FCC/S1.1.2.1 Fan Coil Controller,PWM,3-speed,manual operation,MDRC 2CDG 110 211 R0011
ABB AG - STOTZ-KONTAKT · Order number 2CDG 110 211 R0011 · Heating, Ventilation and Air Conditioning › Fan Coil Controllers
Fan Coil Controller, PWM, 3-speed, manual operation/1.3
Download .knxprod Fan Coil Controller, PWM, 3-speed, manual operation/1.3 1.3 · 350 KB
Product
| Manufacturer | ABB AG - STOTZ-KONTAKT |
|---|---|
| Product name | FCC/S1.1.2.1 Fan Coil Controller,PWM,3-speed,manual operation,MDRC |
| Order number | 2CDG 110 211 R0011 |
| Hardware | FCC/S1.1.2.1 Fan Coil Controller,PWM,3-stufig,manuelle Bedienung,REG |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | Yes |
| Width (mm) | 70 |
| Registration | Certified · 2021-11-17 |
| Languages | en-US, de-DE, es-ES, fr-FR, it-IT, nl-NL, pl-PL, ru-RU |
| Catalog entry | M-0002_H-2CDG.20110.20211.20R0011-2_HP-A0B1-13-2BE2_CI-2CDG.20110.20211.20R0011-1 |
| Fingerprint | 2BE2 |
| SHA-256 | 2849a676b70acd2e09f977987a6e2e4b85537cefd77ab802199acd952ad9d404 |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: Fan Coil Controller, PWM, 3-speed, manual operation/1.3 1.3
| Application number | $A0B1 |
|---|---|
| Version | 1.3 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 462 |
| Group objects | 146 |
Group objects (146)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | General | In operation | 1 Bit | 1.2 boolean | CRT |
| 2 | General | Status byte Device | 1 Byte | CRT | |
| 3 | General | Request status values | 1 Bit | 1.17 trigger | CW |
| 4 | General | Status Manual operation | 1 Bit | 1.11 state | CRT |
| 5 | General | Enable/block manual operation | 1 Bit | 1.3 enable | CW |
| 10 | Channel - General | Forced operation, 2-bit | 2 Bit | 2.1 switch control | CW |
| 11 | Channel - General | Forced operation, 1-bit | 1 Bit | 1.2 boolean | CW |
| 12 | Channel - General | Error "Heating/cooling changeover" receipt | 1 Bit | 1.5 alarm | CRT |
| 13 | Channel - General | Error "Window status" receipt | 1 Bit | 1.5 alarm | CRT |
| 14 | Channel - General | Error "Dew point status" receipt | 1 Bit | 1.5 alarm | CRT |
| 15 | Channel - General | Error "Fill level status" receipt | 1 Bit | 1.5 alarm | CRT |
| 16 | Channel - General | Error "Operating mode" receipt | 1 Bit | 1.5 alarm | CRT |
| 16 | Channel - General | Error "Control value" receipt | 1 Bit | 1.5 alarm | CRT |
| 18 | Channel - Fan | Status Fan On/Off | 1 Bit | 1.1 switch | CRT |
| 19 | Channel - Fan | Status byte Fan | 1 Byte | CRT | |
| 20 | Channel - Fan | Status Fan automatic | 1 Bit | 1.11 state | CRT |
| 21 | Channel - Fan | Status Fan speed | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 21 | Channel - Fan | Status Fan speed | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 22 | Channel - Fan | Status Fan speed 1 | 1 Bit | 1.1 switch | CRT |
| 23 | Channel - Fan | Status Fan speed 2 | 1 Bit | 1.1 switch | CRT |
| 24 | Channel - Fan | Status Fan speed 3 | 1 Bit | 1.1 switch | CRT |
| 25 | Channel - Fan | Activate/deactivate fan automatic | 1 Bit | 1.3 enable | CW |
| 26 | Channel - Fan | Switch fan speed 1 | 1 Bit | 1.1 switch | CW |
| 27 | Channel - Fan | Switch fan speed 2 | 1 Bit | 1.1 switch | CW |
| 28 | Channel - Fan | Switch fan speed 3 | 1 Bit | 1.1 switch | CW |
| 29 | Channel - Fan | Switch fan speed | 1 Byte | 5.1 percentage (0..100%) | CW |
| 30 | Channel - Fan | Increase/decrease fan speed | 1 Bit | 1.7 step | CW |
| 31 | Channel - Fan | Limitation 1 | 1 Bit | 1.3 enable | CW |
| 32 | Channel - Fan | Limitation 2 | 1 Bit | 1.3 enable | CW |
| 33 | Channel - Fan | Limitation 3 | 1 Bit | 1.3 enable | CW |
| 35 | Channel - Valve A | Status byte valve A | 1 Byte | CRT | |
| 36 | Channel - Valve A | Status Control value valve A | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 37 | Channel - Valve A | Fault Valve output A | 1 Bit | 1.5 alarm | CRT |
| 38 | Channel - Valve A | Status Valve purge A | 1 Bit | 1.11 state | CRT |
| 39 | Channel - Valve A | Reset fault Valve output A | 1 Bit | 1.15 reset | CW |
| 40 | Channel - Valve A | Activate valve purge A | 1 Bit | 1.17 trigger | CW |
| 41 | Channel - Valve A | Enable/block manual valve override A | 1 Bit | 1.3 enable | CW |
| 42 | Channel - Valve A | Override valve control value A | 1 Byte | 5.1 percentage (0..100%) | CW |
| 44 | Channel - Valve B | Status byte valve B | 1 Byte | CRT | |
| 45 | Channel - Valve B | Status Control value valve B | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 46 | Channel - Valve B | Fault Valve output B | 1 Bit | 1.5 alarm | CRT |
| 47 | Channel - Valve B | Status Valve purge B | 1 Bit | 1.11 state | CRT |
| 48 | Channel - Valve B | Reset fault Valve output B | 1 Bit | 1.15 reset | CW |
| 49 | Channel - Valve B | Activate valve purge B | 1 Bit | 1.17 trigger | CW |
| 50 | Channel - Valve B | Enable/block manual valve override B | 1 Bit | 1.3 enable | CW |
| 51 | Channel - Valve B | Override valve control value B | 1 Byte | 5.1 percentage (0..100%) | CW |
| 53 | Channel - Relay | Status Relay | 1 Bit | 1.9 open/close | CRT |
| 54 | Channel - Relay | Switch | 1 Bit | 1.1 switch | CW |
| 55 | Channel - Input a | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 56 | Channel - Input a | Error Input | 1 Bit | 1.5 alarm | CRT |
| 57 | Channel - Input a | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 57 | Channel - Input a | Window contact | 1 Bit | 1.19 window/door | CRT |
| 57 | Channel - Input a | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 57 | Channel - Input a | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 58 | Channel - Input a | Block input | 1 Bit | 1.3 enable | CW |
| 59 | Channel - Input b | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 60 | Channel - Input b | Error Input | 1 Bit | 1.5 alarm | CRT |
| 61 | Channel - Input b | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 61 | Channel - Input b | Window contact | 1 Bit | 1.19 window/door | CRT |
| 61 | Channel - Input b | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 61 | Channel - Input b | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 62 | Channel - Input b | Block input | 1 Bit | 1.3 enable | CW |
| 63 | Channel - Input c | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 64 | Channel - Input c | Error Input | 1 Bit | 1.5 alarm | CRT |
| 65 | Channel - Input c | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 65 | Channel - Input c | Window contact | 1 Bit | 1.19 window/door | CRT |
| 65 | Channel - Input c | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 65 | Channel - Input c | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 66 | Channel - Input c | Block input | 1 Bit | 1.3 enable | CW |
| 67 | Channel - Input d | Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 68 | Channel - Input d | Error Input | 1 Bit | 1.5 alarm | CRT |
| 69 | Channel - Input d | Contact position binary input | 1 Bit | 1.1 switch | CRT |
| 69 | Channel - Input d | Window contact | 1 Bit | 1.19 window/door | CRT |
| 69 | Channel - Input d | Dew point alarm | 1 Bit | 1.5 alarm | CRT |
| 69 | Channel - Input d | Fill level alarm | 1 Bit | 1.5 alarm | CRT |
| 70 | Channel - Input d | Block input | 1 Bit | 1.3 enable | CW |
| 71 | Channel - Controller | Status Heating/cooling | 1 Bit | 1.100 cooling/heating | CRT |
| 72 | Channel - Controller | Status Control value basic-stage heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 72 | Channel - Controller | Status Control value basic-stage heating | 1 Bit | 1.1 switch | CRT |
| 73 | Channel - Controller | Status Control value additional-stage heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 73 | Channel - Controller | Status Control value additional-stage heating | 1 Bit | 1.1 switch | CRT |
| 74 | Channel - Controller | Status Control value basic-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 74 | Channel - Controller | Status Control value basic-stage cooling | 1 Bit | 1.1 switch | CRT |
| 75 | Channel - Controller | Status Control value additional-stage cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 75 | Channel - Controller | Status Control value additional-stage cooling | 1 Bit | 1.1 switch | CRT |
| 77 | Channel - Controller | Actual temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 78 | Channel - Controller | External temperature 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 79 | Channel - Controller | External temperature 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 80 | Channel - Controller | Fault Actual temperature (master) | 1 Bit | 1.5 alarm | CRT |
| 81 | Channel - Controller | Current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 82 | Channel - Controller | Operating mode Normal (master) | 1 Byte | 20.102 HVAC mode | CWTU |
| 83 | Channel - Controller | Operating mode override (master) | 1 Byte | 20.102 HVAC mode | CWTU |
| 84 | Channel - Controller | Window contact (master/slave) | 1 Bit | 1.19 window/door | CW |
| 85 | Channel - Controller | Presence detector (master/slave) | 1 Bit | 1.18 occupancy | CW |
| 86 | Channel - Controller | Status Heating | 1 Bit | 1.1 switch | CRT |
| 87 | Channel - Controller | Status Cooling | 1 Bit | 1.1 switch | CRT |
| 88 | Channel - Controller | Activation of minimum control value (basic load) | 1 Bit | 1.3 enable | CW |
| 89 | Channel - Controller | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 89 | Channel - Actuator | Heating/cooling changeover | 1 Bit | 1.100 cooling/heating | CWTU |
| 90 | Channel - Controller | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 91 | Channel - Controller | Reset manual setpoint adjustment | 1 Bit | 1.17 trigger | CW |
| 92 | Channel - Controller | Dew point alarm | 1 Bit | 1.5 alarm | CWTU |
| 93 | Channel - Controller | Fill level alarm | 1 Bit | 1.5 alarm | CWTU |
| 94 | Channel - Controller | Outside temperature for summer compensation | 2 Bytes | 9.1 temperature (°C) | CW |
| 95 | Channel - Controller | Summer compensation active/inactive | 1 Bit | 1.2 boolean | CRT |
| 96 | Channel - Controller | Comfort setpoint reached | 1 Bit | 1.2 boolean | CRT |
| 97 | Channel - Controller | Request On/Off (master) | 1 Bit | 1.1 switch | CW |
| 98 | Channel - Controller | Confirm On/Off (master) | 1 Bit | 1.1 switch | CRT |
| 99 | Channel - Controller | Setpoint display (master) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 100 | Channel - Controller | Request setpoint adjustment (master) | 2 Bytes | 9.1 temperature (°C) | CW |
| 100 | Channel - Controller | Request setpoint adjustment (master) | 2 Bytes | 9.2 temperature difference (K) | CW |
| 100 | Channel - Controller | Request setpoint adjustment (master) | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 100 | Channel - Actuator | Request setpoint adjustment (slave) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 100 | Channel - Actuator | Request setpoint adjustment (slave) | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 101 | Channel - Controller | Confirm setpoint adjustment (master) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 101 | Channel - Controller | Confirm setpoint adjustment (master) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 101 | Channel - Controller | Confirm setpoint adjustment (master) | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 102 | Channel - Controller | Request heating/cooling (master) | 1 Bit | 1.100 cooling/heating | CW |
| 103 | Channel - Controller | Request fan manually (master) | 1 Bit | 1.1 switch | CW |
| 103 | Channel - Actuator | Request fan manually (slave) | 1 Bit | 1.1 switch | CRT |
| 104 | Channel - Controller | Confirm fan manually (master) | 1 Bit | 1.1 switch | CRT |
| 104 | Channel - Actuator | Confirm fan manually (slave) | 1 Bit | 1.1 switch | CW |
| 105 | Channel - Controller | Request fan speed (master) | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 105 | Channel - Controller | Request fan speed (master) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 105 | Channel - Actuator | Request fan speed (slave) | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 105 | Channel - Actuator | Request fan speed (slave) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 106 | Channel - Controller | Confirm fan speed (master) | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 106 | Channel - Controller | Confirm fan speed (master) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 107 | Channel - Controller | Status Controller RHCC | 2 Bytes | 22.101 RHCC status | CRT |
| 108 | Channel - Controller | Status Controller HVAC (master) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 109 | Channel - Controller | Current HVAC operating mode | 1 Byte | 20.102 HVAC mode | CRT |
| 110 | Channel - Controller | Comfort heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 110 | Channel - Controller | Comfort heating/cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 111 | Channel - Controller | Comfort cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 112 | Channel - Controller | Economy heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 113 | Channel - Controller | Economy cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 114 | Channel - Controller | Standby heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 115 | Channel - Controller | Standby cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 116 | Channel - Controller | Building Protection heating setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 117 | Channel - Controller | Building Protection cooling setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 118 | Channel - Actuator | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 119 | Channel - Actuator | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 120 | Channel - Controller | Basic-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 121 | Channel - Controller | Additional-stage heating limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 122 | Channel - Controller | Basic-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 123 | Channel - Controller | Additional-stage cooling limit temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
Parameters (244)
| Parameter | Type | Default |
|---|---|---|
| Hardware_Type | list | HW |
| Device function | list | Standalone |
| Sending and switching delay after bus voltage recovery | unsignedInt 2…255 | 2 |
| Value after sending and switching delay has expired | list | Last value received |
| Limit number of telegrams | list | No |
| Enable Group Object "In operation" | list | No |
| Send value of Group Object "In operation" | list | Value 1 |
| In period | list | 1 s |
| Maximum number of sent telegrams | unsignedInt 1…50 | 20 |
| i-bus® Tool access | list | Full access |
| Sending cycle | time | 60 |
| Device function | list | Controller |
| Switch relay output independently of fan speed (including when fan = 0) | list | Yes |
| Window status receipt | list | Deactivated |
| Window open when | list | Value 1 |
| Dew point status receipt | list | Deactivated |
| Dew point reached when | list | Value 1 |
| Fill level status receipt | list | Deactivated |
| Fill level reached when | list | Value 1 |
| Actual temperature receipt | list | Via physical device input |
| Number of Group Objects Actual temperature | list | 1 |
| Weighting of internal measurement | unsignedInt 0…100 | 100 |
| Weighting of external measurement 1 | unsignedInt 0…100 | 50 |
| Weighting of external measurement 2 | unsignedInt 0…100 | 50 |
| Switching reaction of relay output on bus voltage failure | list | Unchanged |
| Switching behavior of relay output after bus voltage recovery | list | Unchanged |
| Switching behavior of relay output after ETS download | list | Unchanged |
| Operating mode after bus voltage recovery | list | As before bus voltage failure |
| Control value after bus voltage recovery | list | As before bus voltage failure |
| Control value after ETS download | list | Unchanged |
| Control value | unsignedInt 0…100 | 0 |
| Status after ETS download/reset | list | Unchanged |
| Limitation of fan speed | list | Deactivated |
| Cyclical monitoring | list | Deactivated |
| Monitor receipt of Group Object "Operating mode Normal (master)" | list | Deactivated |
| Monitor receipt of Group Objects "Heating/cooling control value" | list | Deactivated |
| Monitor receipt of Group Object "Heating/cooling changeover" | list | Deactivated |
| Monitor receipt of Group Object "Window contact" | list | Deactivated |
| Monitor receipt of Group Object "Dew point alarm" | list | Deactivated |
| Monitor receipt of Group Object "Fill level alarm" | list | Deactivated |
| Forced operation | list | Deactivated |
| Switching reaction of relay output during forced operation | list | Unchanged |
| Switching reaction of relay output during forced operation active "ON" | list | Unchanged |
| Switching reaction of relay output during forced operation active "OFF" | list | Unchanged |
| Control value on forced operation | unsignedInt 0…100 | 0 |
| Control value during forced operation active "ON" | unsignedInt 0…100 | 0 |
| Control value during forced operation active "OFF" | unsignedInt 0…100 | 0 |
| Temperature input monitoring | list | Deactivated |
| Time interval for cyclical monitoring | time | 300 |
| Operating mode on exceeding the monitoring time | list | Unchanged |
| Threshold value fan speed 0 <-> 1 | unsignedInt 0…10 | 1 |
| Threshold value fan speed 1 <-> 2 | unsignedInt 1…100 | 30 |
| Threshold value fan speed 2 <-> 3 | unsignedInt 1…100 | 70 |
| Threshold values hysteresis | unsignedInt 0…20 | 5 |
| Delay between fan speed switchover | unsignedInt 50…5000 | 500 |
| Minimum dwell time at fan speed | unsignedInt 0…600 | 5 |
| Number of fan speeds | list | 3 |
| Fan operating mode | list | Changeover switch |
| Enable automatic mode based on control value | list | Yes |
| Return from manual fan adjustment to automatic mode | list | Via Group Object |
| Start-up behavior | list | No |
| Run-on reaction | list | No |
| Minimum dwell time at switch-on speed | unsignedInt 0…600 | 5 |
| Run-on speed 1 | unsignedInt 0…600 | 20 |
| Run-on speed 2 | unsignedInt 0…600 | 20 |
| Run-on speed 3 | unsignedInt 0…600 | 20 |
| Reset time | time | 3600 |
| Relay output | list | Activated |
| Valve purge | list | Automatic or via Group Object |
| Reaction of output | list | NO contact |
| Send value of Group Object "Status Valve purge" | list | No, update only |
| Value of Group Object "Status Relay" | list | 1: closed, 0: open |
| Purge cycle in weeks | unsignedInt 1…12 | 4 |
| Resistance in ohms at +120 °C | unsignedInt 650…4600 | 3607 |
| Temperature offset | float -10…10 | 0 |
| Cable length, single distance | float 1…100 | 10 |
| Cross-section of conductor Value* 0.01 mm² | unsignedInt 1…150 | 100 |
| Cable resistance (total of fwd and rtn conductor) | unsignedInt 0…10000 | 500 |
| Value is sent from a change of | float 0.2…10 | 1 |
| Send cyclically every | time | 30 |
| Input | list | Deactivated |
| Minimum control value for basic load > 0 | list | Always active |
| Setpoint temperature offset when summer compensation starts | float 0…12.7 | 0 |
| Setpoint temperature offset when summer compensation ends | float 0…12.7 | 6 |
| Type of control value Basic-stage heating | list | PI continuous (0...100%) |
| Control value direction | list | Normal |
| Extended settings | list | No |
| Control value difference for sending control value | list | 5 % |
| I-proportion | unsignedInt 0…255 | 100 |
| Send control value cyclically (0 = deactivated) | unsignedInt 0…60 | 15 |
| P-proportion | float 1…10 | 1.5 |
| Hysteresis | float 0.3…25.5 | 0.5 |
| Maximum control value | unsignedInt 1…100 | 100 |
| Minimum control value (basic load) | unsignedInt 0…100 | 0 |
| Type of control value Additional-stage heating | list | PI continuous (0...100%) |
| Temperature difference from basic-stage heating | float 0…25.5 | 2 |
| Type of control value Basic-stage cooling | list | PI continuous (0...100%) |
| P-proportion | float 1…10 | 2 |
| Type of control value Additional-stage cooling | list | PI continuous (0...100%) |
| Economy cooling increase | unsignedInt 0…15 | 4 |
| Economy cooling setpoint | unsignedInt 10…40 | 29 |
| Comfort heating and cooling setpoint | unsignedInt 10…40 | 21 |
| Comfort heating setpoint | unsignedInt 10…40 | 21 |
| Standby heating reduction | unsignedInt 0…15 | 2 |
| Economy heating reduction | unsignedInt 0…15 | 4 |
| Standby cooling increase | unsignedInt 0…15 | 2 |
| Standby heating setpoint | unsignedInt 10…40 | 19 |
| Economy heating setpoint | unsignedInt 10…40 | 17 |
| Standby cooling setpoint | unsignedInt 10…40 | 27 |
| Setpoint for frost protection (Building Protection heating) | unsignedInt 5…15 | 7 |
| Setpoint for heat protection (Building Protection cooling) | unsignedInt 27…45 | 35 |
| Cycle for sending the setpoint | unsignedInt 5…240 | 15 |
| Max. manual increase in heating mode via KNX | unsignedInt 0…9 | 3 |
| Max. manual reduction in heating mode via KNX | unsignedInt 0…9 | 3 |
| Max. manual increase in cooling mode via KNX | unsignedInt 0…9 | 3 |
| Max. manual reduction in cooling mode via KNX | unsignedInt 0…9 | 3 |
| Operating modes | list | Comfort, Standby, Economy, Building Protection |
| Comfort heating setpoint = Comfort cooling setpoint | list | No |
| Setpoint specification and adjustment | list | Relative |
| Send current setpoint | list | On change |
| Base setpoint is | list | Comfort heating setpoint |
| Reset manual setpoint adjustment via KNX when base setpoint received | list | Yes |
| Reset manual setpoint adjustment via KNX when operating mode changes | list | Yes |
| Reset manual setpoint adjustment via KNX using Group Object | list | Yes |
| Manual operation | list | Enabled |
| Automatic reset after | time | 300 |
| Automatic reset from manual operation to KNX operation | list | No |
| Temperature difference from basic-stage cooling | float 0…25.5 | 2 |
| Activate summer compensation | list | No |
| Starting temperature for summer compensation | signedInt 10…50 | 21 |
| Ending temperature for summer compensation | signedInt 10…50 | 32 |
| Control value on exceeding the monitoring time | unsignedInt 0…100 | 25 |
| Control value on input fault | unsignedInt 0…100 | 25 |
| Send status values | list | On change or on request |
| Send cyclically every | time | 300 |
| Object value request on restart and bus voltage recovery | list | No |
| Additional-stage heating | list | Deactivated |
| Additional-stage cooling | list | Deactivated |
| Type of heating/cooling system | list | 4-pipe |
| Setpoint indication on slave display | list | Absolute |
| Hysteresis for Heating/cooling changeover | float 0.5…10 | 2 |
| Heating/cooling changeover | list | Automatic |
| Automatic adjustment of valve drive | list | No |
| Valve output | list | Thermoelectric (PWM) |
| Open if control value greater than or equal to | unsignedInt 1…100 | 1 |
| Valve drive operating principle, de-energized | list | Closed |
| PWM cycle time | unsignedInt 10…900 | 180 |
| Valve drive opening/closing time | unsignedInt 10…900 | 180 |
| Reversing time | unsignedInt 50…1000 | 500 |
| Reset purge cycle from control value greater than or equal to | unsignedInt 1…99 | 99 |
| Switch on time for valve drive from 0 to 100% | unsignedInt 10…6000 | 120 |
| Number of changes until adjustment | unsignedInt 30…65535 | 500 |
| GP_CD_A0B0011F | text | |
| Convertible from version 0.1 | unsignedInt 0…255 | 1 |
| Send temperature value | list | On change |
| Resistance in ohms at +100 °C | unsignedInt 650…4600 | 3182 |
| Heating PWM cycle | unsignedInt 1…60 | 15 |
| Cooling PWM cycle | unsignedInt 1…60 | 15 |
| Activate temperature limitation | list | No |
| I-proportion at temperature limitation | list | Freeze |
| Limit temperature | unsignedInt 20…50 | 30 |
| Input for temperature limit sensor | list | Via Group Object |
| Limit temperature hysteresis | float 0.5…5 | 1 |
| Limit temperature | unsignedInt 1…30 | 10 |
| Use control value for fan automatic | list | Yes |
| Use control value for fan automatic | list | No |
| Switch fan speed via 1-bit Group Objects | list | Deactivated |
| Enable manual valve override | list | No |
| GP_CD_A0B1011F | text | |
| Operating mode after ETS download/reset | list | Heating |
| Cycle for sending the room temperature (0 = deactivated) | unsignedInt 0…255 | 15 |
| Temperature change for sending current room temperature | float 0.1…10 | 0.5 |
| Data point type, manual setpoint adjustment | list | DPT 9.001 (absolute temperature value) |
| Data point type, manual setpoint adjustment | list | DPT 9.002 (relative temperature value) |
| Data point type, manual fan adjustment | list | DPT 5.001 (percentage value) |
| Send inactive control values cyclically | list | No |
| Comfort cooling setpoint | unsignedInt 10…40 | 25 |
| Basic-stage heating | list | Fan coil unit: Water heating coil |
| Basic-stage heating | list | Fan coil unit |
| Basic-stage cooling | list | Fan coil unit: Water cooling coil |
| Basic-stage cooling | list | Fan coil unit |
| Activate additional-stage cooling via | list | Group Object |
| Activate additional-stage heating via | list | Internal output B (valve) |
| Activate additional-stage heating via | list | Internal relay output |
| Activate additional-stage heating via | list | Internal output A (valve) |
| Activate basic-stage cooling via | list | Internal output B (valve) |
| Activate basic-stage cooling via | list | Internal output A (valve) |
| Activate basic-stage heating via | list | Internal output A (valve) |
| Activate basic-stage heating via | list | Internal relay output |
| Fan behavior on bus voltage failure | list | Unchanged |
| Fan speed after bus voltage recovery | list | Unchanged |
| Fan speed after ETS download | list | Unchanged |
| Fan speed during forced operation | list | Unchanged |
| Fan speed during forced operation active "ON" | list | Unchanged |
| Fan speed during forced operation active "OFF" | list | Unchanged |
| Operating mode on exceeding the monitoring time | list | Building Protection |
| Switch on at fan speed | list | 2 |
| Switch on at fan speed | list | 3 |
| Limitation 1 | list | Off, 1, 2 |
| Limitation 1 | list | Off, 1 |
| Limitation 1 | list | Off, 1, 2, 3 |
| Limitation 2 | list | Off, 1 |
| Limitation 2 | list | Off, 1, 2, 3 |
| Limitation 2 | list | Off, 1, 2 |
| Limitation 3 | list | Off, 1 |
| Limitation 3 | list | Off, 1, 2, 3 |
| Limitation 3 | list | Off, 1, 2 |
| Valve output | list | Motor-driven (3-point) |
| Input | list | Analog room control unit |
| Scan input after download, ETS reset or bus voltage recovery | list | Yes |
| Maximum setpoint increase | unsignedInt 0…5 | 3 |
| Window open when | list | Contact open |
| Dew point reached when | list | Contact open |
| Fill level reached when | list | Contact open |
| Send status values | list | On change |
| Internal connection | list | No |
| Cable error compensation | list | None |
| Enable Group Object "Block input" | list | No |
| Input on operation | list | Closed |
| Temperature sensor type | list | PT1000 [-30...+110 C] |
| Activate minimum signal duration | list | No |
| Distinction between long and short operation | list | No |
| On Group Object value | list | 0 or 1 |
| KTY type | list | KT 100/110/130 |
| Maximum setpoint reduction | unsignedInt 0…5 | 3 |
| Reaction on event 1 | list | On |
| Reaction on event 0 | list | Off |
| NTC type | list | NTC 10-01 [-15...+100 °C] |
| Filter | list | Inactive |
| Resistance in ohms at -20 °C | unsignedInt 650…4600 | 1247 |
| When closing the contact | float 0…100 | 1 |
| Connect analog room control unit to physical device input | list | No |
| Resistance in ohms at 0 °C | unsignedInt 650…4600 | 1495 |
| Resistance in ohms at +20 °C | unsignedInt 650…4600 | 1772 |
| When opening the contact | float 0…100 | 1 |
| Resistance in ohms at +40 °C | unsignedInt 650…4600 | 2080 |
| Resistance in ohms at +60 °C | unsignedInt 650…4600 | 2417 |
| Long operation after | float 1…10 | 1 |
| Resistance in ohms at +80 °C | unsignedInt 650…4600 | 2785 |
| Operating mode after bus voltage recovery or ETS download | list | Comfort |
| Basic load active when controller off | list | No |
| Automatic reset of manual relay override to controller operation after | time | 1800 |
| Send value of Group Object "Activate/deactivate fan automatic" | list | 1: activate, 0: deactivate |
| Data point type, Group Object "Status Fan speed" | list | DPT 5.001 (percentage value) |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Fan Coil Controller, PWM, 3-speed, manual operation/1.3 1.3 latest | $A0B1 | 2BE2 | 2026-11-25 | 350 KB | Download |
About this file
This is the official ETS product database for the ABB AG - STOTZ-KONTAKT FCC/S1.1.2.1 Fan Coil Controller,PWM,3-speed,manual operation,MDRC (2CDG 110 211 R0011), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from ABB AG - STOTZ-KONTAKT
- PS5604-KNX AC500 1SAP 195 800 R0101
- RDF/A x.1 RTR fan coil with display, SM 2CDG 006 138 R001x
- ES/S4.1.2.1 Electronic Switch Actuator,4f,1A,MDRC 2CDG 110 058 R0011
- ES/S8.1.2.1 Electronic Switch Actuator,8f,1A,MDRC 2CDG 110 059 R0011
- VAA/S6.230.2.1 Valve Drive Actuator, 6f, 230V,MDRC 2CDG 110 116 R0011
- VAA/S12.230.2.1 Valve Drive Actuator, 12f, 230V 2CDG 110 117 R0011
- FCL/S1.6.1.1 Blower Actuator, 1f, 6 A, MDRC 2CDG 110 163 R0011
- FCL/S2.6.1.1 Blower Actuator, 2f, 6 A, MDRC 2CDG 110 164 R0011
- AC/S1.1.1 Application Controller,Basic 2CDG 110 205 R0011
- AC/S1.2.1 Application Controller,BACnet 2CDG 110 206 R0011
- FCC/S1.4.1.1 Fan Coil Controller,PWM,3-speed,2-pipe,MDRC 2CDG 110 209 R0011
- FCC/S1.1.1.1 Fan Coil Controller,PWM,3-speed,MDRC 2CDG 110 210 R0011