KIPI SC ZSYKIPISC
Zennio · Order number ZSYKIPISC · Interface › IP
Secure KNX-IP Interface
Download .knxprod KIPI SC 1.1 1.1 · 669 KB
Product
| Manufacturer | Zennio |
|---|---|
| Product name | KIPI SC |
| Order number | ZSYKIPISC |
| Hardware | KIPI SC |
| Medium | Twisted Pair |
| Bus current (mA) | 20 |
| Rail mounted | Yes |
| Width (mm) | 36 |
| Device kind | IPEnabled |
| Registration | Certified · 2022-02-25 |
| Languages | en-US, es-ES, de-DE, fr-FR, it-IT, ru-RU |
| Catalog entry | M-0071_H-ZSYKIPISC-1_HP-6391-11-346B_CI-ZSYKIPISC-1 |
| Fingerprint | 346B |
| SHA-256 | a0a436b4b7773a65cca99cd0588376597cbb71e48cc9228376fafadfc4c4d270 |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: KIPI SC 1.1 1.1
| Application number | $6391 |
|---|---|
| Version | 1.1 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | Yes |
| Minimum ETS version | 5.0 |
| Parameters | 3116 |
| Group objects | 1807 |
Group objects (1807)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | [Heartbeat] Object to Send '1' | Sending of '1' Periodically | 1 Bit | 1.17 trigger | CT |
| 2 | [NTP] Date | Current Date | 3 Bytes | 11.1 date | CRT |
| 3 | [NTP] Time of Day | Current Time | 3 Bytes | 10.1 time of day | CRT |
| 4 | [NTP] Date and Time | Current Date and Time | 8 Bytes | 19.1 date time | CRT |
| 5 | [NTP] Sending Request | 0 = No Action; 1 = Request Date and Time Sending | 1 Bit | 1.16 acknowledge | CW |
| 6 | [HT1] [A] On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 7 | [HT1] [A] On/Off Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 8 | [HT1] [A] Scene Input | Scene Value | 1 Byte | 18.1 scene control | CW |
| 9 | [HT1] [A] Temperature Source 1 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 10 | [HT1] [A] Temperature Source 2 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 11 | [HT1] [A] Room Temperature | Current Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 12 | [HT1] [A] System Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 13 | [HT1] [A] User Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 14 | [HT1] [A] Force System Mode | 0 = User Mode / Auto Change; 1 = System Mode | 1 Bit | 1.1 switch | CRW |
| 15 | [HT1] [A] Mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 16 | [HT1] [A] Fan Speed | 0% - 100% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 17 | [HT1] [A] Fan: Manual/Automatic | 0 = Manual; 1 = Automatic | 1 Bit | 1.3 enable | CWTU |
| 17 | [HT1] [A] Fan: Manual/Automatic | 0 = Automatic; 1 = Manual | 1 Bit | 1.3 enable | CWTU |
| 18 | [HT1] [A] On/Off Fancoil | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 19 | [HT1] [B] User Comfort Setpoint Reset | 0 = Nothing; 1 = Reset | 1 Bit | 1.15 reset | CW |
| 20 | [HT1] [B] User Setpoint Control | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 20 | [HT1] [B] User Setpoint Offset | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 21 | [HT1] [B] Step User Setpoint | 0 = Decrease; 1 = Increase | 1 Bit | 1.7 step | CW |
| 22 | [HT1] [B] Comfort Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 22 | [HT1] [B] Comfort Setpoint | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 23 | [HT1] [B] Standby Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 24 | [HT1] [B] Economy Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 25 | [HT1] [B] Protection Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 26 | [HT1] [B] Comfort Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 27 | [HT1] [B] Standby Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 28 | [HT1] [B] Economy Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 29 | [HT1] [B] Protection Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 30 | [HT1] [B] Real Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 31 | [HT1] [B] User Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 31 | [HT1] [B] User Setpoint Offset Status | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 32 | [HT1] [C] Transition Time: Comfort to Default Mode | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 32 | [HT1] [C] Transition Time: Comfort to Default Mode | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 32 | [HT1] [C] Transition Time: Comfort to Default Mode | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 33 | [HT1] [C] Transition Time: Standby to Economy | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 33 | [HT1] [C] Transition Time: Standby to Economy | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 33 | [HT1] [C] Transition Time: Standby to Economy | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 34 | [HT1] [C] Comfort Setpoint Reset Time | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 34 | [HT1] [C] Comfort Setpoint Reset Time | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 34 | [HT1] [C] Comfort Setpoint Reset Time | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 35 | [HT1] [C] Presence Detector (Input) | 0 = Not Occupied; 1 = Occupied | 1 Bit | 1.18 occupancy | CRW |
| 36 | [HT1] [C] Lock Presence Detection | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 36 | [HT1] [C] Lock Presence Detection | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 37 | [HT1] [C] Sold/Unsold Room (Input) | 0 = Unsold; 1 = Sold | 1 Bit | 1.2 boolean | CRW |
| 38 | [HT1] [D] Special Mode | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CW |
| 39 | [HT1] [D] Special Mode: Comfort | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 39 | [HT1] [D] Special Mode: Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 40 | [HT1] [D] Special Mode: Standby | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 40 | [HT1] [D] Special Mode: Standby | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 41 | [HT1] [D] Special Mode: Economy | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 41 | [HT1] [D] Special Mode: Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 42 | [HT1] [D] Special Mode: Protection | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 42 | [HT1] [D] Special Mode: Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 43 | [HT1] [D] Special Mode Status | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 44 | [HT1] [D] Comfort Mode Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 45 | [HT1] [D] Window Status 1 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 45 | [HT1] [D] Window Status 1 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 46 | [HT1] [D] Window Status 2 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 46 | [HT1] [D] Window Status 2 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 47 | [HT1] [D] Window Status 3 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 47 | [HT1] [D] Window Status 3 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 48 | [HT1] [D] Window Status 4 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 48 | [HT1] [D] Window Status 4 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 49 | [HT1] [D] Enable Window Status | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRW |
| 50 | [HT1] [D] Thermostat Lock | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 50 | [HT1] [D] Thermostat Lock | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 51 | [HT1] [D] Comfort Lower Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 52 | [HT1] [D] Comfort Upper Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 53 | [HT1] [D] Hidden Offset On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRW |
| 54 | [HT1] [D] Hidden Offset Value | [-20°C, 100°C] | 2 Bytes | 9.2 temperature difference (K) | CRWTU |
| 55 | [HT1] [D] Eco Mode Notification | 0 = Out of eco range; 1 = Setpoint in Eco Range | 1 Bit | 1.2 boolean | CRT |
| 56 | [HT1] [D] Eco Mode Ratio | Percentage of Time Working in Eco Range | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 57 | [HT1] [D] Eco Mode: Lower Limit (Cooling) | Lower Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 58 | [HT1] [D] Eco Mode: Upper Limit (Heating) | Upper Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 59 | [HT1] [D] Setpoint to Split | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 60 | [HT1] [F] Current Humidity | Humidity Sensor Value | 2 Bytes | 9.7 humidity (%) | CW |
| 61 | [HT1] [F] High Humidity Alarm Threshold | Value of High Humidity Alarm Threshold | 2 Bytes | 9.7 humidity (%) | CRWTU |
| 62 | [HT1] [F] Dehumidification Control | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRWTU |
| 63 | [HT1] [F] Dehumidification Status | 0 = No Dehumidifying; 1 = Dehumidifying | 1 Bit | 1.2 boolean | CRT |
| 64 | [HT1] [F] High Humidity | 0 = No Alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CRT |
| 65 | [HT1] [F] Enable Apparent Temperature | 0 = Room Temperature; 1 = Apparent Temperature | 1 Bit | 1.3 enable | CRWTU |
| 66 | [HT1] [Cooling] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 67 | [HT1] [Heating] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 68 | [HT1] [Cooling] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 68 | [HT1] [Cooling] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 69 | [HT1] [Heating] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 69 | [HT1] [Heating] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 70 | [HT1] [Cooling] Additional Cool | Temp >= (Setpoint+Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 71 | [HT1] [Heating] Additional Heat | Temp <= (Setpoint-Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 72 | [HT1] [Cooling] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 73 | [HT1] [Heating] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 74 | [HT2] [A] On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 75 | [HT2] [A] On/Off Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 76 | [HT2] [A] Scene Input | Scene Value | 1 Byte | 18.1 scene control | CW |
| 77 | [HT2] [A] Temperature Source 1 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 78 | [HT2] [A] Temperature Source 2 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 79 | [HT2] [A] Room Temperature | Current Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 80 | [HT2] [A] System Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 81 | [HT2] [A] User Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 82 | [HT2] [A] Force System Mode | 0 = User Mode / Auto Change; 1 = System Mode | 1 Bit | 1.1 switch | CRW |
| 83 | [HT2] [A] Mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 84 | [HT2] [A] Fan Speed | 0% - 100% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 85 | [HT2] [A] Fan: Manual/Automatic | 0 = Manual; 1 = Automatic | 1 Bit | 1.3 enable | CWTU |
| 85 | [HT2] [A] Fan: Manual/Automatic | 0 = Automatic; 1 = Manual | 1 Bit | 1.3 enable | CWTU |
| 86 | [HT2] [A] On/Off Fancoil | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 87 | [HT2] [B] User Comfort Setpoint Reset | 0 = Nothing; 1 = Reset | 1 Bit | 1.15 reset | CW |
| 88 | [HT2] [B] User Setpoint Control | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 88 | [HT2] [B] User Setpoint Offset | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 89 | [HT2] [B] Step User Setpoint | 0 = Decrease; 1 = Increase | 1 Bit | 1.7 step | CW |
| 90 | [HT2] [B] Comfort Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 90 | [HT2] [B] Comfort Setpoint | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 91 | [HT2] [B] Standby Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 92 | [HT2] [B] Economy Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 93 | [HT2] [B] Protection Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 94 | [HT2] [B] Comfort Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 95 | [HT2] [B] Standby Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 96 | [HT2] [B] Economy Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 97 | [HT2] [B] Protection Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 98 | [HT2] [B] Real Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 99 | [HT2] [B] User Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 99 | [HT2] [B] User Setpoint Offset Status | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 100 | [HT2] [C] Transition Time: Comfort to Default Mode | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 100 | [HT2] [C] Transition Time: Comfort to Default Mode | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 100 | [HT2] [C] Transition Time: Comfort to Default Mode | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 101 | [HT2] [C] Transition Time: Standby to Economy | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 101 | [HT2] [C] Transition Time: Standby to Economy | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 101 | [HT2] [C] Transition Time: Standby to Economy | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 102 | [HT2] [C] Comfort Setpoint Reset Time | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 102 | [HT2] [C] Comfort Setpoint Reset Time | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 102 | [HT2] [C] Comfort Setpoint Reset Time | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 103 | [HT2] [C] Presence Detector (Input) | 0 = Not Occupied; 1 = Occupied | 1 Bit | 1.18 occupancy | CRW |
| 104 | [HT2] [C] Lock Presence Detection | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 104 | [HT2] [C] Lock Presence Detection | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 105 | [HT2] [C] Sold/Unsold Room (Input) | 0 = Unsold; 1 = Sold | 1 Bit | 1.2 boolean | CRW |
| 106 | [HT2] [D] Special Mode | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CW |
| 107 | [HT2] [D] Special Mode: Comfort | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 107 | [HT2] [D] Special Mode: Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 108 | [HT2] [D] Special Mode: Standby | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 108 | [HT2] [D] Special Mode: Standby | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 109 | [HT2] [D] Special Mode: Economy | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 109 | [HT2] [D] Special Mode: Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 110 | [HT2] [D] Special Mode: Protection | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 110 | [HT2] [D] Special Mode: Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 111 | [HT2] [D] Special Mode Status | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 112 | [HT2] [D] Comfort Mode Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 113 | [HT2] [D] Window Status 1 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 113 | [HT2] [D] Window Status 1 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 114 | [HT2] [D] Window Status 2 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 114 | [HT2] [D] Window Status 2 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 115 | [HT2] [D] Window Status 3 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 115 | [HT2] [D] Window Status 3 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 116 | [HT2] [D] Window Status 4 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 116 | [HT2] [D] Window Status 4 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 117 | [HT2] [D] Enable Window Status | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRW |
| 118 | [HT2] [D] Thermostat Lock | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 118 | [HT2] [D] Thermostat Lock | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 119 | [HT2] [D] Comfort Lower Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 120 | [HT2] [D] Comfort Upper Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 121 | [HT2] [D] Hidden Offset On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRW |
| 122 | [HT2] [D] Hidden Offset Value | [-20°C, 100°C] | 2 Bytes | 9.2 temperature difference (K) | CRWTU |
| 123 | [HT2] [D] Eco Mode Notification | 0 = Out of eco range; 1 = Setpoint in Eco Range | 1 Bit | 1.2 boolean | CRT |
| 124 | [HT2] [D] Eco Mode Ratio | Percentage of Time Working in Eco Range | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 125 | [HT2] [D] Eco Mode: Lower Limit (Cooling) | Lower Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 126 | [HT2] [D] Eco Mode: Upper Limit (Heating) | Upper Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 127 | [HT2] [D] Setpoint to Split | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 128 | [HT2] [F] Current Humidity | Humidity Sensor Value | 2 Bytes | 9.7 humidity (%) | CW |
| 129 | [HT2] [F] High Humidity Alarm Threshold | Value of High Humidity Alarm Threshold | 2 Bytes | 9.7 humidity (%) | CRWTU |
| 130 | [HT2] [F] Dehumidification Control | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRWTU |
| 131 | [HT2] [F] Dehumidification Status | 0 = No Dehumidifying; 1 = Dehumidifying | 1 Bit | 1.2 boolean | CRT |
| 132 | [HT2] [F] High Humidity | 0 = No Alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CRT |
| 133 | [HT2] [F] Enable Apparent Temperature | 0 = Room Temperature; 1 = Apparent Temperature | 1 Bit | 1.3 enable | CRWTU |
| 134 | [HT2] [Cooling] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 135 | [HT2] [Heating] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 136 | [HT2] [Cooling] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 136 | [HT2] [Cooling] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 137 | [HT2] [Heating] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 137 | [HT2] [Heating] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 138 | [HT2] [Cooling] Additional Cool | Temp >= (Setpoint+Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 139 | [HT2] [Heating] Additional Heat | Temp <= (Setpoint-Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 140 | [HT2] [Cooling] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 141 | [HT2] [Heating] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 142 | [HT3] [A] On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 143 | [HT3] [A] On/Off Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 144 | [HT3] [A] Scene Input | Scene Value | 1 Byte | 18.1 scene control | CW |
| 145 | [HT3] [A] Temperature Source 1 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 146 | [HT3] [A] Temperature Source 2 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 147 | [HT3] [A] Room Temperature | Current Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 148 | [HT3] [A] System Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 149 | [HT3] [A] User Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 150 | [HT3] [A] Force System Mode | 0 = User Mode / Auto Change; 1 = System Mode | 1 Bit | 1.1 switch | CRW |
| 151 | [HT3] [A] Mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 152 | [HT3] [A] Fan Speed | 0% - 100% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 153 | [HT3] [A] Fan: Manual/Automatic | 0 = Manual; 1 = Automatic | 1 Bit | 1.3 enable | CWTU |
| 153 | [HT3] [A] Fan: Manual/Automatic | 0 = Automatic; 1 = Manual | 1 Bit | 1.3 enable | CWTU |
| 154 | [HT3] [A] On/Off Fancoil | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 155 | [HT3] [B] User Comfort Setpoint Reset | 0 = Nothing; 1 = Reset | 1 Bit | 1.15 reset | CW |
| 156 | [HT3] [B] User Setpoint Control | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 156 | [HT3] [B] User Setpoint Offset | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 157 | [HT3] [B] Step User Setpoint | 0 = Decrease; 1 = Increase | 1 Bit | 1.7 step | CW |
| 158 | [HT3] [B] Comfort Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 158 | [HT3] [B] Comfort Setpoint | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 159 | [HT3] [B] Standby Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 160 | [HT3] [B] Economy Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 161 | [HT3] [B] Protection Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 162 | [HT3] [B] Comfort Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 163 | [HT3] [B] Standby Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 164 | [HT3] [B] Economy Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 165 | [HT3] [B] Protection Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 166 | [HT3] [B] Real Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 167 | [HT3] [B] User Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 167 | [HT3] [B] User Setpoint Offset Status | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 168 | [HT3] [C] Transition Time: Comfort to Default Mode | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 168 | [HT3] [C] Transition Time: Comfort to Default Mode | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 168 | [HT3] [C] Transition Time: Comfort to Default Mode | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 169 | [HT3] [C] Transition Time: Standby to Economy | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 169 | [HT3] [C] Transition Time: Standby to Economy | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 169 | [HT3] [C] Transition Time: Standby to Economy | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 170 | [HT3] [C] Comfort Setpoint Reset Time | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 170 | [HT3] [C] Comfort Setpoint Reset Time | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 170 | [HT3] [C] Comfort Setpoint Reset Time | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 171 | [HT3] [C] Presence Detector (Input) | 0 = Not Occupied; 1 = Occupied | 1 Bit | 1.18 occupancy | CRW |
| 172 | [HT3] [C] Lock Presence Detection | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 172 | [HT3] [C] Lock Presence Detection | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 173 | [HT3] [C] Sold/Unsold Room (Input) | 0 = Unsold; 1 = Sold | 1 Bit | 1.2 boolean | CRW |
| 174 | [HT3] [D] Special Mode | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CW |
| 175 | [HT3] [D] Special Mode: Comfort | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 175 | [HT3] [D] Special Mode: Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 176 | [HT3] [D] Special Mode: Standby | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 176 | [HT3] [D] Special Mode: Standby | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 177 | [HT3] [D] Special Mode: Economy | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 177 | [HT3] [D] Special Mode: Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 178 | [HT3] [D] Special Mode: Protection | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 178 | [HT3] [D] Special Mode: Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 179 | [HT3] [D] Special Mode Status | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 180 | [HT3] [D] Comfort Mode Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 181 | [HT3] [D] Window Status 1 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 181 | [HT3] [D] Window Status 1 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 182 | [HT3] [D] Window Status 2 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 182 | [HT3] [D] Window Status 2 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 183 | [HT3] [D] Window Status 3 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 183 | [HT3] [D] Window Status 3 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 184 | [HT3] [D] Window Status 4 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 184 | [HT3] [D] Window Status 4 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 185 | [HT3] [D] Enable Window Status | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRW |
| 186 | [HT3] [D] Thermostat Lock | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 186 | [HT3] [D] Thermostat Lock | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 187 | [HT3] [D] Comfort Lower Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 188 | [HT3] [D] Comfort Upper Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 189 | [HT3] [D] Hidden Offset On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRW |
| 190 | [HT3] [D] Hidden Offset Value | [-20°C, 100°C] | 2 Bytes | 9.2 temperature difference (K) | CRWTU |
| 191 | [HT3] [D] Eco Mode Notification | 0 = Out of eco range; 1 = Setpoint in Eco Range | 1 Bit | 1.2 boolean | CRT |
| 192 | [HT3] [D] Eco Mode Ratio | Percentage of Time Working in Eco Range | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 193 | [HT3] [D] Eco Mode: Lower Limit (Cooling) | Lower Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 194 | [HT3] [D] Eco Mode: Upper Limit (Heating) | Upper Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 195 | [HT3] [D] Setpoint to Split | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 196 | [HT3] [F] Current Humidity | Humidity Sensor Value | 2 Bytes | 9.7 humidity (%) | CW |
| 197 | [HT3] [F] High Humidity Alarm Threshold | Value of High Humidity Alarm Threshold | 2 Bytes | 9.7 humidity (%) | CRWTU |
| 198 | [HT3] [F] Dehumidification Control | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRWTU |
| 199 | [HT3] [F] Dehumidification Status | 0 = No Dehumidifying; 1 = Dehumidifying | 1 Bit | 1.2 boolean | CRT |
| 200 | [HT3] [F] High Humidity | 0 = No Alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CRT |
| 201 | [HT3] [F] Enable Apparent Temperature | 0 = Room Temperature; 1 = Apparent Temperature | 1 Bit | 1.3 enable | CRWTU |
| 202 | [HT3] [Cooling] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 203 | [HT3] [Heating] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 204 | [HT3] [Cooling] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 204 | [HT3] [Cooling] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 205 | [HT3] [Heating] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 205 | [HT3] [Heating] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 206 | [HT3] [Cooling] Additional Cool | Temp >= (Setpoint+Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 207 | [HT3] [Heating] Additional Heat | Temp <= (Setpoint-Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 208 | [HT3] [Cooling] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 209 | [HT3] [Heating] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 210 | [HT4] [A] On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 211 | [HT4] [A] On/Off Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 212 | [HT4] [A] Scene Input | Scene Value | 1 Byte | 18.1 scene control | CW |
| 213 | [HT4] [A] Temperature Source 1 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 214 | [HT4] [A] Temperature Source 2 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 215 | [HT4] [A] Room Temperature | Current Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 216 | [HT4] [A] System Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 217 | [HT4] [A] User Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 218 | [HT4] [A] Force System Mode | 0 = User Mode / Auto Change; 1 = System Mode | 1 Bit | 1.1 switch | CRW |
| 219 | [HT4] [A] Mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 220 | [HT4] [A] Fan Speed | 0% - 100% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 221 | [HT4] [A] Fan: Manual/Automatic | 0 = Manual; 1 = Automatic | 1 Bit | 1.3 enable | CWTU |
| 221 | [HT4] [A] Fan: Manual/Automatic | 0 = Automatic; 1 = Manual | 1 Bit | 1.3 enable | CWTU |
| 222 | [HT4] [A] On/Off Fancoil | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 223 | [HT4] [B] User Comfort Setpoint Reset | 0 = Nothing; 1 = Reset | 1 Bit | 1.15 reset | CW |
| 224 | [HT4] [B] User Setpoint Control | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 224 | [HT4] [B] User Setpoint Offset | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 225 | [HT4] [B] Step User Setpoint | 0 = Decrease; 1 = Increase | 1 Bit | 1.7 step | CW |
| 226 | [HT4] [B] Comfort Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 226 | [HT4] [B] Comfort Setpoint | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 227 | [HT4] [B] Standby Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 228 | [HT4] [B] Economy Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 229 | [HT4] [B] Protection Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 230 | [HT4] [B] Comfort Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 231 | [HT4] [B] Standby Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 232 | [HT4] [B] Economy Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 233 | [HT4] [B] Protection Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 234 | [HT4] [B] Real Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 235 | [HT4] [B] User Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 235 | [HT4] [B] User Setpoint Offset Status | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 236 | [HT4] [C] Transition Time: Comfort to Default Mode | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 236 | [HT4] [C] Transition Time: Comfort to Default Mode | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 236 | [HT4] [C] Transition Time: Comfort to Default Mode | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 237 | [HT4] [C] Transition Time: Standby to Economy | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 237 | [HT4] [C] Transition Time: Standby to Economy | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 237 | [HT4] [C] Transition Time: Standby to Economy | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 238 | [HT4] [C] Comfort Setpoint Reset Time | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 238 | [HT4] [C] Comfort Setpoint Reset Time | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 238 | [HT4] [C] Comfort Setpoint Reset Time | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 239 | [HT4] [C] Presence Detector (Input) | 0 = Not Occupied; 1 = Occupied | 1 Bit | 1.18 occupancy | CRW |
| 240 | [HT4] [C] Lock Presence Detection | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 240 | [HT4] [C] Lock Presence Detection | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 241 | [HT4] [C] Sold/Unsold Room (Input) | 0 = Unsold; 1 = Sold | 1 Bit | 1.2 boolean | CRW |
| 242 | [HT4] [D] Special Mode | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CW |
| 243 | [HT4] [D] Special Mode: Comfort | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 243 | [HT4] [D] Special Mode: Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 244 | [HT4] [D] Special Mode: Standby | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 244 | [HT4] [D] Special Mode: Standby | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 245 | [HT4] [D] Special Mode: Economy | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 245 | [HT4] [D] Special Mode: Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 246 | [HT4] [D] Special Mode: Protection | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 246 | [HT4] [D] Special Mode: Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 247 | [HT4] [D] Special Mode Status | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 248 | [HT4] [D] Comfort Mode Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 249 | [HT4] [D] Window Status 1 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 249 | [HT4] [D] Window Status 1 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 250 | [HT4] [D] Window Status 2 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 250 | [HT4] [D] Window Status 2 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 251 | [HT4] [D] Window Status 3 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 251 | [HT4] [D] Window Status 3 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 252 | [HT4] [D] Window Status 4 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 252 | [HT4] [D] Window Status 4 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 253 | [HT4] [D] Enable Window Status | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRW |
| 254 | [HT4] [D] Thermostat Lock | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 254 | [HT4] [D] Thermostat Lock | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 255 | [HT4] [D] Comfort Lower Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 256 | [HT4] [D] Comfort Upper Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 257 | [HT4] [D] Hidden Offset On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRW |
| 258 | [HT4] [D] Hidden Offset Value | [-20°C, 100°C] | 2 Bytes | 9.2 temperature difference (K) | CRWTU |
| 259 | [HT4] [D] Eco Mode Notification | 0 = Out of eco range; 1 = Setpoint in Eco Range | 1 Bit | 1.2 boolean | CRT |
| 260 | [HT4] [D] Eco Mode Ratio | Percentage of Time Working in Eco Range | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 261 | [HT4] [D] Eco Mode: Lower Limit (Cooling) | Lower Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 262 | [HT4] [D] Eco Mode: Upper Limit (Heating) | Upper Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 263 | [HT4] [D] Setpoint to Split | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 264 | [HT4] [F] Current Humidity | Humidity Sensor Value | 2 Bytes | 9.7 humidity (%) | CW |
| 265 | [HT4] [F] High Humidity Alarm Threshold | Value of High Humidity Alarm Threshold | 2 Bytes | 9.7 humidity (%) | CRWTU |
| 266 | [HT4] [F] Dehumidification Control | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRWTU |
| 267 | [HT4] [F] Dehumidification Status | 0 = No Dehumidifying; 1 = Dehumidifying | 1 Bit | 1.2 boolean | CRT |
| 268 | [HT4] [F] High Humidity | 0 = No Alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CRT |
| 269 | [HT4] [F] Enable Apparent Temperature | 0 = Room Temperature; 1 = Apparent Temperature | 1 Bit | 1.3 enable | CRWTU |
| 270 | [HT4] [Cooling] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 271 | [HT4] [Heating] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 272 | [HT4] [Cooling] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 272 | [HT4] [Cooling] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 273 | [HT4] [Heating] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 273 | [HT4] [Heating] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 274 | [HT4] [Cooling] Additional Cool | Temp >= (Setpoint+Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 275 | [HT4] [Heating] Additional Heat | Temp <= (Setpoint-Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 276 | [HT4] [Cooling] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 277 | [HT4] [Heating] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 278 | [HT5] [A] On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 279 | [HT5] [A] On/Off Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 280 | [HT5] [A] Scene Input | Scene Value | 1 Byte | 18.1 scene control | CW |
| 281 | [HT5] [A] Temperature Source 1 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 282 | [HT5] [A] Temperature Source 2 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 283 | [HT5] [A] Room Temperature | Current Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 284 | [HT5] [A] System Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 285 | [HT5] [A] User Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 286 | [HT5] [A] Force System Mode | 0 = User Mode / Auto Change; 1 = System Mode | 1 Bit | 1.1 switch | CRW |
| 287 | [HT5] [A] Mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 288 | [HT5] [A] Fan Speed | 0% - 100% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 289 | [HT5] [A] Fan: Manual/Automatic | 0 = Manual; 1 = Automatic | 1 Bit | 1.3 enable | CWTU |
| 289 | [HT5] [A] Fan: Manual/Automatic | 0 = Automatic; 1 = Manual | 1 Bit | 1.3 enable | CWTU |
| 290 | [HT5] [A] On/Off Fancoil | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 291 | [HT5] [B] User Comfort Setpoint Reset | 0 = Nothing; 1 = Reset | 1 Bit | 1.15 reset | CW |
| 292 | [HT5] [B] User Setpoint Control | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 292 | [HT5] [B] User Setpoint Offset | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 293 | [HT5] [B] Step User Setpoint | 0 = Decrease; 1 = Increase | 1 Bit | 1.7 step | CW |
| 294 | [HT5] [B] Comfort Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 294 | [HT5] [B] Comfort Setpoint | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 295 | [HT5] [B] Standby Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 296 | [HT5] [B] Economy Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 297 | [HT5] [B] Protection Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 298 | [HT5] [B] Comfort Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 299 | [HT5] [B] Standby Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 300 | [HT5] [B] Economy Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 301 | [HT5] [B] Protection Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 302 | [HT5] [B] Real Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 303 | [HT5] [B] User Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 303 | [HT5] [B] User Setpoint Offset Status | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 304 | [HT5] [C] Transition Time: Comfort to Default Mode | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 304 | [HT5] [C] Transition Time: Comfort to Default Mode | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 304 | [HT5] [C] Transition Time: Comfort to Default Mode | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 305 | [HT5] [C] Transition Time: Standby to Economy | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 305 | [HT5] [C] Transition Time: Standby to Economy | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 305 | [HT5] [C] Transition Time: Standby to Economy | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 306 | [HT5] [C] Comfort Setpoint Reset Time | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 306 | [HT5] [C] Comfort Setpoint Reset Time | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 306 | [HT5] [C] Comfort Setpoint Reset Time | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 307 | [HT5] [C] Presence Detector (Input) | 0 = Not Occupied; 1 = Occupied | 1 Bit | 1.18 occupancy | CRW |
| 308 | [HT5] [C] Lock Presence Detection | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 308 | [HT5] [C] Lock Presence Detection | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 309 | [HT5] [C] Sold/Unsold Room (Input) | 0 = Unsold; 1 = Sold | 1 Bit | 1.2 boolean | CRW |
| 310 | [HT5] [D] Special Mode | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CW |
| 311 | [HT5] [D] Special Mode: Comfort | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 311 | [HT5] [D] Special Mode: Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 312 | [HT5] [D] Special Mode: Standby | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 312 | [HT5] [D] Special Mode: Standby | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 313 | [HT5] [D] Special Mode: Economy | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 313 | [HT5] [D] Special Mode: Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 314 | [HT5] [D] Special Mode: Protection | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 314 | [HT5] [D] Special Mode: Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 315 | [HT5] [D] Special Mode Status | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 316 | [HT5] [D] Comfort Mode Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 317 | [HT5] [D] Window Status 1 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 317 | [HT5] [D] Window Status 1 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 318 | [HT5] [D] Window Status 2 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 318 | [HT5] [D] Window Status 2 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 319 | [HT5] [D] Window Status 3 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 319 | [HT5] [D] Window Status 3 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 320 | [HT5] [D] Window Status 4 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 320 | [HT5] [D] Window Status 4 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 321 | [HT5] [D] Enable Window Status | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRW |
| 322 | [HT5] [D] Thermostat Lock | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 322 | [HT5] [D] Thermostat Lock | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 323 | [HT5] [D] Comfort Lower Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 324 | [HT5] [D] Comfort Upper Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 325 | [HT5] [D] Hidden Offset On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRW |
| 326 | [HT5] [D] Hidden Offset Value | [-20°C, 100°C] | 2 Bytes | 9.2 temperature difference (K) | CRWTU |
| 327 | [HT5] [D] Eco Mode Notification | 0 = Out of eco range; 1 = Setpoint in Eco Range | 1 Bit | 1.2 boolean | CRT |
| 328 | [HT5] [D] Eco Mode Ratio | Percentage of Time Working in Eco Range | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 329 | [HT5] [D] Eco Mode: Lower Limit (Cooling) | Lower Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 330 | [HT5] [D] Eco Mode: Upper Limit (Heating) | Upper Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 331 | [HT5] [D] Setpoint to Split | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 332 | [HT5] [F] Current Humidity | Humidity Sensor Value | 2 Bytes | 9.7 humidity (%) | CW |
| 333 | [HT5] [F] High Humidity Alarm Threshold | Value of High Humidity Alarm Threshold | 2 Bytes | 9.7 humidity (%) | CRWTU |
| 334 | [HT5] [F] Dehumidification Control | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRWTU |
| 335 | [HT5] [F] Dehumidification Status | 0 = No Dehumidifying; 1 = Dehumidifying | 1 Bit | 1.2 boolean | CRT |
| 336 | [HT5] [F] High Humidity | 0 = No Alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CRT |
| 337 | [HT5] [F] Enable Apparent Temperature | 0 = Room Temperature; 1 = Apparent Temperature | 1 Bit | 1.3 enable | CRWTU |
| 338 | [HT5] [Cooling] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 339 | [HT5] [Heating] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 340 | [HT5] [Cooling] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 340 | [HT5] [Cooling] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 341 | [HT5] [Heating] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 341 | [HT5] [Heating] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 342 | [HT5] [Cooling] Additional Cool | Temp >= (Setpoint+Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 343 | [HT5] [Heating] Additional Heat | Temp <= (Setpoint-Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 344 | [HT5] [Cooling] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 345 | [HT5] [Heating] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 346 | [HT6] [A] On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 347 | [HT6] [A] On/Off Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 348 | [HT6] [A] Scene Input | Scene Value | 1 Byte | 18.1 scene control | CW |
| 349 | [HT6] [A] Temperature Source 1 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 350 | [HT6] [A] Temperature Source 2 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 351 | [HT6] [A] Room Temperature | Current Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 352 | [HT6] [A] System Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 353 | [HT6] [A] User Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 354 | [HT6] [A] Force System Mode | 0 = User Mode / Auto Change; 1 = System Mode | 1 Bit | 1.1 switch | CRW |
| 355 | [HT6] [A] Mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 356 | [HT6] [A] Fan Speed | 0% - 100% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 357 | [HT6] [A] Fan: Manual/Automatic | 0 = Manual; 1 = Automatic | 1 Bit | 1.3 enable | CWTU |
| 357 | [HT6] [A] Fan: Manual/Automatic | 0 = Automatic; 1 = Manual | 1 Bit | 1.3 enable | CWTU |
| 358 | [HT6] [A] On/Off Fancoil | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 359 | [HT6] [B] User Comfort Setpoint Reset | 0 = Nothing; 1 = Reset | 1 Bit | 1.15 reset | CW |
| 360 | [HT6] [B] User Setpoint Control | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 360 | [HT6] [B] User Setpoint Offset | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 361 | [HT6] [B] Step User Setpoint | 0 = Decrease; 1 = Increase | 1 Bit | 1.7 step | CW |
| 362 | [HT6] [B] Comfort Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 362 | [HT6] [B] Comfort Setpoint | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 363 | [HT6] [B] Standby Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 364 | [HT6] [B] Economy Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 365 | [HT6] [B] Protection Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 366 | [HT6] [B] Comfort Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 367 | [HT6] [B] Standby Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 368 | [HT6] [B] Economy Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 369 | [HT6] [B] Protection Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 370 | [HT6] [B] Real Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 371 | [HT6] [B] User Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 371 | [HT6] [B] User Setpoint Offset Status | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 372 | [HT6] [C] Transition Time: Comfort to Default Mode | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 372 | [HT6] [C] Transition Time: Comfort to Default Mode | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 372 | [HT6] [C] Transition Time: Comfort to Default Mode | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 373 | [HT6] [C] Transition Time: Standby to Economy | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 373 | [HT6] [C] Transition Time: Standby to Economy | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 373 | [HT6] [C] Transition Time: Standby to Economy | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 374 | [HT6] [C] Comfort Setpoint Reset Time | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 374 | [HT6] [C] Comfort Setpoint Reset Time | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 374 | [HT6] [C] Comfort Setpoint Reset Time | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 375 | [HT6] [C] Presence Detector (Input) | 0 = Not Occupied; 1 = Occupied | 1 Bit | 1.18 occupancy | CRW |
| 376 | [HT6] [C] Lock Presence Detection | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 376 | [HT6] [C] Lock Presence Detection | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 377 | [HT6] [C] Sold/Unsold Room (Input) | 0 = Unsold; 1 = Sold | 1 Bit | 1.2 boolean | CRW |
| 378 | [HT6] [D] Special Mode | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CW |
| 379 | [HT6] [D] Special Mode: Comfort | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 379 | [HT6] [D] Special Mode: Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 380 | [HT6] [D] Special Mode: Standby | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 380 | [HT6] [D] Special Mode: Standby | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 381 | [HT6] [D] Special Mode: Economy | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 381 | [HT6] [D] Special Mode: Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 382 | [HT6] [D] Special Mode: Protection | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 382 | [HT6] [D] Special Mode: Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 383 | [HT6] [D] Special Mode Status | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 384 | [HT6] [D] Comfort Mode Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 385 | [HT6] [D] Window Status 1 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 385 | [HT6] [D] Window Status 1 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 386 | [HT6] [D] Window Status 2 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 386 | [HT6] [D] Window Status 2 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 387 | [HT6] [D] Window Status 3 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 387 | [HT6] [D] Window Status 3 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 388 | [HT6] [D] Window Status 4 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 388 | [HT6] [D] Window Status 4 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 389 | [HT6] [D] Enable Window Status | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRW |
| 390 | [HT6] [D] Thermostat Lock | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 390 | [HT6] [D] Thermostat Lock | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 391 | [HT6] [D] Comfort Lower Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 392 | [HT6] [D] Comfort Upper Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 393 | [HT6] [D] Hidden Offset On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRW |
| 394 | [HT6] [D] Hidden Offset Value | [-20°C, 100°C] | 2 Bytes | 9.2 temperature difference (K) | CRWTU |
| 395 | [HT6] [D] Eco Mode Notification | 0 = Out of eco range; 1 = Setpoint in Eco Range | 1 Bit | 1.2 boolean | CRT |
| 396 | [HT6] [D] Eco Mode Ratio | Percentage of Time Working in Eco Range | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 397 | [HT6] [D] Eco Mode: Lower Limit (Cooling) | Lower Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 398 | [HT6] [D] Eco Mode: Upper Limit (Heating) | Upper Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 399 | [HT6] [D] Setpoint to Split | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 400 | [HT6] [F] Current Humidity | Humidity Sensor Value | 2 Bytes | 9.7 humidity (%) | CW |
| 401 | [HT6] [F] High Humidity Alarm Threshold | Value of High Humidity Alarm Threshold | 2 Bytes | 9.7 humidity (%) | CRWTU |
| 402 | [HT6] [F] Dehumidification Control | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRWTU |
| 403 | [HT6] [F] Dehumidification Status | 0 = No Dehumidifying; 1 = Dehumidifying | 1 Bit | 1.2 boolean | CRT |
| 404 | [HT6] [F] High Humidity | 0 = No Alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CRT |
| 405 | [HT6] [F] Enable Apparent Temperature | 0 = Room Temperature; 1 = Apparent Temperature | 1 Bit | 1.3 enable | CRWTU |
| 406 | [HT6] [Cooling] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 407 | [HT6] [Heating] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 408 | [HT6] [Cooling] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 408 | [HT6] [Cooling] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 409 | [HT6] [Heating] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 409 | [HT6] [Heating] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 410 | [HT6] [Cooling] Additional Cool | Temp >= (Setpoint+Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 411 | [HT6] [Heating] Additional Heat | Temp <= (Setpoint-Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 412 | [HT6] [Cooling] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 413 | [HT6] [Heating] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 414 | [HT7] [A] On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 415 | [HT7] [A] On/Off Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 416 | [HT7] [A] Scene Input | Scene Value | 1 Byte | 18.1 scene control | CW |
| 417 | [HT7] [A] Temperature Source 1 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 418 | [HT7] [A] Temperature Source 2 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 419 | [HT7] [A] Room Temperature | Current Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 420 | [HT7] [A] System Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 421 | [HT7] [A] User Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 422 | [HT7] [A] Force System Mode | 0 = User Mode / Auto Change; 1 = System Mode | 1 Bit | 1.1 switch | CRW |
| 423 | [HT7] [A] Mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 424 | [HT7] [A] Fan Speed | 0% - 100% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 425 | [HT7] [A] Fan: Manual/Automatic | 0 = Manual; 1 = Automatic | 1 Bit | 1.3 enable | CWTU |
| 425 | [HT7] [A] Fan: Manual/Automatic | 0 = Automatic; 1 = Manual | 1 Bit | 1.3 enable | CWTU |
| 426 | [HT7] [A] On/Off Fancoil | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 427 | [HT7] [B] User Comfort Setpoint Reset | 0 = Nothing; 1 = Reset | 1 Bit | 1.15 reset | CW |
| 428 | [HT7] [B] User Setpoint Control | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 428 | [HT7] [B] User Setpoint Offset | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 429 | [HT7] [B] Step User Setpoint | 0 = Decrease; 1 = Increase | 1 Bit | 1.7 step | CW |
| 430 | [HT7] [B] Comfort Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 430 | [HT7] [B] Comfort Setpoint | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 431 | [HT7] [B] Standby Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 432 | [HT7] [B] Economy Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 433 | [HT7] [B] Protection Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 434 | [HT7] [B] Comfort Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 435 | [HT7] [B] Standby Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 436 | [HT7] [B] Economy Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 437 | [HT7] [B] Protection Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 438 | [HT7] [B] Real Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 439 | [HT7] [B] User Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 439 | [HT7] [B] User Setpoint Offset Status | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 440 | [HT7] [C] Transition Time: Comfort to Default Mode | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 440 | [HT7] [C] Transition Time: Comfort to Default Mode | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 440 | [HT7] [C] Transition Time: Comfort to Default Mode | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 441 | [HT7] [C] Transition Time: Standby to Economy | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 441 | [HT7] [C] Transition Time: Standby to Economy | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 441 | [HT7] [C] Transition Time: Standby to Economy | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 442 | [HT7] [C] Comfort Setpoint Reset Time | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 442 | [HT7] [C] Comfort Setpoint Reset Time | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 442 | [HT7] [C] Comfort Setpoint Reset Time | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 443 | [HT7] [C] Presence Detector (Input) | 0 = Not Occupied; 1 = Occupied | 1 Bit | 1.18 occupancy | CRW |
| 444 | [HT7] [C] Lock Presence Detection | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 444 | [HT7] [C] Lock Presence Detection | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 445 | [HT7] [C] Sold/Unsold Room (Input) | 0 = Unsold; 1 = Sold | 1 Bit | 1.2 boolean | CRW |
| 446 | [HT7] [D] Special Mode | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CW |
| 447 | [HT7] [D] Special Mode: Comfort | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 447 | [HT7] [D] Special Mode: Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 448 | [HT7] [D] Special Mode: Standby | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 448 | [HT7] [D] Special Mode: Standby | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 449 | [HT7] [D] Special Mode: Economy | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 449 | [HT7] [D] Special Mode: Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 450 | [HT7] [D] Special Mode: Protection | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 450 | [HT7] [D] Special Mode: Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 451 | [HT7] [D] Special Mode Status | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 452 | [HT7] [D] Comfort Mode Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 453 | [HT7] [D] Window Status 1 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 453 | [HT7] [D] Window Status 1 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 454 | [HT7] [D] Window Status 2 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 454 | [HT7] [D] Window Status 2 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 455 | [HT7] [D] Window Status 3 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 455 | [HT7] [D] Window Status 3 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 456 | [HT7] [D] Window Status 4 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 456 | [HT7] [D] Window Status 4 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 457 | [HT7] [D] Enable Window Status | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRW |
| 458 | [HT7] [D] Thermostat Lock | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 458 | [HT7] [D] Thermostat Lock | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 459 | [HT7] [D] Comfort Lower Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 460 | [HT7] [D] Comfort Upper Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 461 | [HT7] [D] Hidden Offset On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRW |
| 462 | [HT7] [D] Hidden Offset Value | [-20°C, 100°C] | 2 Bytes | 9.2 temperature difference (K) | CRWTU |
| 463 | [HT7] [D] Eco Mode Notification | 0 = Out of eco range; 1 = Setpoint in Eco Range | 1 Bit | 1.2 boolean | CRT |
| 464 | [HT7] [D] Eco Mode Ratio | Percentage of Time Working in Eco Range | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 465 | [HT7] [D] Eco Mode: Lower Limit (Cooling) | Lower Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 466 | [HT7] [D] Eco Mode: Upper Limit (Heating) | Upper Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 467 | [HT7] [D] Setpoint to Split | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 468 | [HT7] [F] Current Humidity | Humidity Sensor Value | 2 Bytes | 9.7 humidity (%) | CW |
| 469 | [HT7] [F] High Humidity Alarm Threshold | Value of High Humidity Alarm Threshold | 2 Bytes | 9.7 humidity (%) | CRWTU |
| 470 | [HT7] [F] Dehumidification Control | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRWTU |
| 471 | [HT7] [F] Dehumidification Status | 0 = No Dehumidifying; 1 = Dehumidifying | 1 Bit | 1.2 boolean | CRT |
| 472 | [HT7] [F] High Humidity | 0 = No Alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CRT |
| 473 | [HT7] [F] Enable Apparent Temperature | 0 = Room Temperature; 1 = Apparent Temperature | 1 Bit | 1.3 enable | CRWTU |
| 474 | [HT7] [Cooling] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 475 | [HT7] [Heating] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 476 | [HT7] [Cooling] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 476 | [HT7] [Cooling] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 477 | [HT7] [Heating] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 477 | [HT7] [Heating] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 478 | [HT7] [Cooling] Additional Cool | Temp >= (Setpoint+Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 479 | [HT7] [Heating] Additional Heat | Temp <= (Setpoint-Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 480 | [HT7] [Cooling] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 481 | [HT7] [Heating] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 482 | [HT8] [A] On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 483 | [HT8] [A] On/Off Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 484 | [HT8] [A] Scene Input | Scene Value | 1 Byte | 18.1 scene control | CW |
| 485 | [HT8] [A] Temperature Source 1 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 486 | [HT8] [A] Temperature Source 2 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 487 | [HT8] [A] Room Temperature | Current Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 488 | [HT8] [A] System Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 489 | [HT8] [A] User Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 490 | [HT8] [A] Force System Mode | 0 = User Mode / Auto Change; 1 = System Mode | 1 Bit | 1.1 switch | CRW |
| 491 | [HT8] [A] Mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 492 | [HT8] [A] Fan Speed | 0% - 100% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 493 | [HT8] [A] Fan: Manual/Automatic | 0 = Manual; 1 = Automatic | 1 Bit | 1.3 enable | CWTU |
| 493 | [HT8] [A] Fan: Manual/Automatic | 0 = Automatic; 1 = Manual | 1 Bit | 1.3 enable | CWTU |
| 494 | [HT8] [A] On/Off Fancoil | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 495 | [HT8] [B] User Comfort Setpoint Reset | 0 = Nothing; 1 = Reset | 1 Bit | 1.15 reset | CW |
| 496 | [HT8] [B] User Setpoint Control | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 496 | [HT8] [B] User Setpoint Offset | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 497 | [HT8] [B] Step User Setpoint | 0 = Decrease; 1 = Increase | 1 Bit | 1.7 step | CW |
| 498 | [HT8] [B] Comfort Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 498 | [HT8] [B] Comfort Setpoint | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 499 | [HT8] [B] Standby Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 500 | [HT8] [B] Economy Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 501 | [HT8] [B] Protection Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 502 | [HT8] [B] Comfort Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 503 | [HT8] [B] Standby Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 504 | [HT8] [B] Economy Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 505 | [HT8] [B] Protection Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 506 | [HT8] [B] Real Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 507 | [HT8] [B] User Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 507 | [HT8] [B] User Setpoint Offset Status | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 508 | [HT8] [C] Transition Time: Comfort to Default Mode | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 508 | [HT8] [C] Transition Time: Comfort to Default Mode | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 508 | [HT8] [C] Transition Time: Comfort to Default Mode | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 509 | [HT8] [C] Transition Time: Standby to Economy | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 509 | [HT8] [C] Transition Time: Standby to Economy | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 509 | [HT8] [C] Transition Time: Standby to Economy | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 510 | [HT8] [C] Comfort Setpoint Reset Time | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 510 | [HT8] [C] Comfort Setpoint Reset Time | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 510 | [HT8] [C] Comfort Setpoint Reset Time | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 511 | [HT8] [C] Presence Detector (Input) | 0 = Not Occupied; 1 = Occupied | 1 Bit | 1.18 occupancy | CRW |
| 512 | [HT8] [C] Lock Presence Detection | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 512 | [HT8] [C] Lock Presence Detection | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 513 | [HT8] [C] Sold/Unsold Room (Input) | 0 = Unsold; 1 = Sold | 1 Bit | 1.2 boolean | CRW |
| 514 | [HT8] [D] Special Mode | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CW |
| 515 | [HT8] [D] Special Mode: Comfort | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 515 | [HT8] [D] Special Mode: Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 516 | [HT8] [D] Special Mode: Standby | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 516 | [HT8] [D] Special Mode: Standby | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 517 | [HT8] [D] Special Mode: Economy | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 517 | [HT8] [D] Special Mode: Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 518 | [HT8] [D] Special Mode: Protection | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 518 | [HT8] [D] Special Mode: Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 519 | [HT8] [D] Special Mode Status | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 520 | [HT8] [D] Comfort Mode Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 521 | [HT8] [D] Window Status 1 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 521 | [HT8] [D] Window Status 1 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 522 | [HT8] [D] Window Status 2 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 522 | [HT8] [D] Window Status 2 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 523 | [HT8] [D] Window Status 3 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 523 | [HT8] [D] Window Status 3 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 524 | [HT8] [D] Window Status 4 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 524 | [HT8] [D] Window Status 4 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 525 | [HT8] [D] Enable Window Status | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRW |
| 526 | [HT8] [D] Thermostat Lock | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 526 | [HT8] [D] Thermostat Lock | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 527 | [HT8] [D] Comfort Lower Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 528 | [HT8] [D] Comfort Upper Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 529 | [HT8] [D] Hidden Offset On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRW |
| 530 | [HT8] [D] Hidden Offset Value | [-20°C, 100°C] | 2 Bytes | 9.2 temperature difference (K) | CRWTU |
| 531 | [HT8] [D] Eco Mode Notification | 0 = Out of eco range; 1 = Setpoint in Eco Range | 1 Bit | 1.2 boolean | CRT |
| 532 | [HT8] [D] Eco Mode Ratio | Percentage of Time Working in Eco Range | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 533 | [HT8] [D] Eco Mode: Lower Limit (Cooling) | Lower Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 534 | [HT8] [D] Eco Mode: Upper Limit (Heating) | Upper Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 535 | [HT8] [D] Setpoint to Split | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 536 | [HT8] [F] Current Humidity | Humidity Sensor Value | 2 Bytes | 9.7 humidity (%) | CW |
| 537 | [HT8] [F] High Humidity Alarm Threshold | Value of High Humidity Alarm Threshold | 2 Bytes | 9.7 humidity (%) | CRWTU |
| 538 | [HT8] [F] Dehumidification Control | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRWTU |
| 539 | [HT8] [F] Dehumidification Status | 0 = No Dehumidifying; 1 = Dehumidifying | 1 Bit | 1.2 boolean | CRT |
| 540 | [HT8] [F] High Humidity | 0 = No Alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CRT |
| 541 | [HT8] [F] Enable Apparent Temperature | 0 = Room Temperature; 1 = Apparent Temperature | 1 Bit | 1.3 enable | CRWTU |
| 542 | [HT8] [Cooling] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 543 | [HT8] [Heating] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 544 | [HT8] [Cooling] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 544 | [HT8] [Cooling] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 545 | [HT8] [Heating] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 545 | [HT8] [Heating] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 546 | [HT8] [Cooling] Additional Cool | Temp >= (Setpoint+Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 547 | [HT8] [Heating] Additional Heat | Temp <= (Setpoint-Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 548 | [HT8] [Cooling] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 549 | [HT8] [Heating] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 550 | [HT9] [A] On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 551 | [HT9] [A] On/Off Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 552 | [HT9] [A] Scene Input | Scene Value | 1 Byte | 18.1 scene control | CW |
| 553 | [HT9] [A] Temperature Source 1 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 554 | [HT9] [A] Temperature Source 2 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 555 | [HT9] [A] Room Temperature | Current Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 556 | [HT9] [A] System Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 557 | [HT9] [A] User Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 558 | [HT9] [A] Force System Mode | 0 = User Mode / Auto Change; 1 = System Mode | 1 Bit | 1.1 switch | CRW |
| 559 | [HT9] [A] Mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 560 | [HT9] [A] Fan Speed | 0% - 100% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 561 | [HT9] [A] Fan: Manual/Automatic | 0 = Manual; 1 = Automatic | 1 Bit | 1.3 enable | CWTU |
| 561 | [HT9] [A] Fan: Manual/Automatic | 0 = Automatic; 1 = Manual | 1 Bit | 1.3 enable | CWTU |
| 562 | [HT9] [A] On/Off Fancoil | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 563 | [HT9] [B] User Comfort Setpoint Reset | 0 = Nothing; 1 = Reset | 1 Bit | 1.15 reset | CW |
| 564 | [HT9] [B] User Setpoint Control | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 564 | [HT9] [B] User Setpoint Offset | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 565 | [HT9] [B] Step User Setpoint | 0 = Decrease; 1 = Increase | 1 Bit | 1.7 step | CW |
| 566 | [HT9] [B] Comfort Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 566 | [HT9] [B] Comfort Setpoint | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 567 | [HT9] [B] Standby Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 568 | [HT9] [B] Economy Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 569 | [HT9] [B] Protection Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 570 | [HT9] [B] Comfort Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 571 | [HT9] [B] Standby Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 572 | [HT9] [B] Economy Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 573 | [HT9] [B] Protection Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 574 | [HT9] [B] Real Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 575 | [HT9] [B] User Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 575 | [HT9] [B] User Setpoint Offset Status | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 576 | [HT9] [C] Transition Time: Comfort to Default Mode | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 576 | [HT9] [C] Transition Time: Comfort to Default Mode | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 576 | [HT9] [C] Transition Time: Comfort to Default Mode | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 577 | [HT9] [C] Transition Time: Standby to Economy | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 577 | [HT9] [C] Transition Time: Standby to Economy | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 577 | [HT9] [C] Transition Time: Standby to Economy | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 578 | [HT9] [C] Comfort Setpoint Reset Time | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 578 | [HT9] [C] Comfort Setpoint Reset Time | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 578 | [HT9] [C] Comfort Setpoint Reset Time | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 579 | [HT9] [C] Presence Detector (Input) | 0 = Not Occupied; 1 = Occupied | 1 Bit | 1.18 occupancy | CRW |
| 580 | [HT9] [C] Lock Presence Detection | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 580 | [HT9] [C] Lock Presence Detection | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 581 | [HT9] [C] Sold/Unsold Room (Input) | 0 = Unsold; 1 = Sold | 1 Bit | 1.2 boolean | CRW |
| 582 | [HT9] [D] Special Mode | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CW |
| 583 | [HT9] [D] Special Mode: Comfort | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 583 | [HT9] [D] Special Mode: Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 584 | [HT9] [D] Special Mode: Standby | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 584 | [HT9] [D] Special Mode: Standby | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 585 | [HT9] [D] Special Mode: Economy | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 585 | [HT9] [D] Special Mode: Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 586 | [HT9] [D] Special Mode: Protection | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 586 | [HT9] [D] Special Mode: Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 587 | [HT9] [D] Special Mode Status | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 588 | [HT9] [D] Comfort Mode Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 589 | [HT9] [D] Window Status 1 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 589 | [HT9] [D] Window Status 1 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 590 | [HT9] [D] Window Status 2 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 590 | [HT9] [D] Window Status 2 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 591 | [HT9] [D] Window Status 3 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 591 | [HT9] [D] Window Status 3 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 592 | [HT9] [D] Window Status 4 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 592 | [HT9] [D] Window Status 4 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 593 | [HT9] [D] Enable Window Status | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRW |
| 594 | [HT9] [D] Thermostat Lock | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 594 | [HT9] [D] Thermostat Lock | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 595 | [HT9] [D] Comfort Lower Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 596 | [HT9] [D] Comfort Upper Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 597 | [HT9] [D] Hidden Offset On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRW |
| 598 | [HT9] [D] Hidden Offset Value | [-20°C, 100°C] | 2 Bytes | 9.2 temperature difference (K) | CRWTU |
| 599 | [HT9] [D] Eco Mode Notification | 0 = Out of eco range; 1 = Setpoint in Eco Range | 1 Bit | 1.2 boolean | CRT |
| 600 | [HT9] [D] Eco Mode Ratio | Percentage of Time Working in Eco Range | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 601 | [HT9] [D] Eco Mode: Lower Limit (Cooling) | Lower Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 602 | [HT9] [D] Eco Mode: Upper Limit (Heating) | Upper Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 603 | [HT9] [D] Setpoint to Split | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 604 | [HT9] [F] Current Humidity | Humidity Sensor Value | 2 Bytes | 9.7 humidity (%) | CW |
| 605 | [HT9] [F] High Humidity Alarm Threshold | Value of High Humidity Alarm Threshold | 2 Bytes | 9.7 humidity (%) | CRWTU |
| 606 | [HT9] [F] Dehumidification Control | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRWTU |
| 607 | [HT9] [F] Dehumidification Status | 0 = No Dehumidifying; 1 = Dehumidifying | 1 Bit | 1.2 boolean | CRT |
| 608 | [HT9] [F] High Humidity | 0 = No Alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CRT |
| 609 | [HT9] [F] Enable Apparent Temperature | 0 = Room Temperature; 1 = Apparent Temperature | 1 Bit | 1.3 enable | CRWTU |
| 610 | [HT9] [Cooling] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 611 | [HT9] [Heating] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 612 | [HT9] [Cooling] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 612 | [HT9] [Cooling] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 613 | [HT9] [Heating] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 613 | [HT9] [Heating] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 614 | [HT9] [Cooling] Additional Cool | Temp >= (Setpoint+Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 615 | [HT9] [Heating] Additional Heat | Temp <= (Setpoint-Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 616 | [HT9] [Cooling] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 617 | [HT9] [Heating] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 618 | [HT10] [A] On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 619 | [HT10] [A] On/Off Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 620 | [HT10] [A] Scene Input | Scene Value | 1 Byte | 18.1 scene control | CW |
| 621 | [HT10] [A] Temperature Source 1 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 622 | [HT10] [A] Temperature Source 2 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 623 | [HT10] [A] Room Temperature | Current Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 624 | [HT10] [A] System Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 625 | [HT10] [A] User Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 626 | [HT10] [A] Force System Mode | 0 = User Mode / Auto Change; 1 = System Mode | 1 Bit | 1.1 switch | CRW |
| 627 | [HT10] [A] Mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 628 | [HT10] [A] Fan Speed | 0% - 100% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 629 | [HT10] [A] Fan: Manual/Automatic | 0 = Manual; 1 = Automatic | 1 Bit | 1.3 enable | CWTU |
| 629 | [HT10] [A] Fan: Manual/Automatic | 0 = Automatic; 1 = Manual | 1 Bit | 1.3 enable | CWTU |
| 630 | [HT10] [A] On/Off Fancoil | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 631 | [HT10] [B] User Comfort Setpoint Reset | 0 = Nothing; 1 = Reset | 1 Bit | 1.15 reset | CW |
| 632 | [HT10] [B] User Setpoint Control | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 632 | [HT10] [B] User Setpoint Offset | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 633 | [HT10] [B] Step User Setpoint | 0 = Decrease; 1 = Increase | 1 Bit | 1.7 step | CW |
| 634 | [HT10] [B] Comfort Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 634 | [HT10] [B] Comfort Setpoint | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 635 | [HT10] [B] Standby Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 636 | [HT10] [B] Economy Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 637 | [HT10] [B] Protection Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 638 | [HT10] [B] Comfort Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 639 | [HT10] [B] Standby Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 640 | [HT10] [B] Economy Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 641 | [HT10] [B] Protection Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 642 | [HT10] [B] Real Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 643 | [HT10] [B] User Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 643 | [HT10] [B] User Setpoint Offset Status | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 644 | [HT10] [C] Transition Time: Comfort to Default Mode | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 644 | [HT10] [C] Transition Time: Comfort to Default Mode | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 644 | [HT10] [C] Transition Time: Comfort to Default Mode | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 645 | [HT10] [C] Transition Time: Standby to Economy | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 645 | [HT10] [C] Transition Time: Standby to Economy | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 645 | [HT10] [C] Transition Time: Standby to Economy | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 646 | [HT10] [C] Comfort Setpoint Reset Time | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 646 | [HT10] [C] Comfort Setpoint Reset Time | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 646 | [HT10] [C] Comfort Setpoint Reset Time | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 647 | [HT10] [C] Presence Detector (Input) | 0 = Not Occupied; 1 = Occupied | 1 Bit | 1.18 occupancy | CRW |
| 648 | [HT10] [C] Lock Presence Detection | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 648 | [HT10] [C] Lock Presence Detection | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 649 | [HT10] [C] Sold/Unsold Room (Input) | 0 = Unsold; 1 = Sold | 1 Bit | 1.2 boolean | CRW |
| 650 | [HT10] [D] Special Mode | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CW |
| 651 | [HT10] [D] Special Mode: Comfort | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 651 | [HT10] [D] Special Mode: Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 652 | [HT10] [D] Special Mode: Standby | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 652 | [HT10] [D] Special Mode: Standby | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 653 | [HT10] [D] Special Mode: Economy | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 653 | [HT10] [D] Special Mode: Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 654 | [HT10] [D] Special Mode: Protection | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 654 | [HT10] [D] Special Mode: Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 655 | [HT10] [D] Special Mode Status | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 656 | [HT10] [D] Comfort Mode Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 657 | [HT10] [D] Window Status 1 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 657 | [HT10] [D] Window Status 1 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 658 | [HT10] [D] Window Status 2 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 658 | [HT10] [D] Window Status 2 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 659 | [HT10] [D] Window Status 3 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 659 | [HT10] [D] Window Status 3 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 660 | [HT10] [D] Window Status 4 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 660 | [HT10] [D] Window Status 4 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 661 | [HT10] [D] Enable Window Status | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRW |
| 662 | [HT10] [D] Thermostat Lock | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 662 | [HT10] [D] Thermostat Lock | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 663 | [HT10] [D] Comfort Lower Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 664 | [HT10] [D] Comfort Upper Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 665 | [HT10] [D] Hidden Offset On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRW |
| 666 | [HT10] [D] Hidden Offset Value | [-20°C, 100°C] | 2 Bytes | 9.2 temperature difference (K) | CRWTU |
| 667 | [HT10] [D] Eco Mode Notification | 0 = Out of eco range; 1 = Setpoint in Eco Range | 1 Bit | 1.2 boolean | CRT |
| 668 | [HT10] [D] Eco Mode Ratio | Percentage of Time Working in Eco Range | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 669 | [HT10] [D] Eco Mode: Lower Limit (Cooling) | Lower Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 670 | [HT10] [D] Eco Mode: Upper Limit (Heating) | Upper Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 671 | [HT10] [D] Setpoint to Split | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 672 | [HT10] [F] Current Humidity | Humidity Sensor Value | 2 Bytes | 9.7 humidity (%) | CW |
| 673 | [HT10] [F] High Humidity Alarm Threshold | Value of High Humidity Alarm Threshold | 2 Bytes | 9.7 humidity (%) | CRWTU |
| 674 | [HT10] [F] Dehumidification Control | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRWTU |
| 675 | [HT10] [F] Dehumidification Status | 0 = No Dehumidifying; 1 = Dehumidifying | 1 Bit | 1.2 boolean | CRT |
| 676 | [HT10] [F] High Humidity | 0 = No Alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CRT |
| 677 | [HT10] [F] Enable Apparent Temperature | 0 = Room Temperature; 1 = Apparent Temperature | 1 Bit | 1.3 enable | CRWTU |
| 678 | [HT10] [Cooling] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 679 | [HT10] [Heating] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 680 | [HT10] [Cooling] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 680 | [HT10] [Cooling] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 681 | [HT10] [Heating] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 681 | [HT10] [Heating] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 682 | [HT10] [Cooling] Additional Cool | Temp >= (Setpoint+Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 683 | [HT10] [Heating] Additional Heat | Temp <= (Setpoint-Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 684 | [HT10] [Cooling] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 685 | [HT10] [Heating] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 686 | [HT11] [A] On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 687 | [HT11] [A] On/Off Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 688 | [HT11] [A] Scene Input | Scene Value | 1 Byte | 18.1 scene control | CW |
| 689 | [HT11] [A] Temperature Source 1 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 690 | [HT11] [A] Temperature Source 2 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 691 | [HT11] [A] Room Temperature | Current Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 692 | [HT11] [A] System Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 693 | [HT11] [A] User Mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRW |
| 694 | [HT11] [A] Force System Mode | 0 = User Mode / Auto Change; 1 = System Mode | 1 Bit | 1.1 switch | CRW |
| 695 | [HT11] [A] Mode Status | 0 = Cooling; 1 = Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 696 | [HT11] [A] Fan Speed | 0% - 100% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 697 | [HT11] [A] Fan: Manual/Automatic | 0 = Manual; 1 = Automatic | 1 Bit | 1.3 enable | CWTU |
| 697 | [HT11] [A] Fan: Manual/Automatic | 0 = Automatic; 1 = Manual | 1 Bit | 1.3 enable | CWTU |
| 698 | [HT11] [A] On/Off Fancoil | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 699 | [HT11] [B] User Comfort Setpoint Reset | 0 = Nothing; 1 = Reset | 1 Bit | 1.15 reset | CW |
| 700 | [HT11] [B] User Setpoint Control | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 700 | [HT11] [B] User Setpoint Offset | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 701 | [HT11] [B] Step User Setpoint | 0 = Decrease; 1 = Increase | 1 Bit | 1.7 step | CW |
| 702 | [HT11] [B] Comfort Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 702 | [HT11] [B] Comfort Setpoint | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 703 | [HT11] [B] Standby Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 704 | [HT11] [B] Economy Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 705 | [HT11] [B] Protection Setpoint (Cooling) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 706 | [HT11] [B] Comfort Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 707 | [HT11] [B] Standby Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 708 | [HT11] [B] Economy Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 709 | [HT11] [B] Protection Setpoint (Heating) | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 710 | [HT11] [B] Real Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 711 | [HT11] [B] User Setpoint Status | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 711 | [HT11] [B] User Setpoint Offset Status | [-15°C, 15°C] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 712 | [HT11] [C] Transition Time: Comfort to Default Mode | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 712 | [HT11] [C] Transition Time: Comfort to Default Mode | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 712 | [HT11] [C] Transition Time: Comfort to Default Mode | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 713 | [HT11] [C] Transition Time: Standby to Economy | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 713 | [HT11] [C] Transition Time: Standby to Economy | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 713 | [HT11] [C] Transition Time: Standby to Economy | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 714 | [HT11] [C] Comfort Setpoint Reset Time | Seconds (0 = Disabled) | 2 Bytes | 7.5 time (s) | CRWTU |
| 714 | [HT11] [C] Comfort Setpoint Reset Time | Minutes (0 = Disabled) | 2 Bytes | 7.6 time (min) | CRWTU |
| 714 | [HT11] [C] Comfort Setpoint Reset Time | Hours (0 = Disabled) | 2 Bytes | 7.7 time (h) | CRWTU |
| 715 | [HT11] [C] Presence Detector (Input) | 0 = Not Occupied; 1 = Occupied | 1 Bit | 1.18 occupancy | CRW |
| 716 | [HT11] [C] Lock Presence Detection | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 716 | [HT11] [C] Lock Presence Detection | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 717 | [HT11] [C] Sold/Unsold Room (Input) | 0 = Unsold; 1 = Sold | 1 Bit | 1.2 boolean | CRW |
| 718 | [HT11] [D] Special Mode | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CW |
| 719 | [HT11] [D] Special Mode: Comfort | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 719 | [HT11] [D] Special Mode: Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 720 | [HT11] [D] Special Mode: Standby | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 720 | [HT11] [D] Special Mode: Standby | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 721 | [HT11] [D] Special Mode: Economy | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 721 | [HT11] [D] Special Mode: Economy | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 722 | [HT11] [D] Special Mode: Protection | 0 = Nothing; 1 = Trigger | 1 Bit | 1.16 acknowledge | CW |
| 722 | [HT11] [D] Special Mode: Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 723 | [HT11] [D] Special Mode Status | 1-byte HVAC Mode | 1 Byte | 20.102 HVAC mode | CRT |
| 724 | [HT11] [D] Comfort Mode Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 725 | [HT11] [D] Window Status 1 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 725 | [HT11] [D] Window Status 1 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 726 | [HT11] [D] Window Status 2 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 726 | [HT11] [D] Window Status 2 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 727 | [HT11] [D] Window Status 3 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 727 | [HT11] [D] Window Status 3 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 728 | [HT11] [D] Window Status 4 (Input) | 0 = Closed; 1 = Open | 1 Bit | 1.19 window/door | CW |
| 728 | [HT11] [D] Window Status 4 (Input) | 0 = Open; 1 = Closed | 1 Bit | 1.19 window/door | CW |
| 729 | [HT11] [D] Enable Window Status | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRW |
| 730 | [HT11] [D] Thermostat Lock | 0 = Locked; 1 = Unlocked | 1 Bit | 1.3 enable | CRW |
| 730 | [HT11] [D] Thermostat Lock | 0 = Unlocked; 1 = Locked | 1 Bit | 1.3 enable | CRW |
| 731 | [HT11] [D] Comfort Lower Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 732 | [HT11] [D] Comfort Upper Limit | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 733 | [HT11] [D] Hidden Offset On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRW |
| 734 | [HT11] [D] Hidden Offset Value | [-20°C, 100°C] | 2 Bytes | 9.2 temperature difference (K) | CRWTU |
| 735 | [HT11] [D] Eco Mode Notification | 0 = Out of eco range; 1 = Setpoint in Eco Range | 1 Bit | 1.2 boolean | CRT |
| 736 | [HT11] [D] Eco Mode Ratio | Percentage of Time Working in Eco Range | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 737 | [HT11] [D] Eco Mode: Lower Limit (Cooling) | Lower Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 738 | [HT11] [D] Eco Mode: Upper Limit (Heating) | Upper Value for the Ecological Range | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 739 | [HT11] [D] Setpoint to Split | [-20°C, 100°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 740 | [HT11] [F] Current Humidity | Humidity Sensor Value | 2 Bytes | 9.7 humidity (%) | CW |
| 741 | [HT11] [F] High Humidity Alarm Threshold | Value of High Humidity Alarm Threshold | 2 Bytes | 9.7 humidity (%) | CRWTU |
| 742 | [HT11] [F] Dehumidification Control | 0 = Disabled; 1 = Enabled | 1 Bit | 1.3 enable | CRWTU |
| 743 | [HT11] [F] Dehumidification Status | 0 = No Dehumidifying; 1 = Dehumidifying | 1 Bit | 1.2 boolean | CRT |
| 744 | [HT11] [F] High Humidity | 0 = No Alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CRT |
| 745 | [HT11] [F] Enable Apparent Temperature | 0 = Room Temperature; 1 = Apparent Temperature | 1 Bit | 1.3 enable | CRWTU |
| 746 | [HT11] [Cooling] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 747 | [HT11] [Heating] Control Variable | PI Control (Continuous) | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 748 | [HT11] [Cooling] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 748 | [HT11] [Cooling] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 749 | [HT11] [Heating] Control Variable | 2-Point Control | 1 Bit | 1.1 switch | CRT |
| 749 | [HT11] [Heating] Control Variable | PI Control (PWM) | 1 Bit | 1.1 switch | CRT |
| 750 | [HT11] [Cooling] Additional Cool | Temp >= (Setpoint+Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 751 | [HT11] [Heating] Additional Heat | Temp <= (Setpoint-Band) => "1" | 1 Bit | 1.1 switch | CRT |
| 752 | [HT11] [Cooling] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 753 | [HT11] [Heating] PI State | 0 = PI Signal 0%; 1 = PI Signal Greater than 0% | 1 Bit | 1.1 switch | CRT |
| 754 | [HT12] [A] On/Off | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 755 | [HT12] [A] On/Off Status | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CRT |
| 756 | [HT12] [A] Scene Input | Scene Value | 1 Byte | 18.1 scene control | CW |
| 757 | [HT12] [A] Temperature Source 1 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 758 | [HT12] [A] Temperature Source 2 | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
First 1000 of 1807 group objects shown. Download the .knxprod for the full list.
Parameters (156)
| Parameter | Type | Default |
|---|---|---|
| Heartbeat (Periodic Alive Notification) | unsignedInt 0…255 | 0 |
| Period | unsignedInt 1…65535 | 1 |
| Synchronize Clock Master via NTP | unsignedInt 0…1 | 0 |
| IP Address of DNS Server 1 | ipAddress | 192.168.1.1 |
| IP Address of DNS Server 2 | ipAddress | 192.168.1.2 |
| Domain/IP of NTP Server 1 | text | 0.pool.ntp.org |
| Domain/IP of NTP Server 2 | text | 1.pool.ntp.org |
| Time Zone | list | (UTC+00:00) Dublin, Edinburgh, Lisbon, London, Reykjavik |
| Offset | signedInt -720…840 | 0 |
| Daylight Saving Time (DST) | unsignedInt 0…1 | 0 |
| Day | list | Last |
| Month | list | March |
| Local Hour | list | 02:00 |
| Month | list | October |
| Summer Time Changeover | list | Europe |
| Send Date/Time after initial connection | unsignedInt 0…1 | 0 |
| Delay | unsignedInt 0…255 | 0 |
| Date and Time Periodical Sending | unsignedInt 0…1 | 1 |
| Value | unsignedInt 0…255 | 10 |
| Value | unsignedInt 0…24 | 1 |
| Fixed Time Sending | unsignedInt 0…1 | 0 |
| Time | time | 0 |
| Send Date/Time after a net reconnection | unsignedInt 0…1 | 0 |
| Enable Debug Objects | unsignedInt 0…1 | 0 |
| Send Time with Changeover | unsignedInt 0…1 | 0 |
| Temperature Source | list | Temperature Source 1 |
| 1-Bit Objects Working Mode (See User Manual) | list | Switch |
| Default Mode | list | Economy |
| Economy Setpoint | float -20…100 | 30 |
| Economy Setpoint | float -20…100 | 16 |
| Thermostat Function | list | Heating and Cooling |
| H/C Automatic Changeover | list | Disabled |
| H/C Mode after Programming | list | Heating |
| Additional Cooling Band | signedInt 5…100 | 25 |
| Additional Heating Band | signedInt -100…-5 | -25 |
| Control Method | list | 2-Point Control |
| Upper Hysteresis | unsignedInt 1…200 | 10 |
| Lower Hysteresis | unsignedInt 1…200 | 10 |
| Control Type | list | Continuous (1 Byte) |
| Control Parameters | list | Cooling Ceiling (5K/240min) |
| Control Parameters | list | Warm Water (5K/150min) |
| Proportional Band | unsignedInt 1…15 | 4 |
| Integral Time | unsignedInt 5…255 | 150 |
| Restart Accumulated Error on Saturation? | list | Yes |
| Thermostat Always On? | list | Yes |
| Startup Setting (on Bus Voltage Recovery) | list | Last (before Bus Failure) |
| Sending Statuses on Bus Voltage Recovery | list | No |
| Sending Delay | unsignedInt 0…255 | 0 |
| Standby Setpoint | float -20…100 | 19 |
| Comfort Setpoint | float -20…100 | 22 |
| Comfort Setpoint | float -20…100 | 24 |
| Standby Setpoint | float -20…100 | 27 |
| Additional Cooling | list | No |
| Additional Heating | list | No |
| Window Status | unsignedInt 0…1 | 0 |
| Resending Period (0 = Disabled) | unsignedInt 0…255 | 0 |
| Control Variables | list | Independent Objects for Heating and Cooling |
| Send both H/C Control Signals Periodically? | list | No |
| PI Cycle | unsignedInt 0…255 | 15 |
| PWM Minimum Time | unsignedInt 1…255 | 10 |
| If the Switching Time Is Lower than the Minimum | list | Switch the Control Signal Using the Minimum Time |
| Scenes | unsignedInt 0…1 | 0 |
| Scene 1 | unsignedInt 0…1 | 0 |
| Scene Number | unsignedInt 1…64 | 1 |
| On/Off | list | Do Not Change |
| H/C Mode | list | Do Not Change |
| Special Mode | list | Do Not Change |
| Scene 2 | unsignedInt 0…1 | 0 |
| Scene 3 | unsignedInt 0…1 | 0 |
| Scene 4 | unsignedInt 0…1 | 0 |
| Scene 5 | unsignedInt 0…1 | 0 |
| Initial Mode (after Programming) | list | Economy |
| Comfort to Default Mode Time (0 = Disabled) | unsignedInt 0…255 | 0 |
| Standby to Economy Time (0 = Disabled) | unsignedInt 0…255 | 0 |
| Time to Reset the User Comfort Setpoint (0 = Disabled) | unsignedInt 0…255 | 0 |
| Setpoint after Returning to Comfort Mode | list | System Comfort (Delayed) |
| User Comfort Setpoint Constraints | unsignedInt 0…1 | 0 |
| Lower Limit | float -20…100 | 15 |
| Upper Limit | float -20…100 | 30 |
| Offset Value | float -20…100 | 2 |
| Cooling Lower Limit | float -20…100 | 23 |
| Heating Upper Limit | float -20…100 | 23 |
| Eco Mode Notification | unsignedInt 0…1 | 0 |
| Hidden Offset | unsignedInt 0…1 | 0 |
| Comfort Lower Band | unsignedInt 0…255 | 30 |
| Comfort Upper Band | unsignedInt 0…255 | 30 |
| Allow Scene Recording | unsignedInt 0…1 | 1 |
| 1-Bit Occupancy Object | unsignedInt 0…1 | 0 |
| Mode to Activate after Switching to Occupied | list | Last Mode |
| Overheating Protection Setpoint | float -20…100 | 35 |
| Freezing Protection Setpoint | float -20…100 | 7 |
| Number of Objects | unsignedInt 1…4 | 1 |
| 1-Byte Special Mode Control | unsignedInt 0…1 | 0 |
| Scenes | unsignedInt 0…1 | 1 |
| Day Occupation (0 = Disabled) | unsignedInt 0…64 | 0 |
| Not Occupied (0 = Disabled) | unsignedInt 0…64 | 0 |
| False Non-Occupied Detection (0 = Disabled) | unsignedInt 0…64 | 0 |
| Restrict the State Object to the Setpoint Limit | unsignedInt 0…1 | 0 |
| Sold/Unsold Room Object | unsignedInt 0…1 | 1 |
| Mode after Exiting Comfort | list | Stay in the Same H/C Mode |
| Default Mode | list | Standby |
| Mode to Activate when the Room Is not Sold | list | Economy |
| Configuration | list | 0 = Closed; 1 = Open |
| Configuration | list | 0 = Unlocked; 1 = Locked |
| Thermostat Locking Object | unsignedInt 0…1 | 0 |
| Fan Mode Object Value | list | 0 = Automatic; 1 = Manual |
| Initial Fan Speed | unsignedInt 0…100 | 100 |
| Initial Fan Mode for Comfort | list | Manual |
| Night Occupation (0 = Disabled) | unsignedInt 0…64 | 0 |
| Setpoint to Split | unsignedInt 0…1 | 0 |
| Offset Value when System Mode is Heating | signedInt -50…50 | 20 |
| Offset Value when System Mode is Cooling | signedInt -50…50 | -20 |
| Value to Lock Occupancy Object | list | 0 = Unlocked; 1 = Locked |
| Dehumidification | unsignedInt 0…1 | 0 |
| Reference Temperature | list | Room Temperature |
| High Humidity | unsignedInt 0…100 | 65 |
| Hysteresis | unsignedInt 1…25 | 5 |
| Fan Speed | unsignedInt 0…100 | 10 |
| Comfort | unsignedInt 0…200 | 0 |
| Standby | unsignedInt 0…200 | 10 |
| Economy | unsignedInt 0…200 | 10 |
| Dehumidification in Occupied Room | unsignedInt 0…1 | 0 |
| Return Hysteresis | unsignedInt 0…200 | 5 |
| Protection | unsignedInt 0…200 | 20 |
| Setpoint Type | list | Absolute |
| th[0].hcAuto_relative | unsignedInt 0…1 | 0 |
| Out of Comfort Lower Band | unsignedInt 0…255 | 0 |
| Out of Comfort Upper Band | unsignedInt 0…255 | 0 |
| Step User Setpoint Object | unsignedInt 0…1 | 0 |
| Temperature Increment | float 1…100 | 5 |
| PWM Minimum Time | unsignedInt 1…30 | 1 |
| Restart Accumulated Error after Setpoint Change? | list | Yes |
| Maximum Sending Objects | unsignedInt 0…255 | 5 |
| Minimum Time between Object Sendings | unsignedInt 0…255 | 2 |
| Hospitality Thermostat 1 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 2 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 3 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 5 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 6 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 7 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 8 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 9 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 10 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 11 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 12 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 13 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 14 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 15 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 16 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 17 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 18 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 19 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 20 | unsignedInt 0…1 | 0 |
| Hospitality Thermostat 4 | unsignedInt 0…1 | 0 |
| checkHW | list | |
| DEVICE_TYPE (virtual) | list | KIPI SC |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| KIPI SC 1.1 1.1 latest | $6391 | 346B | 2026-11-25 | 669 KB | Download |
About this file
This is the official ETS product database for the Zennio KIPI SC (ZSYKIPISC), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.