ABB AG - STOTZ-KONTAKT 2CDG 110 222 R0011 BCI/S1.1.1 Boiler/Chiller Interface,MDRC

BCI/S1.1.1 Boiler/Chiller Interface,MDRC 2CDG 110 222 R0011

ABB AG - STOTZ-KONTAKT · Order number 2CDG 110 222 R0011 · Heating, Ventilation and Air Conditioning › Central HVAC Controllers

Boiler/Chiller Interface/1.1

Download .knxprod Boiler/Chiller Interface/1.1 1.1 · 217 KB

Product

ManufacturerABB AG - STOTZ-KONTAKT
Product nameBCI/S1.1.1 Boiler/Chiller Interface,MDRC
Order number2CDG 110 222 R0011
HardwareBCI/S1.1.1 Wärme-/Kälteerzeuger Interface,REG
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)70
RegistrationRegistered · 2021-11-18
Languagesen-US, de-DE, es-ES, fr-FR, it-IT, nl-NL, pl-PL, ru-RU
Catalog entryM-0002_H-2CDG.20110.20222.20R0011-2_HP-A0BD-11-AFA7_CI-2CDG.20110.20222.20R0011-1
FingerprintAFA7
SHA-25676abe8e85e540b9ac47e75e504d03145aef181cd7fc69c89e215a673395c12cd
First seen2026-11-25
Markets59 markets

Application program: Boiler/Chiller Interface/1.1 1.1

Application number$A0BD
Version1.1
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters232
Group objects51
Group objects (51)
NoNameFunctionSizeDPTFlags
1GeneralIn operation1 Bit1.2 booleanCRT
2GeneralStatus byte Device1 ByteCRT
3GeneralRequest status values1 Bit1.17 triggerCW
10Channel - GeneralForced operation, 2-bit2 Bit2.1 switch controlCW
11Channel - GeneralForced operation, 1-bit1 Bit1.2 booleanCW
12Channel - GeneralError "Setpoint temperature" receipt1 Bit1.5 alarmCRT
12Channel - GeneralError "Setpoint power" receipt1 Bit1.5 alarmCRT
13Channel - GeneralError "Pump fault" receipt1 Bit1.5 alarmCRT
14Channel - GeneralError "Pump repair switch" receipt1 Bit1.5 alarmCRT
15Channel - GeneralError "Generator error" receipt1 Bit1.5 alarmCRT
16Channel - PumpOverride pump1 Bit1.1 switchCW
17Channel - PumpStatus pump relay1 Bit1.9 open/closeCRT
19Channel - PumpPump fault1 Bit1.5 alarmCWTU
20Channel - PumpPump repair switch1 Bit1.11 stateCWTU
22Channel - PumpEnable/block manual pump override1 Bit1.3 enableCW
23Channel - PumpStatus pump automatic mode1 Bit1.11 stateCRT
26Channel - PumpPump On/Off1 Bit1.1 switchCW
27Channel - Generator relayStatus generator relay1 Bit1.9 open/closeCRT
28Channel - Generator relaySwitch1 Bit1.1 switchCW
29Channel - Input aSupply flow temperature2 Bytes9.1 temperature (°C)CRT
30Channel - Input aError Input1 Bit1.5 alarmCRT
31Channel - Input bReturn flow temperature2 Bytes9.1 temperature (°C)CRT
32Channel - Input bError Input1 Bit1.5 alarmCRT
33Channel - Binary input cStatus pump1 Bit1.11 stateCRT
33Channel - Binary input cContact position binary input1 Bit1.1 switchCRT
34Channel - Binary input cBlock input1 Bit1.3 enableCW
35Channel - Binary input dPump fault alarm1 Bit1.5 alarmCRT
35Channel - Binary input dContact position binary input1 Bit1.1 switchCRT
36Channel - Binary input dBlock input1 Bit1.3 enableCW
37Channel - Binary input ePump repair switch 1 Bit1.11 stateCRT
37Channel - Binary input eContact position binary input1 Bit1.1 switchCRT
38Channel - Binary input eBlock input1 Bit1.3 enableCW
39Channel - Binary input fGenerator status1 Bit1.11 stateCRT
39Channel - Binary input fContact position binary input1 Bit1.1 switchCRT
40Channel - Binary input fBlock input1 Bit1.3 enableCW
41Channel - Binary input gGenerator error alarm1 Bit1.5 alarmCRT
41Channel - Binary input gContact position binary input1 Bit1.1 switchCRT
42Channel - Binary input gBlock input1 Bit1.3 enableCW
43Channel - GeneratorAbsolute setpoint temperature2 Bytes9.1 temperature (°C)CWTU
43Channel - GeneratorSetpoint temperature offset2 Bytes9.2 temperature difference (K)CWTU
44Channel - GeneratorSetpoint power1 Byte5.1 percentage (0..100%)CWTU
45Channel - GeneratorGenerator On/Off1 Bit1.1 switchCW
46Channel - GeneratorGenerator status On/Off1 Bit1.1 switchCRT
47Channel - GeneratorGenerator error1 Bit1.5 alarmCWTU
48Channel - GeneratorEnable/block manual generator override1 Bit1.3 enableCW
49Channel - GeneratorGenerator relay override1 Bit1.1 switchCW
50Channel - GeneratorGenerator setpoint override1 Byte5.1 percentage (0..100%)CW
50Channel - GeneratorGenerator setpoint override2 Bytes9.1 temperature (°C)CW
50Channel - GeneratorGenerator setpoint override2 Bytes9.2 temperature difference (K)CW
51Channel - GeneratorGenerator activation status2 Bytes9.20 voltage (mV)CRT
52Channel - GeneratorFault Generator output1 Bit1.5 alarmCRT
Parameters (132)
ParameterTypeDefault
Hardware_TypelistHW
Device functionlistStandalone
Sending and switching delay after bus voltage recoveryunsignedInt 2…2552
Value after sending and switching delay has expiredlistLast value received
Limit number of telegramslistNo
Enable group object "In operation"listNo
Send value of group object "In operation"listValue 1
In periodlist1 s
Maximum number of telegramsunsignedInt 1…5020
i-bus Tool accesslistFull access
Sending cycletime60
Generator activation after ETS downloadlistUnchanged
Status after ETS downloadlistSelection
Monitor receipt of group object "Setpoint temperature"listDeactivated
Monitor receipt of group object "Setpoint power"listDeactivated
Cyclical monitoringlistDeactivated
Setpoint generator signalunsignedInt 0…10050
Setpoint generator signalsignedInt -50…500
Forced operationlistDeactivated
Time interval for cyclical monitoringtime300
Temperature inputlistDeactivated
Temperature offsetfloat -10…100
Cable length, single distancefloat 1…10010
Cross-section of conductor Value* 0.01 mm²unsignedInt 1…150100
Value is sent from a change offloat 0.2…101
Send cyclically everytime30
Resistance in ohms at +120°CunsignedInt 650…46003607
Cable resistance (total of fwd and rtn conductor)unsignedInt 0…10000500
Object value request on restart and bus voltage recoverylistNo
Send temperature valuelistAfter change
NTC typelistNTC 10-01 [-15...+100 °C]
FilterlistInactive
Cable error compensationlistNone
Temperature sensor typelistPT1000 [-30...+110 °C]
KTY typelistKT 100/110/130
Resistance in ohms at +40°CunsignedInt 650…46002080
Resistance in ohms at 0°CunsignedInt 650…46001495
Resistance in ohms at +20°CunsignedInt 650…46001772
Resistance in ohms at +60°CunsignedInt 650…46002417
Resistance in ohms at +80°CunsignedInt 650…46002785
Resistance in ohms at +100°CunsignedInt 650…46003182
Reaction on event 1listOn
GP_CD_A0B1011Ftext
Convertible from version 0.1unsignedInt 0…2551
Switch on pump when control value greater thanunsignedInt 0…991
Switch off pump when control value less than (0% = deactivated)unsignedInt 0…1001
Switch-off delaytime5
Send status valueslistAfter change or on request
Send cyclically everytime60
Enable manual pump overridelistNo
Pump reaction on bus voltage failurelistUnchanged
Pump reaction after bus voltage recoverylistFollows generator activation
Pump reaction after bus voltage recoverylistUnchanged
Monitor receipt of group object "Pump fault"listDeactivated
Monitor receipt of group object "Pump repair switch"listDeactivated
Generator activation after bus voltage recoverylistAs before bus voltage failure
On group object valuelist0 or 1
Setpoint generator signalunsignedInt 0…10015
Resistance in ohms at -20°CunsignedInt 650…46001247
Pump reaction on forced operationlistOn
Pump reaction during forced operation active "ON"listOn
Pump reaction during forced operation active "OFF"listOff
When closing the contactfloat 0…1001
When opening the contactfloat 0…1001
Long operation afterfloat 1…101
Relay outputlistActivated
Reaction of outputlistNO contact
Value of group object "Status Relay"list1: closed, 0: open
Send cyclically everytime300
Return from manual pump override to automatic modelistVia group object or automatic
Monitor pump repair switchlistDeactivated
Monitor pump errorlistDeactivated
Monitor pump statuslistDeactivated
Reset timetime300
Type of generator activationlistAbsolute temperature
Signal output (voltage to temperature/power)listNormal
Max. output voltage for generator Off Min. output voltage for generator activationfloat 0…105
Max. output voltage for generator activationfloat 0…1010
Monitor generator errorlistDeactivated
Monitor generator statuslistDeactivated
Use generator relay output for generator activationlistNo
Min. output voltage generator faultfloat 0…100
Max. output voltage generator faultfloat 0…102
Min. output voltage generator Offfloat 0…102.1
Pump reaction after ETS downloadlistFollows generator activation
Pump reaction after ETS downloadlistUnchanged
Enable manual generator overridelistNo
Return from manual generator override to automatic modelistVia group object or automatic
Switch on pump when generator is in activation rangelistYes
Monitor receipt of group object "Generator fault"listDeactivated
Generator reaction during forced operationlistOn
Generator reaction during forced operation active "ON"listOn
Generator reaction during forced operation active "OFF"listOn
Switching reaction of generator relay on bus voltage failurelistUnchanged
Setpoint generator signal during forced operationsignedInt -50…500
Setpoint generator signal during forced operation active "ON"signedInt -50…500
Setpoint generator signal during forced operationunsignedInt 0…10050
Setpoint generator signal during forced operation active "ON"unsignedInt 0…10050
Setpoint generator signal during forced operation active "OFF"unsignedInt 0…10050
Setpoint generator signal during forced operation active "OFF"signedInt -50…500
Temperature offset on exceeding the monitoring timesignedInt -50…500
Setpoint temperature on exceeding the monitoring timeunsignedInt 0…10050
Setpoint power on exceeding the monitoring timeunsignedInt 0…10050
Setpoint temperature on exceeding the monitoring timeunsignedInt 0…10015
Setpoint power on exceeding the monitoring timeunsignedInt 0…10015
InputlistPump status input
InputlistDeactivated
Scan input after download, ETS reset or bus voltage recoverylistYes
Active detected iflistContact closed
Send status valueslistAfter change
Enable group object "Block input"listNo
Input on operationlistClosed
Activate minimum signal durationlistNo
Distinction between long and short operationlistNo
Reaction on event 0listOff
InputlistPump error input
InputlistPump repair status input
InputlistGenerator status input
InputlistGenerator error input
Lower temperature limit for generator activationfloat 0…10025
Max. temperature decrease for generator activationfloat -50…50-10
Min. power specified for generator activationfloat 0…991
Max. temperature increase for generator activationfloat -50…5010
Upper temperature limit for generator activationfloat 0…10060
Max. power specified for generator activationfloat 1…100100
Switching reaction of generator relay after bus voltage recoverylistUnchanged
Switching reaction of generator relay after ETS downloadlistUnchanged
Generator reaction after bus voltage recoverylistOn
Generator reaction after ETS downloadlistOn
Switching reaction of generator relay during forced operationlistUnchanged
Switching reaction of generator relay during forced operation active "ON"listUnchanged
Switching reaction of generator relay during forced operation active "OFF"listUnchanged

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Boiler/Chiller Interface/1.1 1.1 latest$A0BDAFA72026-11-25217 KBDownload

About this file

This is the official ETS product database for the ABB AG - STOTZ-KONTAKT BCI/S1.1.1 Boiler/Chiller Interface,MDRC (2CDG 110 222 R0011), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.