6164/40-101 Elektronischer Schaltaktor 4f,1A,REG 6164/40-101
ABB AG - BUSCH-JAEGER · Order number 6164/40-101 · Heating, Ventilation and Air Conditioning › Valve Drive Actuators
Download .knxprod Switching Valve Drive 4f 1A/2.0a 2.0 · 498 KB
Product
| Manufacturer | ABB AG - BUSCH-JAEGER |
|---|---|
| Product name | 6164/40-101 Elektronischer Schaltaktor 4f,1A,REG |
| Order number | 6164/40-101 |
| Product text | 6164/40-101 Electronic Switch Actuator,4f,1A,MDRC |
| Hardware | ES/S4.1.2.1 |
| Medium | Twisted Pair |
| Bus current (mA) | 7 |
| Rail mounted | Yes |
| Width (mm) | 72 |
| Registration | Registered |
| Languages | de-DE, en-US |
| Catalog entry | M-0007_H-2CDG.20110.20058.20R0011-1-O0002_HP-A074-20-E164-O0002_CI-6164.2F40.2D101-1 |
| Fingerprint | E164 |
| SHA-256 | bb9ab8092c049b41ad81ecc1c4ed618d903716ca41ca42713d0bd2cbdf1179d2 |
| First seen | 2026-11-25 |
| Markets | Austria, Belgium, Germany, Netherlands |
Application program: Switching Valve Drive 4f 1A/2.0a 2.0
| Application number | $A074 |
|---|---|
| Version | 2.0 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Parameters | 728 |
| Group objects | 183 |
Group objects (183)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | General | In operation | 1 Bit | 1.2 boolean | CRT |
| 1 | General | Request status values | 1 Bit | CWT | |
| 2 | General | Block manual operation | 1 Bit | 1.1 switch | CW |
| 3 | General | Status of manual operation | 1 Bit | 1.3 enable | CRT |
| 4 | Object 4 | Dummy | 1 Bit | ||
| 5 | Object 5 | Dummy | 1 Bit | ||
| 6 | Object 6 | Dummy | 1 Bit | ||
| 7 | Object 7 | Dummy | 1 Bit | ||
| 8 | Object 8 | Dummy | 1 Bit | ||
| 9 | Object 9 | Dummy | 1 Bit | ||
| 10 | Output A | Switch | 1 Bit | 1.1 switch | CW |
| 10 | Output AB | Control value, cont. (3-point) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 10 | Output A | Control value, cont. (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 10 | Output A | Control value | 1 Bit | 1.1 switch | CW |
| 11 | Output A | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 11 | Output A | Status control value | 1 Bit | CRT | |
| 11 | Output A | Status switch | 1 Bit | 1.1 switch | CRT |
| 11 | Output AB | Status control value | 1 Bit | CRT | |
| 11 | Output AB | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 12 | Output A | Fault control value | 1 Bit | CRT | |
| 12 | Output AB | Fault control value | 1 Bit | CRT | |
| 12 | Output A | Permanent ON | 1 Bit | 1.1 switch | CRWT |
| 13 | Output A | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 13 | Output A | Disable function time | 1 Bit | 1.3 enable | CW |
| 13 | Output AB | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 14 | Output A | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 14 | Output AB | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 14 | Output A | Staircase lighting duration | 2 Bytes | CRW | |
| 15 | Output A | Staircase lighting warning | 1 Bit | CT | |
| 16 | Output A | 8 bit scene | 1 Byte | CW | |
| 17 | Output A | Logical connection 1 | 1 Bit | 1.2 boolean | CW |
| 18 | Output A | Logical connection 2 | 1 Bit | 1.2 boolean | CW |
| 19 | Output A | Threshold | 2 Bytes | 7.1 pulses | CW |
| 19 | Output A | Threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 20 | Output A | Set threshold 1 | 2 Bytes | 7.1 pulses | CW |
| 20 | Output A | Set threshold 1 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 21 | Object 21 | Dummy | 1 Bit | ||
| 22 | Output A | Priority 1, Forced operation | 2 Bit | 2.1 switch control | CW |
| 22 | Output A | Priority 1, Forced operation | 1 Bit | 1.1 switch | CW |
| 22 | Output A | Priority 1, Block | 1 Bit | 1.1 switch | CW |
| 22 | Output AB | Priority 1, Block | 1 Bit | 1.1 switch | CW |
| 22 | Output AB | Priority 1, Forced operation | 1 Bit | 1.1 switch | CW |
| 23 | Output A | Priority 2, Forced operation | 1 Bit | 1.1 switch | CW |
| 23 | Output A | Priority 2, Block | 1 Bit | 1.1 switch | CW |
| 23 | Output A | Priority 2, Forced operation | 2 Bit | 2.1 switch control | CW |
| 23 | Output AB | Priority 2, Block | 1 Bit | 1.1 switch | CW |
| 23 | Output AB | Priority 2, Forced operation | 1 Bit | 1.1 switch | CW |
| 24 | Output A | Priority 3, Forced operation | 2 Bit | 2.1 switch control | CW |
| 24 | Output A | Priority 3, Forced operation | 1 Bit | 1.1 switch | CW |
| 24 | Output A | Priority 3, Block | 1 Bit | 1.1 switch | CW |
| 24 | Output AB | Priority 3, Forced operation | 1 Bit | 1.1 switch | CW |
| 24 | Output AB | Priority 3, Block | 1 Bit | 1.1 switch | CW |
| 25 | Object 25 | Dummy | 1 Bit | ||
| 26 | Output A | Status byte | 1 Byte | CRT | |
| 26 | Output AB | Status byte | 1 Byte | CRT | |
| 27 | Output A | Fault (overload/short-circuit) | 1 Bit | CRT | |
| 27 | Output AB | Fault (overload/short-circuit) | 1 Bit | CRT | |
| 28 | Output A | Reset fault | 1 Bit | CWT | |
| 28 | Output AB | Reset fault | 1 Bit | CWT | |
| 29 | Output A | Supply voltage failure | 1 Bit | CRT | |
| 29 | Output AB | Supply voltage failure | 1 Bit | CRT | |
| 30 | Output B | Control value, cont. (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 30 | Output B | Control value | 1 Bit | 1.1 switch | CW |
| 30 | Output B | Switch | 1 Bit | 1.1 switch | CW |
| 31 | Output B | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 31 | Output B | Status control value | 1 Bit | CRT | |
| 31 | Output B | Status switch | 1 Bit | 1.1 switch | CRT |
| 32 | Output B | Fault control value | 1 Bit | CRT | |
| 32 | Output B | Permanent ON | 1 Bit | 1.1 switch | CRWT |
| 33 | Output B | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 33 | Output B | Disable function time | 1 Bit | 1.3 enable | CW |
| 34 | Output B | Staircase lighting duration | 2 Bytes | CRW | |
| 34 | Output B | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 35 | Output B | Staircase lighting warning | 1 Bit | CT | |
| 36 | Output B | 8 bit scene | 1 Byte | CW | |
| 37 | Output B | Logical connection 1 | 1 Bit | 1.2 boolean | CW |
| 38 | Output B | Logical connection 2 | 1 Bit | 1.2 boolean | CW |
| 39 | Output B | Threshold | 2 Bytes | 7.1 pulses | CW |
| 39 | Output B | Threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 40 | Output B | Set threshold 1 | 2 Bytes | 7.1 pulses | CW |
| 40 | Output B | Set threshold 1 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 41 | Object 41 | Dummy | 1 Bit | ||
| 42 | Output B | Priority 1, Forced operation | 2 Bit | 2.1 switch control | CW |
| 42 | Output B | Priority 1, Forced operation | 1 Bit | 1.1 switch | CW |
| 42 | Output B | Priority 1, Block | 1 Bit | 1.3 enable | CW |
| 42 | Output B | Priority 1, Block | 1 Bit | 1.1 switch | CW |
| 43 | Output B | Priority 2, Forced operation | 2 Bit | 2.1 switch control | CW |
| 43 | Output B | Priority 2, Forced operation | 1 Bit | 1.1 switch | CW |
| 43 | Output B | Priority 2, Block | 1 Bit | 1.1 switch | CW |
| 44 | Output B | Priority 3, Forced operation | 2 Bit | 2.1 switch control | CW |
| 44 | Output B | Priority 3, Forced operation | 1 Bit | 1.1 switch | CW |
| 44 | Output B | Priority 3, Block | 1 Bit | 1.1 switch | CW |
| 45 | Object 45 | Dummy | 1 Bit | ||
| 46 | Output B | Status byte | 1 Byte | CRT | |
| 47 | Output B | Fault (overload/short-circuit) | 1 Bit | CRT | |
| 48 | Output B | Reset fault | 1 Bit | CWT | |
| 49 | Output B | Supply voltage failure | 1 Bit | CRT | |
| 50 | Output C | Control value, cont. (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 50 | Output C | Control value | 1 Bit | 1.1 switch | CW |
| 50 | Output C | Switch | 1 Bit | 1.1 switch | CW |
| 50 | Output CD | Control value, cont. (3-point) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 51 | Output C | Status control value | 1 Bit | CRT | |
| 51 | Output C | Status switch | 1 Bit | 1.1 switch | CRT |
| 51 | Output C | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 51 | Output CD | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 51 | Output CD | Status control value | 1 Bit | CRT | |
| 52 | Output C | Fault control value | 1 Bit | CRT | |
| 52 | Output CD | Fault control value | 1 Bit | CRT | |
| 52 | Output C | Permanent ON | 1 Bit | 1.1 switch | CRWT |
| 53 | Output C | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 53 | Output CD | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 53 | Output C | Disable function time | 1 Bit | 1.3 enable | CW |
| 54 | Output C | Staircase lighting duration | 2 Bytes | CRW | |
| 54 | Output CD | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 54 | Output C | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 55 | Output C | Staircase lighting warning | 1 Bit | CT | |
| 56 | Output C | 8 bit scene | 1 Byte | CW | |
| 57 | Output C | Logical connection 1 | 1 Bit | 1.2 boolean | CW |
| 58 | Output C | Logical connection 2 | 1 Bit | 1.2 boolean | CW |
| 59 | Output C | Threshold | 2 Bytes | 7.1 pulses | CW |
| 59 | Output C | Threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 60 | Output C | Set threshold 1 | 2 Bytes | 7.1 pulses | CW |
| 60 | Output C | Set threshold 1 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 61 | Object 61 | Dummy | 1 Bit | ||
| 62 | Output C | Priority 1, Forced operation | 2 Bit | 2.1 switch control | CW |
| 62 | Output C | Priority 1, Forced operation | 1 Bit | 1.1 switch | CW |
| 62 | Output C | Priority 1, Block | 1 Bit | 1.1 switch | CW |
| 62 | Output CD | Priority 1, Block | 1 Bit | 1.1 switch | CW |
| 62 | Output CD | Priority 1, Forced operation | 1 Bit | 1.1 switch | CW |
| 63 | Output C | Priority 2, Forced operation | 2 Bit | 2.1 switch control | CW |
| 63 | Output C | Priority 2, Forced operation | 1 Bit | 1.1 switch | CW |
| 63 | Output C | Priority 2, Block | 1 Bit | 1.1 switch | CW |
| 63 | Output CD | Priority 2, Block | 1 Bit | 1.1 switch | CW |
| 63 | Output CD | Priority 2, Forced operation | 1 Bit | 1.1 switch | CW |
| 64 | Output C | Priority 3, Forced operation | 2 Bit | 2.1 switch control | CW |
| 64 | Output C | Priority 3, Forced operation | 1 Bit | 1.1 switch | CW |
| 64 | Output C | Priority 3, Block | 1 Bit | 1.1 switch | CW |
| 64 | Output CD | Priority 3, Block | 1 Bit | 1.1 switch | CW |
| 64 | Output CD | Priority 3, Forced operation | 1 Bit | 1.1 switch | CW |
| 65 | Object 65 | Dummy | 1 Bit | ||
| 66 | Output C | Status byte | 1 Byte | CRT | |
| 66 | Output CD | Status byte | 1 Byte | CRT | |
| 67 | Output C | Fault (overload/short-circuit) | 1 Bit | CRT | |
| 67 | Output CD | Fault (overload/short-circuit) | 1 Bit | CRT | |
| 68 | Output C | Reset fault | 1 Bit | CWT | |
| 68 | Output CD | Reset fault | 1 Bit | CWT | |
| 69 | Output C | Supply voltage failure | 1 Bit | CRT | |
| 69 | Output CD | Supply voltage failure | 1 Bit | CRT | |
| 70 | Output D | Control value, cont. (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 70 | Output D | Control value | 1 Bit | 1.1 switch | CW |
| 70 | Output D | Switch | 1 Bit | 1.1 switch | CW |
| 71 | Output D | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 71 | Output D | Status control value | 1 Bit | CRT | |
| 71 | Output D | Status switch | 1 Bit | 1.1 switch | CRT |
| 72 | Output D | Fault control value | 1 Bit | CRT | |
| 72 | Output D | Permanent ON | 1 Bit | 1.1 switch | CRWT |
| 73 | Output D | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 73 | Output D | Disable function time | 1 Bit | 1.3 enable | CW |
| 74 | Output D | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 74 | Output D | Staircase lighting duration | 2 Bytes | CRW | |
| 75 | Output D | Staircase lighting warning | 1 Bit | CT | |
| 76 | Output D | 8 bit scene | 1 Byte | CW | |
| 77 | Output D | Logical connection 1 | 1 Bit | 1.2 boolean | CW |
| 78 | Output D | Logical connection 2 | 1 Bit | 1.2 boolean | CW |
| 79 | Output D | Threshold | 2 Bytes | 7.1 pulses | CW |
| 79 | Output D | Threshold | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 80 | Output D | Set threshold 1 | 2 Bytes | 7.1 pulses | CW |
| 80 | Output D | Set threshold 1 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 81 | Object 81 | Dummy | 1 Bit | ||
| 82 | Output D | Priority 1, Forced operation | 2 Bit | 2.1 switch control | CW |
| 82 | Output D | Priority 1, Forced operation | 1 Bit | 1.1 switch | CW |
| 82 | Output D | Priority 1, Block | 1 Bit | 1.1 switch | CW |
| 83 | Output D | Priority 2, Forced operation | 2 Bit | 2.1 switch control | CW |
| 83 | Output D | Priority 2, Forced operation | 1 Bit | 1.1 switch | CW |
| 83 | Output D | Priority 2, Block | 1 Bit | 1.1 switch | CW |
| 84 | Output D | Priority 3, Forced operation | 2 Bit | 2.1 switch control | CW |
| 84 | Output D | Priority 3, Forced operation | 1 Bit | 1.1 switch | CW |
| 84 | Output D | Priority 3, Block | 1 Bit | 1.1 switch | CW |
| 85 | Object 85 | Dummy | 1 Bit | ||
| 86 | Output D | Status byte | 1 Byte | CRT | |
| 87 | Output D | Fault (overload/short-circuit) | 1 Bit | CRT | |
| 88 | Output D | Reset fault | 1 Bit | CWT | |
| 89 | Output D | Supply voltage failure | 1 Bit | CRT |
Parameters (146)
| Parameter | Type | Default |
|---|---|---|
| Sending delay after bus voltage recovery in s [2...255] | unsignedInt 2…255 | 2 |
| Limit number of telegrams | list | no |
| DUMMY -> NO_TEXT | unsignedInt 0…255 | 10 |
| DUMMY -> NO_TEXT | unsignedInt 0…65535 | 56 |
| Max. number of sent telegrams [1...255] | unsignedInt 1…255 | 20 |
| in period | list | 1 s |
| Send communication object "In operation" | list | no |
| DUMMY -> NO_TEXT | unsignedInt 0…65535 | 0 |
| Sending cycle time in s [1...65,535] | unsignedInt 1…65535 | 60 |
| Enable communication object "Request status values" 1 bit | list | no |
| Request with object value | list | 1 |
| DUMMY -> NO_TEXT | unsignedInt 0…0 | 0 |
| DUMMY -> NO_TEXT | list | no |
| Manual operation | list | enabled |
| Object value "Block manual operation" after download | list | unchanged |
| Automatic reset of manual operation to KNX operation | list | after 3 minutes |
| Enable communication object "Status man. operation" 1 bit | list | no |
| Send object value | list | after a change |
| Operation mode output A and B | list | Individual |
| Output A | list | open |
| Output B | list | close |
| Output A | list | Valve drive, thermoelectric (PWM) |
| Output B | list | Valve drive, thermoelectric (PWM) |
| Operation mode output C and D | list | Individual |
| Output C | list | Valve drive, thermoelectric (PWM) |
| Output D | list | Valve drive, thermoelectric (PWM) |
| Output C | list | open |
| Output D | list | close |
| DUMMY -> NO_TEXT | unsignedInt 5…5 | 5 |
| Type of valve drive | list | de-energized closed |
| Reaction on bus voltage failure and download | list | unchanged |
| DUMMY -> NO_TEXT | unsignedInt 1…255 | 255 |
| Control value in % [0...100] | unsignedInt 0…100 | 30 |
| Reaction after bus voltage recovery | list | unchanged |
| Control value in % [0...100] | unsignedInt 0…100 | 0 |
| Control value is received as | list | 1 byte |
| Set cycle time PWM, open./closing time for contr. value of actuator in % | list | <--- NOTE |
| Convert control value to | list | PWM (pulse width modulated) |
| OPEN at control value greater or equal in % [1...100] | unsignedInt 1…100 | 1 |
| Cycle time of PWM in s [10...6,000] | unsignedInt 10…6000 | 180 |
| Opening time of valve drive in s [10...6,000] | unsignedInt 10…6000 | 180 |
| Closing time of valve drive in s [10...6,000] | unsignedInt 10…6000 | 180 |
| Activate monitoring control values | list | no |
| Control period in s [30...65,535] | unsignedInt 30…65535 | 120 |
| Send object value (Object "Control value fault" 1 bit) | list | after a change |
| Control value after control fault | list | unchanged |
| Enable function safety | list | no |
| Enable communication object "Status control value" 1 bit/byte | list | no |
| Data type | list | 1 byte |
| Object value with control > 0 | list | 1 |
| Enable valve purge | list | no |
| Enable communication object "Status valve purge" 1 bit | list | no |
| Duration of valve purge in min [1...255] | unsignedInt 1…255 | 10 |
| Automatic valve purge | list | no |
| Purge cycle in weeks [1...12] | unsignedInt 1…12 | 6 |
| Reset purge cycle from control value in % [1...99] | unsignedInt 1…99 | 99 |
| DUMMY -> NO_TEXT | unsignedInt 1…255 | 111 |
| Enable characteristic adjustment | list | no |
| Safety priority 1 | list | inactive |
| Control value on forced operation in % [0...100] | unsignedInt 0…100 | 50 |
| Trigger with object value | list | 1 |
| Control period in seconds [1...65,535, 0 = inactive] | unsignedInt 0…65535 | 0 |
| Object value "Priority 1, Forced operation" after download | list | unchanged |
| Object value "Priority 1, Block" after download | list | unchanged |
| Safety priority 2 | list | inactive |
| Object value "Priority 2, Forced operation" after download | list | unchanged |
| Object value "Priority 2, Block" after download | list | unchanged |
| Safety priority 3 | list | inactive |
| Object value "Priority 3, Forced operation" after download | list | unchanged |
| Object value "Priority 3, Block" after download | list | unchanged |
| Prio END valve | unsignedInt 129…129 | 1 |
| Value pair 1 Control value in % [0...100] | unsignedInt 0…100 | 0 |
| Value pair 2 Control value in % [0...100] | unsignedInt 0…100 | 100 |
| Control value in % [0...100] | unsignedInt 0…100 | 100 |
| Enable value pair 3 | list | no |
| Value pair 3 Control value in % [0...100] | unsignedInt 0…100 | 50 |
| Control value in % [0...100] | unsignedInt 0…100 | 50 |
| Enable value pair 4 | list | no |
| Value pair 4 Control value in % [0...100] | unsignedInt 0…100 | 50 |
| Reaction of output | list | N/O |
| Status response of contact position | list | no |
| Inverted | list | no: 0 = OFF, 1 = ON |
| DUMMY -> NO_TEXT | unsignedInt 1…1 | 1 |
| Value object "Switch" on bus voltage recovery | list | not write |
| Enable function time: Delay, staircase lighting, flashing | list | no |
| "Disable function time" after download | list | unchanged |
| Enable function scene (8 bit) | list | no |
| Enable function logic | list | no |
| Enable function threshold | list | no |
| Function Time | list | Staircase lighting |
| Staircase lighting duration in s [1...65,535] | unsignedInt 1…65535 | 30 |
| Extending staircase lighting by multiple operation ["pumping up"] | list | no (not retriggerable) |
| Staircase lighting can be switched | list | ON with 1 and OFF with 0 |
| Warning before end of staircase lighting | list | no |
| Warning time in sec. [0...65,535] add to duration of staircase lighting | unsignedInt 0…65535 | 45 |
| Staircase lighting duration changeable via object "Staircase lighting duration" | list | no |
| Object value "Staircase lighting duration" after download | list | unchanged |
| Restart of staircase time after end of permanent ON | list | no |
| Delay for switching ON in s [1...65,535] | unsignedInt 1…65535 | 30 |
| Delay for switching OFF in s [1...65,535] | unsignedInt 1…65535 | 5 |
| Flash if communication object "Switch" is | list | ON (1) or OFF (0) |
| Time for ON in s [0...65,535] | unsignedInt 0…65535 | 5 |
| Time for OFF in s [0...65,535] | unsignedInt 0…65535 | 5 |
| Number of impulses [1...100] | unsignedInt 1…100 | 5 |
| Contact position after flashing | list | update |
| Set standard value after the download | list | yes |
| Assignment to scene number [No. 1...64, 0 = no assignment] | unsignedInt 0…64 | 0 |
| Standard value | list | ON |
| Logical connection 1 | list | inactive |
| Function of object Logical connection 1 | list | AND |
| GATE disabled, if object value "Logical connection 1" is | list | 1 |
| Result is inverted | list | no |
| Object value "Logical connection 1" after ETS reset | list | 1 |
| Object value "Logical connection 1” after download | list | unchanged |
| Logical connection 2 | list | inactive |
| Function of object Logical connection 2 | list | AND |
| GATE disabled, if object value "Logical connection 2" is | list | 1 |
| Object value "Logical connection 2" after ETS reset | list | 1 |
| Object value "Logical connection 2” after download | list | unchanged |
| Contact position if forced operation | list | ON |
| Contact position after all priorities end | list | unchanged |
| Value | list | ON |
| Data type of object "Threshold input" | list | 1 byte (0...255) |
| Threshold 1 change via bus | list | no |
| Overwrite object value after download | list | no |
| Threshold value 1 [0...255] | unsignedInt 0…255 | 80 |
| Threshold value 2 [0...255] | unsignedInt 0…255 | 160 |
| Threshold value 1 [0...65,535] | unsignedInt 0…65535 | 20000 |
| Threshold value 2 [0...65,535] | unsignedInt 0…65535 | 40000 |
| Threshold values define hysteresis | list | no |
| Object value < lower threshold | list | unchanged |
| Lower threshold <= object value <= upper threshold | list | unchanged |
| Object value > upper threshold | list | OFF |
| Falling below lower threshold | list | unchanged |
| Exceeding upper threshold | list | OFF |
| Object value "Threshold input" after ETS reset | unsignedInt 0…255 | 0 |
| Object value "Threshold input" after ETS reset | unsignedInt 0…65535 | 0 |
| Object value "Threshold input" after download | list | unchanged |
| Object value > upper threshold | list | unchanged |
| Exceeding upper threshold | list | unchanged |
| Reversing time delay in ms [100...1,000] | list | 300 |
| Switch on time for valve drive from 0 to 100 % in s [10...6,000] | unsignedInt 10…6000 | 180 |
| Automatic adjustment of the valve drive | list | no |
| Number of valve controls up to adjustment [30...65,535] | unsignedInt 30…65535 | 500 |
| GP_ConvertibleVersion | unsignedInt 0…255 | 255 |
| DUMMY -> NO_TEXT | list | Output pair, ES/S |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Switching Valve Drive 4f 1A/2.0a 2.0 latest | $A074 | E164 | 2026-11-25 | 498 KB | Download |
About this file
This is the official ETS product database for the ABB AG - BUSCH-JAEGER 6164/40-101 Elektronischer Schaltaktor 4f,1A,REG (6164/40-101), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from ABB AG - BUSCH-JAEGER
- FCC/S1.1.2.11 Fan Coil Controller,PWM,3-speed,manual operation,MDRC 2CDG 110 211 R0021
- FCC/S1.2.2.11 Fan Coil Controller,0-10V,3-speed,manual operation,MDRC 2CDG 110 213 R0021
- FCC/S1.3.2.11 Fan Coil Controller,0-10V,0-10V,manual operation,MDRC 2CDG 110 215 R0021
- VC/S4.1.11 Valve Drive Controller,4-fold,MDRC 2CDG 110 216 R0021
- VC/S4.2.11 Valve Drive Controller,manual operation,4-fold,MDRC 2CDG 110 217 R0021
- FCC/S1.5.2.11 Fan Coil Controller,PWM,0-10V,manual operation,MDRC 2CDG 110 235 R0021
- 6138/11-xx RTR fan coil with display, SM 6138/11-xx
- 6164/44 Electronic Switch Actuator,8f,1A,MDRC 6164/44
- VAA/S6.230.2.1 Valve Drive Actuator, 6f, 230V,MDRC 6164/45
- VAA/S12.230.2.1 Valve Drive Actuator, 12f, 230V 6164/46
- SUG/U 1.1 Split Unit Gateway 6186/40
- IPS/S3.5.11 IP Interface Secure,MDRC 2CDG 110 204 R0021