ABB AG - BUSCH-JAEGER 6164/40-101 6164/40-101 Elektronischer Schaltaktor 4f,1A,REG

6164/40-101 Elektronischer Schaltaktor 4f,1A,REG 6164/40-101

ABB AG - BUSCH-JAEGER · Order number 6164/40-101 · Heating, Ventilation and Air Conditioning › Valve Drive Actuators

Download .knxprod Switching Valve Drive 4f 1A/2.0a 2.0 · 498 KB

Product

ManufacturerABB AG - BUSCH-JAEGER
Product name6164/40-101 Elektronischer Schaltaktor 4f,1A,REG
Order number6164/40-101
Product text6164/40-101 Electronic Switch Actuator,4f,1A,MDRC
HardwareES/S4.1.2.1
MediumTwisted Pair
Bus current (mA)7
Rail mountedYes
Width (mm)72
RegistrationRegistered
Languagesde-DE, en-US
Catalog entryM-0007_H-2CDG.20110.20058.20R0011-1-O0002_HP-A074-20-E164-O0002_CI-6164.2F40.2D101-1
FingerprintE164
SHA-256bb9ab8092c049b41ad81ecc1c4ed618d903716ca41ca42713d0bd2cbdf1179d2
First seen2026-11-25
MarketsAustria, Belgium, Germany, Netherlands

Application program: Switching Valve Drive 4f 1A/2.0a 2.0

Application number$A074
Version2.0
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Parameters728
Group objects183
Group objects (183)
NoNameFunctionSizeDPTFlags
0GeneralIn operation1 Bit1.2 booleanCRT
1GeneralRequest status values1 BitCWT
2GeneralBlock manual operation1 Bit1.1 switchCW
3GeneralStatus of manual operation1 Bit1.3 enableCRT
4Object 4Dummy1 Bit
5Object 5Dummy1 Bit
6Object 6Dummy1 Bit
7Object 7Dummy1 Bit
8Object 8Dummy1 Bit
9Object 9Dummy1 Bit
10Output ASwitch1 Bit1.1 switchCW
10Output ABControl value, cont. (3-point)1 Byte5.1 percentage (0..100%)CW
10Output AControl value, cont. (PWM)1 Byte5.1 percentage (0..100%)CW
10Output AControl value1 Bit1.1 switchCW
11Output AStatus control value1 Byte5.1 percentage (0..100%)CRT
11Output AStatus control value1 BitCRT
11Output AStatus switch1 Bit1.1 switchCRT
11Output ABStatus control value1 BitCRT
11Output ABStatus control value1 Byte5.1 percentage (0..100%)CRT
12Output AFault control value1 BitCRT
12Output ABFault control value1 BitCRT
12Output APermanent ON1 Bit1.1 switchCRWT
13Output ATrigger valve purge1 Bit1.3 enableCW
13Output ADisable function time1 Bit1.3 enableCW
13Output ABTrigger valve purge1 Bit1.3 enableCW
14Output AStatus valve purge1 Bit1.3 enableCRT
14Output ABStatus valve purge1 Bit1.3 enableCRT
14Output AStaircase lighting duration2 BytesCRW
15Output AStaircase lighting warning1 BitCT
16Output A8 bit scene1 ByteCW
17Output ALogical connection 11 Bit1.2 booleanCW
18Output ALogical connection 21 Bit1.2 booleanCW
19Output AThreshold2 Bytes7.1 pulsesCW
19Output AThreshold1 Byte5.10 counter pulses (0..255)CW
20Output ASet threshold 12 Bytes7.1 pulsesCW
20Output ASet threshold 11 Byte5.10 counter pulses (0..255)CW
21Object 21Dummy1 Bit
22Output APriority 1, Forced operation2 Bit2.1 switch controlCW
22Output APriority 1, Forced operation1 Bit1.1 switchCW
22Output APriority 1, Block1 Bit1.1 switchCW
22Output ABPriority 1, Block1 Bit1.1 switchCW
22Output ABPriority 1, Forced operation1 Bit1.1 switchCW
23Output APriority 2, Forced operation1 Bit1.1 switchCW
23Output APriority 2, Block1 Bit1.1 switchCW
23Output APriority 2, Forced operation2 Bit2.1 switch controlCW
23Output ABPriority 2, Block1 Bit1.1 switchCW
23Output ABPriority 2, Forced operation1 Bit1.1 switchCW
24Output APriority 3, Forced operation2 Bit2.1 switch controlCW
24Output APriority 3, Forced operation1 Bit1.1 switchCW
24Output APriority 3, Block1 Bit1.1 switchCW
24Output ABPriority 3, Forced operation1 Bit1.1 switchCW
24Output ABPriority 3, Block1 Bit1.1 switchCW
25Object 25Dummy1 Bit
26Output AStatus byte1 ByteCRT
26Output ABStatus byte1 ByteCRT
27Output AFault (overload/short-circuit)1 BitCRT
27Output ABFault (overload/short-circuit)1 BitCRT
28Output AReset fault1 BitCWT
28Output ABReset fault1 BitCWT
29Output ASupply voltage failure1 BitCRT
29Output ABSupply voltage failure1 BitCRT
30Output BControl value, cont. (PWM)1 Byte5.1 percentage (0..100%)CW
30Output BControl value1 Bit1.1 switchCW
30Output BSwitch1 Bit1.1 switchCW
31Output BStatus control value1 Byte5.1 percentage (0..100%)CRT
31Output BStatus control value1 BitCRT
31Output BStatus switch1 Bit1.1 switchCRT
32Output BFault control value1 BitCRT
32Output BPermanent ON1 Bit1.1 switchCRWT
33Output BTrigger valve purge1 Bit1.3 enableCW
33Output BDisable function time1 Bit1.3 enableCW
34Output BStaircase lighting duration2 BytesCRW
34Output BStatus valve purge1 Bit1.3 enableCRT
35Output BStaircase lighting warning1 BitCT
36Output B8 bit scene1 ByteCW
37Output BLogical connection 11 Bit1.2 booleanCW
38Output BLogical connection 21 Bit1.2 booleanCW
39Output BThreshold2 Bytes7.1 pulsesCW
39Output BThreshold1 Byte5.10 counter pulses (0..255)CW
40Output BSet threshold 12 Bytes7.1 pulsesCW
40Output BSet threshold 11 Byte5.10 counter pulses (0..255)CW
41Object 41Dummy1 Bit
42Output BPriority 1, Forced operation2 Bit2.1 switch controlCW
42Output BPriority 1, Forced operation1 Bit1.1 switchCW
42Output BPriority 1, Block1 Bit1.3 enableCW
42Output BPriority 1, Block1 Bit1.1 switchCW
43Output BPriority 2, Forced operation2 Bit2.1 switch controlCW
43Output BPriority 2, Forced operation1 Bit1.1 switchCW
43Output BPriority 2, Block1 Bit1.1 switchCW
44Output BPriority 3, Forced operation2 Bit2.1 switch controlCW
44Output BPriority 3, Forced operation1 Bit1.1 switchCW
44Output BPriority 3, Block1 Bit1.1 switchCW
45Object 45Dummy1 Bit
46Output BStatus byte1 ByteCRT
47Output BFault (overload/short-circuit)1 BitCRT
48Output BReset fault1 BitCWT
49Output BSupply voltage failure1 BitCRT
50Output CControl value, cont. (PWM)1 Byte5.1 percentage (0..100%)CW
50Output CControl value1 Bit1.1 switchCW
50Output CSwitch1 Bit1.1 switchCW
50Output CDControl value, cont. (3-point)1 Byte5.1 percentage (0..100%)CW
51Output CStatus control value1 BitCRT
51Output CStatus switch1 Bit1.1 switchCRT
51Output CStatus control value1 Byte5.1 percentage (0..100%)CRT
51Output CDStatus control value1 Byte5.1 percentage (0..100%)CRT
51Output CDStatus control value1 BitCRT
52Output CFault control value1 BitCRT
52Output CDFault control value1 BitCRT
52Output CPermanent ON1 Bit1.1 switchCRWT
53Output CTrigger valve purge1 Bit1.3 enableCW
53Output CDTrigger valve purge1 Bit1.3 enableCW
53Output CDisable function time1 Bit1.3 enableCW
54Output CStaircase lighting duration2 BytesCRW
54Output CDStatus valve purge1 Bit1.3 enableCRT
54Output CStatus valve purge1 Bit1.3 enableCRT
55Output CStaircase lighting warning1 BitCT
56Output C8 bit scene1 ByteCW
57Output CLogical connection 11 Bit1.2 booleanCW
58Output CLogical connection 21 Bit1.2 booleanCW
59Output CThreshold2 Bytes7.1 pulsesCW
59Output CThreshold1 Byte5.10 counter pulses (0..255)CW
60Output CSet threshold 12 Bytes7.1 pulsesCW
60Output CSet threshold 11 Byte5.10 counter pulses (0..255)CW
61Object 61Dummy1 Bit
62Output CPriority 1, Forced operation2 Bit2.1 switch controlCW
62Output CPriority 1, Forced operation1 Bit1.1 switchCW
62Output CPriority 1, Block1 Bit1.1 switchCW
62Output CDPriority 1, Block1 Bit1.1 switchCW
62Output CDPriority 1, Forced operation1 Bit1.1 switchCW
63Output CPriority 2, Forced operation2 Bit2.1 switch controlCW
63Output CPriority 2, Forced operation1 Bit1.1 switchCW
63Output CPriority 2, Block1 Bit1.1 switchCW
63Output CDPriority 2, Block1 Bit1.1 switchCW
63Output CDPriority 2, Forced operation1 Bit1.1 switchCW
64Output CPriority 3, Forced operation2 Bit2.1 switch controlCW
64Output CPriority 3, Forced operation1 Bit1.1 switchCW
64Output CPriority 3, Block1 Bit1.1 switchCW
64Output CDPriority 3, Block1 Bit1.1 switchCW
64Output CDPriority 3, Forced operation1 Bit1.1 switchCW
65Object 65Dummy1 Bit
66Output CStatus byte1 ByteCRT
66Output CDStatus byte1 ByteCRT
67Output CFault (overload/short-circuit)1 BitCRT
67Output CDFault (overload/short-circuit)1 BitCRT
68Output CReset fault1 BitCWT
68Output CDReset fault1 BitCWT
69Output CSupply voltage failure1 BitCRT
69Output CDSupply voltage failure1 BitCRT
70Output DControl value, cont. (PWM)1 Byte5.1 percentage (0..100%)CW
70Output DControl value1 Bit1.1 switchCW
70Output DSwitch1 Bit1.1 switchCW
71Output DStatus control value1 Byte5.1 percentage (0..100%)CRT
71Output DStatus control value1 BitCRT
71Output DStatus switch1 Bit1.1 switchCRT
72Output DFault control value1 BitCRT
72Output DPermanent ON1 Bit1.1 switchCRWT
73Output DTrigger valve purge1 Bit1.3 enableCW
73Output DDisable function time1 Bit1.3 enableCW
74Output DStatus valve purge1 Bit1.3 enableCRT
74Output DStaircase lighting duration2 BytesCRW
75Output DStaircase lighting warning1 BitCT
76Output D8 bit scene1 ByteCW
77Output DLogical connection 11 Bit1.2 booleanCW
78Output DLogical connection 21 Bit1.2 booleanCW
79Output DThreshold2 Bytes7.1 pulsesCW
79Output DThreshold1 Byte5.10 counter pulses (0..255)CW
80Output DSet threshold 12 Bytes7.1 pulsesCW
80Output DSet threshold 11 Byte5.10 counter pulses (0..255)CW
81Object 81Dummy1 Bit
82Output DPriority 1, Forced operation2 Bit2.1 switch controlCW
82Output DPriority 1, Forced operation1 Bit1.1 switchCW
82Output DPriority 1, Block1 Bit1.1 switchCW
83Output DPriority 2, Forced operation2 Bit2.1 switch controlCW
83Output DPriority 2, Forced operation1 Bit1.1 switchCW
83Output DPriority 2, Block1 Bit1.1 switchCW
84Output DPriority 3, Forced operation2 Bit2.1 switch controlCW
84Output DPriority 3, Forced operation1 Bit1.1 switchCW
84Output DPriority 3, Block1 Bit1.1 switchCW
85Object 85Dummy1 Bit
86Output DStatus byte1 ByteCRT
87Output DFault (overload/short-circuit)1 BitCRT
88Output DReset fault1 BitCWT
89Output DSupply voltage failure1 BitCRT
Parameters (146)
ParameterTypeDefault
Sending delay after bus voltage recovery in s [2...255]unsignedInt 2…2552
Limit number of telegramslistno
DUMMY -> NO_TEXTunsignedInt 0…25510
DUMMY -> NO_TEXTunsignedInt 0…6553556
Max. number of sent telegrams [1...255]unsignedInt 1…25520
in periodlist1 s
Send communication object "In operation"listno
DUMMY -> NO_TEXTunsignedInt 0…655350
Sending cycle time in s [1...65,535]unsignedInt 1…6553560
Enable communication object "Request status values" 1 bitlistno
Request with object valuelist1
DUMMY -> NO_TEXTunsignedInt 0…00
DUMMY -> NO_TEXTlistno
Manual operationlistenabled
Object value "Block manual operation" after downloadlistunchanged
Automatic reset of manual operation to KNX operationlistafter 3 minutes
Enable communication object "Status man. operation" 1 bitlistno
Send object valuelistafter a change
Operation mode output A and BlistIndividual
Output Alistopen
Output Blistclose
Output AlistValve drive, thermoelectric (PWM)
Output BlistValve drive, thermoelectric (PWM)
Operation mode output C and DlistIndividual
Output ClistValve drive, thermoelectric (PWM)
Output DlistValve drive, thermoelectric (PWM)
Output Clistopen
Output Dlistclose
DUMMY -> NO_TEXTunsignedInt 5…55
Type of valve drivelistde-energized closed
Reaction on bus voltage failure and downloadlistunchanged
DUMMY -> NO_TEXTunsignedInt 1…255255
Control value in % [0...100]unsignedInt 0…10030
Reaction after bus voltage recoverylistunchanged
Control value in % [0...100]unsignedInt 0…1000
Control value is received aslist1 byte
Set cycle time PWM, open./closing time for contr. value of actuator in %list<--- NOTE
Convert control value tolistPWM (pulse width modulated)
OPEN at control value greater or equal in % [1...100]unsignedInt 1…1001
Cycle time of PWM in s [10...6,000]unsignedInt 10…6000180
Opening time of valve drive in s [10...6,000]unsignedInt 10…6000180
Closing time of valve drive in s [10...6,000]unsignedInt 10…6000180
Activate monitoring control valueslistno
Control period in s [30...65,535]unsignedInt 30…65535120
Send object value (Object "Control value fault" 1 bit)listafter a change
Control value after control faultlistunchanged
Enable function safetylistno
Enable communication object "Status control value" 1 bit/bytelistno
Data typelist1 byte
Object value with control > 0list1
Enable valve purgelistno
Enable communication object "Status valve purge" 1 bitlistno
Duration of valve purge in min [1...255]unsignedInt 1…25510
Automatic valve purgelistno
Purge cycle in weeks [1...12]unsignedInt 1…126
Reset purge cycle from control value in % [1...99]unsignedInt 1…9999
DUMMY -> NO_TEXTunsignedInt 1…255111
Enable characteristic adjustmentlistno
Safety priority 1listinactive
Control value on forced operation in % [0...100]unsignedInt 0…10050
Trigger with object valuelist1
Control period in seconds [1...65,535, 0 = inactive]unsignedInt 0…655350
Object value "Priority 1, Forced operation" after downloadlistunchanged
Object value "Priority 1, Block" after downloadlistunchanged
Safety priority 2listinactive
Object value "Priority 2, Forced operation" after downloadlistunchanged
Object value "Priority 2, Block" after downloadlistunchanged
Safety priority 3listinactive
Object value "Priority 3, Forced operation" after downloadlistunchanged
Object value "Priority 3, Block" after downloadlistunchanged
Prio END valveunsignedInt 129…1291
Value pair 1 Control value in % [0...100]unsignedInt 0…1000
Value pair 2 Control value in % [0...100]unsignedInt 0…100100
Control value in % [0...100]unsignedInt 0…100100
Enable value pair 3listno
Value pair 3 Control value in % [0...100]unsignedInt 0…10050
Control value in % [0...100]unsignedInt 0…10050
Enable value pair 4listno
Value pair 4 Control value in % [0...100]unsignedInt 0…10050
Reaction of outputlistN/O
Status response of contact positionlistno
Invertedlistno: 0 = OFF, 1 = ON
DUMMY -> NO_TEXTunsignedInt 1…11
Value object "Switch" on bus voltage recoverylistnot write
Enable function time: Delay, staircase lighting, flashinglistno
"Disable function time" after downloadlistunchanged
Enable function scene (8 bit)listno
Enable function logiclistno
Enable function thresholdlistno
Function TimelistStaircase lighting
Staircase lighting duration in s [1...65,535]unsignedInt 1…6553530
Extending staircase lighting by multiple operation ["pumping up"]listno (not retriggerable)
Staircase lighting can be switchedlistON with 1 and OFF with 0
Warning before end of staircase lightinglistno
Warning time in sec. [0...65,535] add to duration of staircase lightingunsignedInt 0…6553545
Staircase lighting duration changeable via object "Staircase lighting duration"listno
Object value "Staircase lighting duration" after downloadlistunchanged
Restart of staircase time after end of permanent ONlistno
Delay for switching ON in s [1...65,535]unsignedInt 1…6553530
Delay for switching OFF in s [1...65,535]unsignedInt 1…655355
Flash if communication object "Switch" islistON (1) or OFF (0)
Time for ON in s [0...65,535]unsignedInt 0…655355
Time for OFF in s [0...65,535]unsignedInt 0…655355
Number of impulses [1...100]unsignedInt 1…1005
Contact position after flashinglistupdate
Set standard value after the downloadlistyes
Assignment to scene number [No. 1...64, 0 = no assignment]unsignedInt 0…640
Standard valuelistON
Logical connection 1listinactive
Function of object Logical connection 1listAND
GATE disabled, if object value "Logical connection 1" islist1
Result is invertedlistno
Object value "Logical connection 1" after ETS resetlist1
Object value "Logical connection 1” after downloadlistunchanged
Logical connection 2listinactive
Function of object Logical connection 2listAND
GATE disabled, if object value "Logical connection 2" islist1
Object value "Logical connection 2" after ETS resetlist1
Object value "Logical connection 2” after downloadlistunchanged
Contact position if forced operationlistON
Contact position after all priorities endlistunchanged
ValuelistON
Data type of object "Threshold input"list1 byte (0...255)
Threshold 1 change via buslistno
Overwrite object value after downloadlistno
Threshold value 1 [0...255]unsignedInt 0…25580
Threshold value 2 [0...255]unsignedInt 0…255160
Threshold value 1 [0...65,535]unsignedInt 0…6553520000
Threshold value 2 [0...65,535]unsignedInt 0…6553540000
Threshold values define hysteresislistno
Object value < lower thresholdlistunchanged
Lower threshold <= object value <= upper thresholdlistunchanged
Object value > upper thresholdlistOFF
Falling below lower thresholdlistunchanged
Exceeding upper thresholdlistOFF
Object value "Threshold input" after ETS resetunsignedInt 0…2550
Object value "Threshold input" after ETS resetunsignedInt 0…655350
Object value "Threshold input" after downloadlistunchanged
Object value > upper thresholdlistunchanged
Exceeding upper thresholdlistunchanged
Reversing time delay in ms [100...1,000]list300
Switch on time for valve drive from 0 to 100 % in s [10...6,000]unsignedInt 10…6000180
Automatic adjustment of the valve drivelistno
Number of valve controls up to adjustment [30...65,535]unsignedInt 30…65535500
GP_ConvertibleVersionunsignedInt 0…255255
DUMMY -> NO_TEXTlistOutput pair, ES/S

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Switching Valve Drive 4f 1A/2.0a 2.0 latest$A074E1642026-11-25498 KBDownload

About this file

This is the official ETS product database for the ABB AG - BUSCH-JAEGER 6164/40-101 Elektronischer Schaltaktor 4f,1A,REG (6164/40-101), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from ABB AG - BUSCH-JAEGER

All ABB AG - BUSCH-JAEGER products