ABB AG - STOTZ-KONTAKT 2CDG 110 216 R0011 VC/S4.1.1 Valve Drive Controller,4-fold,MDRC

VC/S4.1.1 Valve Drive Controller,4-fold,MDRC 2CDG 110 216 R0011

ABB AG - STOTZ-KONTAKT · Order number 2CDG 110 216 R0011 · Heating, Ventilation and Air Conditioning › Valve Drive Actuators

Valve Drive Controller, 4-f/1.1

Download .knxprod Valve Drive Controller, 4-f/1.1 1.1 · 437 KB

Product

ManufacturerABB AG - STOTZ-KONTAKT
Product nameVC/S4.1.1 Valve Drive Controller,4-fold,MDRC
Order number2CDG 110 216 R0011
HardwareVC/S4.1.1 Ventilantriebs-Controller,4-fach,REG
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)70
RegistrationRegistered · 2021-11-18
Languagesen-US, de-DE, es-ES, fr-FR, it-IT, nl-NL, pl-PL, ru-RU
Catalog entryM-0002_H-2CDG.20110.20216.20R0011-2_HP-A0BB-11-B916_CI-2CDG.20110.20216.20R0011-1
FingerprintB916
SHA-25697de4f242601408b42f0e1b489e53bbfa7a4e78fb6c306114c05a349d63636e0
First seen2026-11-25
Markets59 markets

Application program: Valve Drive Controller, 4-f/1.1 1.1

Application number$A0BB
Version1.1
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters1111
Group objects386
Group objects (386)
NoNameFunctionSizeDPTFlags
1GeneralIn operation1 Bit1.2 booleanCRT
3GeneralRequest status values1 Bit1.17 triggerCW
10Channel A - GeneralForced operation, 2-bit2 Bit2.1 switch controlCW
11Channel A - GeneralForced operation, 1-bit1 Bit1.2 booleanCW
12Channel A - GeneralError "Heating/cooling changeover" receipt1 Bit1.5 alarmCRT
13Channel A - GeneralError "Window contact" receipt1 Bit1.5 alarmCRT
14Channel A - GeneralError "Dew point alarm" receipt1 Bit1.5 alarmCRT
15Channel A - GeneralError "Fill level alarm" receipt1 Bit1.5 alarmCRT
16Channel A - GeneralError "Operating mode" receipt1 Bit1.5 alarmCRT
16Channel A - GeneralError "Control value" receipt1 Bit1.5 alarmCRT
17Channel A - GeneralStatus byte channel1 ByteCRT
18Channel - Valve AStatus byte valve A1 ByteCRT
19Channel - Valve AStatus Control value valve A1 Byte5.1 percentage (0..100%)CRT
20Channel - Valve AFault Valve output A1 Bit1.5 alarmCRT
21Channel - Valve AStatus Valve purge A1 Bit1.11 stateCRT
22Channel - Valve AReset fault Valve output A1 Bit1.15 resetCW
23Channel - Valve AActivate valve purge A1 Bit1.17 triggerCW
24Channel - Valve AEnable/block manual valve override A1 Bit1.3 enableCW
25Channel - Valve AOverride valve control value A1 Byte5.1 percentage (0..100%)CW
27Channel A - Input aTemperature2 Bytes9.1 temperature (°C)CRT
28Channel A - Input aError Input1 Bit1.5 alarmCRT
29Channel A - Input aContact position binary input1 Bit1.1 switchCRT
29Channel A - Input aWindow contact1 Bit1.19 window/doorCRT
29Channel A - Input aDew point alarm1 Bit1.5 alarmCRT
29Channel A - Input aFill level alarm1 Bit1.5 alarmCRT
30Channel A - Input aBlock input1 Bit1.3 enableCW
31Channel A - Input bTemperature2 Bytes9.1 temperature (°C)CRT
32Channel A - Input bError Input1 Bit1.5 alarmCRT
33Channel A - Input bContact position binary input1 Bit1.1 switchCRT
33Channel A - Input bWindow contact1 Bit1.19 window/doorCRT
33Channel A - Input bDew point alarm1 Bit1.5 alarmCRT
33Channel A - Input bFill level alarm1 Bit1.5 alarmCRT
34Channel A - Input bBlock input1 Bit1.3 enableCW
35Channel A - Binary input cContact position binary input1 Bit1.1 switchCRT
35Channel A - Binary input cWindow contact1 Bit1.19 window/doorCRT
35Channel A - Binary input cDew point alarm1 Bit1.5 alarmCRT
35Channel A - Binary input cFill level alarm1 Bit1.5 alarmCRT
36Channel A - Binary input cBlock input1 Bit1.3 enableCW
37Channel A - ControllerStatus Heating/cooling1 Bit1.100 cooling/heatingCRT
38Channel A - ControllerStatus Control value basic-stage heating1 Byte5.1 percentage (0..100%)CRT
38Channel A - ControllerStatus Control value basic-stage heating1 Bit1.1 switchCRT
39Channel A - ControllerStatus Control value additional-stage heating1 Byte5.1 percentage (0..100%)CRT
39Channel A - ControllerStatus Control value additional-stage heating1 Bit1.1 switchCRT
40Channel A - ControllerStatus Control value basic-stage cooling1 Byte5.1 percentage (0..100%)CRT
40Channel A - ControllerStatus Control value basic-stage cooling1 Bit1.1 switchCRT
41Channel A - ControllerStatus Control value additional-stage cooling1 Byte5.1 percentage (0..100%)CRT
41Channel A - ControllerStatus Control value additional-stage cooling1 Bit1.1 switchCRT
43Channel A - ControllerActual temperature2 Bytes9.1 temperature (°C)CRT
44Channel A - ControllerExternal temperature 12 Bytes9.1 temperature (°C)CWTU
45Channel A - ControllerExternal temperature 22 Bytes9.1 temperature (°C)CWTU
46Channel A - ControllerFault Actual temperature (master)1 Bit1.5 alarmCRT
47Channel A - ControllerCurrent setpoint2 Bytes9.1 temperature (°C)CRT
48Channel A - ControllerOperating mode normal (master)1 Byte20.102 HVAC modeCWTU
49Channel A - ControllerOperating mode override (master)1 Byte20.102 HVAC modeCWTU
50Channel A - ControllerWindow contact (master/slave)1 Bit1.19 window/doorCW
51Channel A - ControllerPresence detector (master/slave)1 Bit1.18 occupancyCW
52Channel A - ControllerStatus Heating1 Bit1.1 switchCRT
53Channel A - ControllerStatus Cooling1 Bit1.1 switchCRT
54Channel A - ControllerActivation of minimum control value (basic load)1 Bit1.3 enableCW
55Channel A - ControllerHeating/cooling changeover1 Bit1.100 cooling/heatingCWTU
55Channel A - ActuatorHeating/cooling changeover1 Bit1.100 cooling/heatingCWTU
56Channel A - ControllerBasic setpoint2 Bytes9.1 temperature (°C)CW
57Channel A - ControllerReset manual setpoint adjustment1 Bit1.17 triggerCW
58Channel A - ControllerDew point alarm1 Bit1.5 alarmCWTU
59Channel A - ControllerFill level alarm1 Bit1.5 alarmCWTU
60Channel A - ControllerOutside temperature for summer compensation2 Bytes9.1 temperature (°C)CW
61Channel A - ControllerSummer compensation active/inactive1 Bit1.2 booleanCRT
62Channel A - ControllerComfort setpoint reached1 Bit1.2 booleanCRT
63Channel A - ControllerRequest On/Off (master)1 Bit1.1 switchCW
64Channel A - ControllerConfirm On/Off (master)1 Bit1.1 switchCRT
65Channel A - ControllerSetpoint display (master)2 Bytes9.2 temperature difference (K)CRT
66Channel A - ControllerRequest setpoint adjustment (master)2 Bytes9.1 temperature (°C)CW
66Channel A - ControllerRequest setpoint adjustment (master)2 Bytes9.2 temperature difference (K)CW
66Channel A - ControllerRequest setpoint adjustment (master)1 Byte6.10 counter pulses (-128..127)CW
66Channel A - ActuatorRequest setpoint adjustment (slave)2 Bytes9.2 temperature difference (K)CRT
66Channel A - ActuatorRequest setpoint adjustment (slave)1 Byte6.10 counter pulses (-128..127)CRT
67Channel A - ControllerConfirm setpoint adjustment (master)2 Bytes9.1 temperature (°C)CRT
67Channel A - ControllerConfirm setpoint adjustment (master)2 Bytes9.2 temperature difference (K)CRT
67Channel A - ControllerConfirm setpoint adjustment (master)1 Byte6.10 counter pulses (-128..127)CRT
68Channel A - ControllerRequest heating/cooling (master)1 Bit1.100 cooling/heatingCW
73Channel A - ControllerStatus Controller RHCC2 Bytes22.101 RHCC statusCRT
74Channel A - ControllerStatus Controller HVAC (master)1 Byte5.1 percentage (0..100%)CRT
75Channel A - ControllerCurrent HVAC operating mode1 Byte20.102 HVAC modeCRT
76Channel A - ControllerComfort heating setpoint2 Bytes9.1 temperature (°C)CW
76Channel A - ControllerComfort heating/cooling setpoint2 Bytes9.1 temperature (°C)CW
77Channel A - ControllerComfort cooling setpoint2 Bytes9.1 temperature (°C)CW
78Channel A - ControllerEconomy heating setpoint2 Bytes9.1 temperature (°C)CW
79Channel A - ControllerEconomy cooling setpoint2 Bytes9.1 temperature (°C)CW
80Channel A - ControllerStandby heating setpoint2 Bytes9.1 temperature (°C)CW
81Channel A - ControllerStandby cooling setpoint2 Bytes9.1 temperature (°C)CW
82Channel A - ControllerBuilding Protection heating setpoint2 Bytes9.1 temperature (°C)CW
83Channel A - ControllerBuilding Protection cooling setpoint2 Bytes9.1 temperature (°C)CW
84Channel A - ActuatorHeating control value1 Byte5.1 percentage (0..100%)CWTU
85Channel A - ActuatorCooling control value1 Byte5.1 percentage (0..100%)CWTU
86Channel A - ControllerBasic-stage heating limit temperature2 Bytes9.1 temperature (°C)CWTU
87Channel A - ControllerAdditional-stage heating limit temperature2 Bytes9.1 temperature (°C)CWTU
88Channel A - ControllerBasic-stage cooling limit temperature2 Bytes9.1 temperature (°C)CWTU
89Channel A - ControllerAdditional-stage cooling limit temperature2 Bytes9.1 temperature (°C)CWTU
91Channel B - GeneralForced operation, 2-bit2 Bit2.1 switch controlCW
92Channel B - GeneralForced operation, 1-bit1 Bit1.2 booleanCW
93Channel B - GeneralError "Heating/cooling changeover" receipt1 Bit1.5 alarmCRT
94Channel B - GeneralError "Window contact" receipt1 Bit1.5 alarmCRT
95Channel B - GeneralError "Dew point alarm" receipt1 Bit1.5 alarmCRT
96Channel B - GeneralError "Fill level alarm" receipt1 Bit1.5 alarmCRT
97Channel B - GeneralError "Operating mode" receipt1 Bit1.5 alarmCRT
97Channel B - GeneralError "Control value" receipt1 Bit1.5 alarmCRT
98Channel B - GeneralStatus byte channel1 ByteCRT
99Channel B - Valve BStatus byte valve B1 ByteCRT
100Channel B - Valve BStatus Control value valve B1 Byte5.1 percentage (0..100%)CRT
101Channel B - Valve BFault Valve output B1 Bit1.5 alarmCRT
102Channel B - Valve BStatus Valve purge B1 Bit1.11 stateCRT
103Channel B - Valve BReset fault Valve output B1 Bit1.15 resetCW
104Channel B - Valve BActivate valve purge B1 Bit1.17 triggerCW
105Channel B - Valve BEnable/block manual valve override B1 Bit1.3 enableCW
106Channel B - Valve BOverride valve control value B1 Byte5.1 percentage (0..100%)CW
108Channel B - Input dTemperature2 Bytes9.1 temperature (°C)CRT
109Channel B - Input dError Input1 Bit1.5 alarmCRT
110Channel B - Input dContact position binary input1 Bit1.1 switchCRT
110Channel B - Input dWindow contact1 Bit1.19 window/doorCRT
110Channel B - Input dDew point alarm1 Bit1.5 alarmCRT
110Channel B - Input dFill level alarm1 Bit1.5 alarmCRT
111Channel B - Input dBlock input1 Bit1.3 enableCW
112Channel B - Input eTemperature2 Bytes9.1 temperature (°C)CRT
113Channel B - Input eError Input1 Bit1.5 alarmCRT
114Channel B - Input eContact position binary input1 Bit1.1 switchCRT
114Channel B - Input eWindow contact1 Bit1.19 window/doorCRT
114Channel B - Input eDew point alarm1 Bit1.5 alarmCRT
114Channel B - Input eFill level alarm1 Bit1.5 alarmCRT
115Channel B - Input eBlock input1 Bit1.3 enableCW
116Channel B - Binary input fContact position binary input1 Bit1.1 switchCRT
116Channel B - Binary input fWindow contact1 Bit1.19 window/doorCRT
116Channel B - Binary input fDew point alarm1 Bit1.5 alarmCRT
116Channel B - Binary input fFill level alarm1 Bit1.5 alarmCRT
117Channel B - Binary input fBlock input1 Bit1.3 enableCW
118Channel B - ControllerStatus Heating/cooling1 Bit1.100 cooling/heatingCRT
119Channel B - ControllerStatus Control value basic-stage heating1 Byte5.1 percentage (0..100%)CRT
119Channel B - ControllerStatus Control value basic-stage heating1 Bit1.1 switchCRT
120Channel B - ControllerStatus Control value additional-stage heating1 Byte5.1 percentage (0..100%)CRT
120Channel B - ControllerStatus Control value additional-stage heating1 Bit1.1 switchCRT
121Channel B - ControllerStatus Control value basic-stage cooling1 Byte5.1 percentage (0..100%)CRT
121Channel B - ControllerStatus Control value basic-stage cooling1 Bit1.1 switchCRT
122Channel B - ControllerStatus Control value additional-stage cooling1 Byte5.1 percentage (0..100%)CRT
122Channel B - ControllerStatus Control value additional-stage cooling1 Bit1.1 switchCRT
124Channel B - ControllerActual temperature2 Bytes9.1 temperature (°C)CRT
125Channel B - ControllerExternal temperature 12 Bytes9.1 temperature (°C)CWTU
126Channel B - ControllerExternal temperature 22 Bytes9.1 temperature (°C)CWTU
127Channel B - ControllerFault Actual temperature (master)1 Bit1.5 alarmCRT
128Channel B - ControllerCurrent setpoint2 Bytes9.1 temperature (°C)CRT
129Channel B - ControllerOperating mode normal (master)1 Byte20.102 HVAC modeCWTU
130Channel B - ControllerOperating mode override (master)1 Byte20.102 HVAC modeCWTU
131Channel B - ControllerWindow contact (master/slave)1 Bit1.19 window/doorCW
132Channel B - ControllerPresence detector (master/slave)1 Bit1.18 occupancyCW
133Channel B - ControllerStatus Heating1 Bit1.1 switchCRT
134Channel B - ControllerStatus Cooling1 Bit1.1 switchCRT
135Channel B - ControllerActivation of minimum control value (basic load)1 Bit1.3 enableCW
136Channel B - ControllerHeating/cooling changeover1 Bit1.100 cooling/heatingCWTU
136Channel B - ActuatorHeating/cooling changeover1 Bit1.100 cooling/heatingCWTU
137Channel B - ControllerBasic setpoint2 Bytes9.1 temperature (°C)CW
138Channel B - ControllerReset manual setpoint adjustment1 Bit1.17 triggerCW
139Channel B - ControllerDew point alarm1 Bit1.5 alarmCWTU
140Channel B - ControllerFill level alarm1 Bit1.5 alarmCWTU
141Channel B - ControllerOutside temperature for summer compensation2 Bytes9.1 temperature (°C)CW
142Channel B - ControllerSummer compensation active/inactive1 Bit1.2 booleanCRT
143Channel B - ControllerComfort setpoint reached1 Bit1.2 booleanCRT
144Channel B - ControllerRequest On/Off (master)1 Bit1.1 switchCW
145Channel B - ControllerConfirm On/Off (master)1 Bit1.1 switchCRT
146Channel B - ControllerSetpoint display (master)2 Bytes9.2 temperature difference (K)CRT
147Channel B - ControllerRequest setpoint adjustment (master)2 Bytes9.1 temperature (°C)CW
147Channel B - ControllerRequest setpoint adjustment (master)2 Bytes9.2 temperature difference (K)CW
147Channel B - ControllerRequest setpoint adjustment (master)1 Byte6.10 counter pulses (-128..127)CW
147Channel B - ActuatorRequest setpoint adjustment (slave)2 Bytes9.2 temperature difference (K)CRT
147Channel B - ActuatorRequest setpoint adjustment (slave)1 Byte6.10 counter pulses (-128..127)CRT
148Channel B - ControllerConfirm setpoint adjustment (master)2 Bytes9.1 temperature (°C)CRT
148Channel B - ControllerConfirm setpoint adjustment (master)2 Bytes9.2 temperature difference (K)CRT
148Channel B - ControllerConfirm setpoint adjustment (master)1 Byte6.10 counter pulses (-128..127)CRT
149Channel B - ControllerRequest heating/cooling (master)1 Bit1.100 cooling/heatingCW
154Channel B - ControllerStatus Controller RHCC2 Bytes22.101 RHCC statusCRT
155Channel B - ControllerStatus Controller HVAC (master)1 Byte5.1 percentage (0..100%)CRT
156Channel B - ControllerCurrent HVAC operating mode1 Byte20.102 HVAC modeCRT
157Channel B - ControllerComfort heating setpoint2 Bytes9.1 temperature (°C)CW
157Channel B - ControllerComfort heating/cooling setpoint2 Bytes9.1 temperature (°C)CW
158Channel B - ControllerComfort cooling setpoint2 Bytes9.1 temperature (°C)CW
159Channel B - ControllerEconomy heating setpoint2 Bytes9.1 temperature (°C)CW
160Channel B - ControllerEconomy cooling setpoint2 Bytes9.1 temperature (°C)CW
161Channel B - ControllerStandby heating setpoint2 Bytes9.1 temperature (°C)CW
162Channel B - ControllerStandby cooling setpoint2 Bytes9.1 temperature (°C)CW
163Channel B - ControllerBuilding Protection heating setpoint2 Bytes9.1 temperature (°C)CW
164Channel B - ControllerBuilding Protection cooling setpoint2 Bytes9.1 temperature (°C)CW
165Channel B - ActuatorHeating control value1 Byte5.1 percentage (0..100%)CWTU
166Channel B - ActuatorCooling control value1 Byte5.1 percentage (0..100%)CWTU
167Channel B - ControllerBasic-stage heating limit temperature2 Bytes9.1 temperature (°C)CWTU
168Channel B - ControllerAdditional-stage heating limit temperature2 Bytes9.1 temperature (°C)CWTU
169Channel B - ControllerBasic-stage cooling limit temperature2 Bytes9.1 temperature (°C)CWTU
170Channel B - ControllerAdditional-stage cooling limit temperature2 Bytes9.1 temperature (°C)CWTU
172Channel C - GeneralForced operation, 2-bit2 Bit2.1 switch controlCW
173Channel C - GeneralForced operation, 1-bit1 Bit1.2 booleanCW
174Channel C - GeneralError "Heating/cooling changeover" receipt1 Bit1.5 alarmCRT
175Channel C - GeneralError "Window contact" receipt1 Bit1.5 alarmCRT
176Channel C - GeneralError "Dew point alarm" receipt1 Bit1.5 alarmCRT
177Channel C - GeneralError "Fill level alarm" receipt1 Bit1.5 alarmCRT
178Channel C - GeneralError "Operating mode" receipt1 Bit1.5 alarmCRT
178Channel C - GeneralError "Control value" receipt1 Bit1.5 alarmCRT
179Channel C - GeneralStatus byte channel1 ByteCRT
180Channel C - Valve CStatus byte valve C1 ByteCRT
181Channel C - Valve CStatus Control value valve C1 Byte5.1 percentage (0..100%)CRT
182Channel C - Valve CFault Valve output C1 Bit1.5 alarmCRT
183Channel C - Valve CStatus Valve purge C1 Bit1.11 stateCRT
184Channel C - Valve CReset fault Valve output C1 Bit1.15 resetCW
185Channel C - Valve CActivate valve purge C1 Bit1.17 triggerCW
186Channel C - Valve CEnable/block manual valve override C1 Bit1.3 enableCW
187Channel C - Valve COverride valve control value C1 Byte5.1 percentage (0..100%)CW
189Channel C - Input gTemperature2 Bytes9.1 temperature (°C)CRT
190Channel C - Input gError Input1 Bit1.5 alarmCRT
191Channel C - Input gContact position binary input1 Bit1.1 switchCRT
191Channel C - Input gWindow contact1 Bit1.19 window/doorCRT
191Channel C - Input gDew point alarm1 Bit1.5 alarmCRT
191Channel C - Input gFill level alarm1 Bit1.5 alarmCRT
192Channel C - Input gBlock input1 Bit1.3 enableCW
193Channel C - Input hTemperature2 Bytes9.1 temperature (°C)CRT
194Channel C - Input hError Input1 Bit1.5 alarmCRT
195Channel C - Input hContact position binary input1 Bit1.1 switchCRT
195Channel C - Input hWindow contact1 Bit1.19 window/doorCRT
195Channel C - Input hDew point alarm1 Bit1.5 alarmCRT
195Channel C - Input hFill level alarm1 Bit1.5 alarmCRT
196Channel C - Input hBlock input1 Bit1.3 enableCW
197Channel C - Binary input iContact position binary input1 Bit1.1 switchCRT
197Channel C - Binary input iWindow contact1 Bit1.19 window/doorCRT
197Channel C - Binary input iDew point alarm1 Bit1.5 alarmCRT
197Channel C - Binary input iFill level alarm1 Bit1.5 alarmCRT
198Channel C - Binary input iBlock input1 Bit1.3 enableCW
199Channel C - ControllerStatus Heating/cooling1 Bit1.100 cooling/heatingCRT
200Channel C - ControllerStatus Control value basic-stage heating1 Byte5.1 percentage (0..100%)CRT
200Channel C - ControllerStatus Control value basic-stage heating1 Bit1.1 switchCRT
201Channel C - ControllerStatus Control value additional-stage heating1 Byte5.1 percentage (0..100%)CRT
201Channel C - ControllerStatus Control value additional-stage heating1 Bit1.1 switchCRT
202Channel C - ControllerStatus Control value basic-stage cooling1 Byte5.1 percentage (0..100%)CRT
202Channel C - ControllerStatus Control value basic-stage cooling1 Bit1.1 switchCRT
203Channel C - ControllerStatus Control value additional-stage cooling1 Byte5.1 percentage (0..100%)CRT
203Channel C - ControllerStatus Control value additional-stage cooling1 Bit1.1 switchCRT
205Channel C - ControllerActual temperature2 Bytes9.1 temperature (°C)CRT
206Channel C - ControllerExternal temperature 12 Bytes9.1 temperature (°C)CWTU
207Channel C - ControllerExternal temperature 22 Bytes9.1 temperature (°C)CWTU
208Channel C - ControllerFault Actual temperature (master)1 Bit1.5 alarmCRT
209Channel C - ControllerCurrent setpoint2 Bytes9.1 temperature (°C)CRT
210Channel C - ControllerOperating mode normal (master)1 Byte20.102 HVAC modeCWTU
211Channel C - ControllerOperating mode override (master)1 Byte20.102 HVAC modeCWTU
212Channel C - ControllerWindow contact (master/slave)1 Bit1.19 window/doorCW
213Channel C - ControllerPresence detector (master/slave)1 Bit1.18 occupancyCW
214Channel C - ControllerStatus Heating1 Bit1.1 switchCRT
215Channel C - ControllerStatus Cooling1 Bit1.1 switchCRT
216Channel C - ControllerActivation of minimum control value (basic load)1 Bit1.3 enableCW
217Channel C - ControllerHeating/cooling changeover1 Bit1.100 cooling/heatingCWTU
217Channel C - ActuatorHeating/cooling changeover1 Bit1.100 cooling/heatingCWTU
218Channel C - ControllerBasic setpoint2 Bytes9.1 temperature (°C)CW
219Channel C - ControllerReset manual setpoint adjustment1 Bit1.17 triggerCW
220Channel C - ControllerDew point alarm1 Bit1.5 alarmCWTU
221Channel C - ControllerFill level alarm1 Bit1.5 alarmCWTU
222Channel C - ControllerOutside temperature for summer compensation2 Bytes9.1 temperature (°C)CW
223Channel C - ControllerSummer compensation active/inactive1 Bit1.2 booleanCRT
224Channel C - ControllerComfort setpoint reached1 Bit1.2 booleanCRT
225Channel C - ControllerRequest On/Off (master)1 Bit1.1 switchCW
226Channel C - ControllerConfirm On/Off (master)1 Bit1.1 switchCRT
227Channel C - ControllerSetpoint display (master)2 Bytes9.2 temperature difference (K)CRT
228Channel C - ControllerRequest setpoint adjustment (master)2 Bytes9.1 temperature (°C)CW
228Channel C - ControllerRequest setpoint adjustment (master)2 Bytes9.2 temperature difference (K)CW
228Channel C - ControllerRequest setpoint adjustment (master)1 Byte6.10 counter pulses (-128..127)CW
228Channel C - ActuatorRequest setpoint adjustment (slave)2 Bytes9.2 temperature difference (K)CRT
228Channel C - ActuatorRequest setpoint adjustment (slave)1 Byte6.10 counter pulses (-128..127)CRT
229Channel C - ControllerConfirm setpoint adjustment (master)2 Bytes9.1 temperature (°C)CRT
229Channel C - ControllerConfirm setpoint adjustment (master)2 Bytes9.2 temperature difference (K)CRT
229Channel C - ControllerConfirm setpoint adjustment (master)1 Byte6.10 counter pulses (-128..127)CRT
230Channel C - ControllerRequest heating/cooling (master)1 Bit1.100 cooling/heatingCW
235Channel C - ControllerStatus Controller RHCC2 Bytes22.101 RHCC statusCRT
236Channel C - ControllerStatus Controller HVAC (master)1 Byte5.1 percentage (0..100%)CRT
237Channel C - ControllerCurrent HVAC operating mode1 Byte20.102 HVAC modeCRT
238Channel C - ControllerComfort heating setpoint2 Bytes9.1 temperature (°C)CW
238Channel C - ControllerComfort heating/cooling setpoint2 Bytes9.1 temperature (°C)CW
239Channel C - ControllerComfort cooling setpoint2 Bytes9.1 temperature (°C)CW
240Channel C - ControllerEconomy heating setpoint2 Bytes9.1 temperature (°C)CW
241Channel C - ControllerEconomy cooling setpoint2 Bytes9.1 temperature (°C)CW
242Channel C - ControllerStandby heating setpoint2 Bytes9.1 temperature (°C)CW
243Channel C - ControllerStandby cooling setpoint2 Bytes9.1 temperature (°C)CW
244Channel C - ControllerBuilding Protection heating setpoint2 Bytes9.1 temperature (°C)CW
245Channel C - ControllerBuilding Protection cooling setpoint2 Bytes9.1 temperature (°C)CW
246Channel C - ActuatorHeating control value1 Byte5.1 percentage (0..100%)CWTU
247Channel C - ActuatorCooling control value1 Byte5.1 percentage (0..100%)CWTU
248Channel C - ControllerBasic-stage heating limit temperature2 Bytes9.1 temperature (°C)CWTU
249Channel C - ControllerAdditional-stage heating limit temperature2 Bytes9.1 temperature (°C)CWTU
250Channel C - ControllerBasic-stage cooling limit temperature2 Bytes9.1 temperature (°C)CWTU
251Channel C - ControllerAdditional-stage cooling limit temperature2 Bytes9.1 temperature (°C)CWTU
253Channel D - GeneralForced operation, 2-bit2 Bit2.1 switch controlCW
254Channel D - GeneralForced operation, 1-bit1 Bit1.2 booleanCW
255Channel D - GeneralError "Heating/cooling changeover" receipt1 Bit1.5 alarmCRT
256Channel D - GeneralError "Window contact" receipt1 Bit1.5 alarmCRT
257Channel D - GeneralError "Dew point alarm" receipt1 Bit1.5 alarmCRT
258Channel D - GeneralError "Fill level alarm" receipt1 Bit1.5 alarmCRT
259Channel D - GeneralError "Operating mode" receipt1 Bit1.5 alarmCRT
259Channel D - GeneralError "Control value" receipt1 Bit1.5 alarmCRT
260Channel D - GeneralStatus byte channel1 ByteCRT
261Channel D - Valve DStatus byte valve D1 ByteCRT
262Channel D - Valve DStatus Control value valve D1 Byte5.1 percentage (0..100%)CRT
263Channel D - Valve DFault Valve output D1 Bit1.5 alarmCRT
264Channel D - Valve DStatus Valve purge D1 Bit1.11 stateCRT
265Channel D - Valve DReset fault Valve output D1 Bit1.15 resetCW
266Channel D - Valve DActivate valve purge D1 Bit1.17 triggerCW
267Channel D - Valve DEnable/block manual valve override D1 Bit1.3 enableCW
268Channel D - Valve DOverride valve control value D1 Byte5.1 percentage (0..100%)CW
270Channel D - Input jTemperature2 Bytes9.1 temperature (°C)CRT
271Channel D - Input jError Input1 Bit1.5 alarmCRT
272Channel D - Input jContact position binary input1 Bit1.1 switchCRT
272Channel D - Input jWindow contact1 Bit1.19 window/doorCRT
272Channel D - Input jDew point alarm1 Bit1.5 alarmCRT
272Channel D - Input jFill level alarm1 Bit1.5 alarmCRT
273Channel D - Input jBlock input1 Bit1.3 enableCW
274Channel D - Input kTemperature2 Bytes9.1 temperature (°C)CRT
275Channel D - Input kError Input1 Bit1.5 alarmCRT
276Channel D - Input kContact position binary input1 Bit1.1 switchCRT
276Channel D - Input kWindow contact1 Bit1.19 window/doorCRT
276Channel D - Input kDew point alarm1 Bit1.5 alarmCRT
276Channel D - Input kFill level alarm1 Bit1.5 alarmCRT
277Channel D - Input kBlock input1 Bit1.3 enableCW
278Channel D - Binary input lContact position binary input1 Bit1.1 switchCRT
278Channel D - Binary input lWindow contact1 Bit1.19 window/doorCRT
278Channel D - Binary input lDew point alarm1 Bit1.5 alarmCRT
278Channel D - Binary input lFill level alarm1 Bit1.5 alarmCRT
279Channel D - Binary input lBlock input1 Bit1.3 enableCW
280Channel D - ControllerStatus Heating/cooling1 Bit1.100 cooling/heatingCRT
281Channel D - ControllerStatus Control value basic-stage heating1 Byte5.1 percentage (0..100%)CRT
281Channel D - ControllerStatus Control value basic-stage heating1 Bit1.1 switchCRT
282Channel D - ControllerStatus Control value additional-stage heating1 Byte5.1 percentage (0..100%)CRT
282Channel D - ControllerStatus Control value additional-stage heating1 Bit1.1 switchCRT
283Channel D - ControllerStatus Control value basic-stage cooling1 Byte5.1 percentage (0..100%)CRT
283Channel D - ControllerStatus Control value basic-stage cooling1 Bit1.1 switchCRT
284Channel D - ControllerStatus Control value additional-stage cooling1 Byte5.1 percentage (0..100%)CRT
284Channel D - ControllerStatus Control value additional-stage cooling1 Bit1.1 switchCRT
286Channel D - ControllerActual temperature2 Bytes9.1 temperature (°C)CRT
287Channel D - ControllerExternal temperature 12 Bytes9.1 temperature (°C)CWTU
288Channel D - ControllerExternal temperature 22 Bytes9.1 temperature (°C)CWTU
289Channel D - ControllerFault Actual temperature (master)1 Bit1.5 alarmCRT
290Channel D - ControllerCurrent setpoint2 Bytes9.1 temperature (°C)CRT
291Channel D - ControllerOperating mode normal (master)1 Byte20.102 HVAC modeCWTU
292Channel D - ControllerOperating mode override (master)1 Byte20.102 HVAC modeCWTU
293Channel D - ControllerWindow contact (master/slave)1 Bit1.19 window/doorCW
294Channel D - ControllerPresence detector (master/slave)1 Bit1.18 occupancyCW
295Channel D - ControllerStatus Heating1 Bit1.1 switchCRT
296Channel D - ControllerStatus Cooling1 Bit1.1 switchCRT
297Channel D - ControllerActivation of minimum control value (basic load)1 Bit1.3 enableCW
298Channel D - ControllerHeating/cooling changeover1 Bit1.100 cooling/heatingCWTU
298Channel D - ActuatorHeating/cooling changeover1 Bit1.100 cooling/heatingCWTU
299Channel D - ControllerBasic setpoint2 Bytes9.1 temperature (°C)CW
300Channel D - ControllerReset manual setpoint adjustment1 Bit1.17 triggerCW
301Channel D - ControllerDew point alarm1 Bit1.5 alarmCWTU
302Channel D - ControllerFill level alarm1 Bit1.5 alarmCWTU
303Channel D - ControllerOutside temperature for summer compensation2 Bytes9.1 temperature (°C)CW
304Channel D - ControllerSummer compensation active/inactive1 Bit1.2 booleanCRT
305Channel D - ControllerComfort setpoint reached1 Bit1.2 booleanCRT
306Channel D - ControllerRequest On/Off (master)1 Bit1.1 switchCW
307Channel D - ControllerConfirm On/Off (master)1 Bit1.1 switchCRT
308Channel D - ControllerSetpoint display (master)2 Bytes9.2 temperature difference (K)CRT
309Channel D - ControllerRequest setpoint adjustment (master)2 Bytes9.1 temperature (°C)CW
309Channel D - ControllerRequest setpoint adjustment (master)2 Bytes9.2 temperature difference (K)CW
309Channel D - ControllerRequest setpoint adjustment (master)1 Byte6.10 counter pulses (-128..127)CW
309Channel D - ActuatorRequest setpoint adjustment (slave)2 Bytes9.2 temperature difference (K)CRT
309Channel D - ActuatorRequest setpoint adjustment (slave)1 Byte6.10 counter pulses (-128..127)CRT
310Channel D - ControllerConfirm setpoint adjustment (master)2 Bytes9.1 temperature (°C)CRT
310Channel D - ControllerConfirm setpoint adjustment (master)2 Bytes9.2 temperature difference (K)CRT
310Channel D - ControllerConfirm setpoint adjustment (master)1 Byte6.10 counter pulses (-128..127)CRT
311Channel D - ControllerRequest heating/cooling (master)1 Bit1.100 cooling/heatingCW
316Channel D - ControllerStatus Controller RHCC2 Bytes22.101 RHCC statusCRT
317Channel D - ControllerStatus Controller HVAC (master)1 Byte5.1 percentage (0..100%)CRT
318Channel D - ControllerCurrent HVAC operating mode1 Byte20.102 HVAC modeCRT
319Channel D - ControllerComfort heating setpoint2 Bytes9.1 temperature (°C)CW
319Channel D - ControllerComfort heating/cooling setpoint2 Bytes9.1 temperature (°C)CW
320Channel D - ControllerComfort cooling setpoint2 Bytes9.1 temperature (°C)CW
321Channel D - ControllerEconomy heating setpoint2 Bytes9.1 temperature (°C)CW
322Channel D - ControllerEconomy cooling setpoint2 Bytes9.1 temperature (°C)CW
323Channel D - ControllerStandby heating setpoint2 Bytes9.1 temperature (°C)CW
324Channel D - ControllerStandby cooling setpoint2 Bytes9.1 temperature (°C)CW
325Channel D - ControllerBuilding Protection heating setpoint2 Bytes9.1 temperature (°C)CW
326Channel D - ControllerBuilding Protection cooling setpoint2 Bytes9.1 temperature (°C)CW
327Channel D - ActuatorHeating control value1 Byte5.1 percentage (0..100%)CWTU
328Channel D - ActuatorCooling control value1 Byte5.1 percentage (0..100%)CWTU
329Channel D - ControllerBasic-stage heating limit temperature2 Bytes9.1 temperature (°C)CWTU
330Channel D - ControllerAdditional-stage heating limit temperature2 Bytes9.1 temperature (°C)CWTU
331Channel D - ControllerBasic-stage cooling limit temperature2 Bytes9.1 temperature (°C)CWTU
332Channel D - ControllerAdditional-stage cooling limit temperature2 Bytes9.1 temperature (°C)CWTU
Parameters (184)
ParameterTypeDefault
Hardware_TypelistHW
Device functionlistStandalone
Sending and switching delay after bus voltage recoveryunsignedInt 2…2552
Value after sending and switching delay has expiredlistLast value received
Limit number of telegramslistNo
Enable group object "In operation"listNo
Send value of group object "In operation"listValue 1
In periodlist1 s
Maximum number of telegramsunsignedInt 1…5020
i-bus Tool accesslistFull access
Sending cycletime60
Actual temperature receiptlistVia physical device input
Number of group objects Actual temperaturelist1
Weighting of internal measurementunsignedInt 0…100100
Weighting of external measurement 2unsignedInt 0…10050
Operating mode after bus voltage recoverylistAs before bus voltage failure
Control value after bus voltage recoverylistAs before bus voltage failure
Control value after ETS downloadlistUnchanged
Status after ETS downloadlistUnchanged
Cyclical monitoringlistDeactivated
Monitor receipt of group object "Operating mode normal (master)"listDeactivated
Monitor receipt of group objects "Heating/cooling control value"listDeactivated
Monitor receipt of group object "Heating/cooling changeover"listDeactivated
Monitor receipt of group object "Window contact"listDeactivated
Monitor receipt of group object "Dew point alarm"listDeactivated
Monitor receipt of group object "Fill level alarm"listDeactivated
Forced operationlistDeactivated
Control value on forced operationunsignedInt 0…1000
Control value during forced operation active "ON"unsignedInt 0…1000
Control value during forced operation active "OFF"unsignedInt 0…1000
Temperature input monitoringlistDeactivated
Operating mode on exceeding the monitoring timelistUnchanged
Time interval for cyclical monitoringtime300
Resistance in ohms at +120°CunsignedInt 650…46003607
Temperature offsetfloat -10…100
Cable length, single distancefloat 1…10010
InputlistDeactivated
Cross-section of conductor Value* 0.01 mm²unsignedInt 1…150100
Cable resistance (total of fwd and rtn conductor)unsignedInt 0…10000500
Value is sent from a change offloat 0.2…101
Send cyclically everytime30
Minimum control value for basic load > 0listAlways active
Setpoint temperature offset when summer compensation startsfloat 0…12.70
Setpoint temperature offset when summer compensation endsfloat 0…12.76
Type of control value Basic-stage heatinglistPI continuous (0...100%)
Control value directionlistNormal
Extended settingslistNo
Control value difference for sending control valuelist5 %
I-proportionunsignedInt 0…255100
Send control value cyclically (0 = deactivated)unsignedInt 0…6015
P-proportionfloat 1…101.5
Hysteresisfloat 0.3…25.50.5
Maximum control valueunsignedInt 1…100100
Min. control value (basic load)unsignedInt 0…1000
Type of control value Additional-stage heatinglistPI continuous (0...100%)
Temperature difference from basic-stage heatingfloat 0…25.52
Type of control value Basic-stage coolinglistPI continuous (0...100%)
P-proportionfloat 1…102
Type of control value Additional-stage coolinglistPI continuous (0...100%)
Economy cooling increaseunsignedInt 0…154
Economy cooling setpointunsignedInt 10…4029
Comfort heating and cooling setpointunsignedInt 10…4021
Comfort heating setpointunsignedInt 10…4021
Standby heating reductionunsignedInt 0…152
Economy heating reductionunsignedInt 0…154
Standby cooling increaseunsignedInt 0…152
Standby heating setpointunsignedInt 10…4019
Economy heating setpointunsignedInt 10…4017
Standby cooling setpointunsignedInt 10…4027
Setpoint for frost protection (Building Protection heating)unsignedInt 5…157
Setpoint for heat protection (Building Protection cooling)unsignedInt 27…4535
Cycle for sending the setpointunsignedInt 5…24015
Max. manual increase in heating mode via KNXunsignedInt 0…93
Max. manual reduction in heating mode via KNXunsignedInt 0…93
Max. manual increase in cooling mode via KNXunsignedInt 0…93
Max. manual reduction in cooling mode via KNXunsignedInt 0…93
Operating modeslistComfort, Standby, Economy, Building Protection
Comfort heating setpoint = Comfort cooling setpointlistNo
Setpoint specification and adjustmentlistRelative
Send current setpointlistAfter change
Base setpoint islistComfort heating setpoint
Reset manual setpoint adjustment via KNX when base setpoint receivedlistYes
Reset manual setpoint adjustment via KNX when operating mode changeslistYes
Reset manual setpoint adjustment via KNX using group objectlistYes
Temperature difference from basic-stage coolingfloat 0…25.52
Activate summer compensationlistNo
Starting temperature for summer compensationsignedInt 10…5021
Ending temperature for summer compensationsignedInt 10…5032
Object value request on restart and bus voltage recoverylistNo
Additional-stage heatinglistDeactivated
Additional-stage coolinglistDeactivated
Type of heating/cooling systemlist4-pipe
Setpoint indication on slave displaylistAbsolute
Hysteresis for Heating/cooling changeoverfloat 0.5…102
Heating/cooling changeoverlistAutomatic
PWM cycle timeunsignedInt 10…900180
Valve drive opening/closing timeunsignedInt 10…900180
Convertible from version 0.1unsignedInt 0…2551
Send cyclically everytime300
Send temperature valuelistAfter change
Resistance in ohms at +100 °CunsignedInt 650…46003182
Heating PWM cycleunsignedInt 1…6015
Cooling PWM cycleunsignedInt 1…6015
Activate temperature limitationlistNo
I-proportion at temperature limitationlistFreeze
Limit temperatureunsignedInt 20…5030
Input for temperature limit sensorlistVia group object
Limit temperature hysteresisfloat 0.5…51
Limit temperatureunsignedInt 1…3010
GP_CD_A0BC011Ftext
Operating mode after ETS download/resetlistHeating
Cycle for sending the room temperature (0 = deactivated)unsignedInt 0…25515
Temperature change for sending current room temperaturefloat 0.1…100.5
Send inactive control values cyclicallylistNo
Comfort cooling setpointunsignedInt 10…4025
Basic load active when controller offlistNo
Weighting of external measurement 1unsignedInt 0…10050
Control valueunsignedInt 0…1000
InputlistAnalog room control unit
Channel functionlistController channel
Dew point reached whenlistValue 1
Dew point status receiptlistDeactivated
Window open whenlistValue 1
Window status receiptlistDeactivated
Fill level reached whenlistValue 1
Fill level status receiptlistDeactivated
Valve outputlistThermoelectric (PWM)
Open if control value greater than or equal tounsignedInt 1…1001
Enable manual valve overridelistNo
Valve drive operating principle, de-energizedlistClosed
Send status valueslistAfter change or on request
Control value on exceeding the monitoring timeunsignedInt 0…10025
Control value on input faultunsignedInt 0…10025
Valve purgelistAutomatic or via group object
Send value of group object "Status Valve purge"listNo, update only
Purge cycle in weeksunsignedInt 1…124
Reset purge cycle from control value greater than or equal tounsignedInt 1…9999
On group object valuelist0 or 1
Reaction on event 1listOn
When closing the contactfloat 0…1001
When opening the contactfloat 0…1001
Long operation afterfloat 1…101
Basic-stage heatinglistActivated
Basic-stage heatinglistConvector (e.g. radiator)
Basic-stage coolinglistArea cooling (e.g. cooling ceiling)
Basic-stage coolinglistActivated
Activate additional-stage cooling vialistGroup object
Activate additional-stage cooling vialistInternal channel output (valve)
Activate additional-stage heating vialistInternal channel output (valve)
Activate additional-stage heating vialistGroup object
Activate basic-stage cooling vialistGroup object
Activate basic-stage cooling vialistInternal channel output (valve)
Activate basic-stage heating vialistInternal channel output (valve)
Activate basic-stage heating vialistGroup object
Control value on exceeding the monitoring timeunsignedInt 0…10025
Operating mode on exceeding the monitoring timelistBuilding Protection
Scan input after download, ETS reset or bus voltage recoverylistYes
Window open whenlistContact open
Dew point reached whenlistContact open
Fill level reached whenlistContact open
Maximum setpoint increaseunsignedInt 0…53
Send status valueslistAfter change
Cable error compensationlistNone
Enable group object "Block input"listNo
Input on operationlistClosed
Temperature sensor typelistPT1000 [-30...+110 °C]
Activate minimum signal durationlistNo
Distinction between long and short operationlistNo
KTY typelistKT 100/110/130
Maximum setpoint reductionunsignedInt 0…53
Reaction on event 0listOff
NTC typelistNTC 10-01 [-15...+100 °C]
FilterlistInactive
Resistance in ohms at -20°CunsignedInt 650…46001247
Connect analog room control unit to physical device inputlistNo
Resistance in ohms at 0°CunsignedInt 650…46001495
Resistance in ohms at +20°CunsignedInt 650…46001772
Resistance in ohms at +40°CunsignedInt 650…46002080
Resistance in ohms at +60°CunsignedInt 650…46002417
Resistance in ohms at +80°CunsignedInt 650…46002785
Operating mode after bus voltage recovery or ETS downloadlistComfort
Data point type, manual setpoint adjustmentlistDPT 9.002 (relative temperature value)
Data point type, manual setpoint adjustmentlistDPT 9.001 (absolute temperature value)
GP_CD_A0BB011Ftext

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Valve Drive Controller, 4-f/1.1 1.1 latest$A0BBB9162026-11-25437 KBDownload

About this file

This is the official ETS product database for the ABB AG - STOTZ-KONTAKT VC/S4.1.1 Valve Drive Controller,4-fold,MDRC (2CDG 110 216 R0011), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.