VAA/S12.230.2.1 Valve Drive Actuator, 12f, 230V 6164/46
ABB AG - BUSCH-JAEGER · Order number 6164/46 · Heating, Ventilation and Air Conditioning › Valve Drive Actuators
Download .knxprod Valve Drive 12f 230V/1.2a 1.2 · 506 KB
Product
| Manufacturer | ABB AG - BUSCH-JAEGER |
|---|---|
| Product name | VAA/S12.230.2.1 Valve Drive Actuator, 12f, 230V |
| Order number | 6164/46 |
| Hardware | VAA/S12.230.2.1 |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | Yes |
| Width (mm) | 144 |
| Registration | Registered · 2014-08-28 |
| Languages | de-DE, en-US, fr-FR, es-ES, it-IT, nl-NL, pl-PL, ru-RU |
| Catalog entry | M-0007_H-2CDG.20110.20117.20R0011-2-O0002_HP-A07C-12-3383-O0002_CI-6164.2F46-2 |
| Fingerprint | 3383 |
| SHA-256 | fce18bf5b0086218966ea9ced3f154fc758fef5ca7183149713c66da9374c2ad |
| First seen | 2026-11-25 |
| Markets | Austria, Belgium, Germany, Netherlands |
Application program: Valve Drive 12f 230V/1.2a 1.2
| Application number | $A07C |
|---|---|
| Version | 1.2 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Parameters | 673 |
| Group objects | 154 |
Group objects (154)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | General | In operation | 1 Bit | 1.2 boolean | CRT |
| 1 | General | Request status values | 1 Bit | DPT.1 | CWT |
| 2 | General | Status manual operation | 1 Bit | DPT.1 | CRT |
| 3 | General | Disable/enable man. operation | 1 Bit | 1.3 enable | CRW |
| 4 | Output A-X | Reset overload/short circuit | 1 Bit | DPT.1 | CWT |
| 5 | Object 5 | Dummy | 1 Bit | DPT.1 | |
| 6 | Object 6 | Dummy | 1 Bit | DPT.1 | |
| 7 | Object 7 | Dummy | 1 Bit | DPT.1 | |
| 8 | Object 8 | Dummy | 1 Bit | DPT.1 | |
| 9 | Object 9 | Dummy | 1 Bit | DPT.1 | |
| 10 | Output A | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 10 | Output A | Control value, switch | 1 Bit | 1.1 switch | CW |
| 11 | Output A | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 12 | Output A | Reset error message | 1 Bit | DPT.1 | CWT |
| 13 | Output A | Fault control value | 1 Bit | DPT.1 | CRT |
| 14 | Output A | Block | 1 Bit | 1.3 enable | CW |
| 15 | Output A | Forced operation | 1 Bit | 1.3 enable | CW |
| 16 | Output A | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 17 | Output A | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 18 | Output A | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 18 | Output A | Status control value | 1 Bit | 1.1 switch | CRT |
| 19 | Output A | Status byte | 1 Byte | CRT | |
| 20 | Output B | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 20 | Output B | Control value, switch | 1 Bit | 1.1 switch | CW |
| 21 | Output B | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 22 | Output B | Reset error message | 1 Bit | DPT.1 | CWT |
| 23 | Output B | Fault control value | 1 Bit | DPT.1 | CRT |
| 24 | Output B | Block | 1 Bit | 1.3 enable | CW |
| 25 | Output B | Forced operation | 1 Bit | 1.3 enable | CW |
| 26 | Output B | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 27 | Output B | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 28 | Output B | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 28 | Output B | Status control value | 1 Bit | 1.1 switch | CRT |
| 29 | Output B | Status byte | 1 Byte | CRT | |
| 30 | Output C | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 30 | Output C | Control value, switch | 1 Bit | 1.1 switch | CW |
| 31 | Output C | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 32 | Output C | Reset error message | 1 Bit | DPT.1 | CWT |
| 33 | Output C | Fault control value | 1 Bit | DPT.1 | CRT |
| 34 | Output C | Block | 1 Bit | 1.3 enable | CW |
| 35 | Output C | Forced operation | 1 Bit | 1.3 enable | CW |
| 36 | Output C | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 37 | Output C | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 38 | Output C | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 38 | Output C | Status control value | 1 Bit | 1.1 switch | CRT |
| 39 | Output C | Status byte | 1 Byte | CRT | |
| 40 | Output D | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 40 | Output D | Control value, switch | 1 Bit | 1.1 switch | CW |
| 41 | Output D | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 42 | Output D | Reset error message | 1 Bit | DPT.1 | CWT |
| 43 | Output D | Fault control value | 1 Bit | DPT.1 | CRT |
| 44 | Output D | Block | 1 Bit | 1.3 enable | CW |
| 45 | Output D | Forced operation | 1 Bit | 1.3 enable | CW |
| 46 | Output D | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 47 | Output D | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 48 | Output D | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 48 | Output D | Status control value | 1 Bit | 1.1 switch | CRT |
| 49 | Output D | Status byte | 1 Byte | CRT | |
| 50 | Output E | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 50 | Output E | Control value, switch | 1 Bit | 1.1 switch | CW |
| 51 | Output E | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 52 | Output E | Reset error message | 1 Bit | DPT.1 | CWT |
| 53 | Output E | Fault control value | 1 Bit | DPT.1 | CRT |
| 54 | Output E | Block | 1 Bit | 1.3 enable | CW |
| 55 | Output E | Forced operation | 1 Bit | 1.3 enable | CW |
| 56 | Output E | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 57 | Output E | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 58 | Output E | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 58 | Output E | Status control value | 1 Bit | 1.1 switch | CRT |
| 59 | Output E | Status byte | 1 Byte | CRT | |
| 60 | Output F | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 60 | Output F | Control value, switch | 1 Bit | 1.1 switch | CW |
| 61 | Output F | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 62 | Output F | Reset error message | 1 Bit | DPT.1 | CWT |
| 63 | Output F | Fault control value | 1 Bit | DPT.1 | CRT |
| 64 | Output F | Block | 1 Bit | 1.3 enable | CW |
| 65 | Output F | Forced operation | 1 Bit | 1.3 enable | CW |
| 66 | Output F | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 67 | Output F | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 68 | Output F | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 68 | Output F | Status control value | 1 Bit | 1.1 switch | CRT |
| 69 | Output F | Status byte | 1 Byte | CRT | |
| 70 | Output G | Control value, switch | 1 Bit | 1.1 switch | CW |
| 70 | Output G | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 71 | Output G | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 72 | Output G | Reset error message | 1 Bit | DPT.1 | CWT |
| 73 | Output G | Fault control value | 1 Bit | DPT.1 | CRT |
| 74 | Output G | Block | 1 Bit | 1.3 enable | CW |
| 75 | Output G | Forced operation | 1 Bit | 1.3 enable | CW |
| 76 | Output G | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 77 | Output G | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 78 | Output G | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 78 | Output G | Status control value | 1 Bit | 1.1 switch | CRT |
| 79 | Output G | Status byte | 1 Byte | CRT | |
| 80 | Output H | Control value, switch | 1 Bit | 1.1 switch | CW |
| 80 | Output H | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 81 | Output H | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 82 | Output H | Reset error message | 1 Bit | DPT.1 | CWT |
| 83 | Output H | Fault control value | 1 Bit | DPT.1 | CRT |
| 84 | Output H | Block | 1 Bit | 1.3 enable | CW |
| 85 | Output H | Forced operation | 1 Bit | 1.3 enable | CW |
| 86 | Output H | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 87 | Output H | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 88 | Output H | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 88 | Output H | Status control value | 1 Bit | 1.1 switch | CRT |
| 89 | Output H | Status byte | 1 Byte | CRT | |
| 90 | Output I | Control value, switch | 1 Bit | 1.1 switch | CW |
| 90 | Output I | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 91 | Output I | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 92 | Output I | Reset error message | 1 Bit | DPT.1 | CWT |
| 93 | Output I | Fault control value | 1 Bit | DPT.1 | CRT |
| 94 | Output I | Block | 1 Bit | 1.3 enable | CW |
| 95 | Output I | Forced operation | 1 Bit | 1.3 enable | CW |
| 96 | Output I | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 97 | Output I | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 98 | Output I | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 98 | Output I | Status control value | 1 Bit | 1.1 switch | CRT |
| 99 | Output I | Status byte | 1 Byte | CRT | |
| 100 | Output J | Control value, switch | 1 Bit | 1.1 switch | CW |
| 100 | Output J | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 101 | Output J | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 102 | Output J | Reset error message | 1 Bit | DPT.1 | CWT |
| 103 | Output J | Fault control value | 1 Bit | DPT.1 | CRT |
| 104 | Output J | Block | 1 Bit | 1.3 enable | CW |
| 105 | Output J | Forced operation | 1 Bit | 1.3 enable | CW |
| 106 | Output J | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 107 | Output J | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 108 | Output J | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 108 | Output J | Status control value | 1 Bit | 1.1 switch | CRT |
| 109 | Output J | Status byte | 1 Byte | CRT | |
| 110 | Output K | Control value, switch | 1 Bit | 1.1 switch | CW |
| 110 | Output K | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 111 | Output K | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 112 | Output K | Reset error message | 1 Bit | DPT.1 | CWT |
| 113 | Output K | Fault control value | 1 Bit | DPT.1 | CRT |
| 114 | Output K | Block | 1 Bit | 1.3 enable | CW |
| 115 | Output K | Forced operation | 1 Bit | 1.3 enable | CW |
| 116 | Output K | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 117 | Output K | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 118 | Output K | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 118 | Output K | Status control value | 1 Bit | 1.1 switch | CRT |
| 119 | Output K | Status byte | 1 Byte | CRT | |
| 120 | Output L | Control value, switch | 1 Bit | 1.1 switch | CW |
| 120 | Output L | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 121 | Output L | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 122 | Output L | Reset error message | 1 Bit | DPT.1 | CWT |
| 123 | Output L | Fault control value | 1 Bit | DPT.1 | CRT |
| 124 | Output L | Block | 1 Bit | 1.3 enable | CW |
| 125 | Output L | Forced operation | 1 Bit | 1.3 enable | CW |
| 126 | Output L | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 127 | Output L | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 128 | Output L | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | Output L | Status control value | 1 Bit | 1.1 switch | CRT |
| 129 | Output L | Status byte | 1 Byte | CRT |
Parameters (54)
| Parameter | Type | Default |
|---|---|---|
| Send communication object "In operation" | list | no |
| Sending cycle time in s [1...65,535] | unsignedInt 0…65535 | 0 |
| Sending cycle time in s [1...65,535] | unsignedInt 1…65535 | 60 |
| Sending and switching delay after bus voltage recovery in s (2...255) | unsignedInt 2…255 | 2 |
| Limit number of telegrams | list | no |
| Max. number of sent telegrams | unsignedInt 0…255 | 10 |
| Max. number of sent telegrams [1...255] | unsignedInt 1…255 | 20 |
| in period | unsignedInt 0…65535 | 56 |
| in period | list | 100 ms |
| Enable communication object "Request status values" 1 bit | list | no |
| Request with object value | list | 0 |
| Manual operation | list | enabled |
| Reset manual operation to KNX operation | list | after 1 Minute |
| Enable communication object "Status man. operation" 1 bit | list | no |
| Send object value | list | after a change |
| Type of valve drive | list | de-energised closed |
| Reaction after bus voltage recovery | list | unchanged |
| Control value after bus voltage recovery in % [0...100] | unsignedInt 1…255 | 255 |
| Control value in % [0...100] | unsignedInt 0…100 | 0 |
| Control value is received as | list | 1 bit |
| Convert control value to | list | PWM (pulse width modulation) |
| OPEN at control value greater or equal in % [1...100] | unsignedInt 1…100 | 1 |
| Cycle time of PWM in s [10...6,000] | unsignedInt 10…6000 | 180 |
| Opening time of valve drive in s [10...6,000] | unsignedInt 10…6000 | 180 |
| Closing time of valve drive in s [10...6,000] | unsignedInt 10…6000 | 180 |
| Set cycle time PWM, open./closing time for contr. value in % on bus voltage | list | <--- NOTE |
| Monitoring control values e.g. thermostat | list | no |
| Monitoring time in s [30...65,535] | unsignedInt 30…65535 | 120 |
| Send object value (Object "Fault control value" 1 bit) | list | after a change |
| Control value after controller fault in % [0...100] | unsignedInt 0…100 | 30 |
| Enable communication object "Block" 1 bit | list | no |
| Block on object value | list | 1 |
| Enable communication object "Forced operation" 1 bit | list | no |
| Forced operation on object value | list | 1 |
| Control value on forced operation in % [0...100] | unsignedInt 0…100 | 30 |
| Enable communication object "Status control value" 1 byte/1 bit | list | no |
| Object value at control value > 0 | list | 1 |
| Enable valve purge | list | no |
| Enable communication object "Status valve purge" 1 bit | list | no |
| Duration of valve purge in min. [1...255] | unsignedInt 1…255 | 10 |
| Automatic valve purge | list | no |
| Purge cycle in weeks [1...12] | unsignedInt 1…12 | 6 |
| Reset purge cycle from control value in % [1...99] | unsignedInt 1…99 | 99 |
| Reset purge cycle from control value in % [1...99] | unsignedInt 1…255 | 111 |
| Enable characteristic curve | list | no |
| Value pair 1 Control value in % [0...100] | unsignedInt 0…100 | 0 |
| Valve position in % [0...100] | unsignedInt 0…100 | 0 |
| Value pair 2 Control value in % [0...100] | unsignedInt 0…100 | 100 |
| Valve position in % [0...100] | unsignedInt 0…100 | 100 |
| Enable value pair 3 | list | no |
| Value pair 3 Control value in % [0...100] | unsignedInt 0…100 | 50 |
| Valve position in % [0...100] | unsignedInt 0…100 | 50 |
| Enable value pair 4 | list | no |
| Value pair 4 Control value in % [0...100] | unsignedInt 0…100 | 50 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Valve Drive 12f 230V/1.2a 1.2 latest | $A07C | 3383 | 2026-11-25 | 506 KB | Download |
About this file
This is the official ETS product database for the ABB AG - BUSCH-JAEGER VAA/S12.230.2.1 Valve Drive Actuator, 12f, 230V (6164/46), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from ABB AG - BUSCH-JAEGER
- FCC/S1.1.2.11 Fan Coil Controller,PWM,3-speed,manual operation,MDRC 2CDG 110 211 R0021
- FCC/S1.2.2.11 Fan Coil Controller,0-10V,3-speed,manual operation,MDRC 2CDG 110 213 R0021
- FCC/S1.3.2.11 Fan Coil Controller,0-10V,0-10V,manual operation,MDRC 2CDG 110 215 R0021
- VC/S4.1.11 Valve Drive Controller,4-fold,MDRC 2CDG 110 216 R0021
- VC/S4.2.11 Valve Drive Controller,manual operation,4-fold,MDRC 2CDG 110 217 R0021
- FCC/S1.5.2.11 Fan Coil Controller,PWM,0-10V,manual operation,MDRC 2CDG 110 235 R0021
- 6138/11-xx RTR fan coil with display, SM 6138/11-xx
- 6164/40-101 Elektronischer Schaltaktor 4f,1A,REG 6164/40-101
- 6164/44 Electronic Switch Actuator,8f,1A,MDRC 6164/44
- VAA/S6.230.2.1 Valve Drive Actuator, 6f, 230V,MDRC 6164/45
- SUG/U 1.1 Split Unit Gateway 6186/40
- IPS/S3.5.11 IP Interface Secure,MDRC 2CDG 110 204 R0021