rotary/damper actuator: {{0}} | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTUI |
| 120 | Channel 3 - Water rotary actuator: {{0}} | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTUI |
| 120 | Channel 3 - VAV universal controller: {{0}} | Start adjustment | 1 Bit | 1.17 trigger | CW |
| 120 | Channel 3 - Water 2-way valve: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 120 | Channel 3 - Thermal energy meter: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 120 | Channel 3 - Room control unit: {{0}} | Confirm fan speed | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 121 | Channel 3 - Air VAV compact controller: {{0}} | Activate heating | 1 Bit | 1.3 enable | CWTUI |
| 121 | Channel 3 - Air rotary/damper actuator: {{0}} | Activate heating | 1 Bit | 1.3 enable | CWTUI |
| 121 | Channel 3 - Water rotary actuator: {{0}} | Activate heating | 1 Bit | 1.3 enable | CWTUI |
| 121 | Channel 3 - VAV universal controller: {{0}} | Start synchronization | 1 Bit | 1.17 trigger | CW |
| 121 | Channel 3 - Water 2-way valve: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 121 | Channel 3 - Thermal energy meter: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 121 | Channel 3 - Room control unit: {{0}} | Request fan automatic mode | 1 Bit | 1.3 enable | CWTUI |
| 122 | Channel 3 - Air VAV compact controller: {{0}} | Activate cooling | 1 Bit | 1.3 enable | CWTUI |
| 122 | Channel 3 - Air rotary/damper actuator: {{0}} | Activate cooling | 1 Bit | 1.3 enable | CWTUI |
| 122 | Channel 3 - Water rotary actuator: {{0}} | Activate cooling | 1 Bit | 1.3 enable | CWTUI |
| 122 | Channel 3 - VAV universal controller: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 122 | Channel 3 - VAV universal controller: {{0}} | Minimum differential pressure | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 122 | Channel 3 - Water 2-way valve: {{0}} | Maximum power limit | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 122 | Channel 3 - Thermal energy meter: {{0}} | Maximum power limit | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 122 | Channel 3 - Room control unit: {{0}} | Display warning icon | 1 Bit | 1.3 enable | CWTUI |
| 123 | Channel 3 - Air VAV compact controller: {{0}} | Override control | 1 Byte | | CWTUI |
| 123 | Channel 3 - Air rotary/damper actuator: {{0}} | Override control | 1 Byte | | CWTUI |
| 123 | Channel 3 - Water rotary actuator: {{0}} | Override control | 1 Byte | | CWTUI |
| 123 | Channel 3 - VAV universal controller: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 123 | Channel 3 - VAV universal controller: {{0}} | Maximum differential pressure | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 123 | Channel 3 - Water 2-way valve: {{0}} | Activate Delta-T Manager | 1 Bit | 1.3 enable | CWTUI |
| 123 | Channel 3 - Thermal energy meter: {{0}} | Activate Delta-T Manager | 1 Bit | 1.3 enable | CWTUI |
| 123 | Channel 3 - Room control unit: {{0}} | Display window icon | 1 Bit | 1.3 enable | CWTUI |
| 124 | Channel 3 - Air VAV compact controller: {{0}} | Minimum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 124 | Channel 3 - Air VAV compact controller: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 124 | Channel 3 - Air rotary/damper actuator: {{0}} | Minimum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 124 | Channel 3 - Air rotary/damper actuator: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 124 | Channel 3 - Water rotary actuator: {{0}} | Minimum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 124 | Channel 3 - Water rotary actuator: {{0}} | Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 124 | Channel 3 - VAV universal controller: {{0}} | Status Analog input signal | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 124 | Channel 3 - Water 2-way valve: {{0}} | Activate Delta-T Manager flow-dependent adjustment (scaling) | 1 Bit | 1.3 enable | CWTUI |
| 124 | Channel 3 - Thermal energy meter: {{0}} | Activate Delta-T Manager flow-dependent adjustment (scaling) | 1 Bit | 1.3 enable | CWTUI |
| 124 | Channel 3 - Room control unit: {{0}} | Status RTC controller | 2 Bytes | 22.103 combined status RTC | CWTUI |
| 125 | Channel 3 - Air VAV compact controller: {{0}} | Maximum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 125 | Channel 3 - Air VAV compact controller: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 125 | Channel 3 - Air rotary/damper actuator: {{0}} | Maximum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 125 | Channel 3 - Air rotary/damper actuator: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 125 | Channel 3 - Water rotary actuator: {{0}} | Maximum position | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 125 | Channel 3 - Water rotary actuator: {{0}} | Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CWTUI |
| 125 | Channel 3 - VAV universal controller: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 125 | Channel 3 - Water 2-way valve: {{0}} | Setpoint Delta-T limitation | 2 Bytes | 9.2 temperature difference (K) | CWTUI |
| 125 | Channel 3 - Thermal energy meter: {{0}} | Setpoint Delta-T limitation | 2 Bytes | 9.2 temperature difference (K) | CWTUI |
| 125 | Channel 3 - Room control unit: {{0}} | Receive status Heating | 1 Bit | 1.3 enable | CWTUI |
| 126 | Channel 3 - Air VAV compact controller: {{0}} | Start test run | 1 Bit | 1.17 trigger | CW |
| 126 | Channel 3 - Air rotary/damper actuator: {{0}} | Start test run | 1 Bit | 1.17 trigger | CW |
| 126 | Channel 3 - Water rotary actuator: {{0}} | Start test run | 1 Bit | 1.17 trigger | CW |
| 126 | Channel 3 - VAV universal controller: {{0}} | Status Absolute position | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 126 | Channel 3 - Water 2-way valve: {{0}} | Setpoint absolute flow at Delta-T | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CWTUI |
| 126 | Channel 3 - Thermal energy meter: {{0}} | Setpoint absolute flow at Delta-T | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CWTUI |
| 126 | Channel 3 - Room control unit: {{0}} | Receive status Cooling | 1 Bit | 1.3 enable | CWTUI |
| 127 | Channel 3 - Air VAV compact controller: {{0}} | Start adjustment | 1 Bit | 1.17 trigger | CW |
| 127 | Channel 3 - Air rotary/damper actuator: {{0}} | Start adjustment | 1 Bit | 1.17 trigger | CW |
| 127 | Channel 3 - Water rotary actuator: {{0}} | Start adjustment | 1 Bit | 1.17 trigger | CW |
| 127 | Channel 3 - VAV universal controller: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 127 | Channel 3 - VAV universal controller: {{0}} | Status Minimum differential pressure | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 127 | Channel 3 - Water 2-way valve: {{0}} | Start synchronization | 1 Bit | 1.17 trigger | CW |
| 127 | Channel 3 - Thermal energy meter: {{0}} | Start synchronization | 1 Bit | 1.17 trigger | CW |
| 127 | Channel 3 - Room control unit: {{0}} | Confirm RTR operating mode | 1 Byte | 20.102 HVAC mode | CWTUI |
| 128 | Channel 3 - Air VAV compact controller: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | Channel 3 - Water rotary actuator: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | Channel 3 - VAV universal controller: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | Channel 3 - VAV universal controller: {{0}} | Status Maximum differential pressure | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | Channel 3 - Water 2-way valve: {{0}} | Override control | 1 Byte | | CWTUI |
| 128 | Channel 3 - Thermal energy meter: {{0}} | Override control | 1 Byte | | CWTUI |
| 128 | Channel 3 - Room control unit: {{0}} | Block local operation | 1 Bit | 1.3 enable | CWTUI |
| 129 | Channel 3 - Air VAV compact controller: {{0}} | Status Absolute position (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 129 | Channel 3 - Air VAV compact controller: {{0}} | Status Absolute position (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 129 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Absolute position (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 129 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Absolute position (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 129 | Channel 3 - Water rotary actuator: {{0}} | Status Absolute position (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 129 | Channel 3 - Water rotary actuator: {{0}} | Status Absolute position (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 129 | Channel 3 - VAV universal controller: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 129 | Channel 3 - Water 2-way valve: {{0}} | Status Analog input signal | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 129 | Channel 3 - Thermal energy meter: {{0}} | Status Analog input signal | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 129 | Channel 3 - Room control unit: {{0}} | Display Boost mode | 1 Bit | 1.1 switch | CWTUI |
| 130 | Channel 3 - Air VAV compact controller: {{0}} | Status Nominal range (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 130 | Channel 3 - Air VAV compact controller: {{0}} | Status Nominal range (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 130 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Nominal range (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 130 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Nominal range (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 130 | Channel 3 - Water rotary actuator: {{0}} | Status Nominal range (rotation angle) | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 130 | Channel 3 - Water rotary actuator: {{0}} | Status Nominal range (millimeters) | 2 Bytes | 7.11 length (mm) | CRT |
| 130 | Channel 3 - VAV universal controller: {{0}} | Status Absolute flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 130 | Channel 3 - VAV universal controller: {{0}} | Status Absolute flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 130 | Channel 3 - Water 2-way valve: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 130 | Channel 3 - Thermal energy meter: {{0}} | Status Relative position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 130 | Channel 3 - Room control unit: {{0}} | Status Room temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 131 | Channel 3 - Air VAV compact controller: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 131 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 131 | Channel 3 - Water rotary actuator: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 131 | Channel 3 - VAV universal controller: {{0}} | Status Nominal flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 131 | Channel 3 - VAV universal controller: {{0}} | Status Nominal flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 131 | Channel 3 - Water 2-way valve: {{0}} | Status Absolute position | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 131 | Channel 3 - Thermal energy meter: {{0}} | Status Absolute position | 2 Bytes | 8.11 rotation angle (°) | CRT |
| 131 | Channel 3 - Room control unit: {{0}} | Status Relative humidity | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 132 | Channel 3 - Air VAV compact controller: {{0}} | Status Absolute flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 132 | Channel 3 - Air VAV compact controller: {{0}} | Status Absolute flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 132 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Absolute flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 132 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Absolute flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 132 | Channel 3 - Water rotary actuator: {{0}} | Status Absolute flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 132 | Channel 3 - Water rotary actuator: {{0}} | Status Absolute flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 132 | Channel 3 - VAV universal controller: {{0}} | Status Relative differential pressure | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 132 | Channel 3 - Water 2-way valve: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 132 | Channel 3 - Water 2-way valve: {{0}} | Status Relative flow rate | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 132 | Channel 3 - Thermal energy meter: {{0}} | Status Relative flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 132 | Channel 3 - Thermal energy meter: {{0}} | Status Relative flow rate | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 132 | Channel 3 - Room control unit: {{0}} | CO2 value | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 133 | Channel 3 - Air VAV compact controller: {{0}} | Status Nominal flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 133 | Channel 3 - Air VAV compact controller: {{0}} | Status Nominal flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 133 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Nominal flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 133 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Nominal flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 133 | Channel 3 - Water rotary actuator: {{0}} | Status Nominal flow rate | 4 Bytes | 14.77 volume flux (m³/s) | CRT |
| 133 | Channel 3 - Water rotary actuator: {{0}} | Status Nominal flow rate | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 133 | Channel 3 - VAV universal controller: {{0}} | Status Absolute differential pressure | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 133 | Channel 3 - Water 2-way valve: {{0}} | Status Absolute flow rate | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CRT |
| 133 | Channel 3 - Thermal energy meter: {{0}} | Status Absolute flow rate | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CRT |
| 133 | Channel 3 - Room control unit: {{0}} | Air quality OK | 1 Bit | 1.2 boolean | CRT |
| 134 | Channel 3 - Air VAV compact controller: {{0}} | Status Minimum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 134 | Channel 3 - Air VAV compact controller: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 134 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Minimum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 134 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 134 | Channel 3 - Water rotary actuator: {{0}} | Status Minimum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 134 | Channel 3 - Water rotary actuator: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 134 | Channel 3 - VAV universal controller: {{0}} | Status Nominal differential pressure | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 134 | Channel 3 - Water 2-way valve: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 134 | Channel 3 - Thermal energy meter: {{0}} | Status Minimum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 134 | Channel 3 - Room control unit: {{0}} | Air quality warning | 1 Bit | 1.2 boolean | CRT |
| 135 | Channel 3 - Air VAV compact controller: {{0}} | Status Maximum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 135 | Channel 3 - Air VAV compact controller: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 135 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Maximum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 135 | Channel 3 - Air rotary/damper actuator: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 135 | Channel 3 - Water rotary actuator: {{0}} | Status Maximum position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 135 | Channel 3 - Water rotary actuator: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 135 | Channel 3 - VAV universal controller: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 135 | Channel 3 - VAV universal controller: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 135 | Channel 3 - VAV universal controller: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 135 | Channel 3 - VAV universal controller: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 135 | Channel 3 - VAV universal controller: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 135 | Channel 3 - VAV universal controller: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 135 | Channel 3 - VAV universal controller: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 135 | Channel 3 - VAV universal controller: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 135 | Channel 3 - VAV universal controller: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 135 | Channel 3 - Water 2-way valve: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 135 | Channel 3 - Thermal energy meter: {{0}} | Status Maximum flow rate | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 135 | Channel 3 - Room control unit: {{0}} | Air quality alarm | 1 Bit | 1.2 boolean | CRT |
| 136 | Channel 3 - Air VAV compact controller: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 136 | Channel 3 - Air VAV compact controller: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 136 | Channel 3 - Air VAV compact controller: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 136 | Channel 3 - Air VAV compact controller: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 136 | Channel 3 - Air VAV compact controller: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 136 | Channel 3 - Air VAV compact controller: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 136 | Channel 3 - Air VAV compact controller: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 136 | Channel 3 - Air VAV compact controller: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 136 | Channel 3 - Air VAV compact controller: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 136 | Channel 3 - Air rotary/damper actuator: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 136 | Channel 3 - Air rotary/damper actuator: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 136 | Channel 3 - Air rotary/damper actuator: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 136 | Channel 3 - Air rotary/damper actuator: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 136 | Channel 3 - Air rotary/damper actuator: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 136 | Channel 3 - Air rotary/damper actuator: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 136 | Channel 3 - Air rotary/damper actuator: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 136 | Channel 3 - Air rotary/damper actuator: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 136 | Channel 3 - Air rotary/damper actuator: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 136 | Channel 3 - Water rotary actuator: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 136 | Channel 3 - Water rotary actuator: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 136 | Channel 3 - Water rotary actuator: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 136 | Channel 3 - Water rotary actuator: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 136 | Channel 3 - Water rotary actuator: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 136 | Channel 3 - Water rotary actuator: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 136 | Channel 3 - Water rotary actuator: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 136 | Channel 3 - Water rotary actuator: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 136 | Channel 3 - Water rotary actuator: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 136 | Channel 3 - VAV universal controller: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 136 | Channel 3 - Water 2-way valve: {{0}} | Status Nominal flow rate | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CRT |
| 136 | Channel 3 - Thermal energy meter: {{0}} | Status Nominal flow rate | 4 Bytes | 14.1201 volume flux for meters (1/ls) | CRT |
| 136 | Channel 3 - Room control unit: {{0}} | Binary input | 1 Bit | 1.1 switch | CRT |
| 137 | Channel 3 - Air VAV compact controller: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 137 | Channel 3 - Air rotary/damper actuator: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 137 | Channel 3 - Water rotary actuator: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 137 | Channel 3 - VAV universal controller: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 137 | Channel 3 - Water 2-way valve: {{0}} | Status Relative power | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 137 | Channel 3 - Water 2-way valve: {{0}} | Status Relative power | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 137 | Channel 3 - Thermal energy meter: {{0}} | Status Relative power | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 137 | Channel 3 - Thermal energy meter: {{0}} | Status Relative power | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 137 | Channel 3 - Room control unit: {{0}} | Dew point temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 138 | Channel 3 - Air VAV compact controller: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 138 | Channel 3 - Air rotary/damper actuator: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 138 | Channel 3 - Water rotary actuator: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 138 | Channel 3 - VAV universal controller: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 138 | Channel 3 - Water 2-way valve: {{0}} | Status Absolute cooling power | 4 Bytes | 14.56 power (W) | CRT |
| 138 | Channel 3 - Thermal energy meter: {{0}} | Status Absolute cooling power | 4 Bytes | 14.56 power (W) | CRT |
| 138 | Channel 3 - Room control unit: {{0}} | Request room temperature setpoint (absolute) | 2 Bytes | 9.1 temperature (°C) | CT |
| 139 | Channel 3 - Air VAV compact controller: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 139 | Channel 3 - Air rotary/damper actuator: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 139 | Channel 3 - Water rotary actuator: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 139 | Channel 3 - VAV universal controller: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 139 | Channel 3 - Water 2-way valve: {{0}} | Status Absolute heating power | 4 Bytes | 14.56 power (W) | CRT |
| 139 | Channel 3 - Thermal energy meter: {{0}} | Status Absolute heating power | 4 Bytes | 14.56 power (W) | CRT |
| 139 | Channel 3 - Room control unit: {{0}} | Request room temperature setpoint (relative) | 2 Bytes | 9.2 temperature difference (K) | CT |
| 140 | Channel 3 - Air VAV compact controller: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 140 | Channel 3 - Air rotary/damper actuator: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 140 | Channel 3 - Water rotary actuator: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 140 | Channel 3 - VAV universal controller: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 140 | Channel 3 - Water 2-way valve: {{0}} | Status Maximum power limit | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 140 | Channel 3 - Thermal energy meter: {{0}} | Status Maximum power limit | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 140 | Channel 3 - Room control unit: {{0}} | Request fan speed | 1 Byte | 5.1 percentage (0..100%) | CT |
| 141 | Channel 3 - Air VAV compact controller: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 141 | Channel 3 - Air rotary/damper actuator: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 141 | Channel 3 - Water rotary actuator: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 141 | Channel 3 - VAV universal controller: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 141 | Channel 3 - Water 2-way valve: {{0}} | Status Nominal power | 4 Bytes | 14.56 power (W) | CRT |
| 141 | Channel 3 - Thermal energy meter: {{0}} | Status Nominal power | 4 Bytes | 14.56 power (W) | CRT |
| 141 | Channel 3 - Room control unit: {{0}} | Confirm fan automatic mode | 1 Bit | 1.3 enable | CT |
| 142 | Channel 3 - Air VAV compact controller: {{0}} | Reset service information | 1 Bit | 1.10 start/stop | CW |
| 142 | Channel 3 - Air rotary/damper actuator: {{0}} | Reset service information | 1 Bit | 1.10 start/stop | CW |
| 142 | Channel 3 - Water rotary actuator: {{0}} | Reset service information | 1 Bit | 1.10 start/stop | CW |
| 142 | Channel 3 - VAV universal controller: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 142 | Channel 3 - Water 2-way valve: {{0}} | Status Relative differential pressure | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 142 | Channel 3 - Room control unit: {{0}} | Request RTR operating mode | 1 Byte | 20.102 HVAC mode | CT |
| 143 | Channel 3 - Air VAV compact controller: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 143 | Channel 3 - Air rotary/damper actuator: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 143 | Channel 3 - Water rotary actuator: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 143 | Channel 3 - VAV universal controller: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 143 | Channel 3 - Water 2-way valve: {{0}} | Status Absolute differential pressure | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 143 | Channel 3 - Room control unit: {{0}} | Activate Boost mode | 1 Bit | 1.1 switch | CT |
| 144 | Channel 3 - Air VAV compact controller: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 144 | Channel 3 - Air rotary/damper actuator: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 144 | Channel 3 - Water rotary actuator: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 144 | Channel 3 - VAV universal controller: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 144 | Channel 3 - Water 2-way valve: {{0}} | Status Nominal differential pressure | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 144 | Channel 3 - Room control unit: {{0}} | Service information | 4 Bytes | 27.1 bit-combined info on/off | CRT |
| 145 | Channel 3 - Air VAV compact controller: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 145 | Channel 3 - Air rotary/damper actuator: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 145 | Channel 3 - Water rotary actuator: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 145 | Channel 3 - Water 2-way valve: {{0}} | Status Glycol concentration | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 145 | Channel 3 - Thermal energy meter: {{0}} | Status Glycol concentration | 2 Bytes | 8.10 percentage difference (%) | CRT |
| 145 | Channel 3 - Room control unit: {{0}} | Communication error | 1 Bit | 1.5 alarm | CRT |
| 146 | Channel 3 - Air VAV compact controller: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 146 | Channel 3 - Air rotary/damper actuator: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 146 | Channel 3 - Water rotary actuator: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 146 | Channel 3 - Water 2-way valve: {{0}} | Certified meter | 1 Bit | 1.2 boolean | CRT |
| 146 | Channel 3 - Thermal energy meter: {{0}} | Certified meter | 1 Bit | 1.2 boolean | CRT |
| 146 | Channel 3 - Room control unit: {{0}} | Addressing error | 1 Bit | 1.5 alarm | CRT |
| 147 | Channel 3 - Water 2-way valve: {{0}} | Status Accumulated volume | 4 Bytes | 14.76 volume (m³) | CRT |
| 147 | Channel 3 - Thermal energy meter: {{0}} | Status Accumulated volume | 4 Bytes | 14.76 volume (m³) | CRT |
| 147 | Channel 3 - Room control unit: {{0}} | Configuration error | 1 Bit | 1.5 alarm | CRT |
| 148 | Channel 3 - Water 2-way valve: {{0}} | Status Total energy cooling | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 148 | Channel 3 - Thermal energy meter: {{0}} | Status Total energy cooling | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 148 | Channel 3 - Room control unit: {{0}} | MP-Bus address | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 149 | Channel 3 - Water 2-way valve: {{0}} | Status Total energy heating | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 149 | Channel 3 - Thermal energy meter: {{0}} | Status Total energy heating | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 150 | Channel 3 - Water 2-way valve: {{0}} | Energy meter serial number (upper digits) | 4 Bytes | | CRT |
| 150 | Channel 3 - Thermal energy meter: {{0}} | Energy meter serial number (upper digits) | 4 Bytes | | CRT |
| 151 | Channel 3 - Water 2-way valve: {{0}} | Energy meter serial number (lower digits) | 4 Bytes | | CRT |
| 151 | Channel 3 - Thermal energy meter: {{0}} | Energy meter serial number (lower digits) | 4 Bytes | | CRT |
| 152 | Channel 3 - Water 2-way valve: {{0}} | Status Delta temperature | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 152 | Channel 3 - Thermal energy meter: {{0}} | Status Delta temperature | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 153 | Channel 3 - Water 2-way valve: {{0}} | Status Delta-T Manager | 1 Bit | 1.2 boolean | CRT |
| 153 | Channel 3 - Thermal energy meter: {{0}} | Status Delta-T Manager | 1 Bit | 1.2 boolean | CRT |
| 154 | Channel 3 - Water 2-way valve: {{0}} | Status Delta-T Manager flow-dependent adjustment (scaling) | 1 Bit | 1.2 boolean | CRT |
| 154 | Channel 3 - Thermal energy meter: {{0}} | Status Delta-T Manager flow-dependent adjustment (scaling) | 1 Bit | 1.2 boolean | CRT |
| 155 | Channel 3 - Water 2-way valve: {{0}} | Temperature internal sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 155 | Channel 3 - Thermal energy meter: {{0}} | Temperature internal sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 156 | Channel 3 - Water 2-way valve: {{0}} | Temperature external sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 156 | Channel 3 - Thermal energy meter: {{0}} | Temperature external sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 157 | Channel 3 - Water 2-way valve: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 157 | Channel 3 - Water 2-way valve: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 157 | Channel 3 - Water 2-way valve: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 157 | Channel 3 - Water 2-way valve: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 157 | Channel 3 - Water 2-way valve: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 157 | Channel 3 - Water 2-way valve: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 157 | Channel 3 - Water 2-way valve: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 157 | Channel 3 - Water 2-way valve: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 157 | Channel 3 - Water 2-way valve: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 157 | Channel 3 - Thermal energy meter: {{0}} | Sensor value (voltage) | 2 Bytes | 9.20 voltage (mV) | CRT |
| 157 | Channel 3 - Thermal energy meter: {{0}} | Sensor value (percent) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 157 | Channel 3 - Thermal energy meter: {{0}} | Sensor value (resistance) | 4 Bytes | 14.60 resistance (Ω) | CRT |
| 157 | Channel 3 - Thermal energy meter: {{0}} | Sensor value (temperature) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 157 | Channel 3 - Thermal energy meter: {{0}} | Sensor value (switch) | 1 Bit | 1.1 switch | CRT |
| 157 | Channel 3 - Thermal energy meter: {{0}} | Sensor value (air quality) | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 157 | Channel 3 - Thermal energy meter: {{0}} | Sensor value (dew point alarm) | 1 Bit | 1.5 alarm | CRT |
| 157 | Channel 3 - Thermal energy meter: {{0}} | Sensor value (humidity) | 2 Bytes | 9.7 humidity (%) | CRT |
| 157 | Channel 3 - Thermal energy meter: {{0}} | Sensor value (humidity) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 158 | Channel 3 - Water 2-way valve: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 158 | Channel 3 - Thermal energy meter: {{0}} | Error cyclical monitoring | 1 Bit | 1.5 alarm | CRT |
| 159 | Channel 3 - Water 2-way valve: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 159 | Channel 3 - Thermal energy meter: {{0}} | Override control active | 1 Bit | 1.11 state | CRT |
| 160 | Channel 3 - Water 2-way valve: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 160 | Channel 3 - Thermal energy meter: {{0}} | Gear disengagement active | 1 Bit | 1.11 state | CRT |
| 161 | Channel 3 - Water 2-way valve: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 161 | Channel 3 - Thermal energy meter: {{0}} | Error | 1 Bit | 1.5 alarm | CRT |
| 162 | Channel 3 - Water 2-way valve: {{0}} | Sensor module must be replaced | 1 Bit | 1.5 alarm | CRT |
| 162 | Channel 3 - Thermal energy meter: {{0}} | Sensor module must be replaced | 1 Bit | 1.5 alarm | CRT |
| 163 | Channel 3 - Water 2-way valve: {{0}} | MP-Bus monitoring timed out | 1 Bit | 1.5 alarm | CRT |