FCL/S1.6.1.1 Blower Actuator, 1f, 6 A, MDRC 2CDG 110 163 R0011
ABB AG - STOTZ-KONTAKT · Order number 2CDG 110 163 R0011 · Heating, Ventilation and Air Conditioning › Blower Actuators
Switch Blower 1f6A/1.3a
Download .knxprod Switch Blower 1f6A/1.3a 1.3 · 161 KB
Product
| Manufacturer | ABB AG - STOTZ-KONTAKT |
|---|---|
| Product name | FCL/S1.6.1.1 Blower Actuator, 1f, 6 A, MDRC |
| Order number | 2CDG 110 163 R0011 |
| Hardware | FCL/S1.6.1.1 |
| Medium | Twisted Pair |
| Bus current (mA) | 12 |
| Rail mounted | Yes |
| Width (mm) | 72 |
| Registration | Certified · 2014-01-20 |
| Languages | en-US, de-DE, es-ES, fr-FR, it-IT, nl-NL, pl-PL, ru-RU |
| Catalog entry | M-0002_H-2CDG.20110.20163.20R0011-1_HP-A08F-13-879B_CI-2CDG.20110.20163.20R0011-1 |
| Fingerprint | 879B |
| SHA-256 | 5c9d05ccf3ea0df5ac04f0f34b7daf9ca24114a08b469c5f732ec62170a84ce3 |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: Switch Blower 1f6A/1.3a 1.3
| Application number | $A08F |
|---|---|
| Version | 1.3 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Parameters | 117 |
| Group objects | 52 |
Group objects (52)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | System | In Operation | 1 Bit | 1.2 boolean | CT |
| 1 | General | Request status values | 1 Bit | CW | |
| 2 | Dummy | 1 Bit | 1.1 switch | ||
| 3 | Dummy | 1 Bit | 1.1 switch | ||
| 4 | Dummy | 1 Bit | 1.1 switch | ||
| 5 | Dummy | 1 Bit | 1.1 switch | ||
| 6 | Dummy | 1 Bit | 1.1 switch | ||
| 7 | Dummy | 1 Bit | 1.1 switch | ||
| 8 | Dummy | 1 Bit | 1.1 switch | ||
| 9 | Dummy | 1 Bit | 1.1 switch | ||
| 10 | Fan A | Fan speed switch | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 11 | Fan A | Switch | 1 Bit | 1.1 switch | CW |
| 11 | Fan A | Switch speed 1 | 1 Bit | 1.1 switch | CW |
| 12 | Fan A | Switch speed 2 | 1 Bit | 1.1 switch | CW |
| 13 | Fan A | Switch speed 3 | 1 Bit | 1.1 switch | CW |
| 14 | Fan A | Fan speed up/down | 1 Bit | CW | |
| 15 | Fan A | Status Fan ON/OFF | 1 Bit | 1.1 switch | CT |
| 16 | Fan A | Status Fan speed | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 17 | Fan A | Status Fan speed 1 | 1 Bit | 1.1 switch | CRT |
| 18 | Fan A | Status Fan speed 2 | 1 Bit | 1.1 switch | CRT |
| 19 | Fan A | Status Fan speed 3 | 1 Bit | 1.1 switch | CRT |
| 20 | Fan A | Run-on | 1 Bit | 1.3 enable | CW |
| 21 | Fan A | Limitation 1 | 1 Bit | 1.3 enable | CW |
| 22 | Fan A | Limitation 2 | 1 Bit | 1.3 enable | CW |
| 23 | Fan A | Limitation 3 | 1 Bit | 1.3 enable | CW |
| 24 | Fan A | Limitation 4 | 1 Bit | 1.3 enable | CW |
| 25 | Fan A | Forced operation | 1 Bit | 1.3 enable | CW |
| 26 | Fan A | Automatic ON/OFF | 1 Bit | 1.3 enable | CW |
| 27 | Fan A | Status Automatic | 1 Bit | 1.3 enable | CRT |
| 28 | Fan A | Status Byte Mode | 1 Byte | CRT | |
| 29 | Fan A | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 29 | Fan A | Control value A | 1 Byte | 5.1 percentage (0..100%) | CW |
| 30 | Fan A | Control value B | 1 Byte | 5.1 percentage (0..100%) | CW |
| 31 | Fan A | Toggle control value A/B | 1 Bit | 1.1 switch | CW |
| 32 | Fan A | Fault control value | 1 Bit | CRT | |
| 33 | Dummy | 1 Bit | 1.1 switch | ||
| 34 | Dummy | 1 Bit | 1.1 switch | ||
| 35 | Dummy | 1 Bit | 1.1 switch | ||
| 36 | Dummy | 1 Bit | 1.1 switch | ||
| 37 | Dummy | 1 Bit | 1.1 switch | ||
| 38 | Dummy | 1 Bit | 1.1 switch | ||
| 39 | Dummy | 1 Bit | 1.1 switch | ||
| 40 | Output B | Switch | 1 Bit | 1.1 switch | CW |
| 41 | Output B | Permanent ON | 1 Bit | 1.3 enable | CW |
| 42 | Output B | Disable function Time | 1 Bit | 1.3 enable | CW |
| 43 | Output B | Status Switch | 1 Bit | 1.1 switch | CRT |
| 44 | Dummy | 1 Bit | 1.1 switch | ||
| 45 | Dummy | 1 Bit | 1.1 switch | ||
| 46 | Dummy | 1 Bit | 1.1 switch | ||
| 47 | Dummy | 1 Bit | 1.1 switch | ||
| 48 | Dummy | 1 Bit | 1.1 switch | ||
| 49 | Dummy | 1 Bit | 1.1 switch |
Parameters (88)
| Parameter | Type | Default |
|---|---|---|
| Sending and switching delay after bus voltage recovery in s [2…255] | unsignedInt 2…255 | 2 |
| Rate of telegrams | list | Not limited |
| Send communication object "In operation" | list | No |
| Telegram is repeated every in s [1...65,535] | unsignedInt 1…65535 | 60 |
| Enable communication object "Request status values" 1 bit | list | No |
| Request with object value | list | 1 |
| _PD_NEIN | list | Yes |
| __Allgemein | text | |
| Output A | list | Enable as fans |
| Output B | list | Block |
| Fan type | list | Multi-level |
| Limit fan speeds to 2 | list | No |
| Fan operating mode (note technical data of fan!) | list | Step switch |
| Delay between speed switchover in ms [50...5,000] | unsignedInt 50…5000 | 500 |
| Fan speed on bus voltage failure | list | Unchanged |
| Fan speed on bus voltage recovery | list | Unchanged |
| Enable communication object "Forced operation" 1 bit | list | No |
| Forced operation on object value | list | 1 |
| Limitation on forced operation | list | Unchanged |
| Enable automatic operation | list | No |
| Enable direct operation | list | No |
| Set startup/run-on | list | No |
| Standardbegrenzung für 1-stufig DUMMY | list | 1, OFF |
| Dummy | list | Step switch |
| Fan on bus voltage failure | list | Unchanged |
| Fan on bus voltage recovery | list | Unchanged |
| Function Time on ON | list | None |
| Time in s [1...65,535] | unsignedInt 1…65535 | 20 |
| Time in s [1...65,535 x 0.1] | unsignedInt 1…65535 | 20 |
| Function Time on OFF | list | None |
| Reaction on forced operation | list | ON |
| _FAN | text | |
| Enable communication objects "Status Fan speed x" 1 bit | list | No |
| Meaning | list | Current fan speed |
| Send object values | list | Only after changing |
| Enable communication object "Status Fan speed" 1 byte | list | No |
| Send object value | list | Only after changing |
| Enable communication object "Status Byte mode" 1 byte | list | No |
| Enable communication object "Status Fan On/Off" 1 bit | list | No |
| Enable communication object "Status Automatic" 1 bit | list | No |
| Objekt "Automatik EIN/AUS" freigeben DUMMY | list | Yes |
| Object value "Automatic On/Off" switch on to the automatic | list | 1 |
| Threshold value OFF <-> speed 1 in % [1...100] | unsignedInt 1…100 | 10 |
| Threshold value speed 1 <-> speed 2 in % [1...100] | unsignedInt 1…100 | 100 |
| Threshold value speed 2 <-> speed 3 in % [1...100] | unsignedInt 1…100 | 100 |
| Hysteresis threshold value in % +/- [0...20 %] | unsignedInt 0…20 | 5 |
| Minimum dwell period in fan speed in s [0...65,535] | unsignedInt 0…65535 | 0 |
| Number of control value inputs | list | 1 |
| select by... | list | Largest value |
| Activate monitoring control values | list | No |
| Monitoring time in s [30...65,535] | unsignedInt 30…65535 | 120 |
| Function of monitoring | list | Monitoring active and inactive control values |
| Send object value "Fault control value" | list | Only after changing |
| Set control value during fault | list | No |
| Control value in % [0...100] | unsignedInt 0…100 | 30 |
| Enable limitations | list | No |
| Speed with limitation 1 | list | 3, 2, 1, OFF |
| Speed with limitation 2 | list | Unchanged |
| Speed with limitation 3 | list | 3, 2, 1, OFF |
| Speed with limitation 4 | list | Unchanged |
| Enable communication objects "Switch speed x" 1 bit | list | Yes |
| Enable communication object "Fan speed up/down" 1 bit | list | No |
| Enable communication object "Fan speed switch" 1 byte | list | No |
| Start-up behavior | list | No |
| Switch on over fan speed | list | 3 |
| Minimum dwell period in switch on fan stage s [1...65,535] | unsignedInt 1…65535 | 20 |
| Run-on behavior | list | No |
| Run-on stage 3 in s [0...65,535] | unsignedInt 0…65535 | 20 |
| Run-on stage 2 in s [0...65,535] | unsignedInt 0…65535 | 20 |
| Run-on stage 1 in s [0...65,535] | unsignedInt 0…65535 | 20 |
| Threshold value OFF <-> ON in % [1...100] | unsignedInt 1…100 | 10 |
| Fan with limitation 1 | list | Inactive |
| Fan with limitation 2 | list | Unchanged |
| Fan with limitation 3 | list | Inactive |
| Fan with limitation 4 | list | Unchanged |
| Reaction of output | list | Normally opened contact |
| Contact position on bus voltage failure | list | Unchanged |
| Object value "Switch" on bus voltage recovery | list | Don't write |
| Enable function Time | list | No |
| Enable communication object "Status Switch" 1 bit | list | No |
| Object value of contact position | list | 1 = closed, 0 = open |
| Dummybytes Ausgang | text | |
| Function Time | list | Staircase light |
| Extending staircase lighting by multiple operation ["pumping up"] | list | Yes (retriggerable) |
| Staircase lighting time in s [1…65,535] | unsignedInt 1…65535 | 30 |
| Staircase lighting can be switched | list | ON with 1 and OFF with 0 |
| Restart of staircase time after end of permanent ON | list | No |
| Object value "Disable function Time" after a download | list | 0 = enable function Time |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Switch Blower 1f6A/1.3a 1.3 latest | $A08F | 879B | 2026-11-25 | 161 KB | Download |
About this file
This is the official ETS product database for the ABB AG - STOTZ-KONTAKT FCL/S1.6.1.1 Blower Actuator, 1f, 6 A, MDRC (2CDG 110 163 R0011), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from ABB AG - STOTZ-KONTAKT
- PS5604-KNX AC500 1SAP 195 800 R0101
- RDF/A x.1 RTR fan coil with display, SM 2CDG 006 138 R001x
- ES/S4.1.2.1 Electronic Switch Actuator,4f,1A,MDRC 2CDG 110 058 R0011
- ES/S8.1.2.1 Electronic Switch Actuator,8f,1A,MDRC 2CDG 110 059 R0011
- VAA/S6.230.2.1 Valve Drive Actuator, 6f, 230V,MDRC 2CDG 110 116 R0011
- VAA/S12.230.2.1 Valve Drive Actuator, 12f, 230V 2CDG 110 117 R0011
- FCL/S2.6.1.1 Blower Actuator, 2f, 6 A, MDRC 2CDG 110 164 R0011
- AC/S1.1.1 Application Controller,Basic 2CDG 110 205 R0011
- AC/S1.2.1 Application Controller,BACnet 2CDG 110 206 R0011
- FCC/S1.4.1.1 Fan Coil Controller,PWM,3-speed,2-pipe,MDRC 2CDG 110 209 R0011
- FCC/S1.1.1.1 Fan Coil Controller,PWM,3-speed,MDRC 2CDG 110 210 R0011
- FCC/S1.1.2.1 Fan Coil Controller,PWM,3-speed,manual operation,MDRC 2CDG 110 211 R0011