KNX Database
Zennio ZSYKIPISC KIPI SC

KIPI SC ZSYKIPISC

Zennio · Order number ZSYKIPISC · Interface › IP

Secure KNX-IP Interface

Download .knxprod KIPI SC 1.1 1.1 · 669 KB

Product

ManufacturerZennio
Product nameKIPI SC
Order numberZSYKIPISC
HardwareKIPI SC
MediumTwisted Pair
Bus current (mA)20
Rail mountedYes
Width (mm)36
Device kindIPEnabled
RegistrationCertified · 2022-02-25
Languagesen-US, es-ES, de-DE, fr-FR, it-IT, ru-RU
Catalog entryM-0071_H-ZSYKIPISC-1_HP-6391-11-346B_CI-ZSYKIPISC-1
Fingerprint346B
SHA-256a0a436b4b7773a65cca99cd0588376597cbb71e48cc9228376fafadfc4c4d270
First seen2026-11-25
Markets59 markets

Application program: KIPI SC 1.1 1.1

Application number$6391
Version1.1
Mask versionMV-07B0 (System B)
KNX Data SecureYes
Minimum ETS version5.0
Parameters3116
Group objects1807
Group objects (1807)
NoNameFunctionSizeDPTFlags
1[Heartbeat] Object to Send '1'Sending of '1' Periodically1 Bit1.17 triggerCT
2[NTP] DateCurrent Date3 Bytes11.1 dateCRT
3[NTP] Time of DayCurrent Time3 Bytes10.1 time of dayCRT
4[NTP] Date and TimeCurrent Date and Time8 Bytes19.1 date timeCRT
5[NTP] Sending Request0 = No Action; 1 = Request Date and Time Sending1 Bit1.16 acknowledgeCW
6[HT1] [A] On/Off0 = Off; 1 = On1 Bit1.1 switchCW
7[HT1] [A] On/Off Status0 = Off; 1 = On1 Bit1.1 switchCRT
8[HT1] [A] Scene InputScene Value1 Byte18.1 scene controlCW
9[HT1] [A] Temperature Source 1External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
10[HT1] [A] Temperature Source 2External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
11[HT1] [A] Room TemperatureCurrent Temperature2 Bytes9.1 temperature (°C)CRT
12[HT1] [A] System Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
13[HT1] [A] User Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
14[HT1] [A] Force System Mode0 = User Mode / Auto Change; 1 = System Mode1 Bit1.1 switchCRW
15[HT1] [A] Mode Status0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRT
16[HT1] [A] Fan Speed0% - 100%1 Byte5.1 percentage (0..100%)CWTU
17[HT1] [A] Fan: Manual/Automatic0 = Manual; 1 = Automatic1 Bit1.3 enableCWTU
17[HT1] [A] Fan: Manual/Automatic0 = Automatic; 1 = Manual1 Bit1.3 enableCWTU
18[HT1] [A] On/Off Fancoil0 = Off; 1 = On1 Bit1.1 switchCRT
19[HT1] [B] User Comfort Setpoint Reset0 = Nothing; 1 = Reset1 Bit1.15 resetCW
20[HT1] [B] User Setpoint Control[-20°C, 100°C]2 Bytes9.1 temperature (°C)CWTU
20[HT1] [B] User Setpoint Offset[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CWTU
21[HT1] [B] Step User Setpoint0 = Decrease; 1 = Increase1 Bit1.7 stepCW
22[HT1] [B] Comfort Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
22[HT1] [B] Comfort Setpoint[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
23[HT1] [B] Standby Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
24[HT1] [B] Economy Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
25[HT1] [B] Protection Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
26[HT1] [B] Comfort Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
27[HT1] [B] Standby Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
28[HT1] [B] Economy Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
29[HT1] [B] Protection Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
30[HT1] [B] Real Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
31[HT1] [B] User Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
31[HT1] [B] User Setpoint Offset Status[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CRT
32[HT1] [C] Transition Time: Comfort to Default ModeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
32[HT1] [C] Transition Time: Comfort to Default ModeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
32[HT1] [C] Transition Time: Comfort to Default ModeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
33[HT1] [C] Transition Time: Standby to EconomySeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
33[HT1] [C] Transition Time: Standby to EconomyMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
33[HT1] [C] Transition Time: Standby to EconomyHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
34[HT1] [C] Comfort Setpoint Reset TimeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
34[HT1] [C] Comfort Setpoint Reset TimeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
34[HT1] [C] Comfort Setpoint Reset TimeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
35[HT1] [C] Presence Detector (Input)0 = Not Occupied; 1 = Occupied1 Bit1.18 occupancyCRW
36[HT1] [C] Lock Presence Detection0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
36[HT1] [C] Lock Presence Detection0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
37[HT1] [C] Sold/Unsold Room (Input)0 = Unsold; 1 = Sold1 Bit1.2 booleanCRW
38[HT1] [D] Special Mode1-byte HVAC Mode1 Byte20.102 HVAC modeCW
39[HT1] [D] Special Mode: Comfort0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
39[HT1] [D] Special Mode: Comfort0 = Off; 1 = On1 Bit1.1 switchCW
40[HT1] [D] Special Mode: Standby0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
40[HT1] [D] Special Mode: Standby0 = Off; 1 = On1 Bit1.1 switchCW
41[HT1] [D] Special Mode: Economy0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
41[HT1] [D] Special Mode: Economy0 = Off; 1 = On1 Bit1.1 switchCW
42[HT1] [D] Special Mode: Protection0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
42[HT1] [D] Special Mode: Protection0 = Off; 1 = On1 Bit1.1 switchCW
43[HT1] [D] Special Mode Status1-byte HVAC Mode1 Byte20.102 HVAC modeCRT
44[HT1] [D] Comfort Mode Status0 = Off; 1 = On1 Bit1.1 switchCRT
45[HT1] [D] Window Status 1 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
45[HT1] [D] Window Status 1 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
46[HT1] [D] Window Status 2 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
46[HT1] [D] Window Status 2 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
47[HT1] [D] Window Status 3 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
47[HT1] [D] Window Status 3 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
48[HT1] [D] Window Status 4 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
48[HT1] [D] Window Status 4 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
49[HT1] [D] Enable Window Status0 = Disabled; 1 = Enabled1 Bit1.3 enableCRW
50[HT1] [D] Thermostat Lock0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
50[HT1] [D] Thermostat Lock0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
51[HT1] [D] Comfort Lower Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
52[HT1] [D] Comfort Upper Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
53[HT1] [D] Hidden Offset On/Off0 = Off; 1 = On1 Bit1.1 switchCRW
54[HT1] [D] Hidden Offset Value[-20°C, 100°C]2 Bytes9.2 temperature difference (K)CRWTU
55[HT1] [D] Eco Mode Notification0 = Out of eco range; 1 = Setpoint in Eco Range1 Bit1.2 booleanCRT
56[HT1] [D] Eco Mode RatioPercentage of Time Working in Eco Range1 Byte5.1 percentage (0..100%)CRT
57[HT1] [D] Eco Mode: Lower Limit (Cooling)Lower Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
58[HT1] [D] Eco Mode: Upper Limit (Heating)Upper Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
59[HT1] [D] Setpoint to Split[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
60[HT1] [F] Current HumidityHumidity Sensor Value2 Bytes9.7 humidity (%)CW
61[HT1] [F] High Humidity Alarm ThresholdValue of High Humidity Alarm Threshold2 Bytes9.7 humidity (%)CRWTU
62[HT1] [F] Dehumidification Control0 = Disabled; 1 = Enabled1 Bit1.3 enableCRWTU
63[HT1] [F] Dehumidification Status0 = No Dehumidifying; 1 = Dehumidifying1 Bit1.2 booleanCRT
64[HT1] [F] High Humidity0 = No Alarm; 1 = Alarm1 Bit1.5 alarmCRT
65[HT1] [F] Enable Apparent Temperature0 = Room Temperature; 1 = Apparent Temperature1 Bit1.3 enableCRWTU
66[HT1] [Cooling] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
67[HT1] [Heating] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
68[HT1] [Cooling] Control Variable2-Point Control1 Bit1.1 switchCRT
68[HT1] [Cooling] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
69[HT1] [Heating] Control Variable2-Point Control1 Bit1.1 switchCRT
69[HT1] [Heating] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
70[HT1] [Cooling] Additional CoolTemp >= (Setpoint+Band) => "1"1 Bit1.1 switchCRT
71[HT1] [Heating] Additional HeatTemp <= (Setpoint-Band) => "1"1 Bit1.1 switchCRT
72[HT1] [Cooling] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
73[HT1] [Heating] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
74[HT2] [A] On/Off0 = Off; 1 = On1 Bit1.1 switchCW
75[HT2] [A] On/Off Status0 = Off; 1 = On1 Bit1.1 switchCRT
76[HT2] [A] Scene InputScene Value1 Byte18.1 scene controlCW
77[HT2] [A] Temperature Source 1External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
78[HT2] [A] Temperature Source 2External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
79[HT2] [A] Room TemperatureCurrent Temperature2 Bytes9.1 temperature (°C)CRT
80[HT2] [A] System Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
81[HT2] [A] User Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
82[HT2] [A] Force System Mode0 = User Mode / Auto Change; 1 = System Mode1 Bit1.1 switchCRW
83[HT2] [A] Mode Status0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRT
84[HT2] [A] Fan Speed0% - 100%1 Byte5.1 percentage (0..100%)CWTU
85[HT2] [A] Fan: Manual/Automatic0 = Manual; 1 = Automatic1 Bit1.3 enableCWTU
85[HT2] [A] Fan: Manual/Automatic0 = Automatic; 1 = Manual1 Bit1.3 enableCWTU
86[HT2] [A] On/Off Fancoil0 = Off; 1 = On1 Bit1.1 switchCRT
87[HT2] [B] User Comfort Setpoint Reset0 = Nothing; 1 = Reset1 Bit1.15 resetCW
88[HT2] [B] User Setpoint Control[-20°C, 100°C]2 Bytes9.1 temperature (°C)CWTU
88[HT2] [B] User Setpoint Offset[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CWTU
89[HT2] [B] Step User Setpoint0 = Decrease; 1 = Increase1 Bit1.7 stepCW
90[HT2] [B] Comfort Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
90[HT2] [B] Comfort Setpoint[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
91[HT2] [B] Standby Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
92[HT2] [B] Economy Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
93[HT2] [B] Protection Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
94[HT2] [B] Comfort Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
95[HT2] [B] Standby Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
96[HT2] [B] Economy Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
97[HT2] [B] Protection Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
98[HT2] [B] Real Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
99[HT2] [B] User Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
99[HT2] [B] User Setpoint Offset Status[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CRT
100[HT2] [C] Transition Time: Comfort to Default ModeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
100[HT2] [C] Transition Time: Comfort to Default ModeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
100[HT2] [C] Transition Time: Comfort to Default ModeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
101[HT2] [C] Transition Time: Standby to EconomySeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
101[HT2] [C] Transition Time: Standby to EconomyMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
101[HT2] [C] Transition Time: Standby to EconomyHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
102[HT2] [C] Comfort Setpoint Reset TimeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
102[HT2] [C] Comfort Setpoint Reset TimeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
102[HT2] [C] Comfort Setpoint Reset TimeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
103[HT2] [C] Presence Detector (Input)0 = Not Occupied; 1 = Occupied1 Bit1.18 occupancyCRW
104[HT2] [C] Lock Presence Detection0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
104[HT2] [C] Lock Presence Detection0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
105[HT2] [C] Sold/Unsold Room (Input)0 = Unsold; 1 = Sold1 Bit1.2 booleanCRW
106[HT2] [D] Special Mode1-byte HVAC Mode1 Byte20.102 HVAC modeCW
107[HT2] [D] Special Mode: Comfort0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
107[HT2] [D] Special Mode: Comfort0 = Off; 1 = On1 Bit1.1 switchCW
108[HT2] [D] Special Mode: Standby0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
108[HT2] [D] Special Mode: Standby0 = Off; 1 = On1 Bit1.1 switchCW
109[HT2] [D] Special Mode: Economy0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
109[HT2] [D] Special Mode: Economy0 = Off; 1 = On1 Bit1.1 switchCW
110[HT2] [D] Special Mode: Protection0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
110[HT2] [D] Special Mode: Protection0 = Off; 1 = On1 Bit1.1 switchCW
111[HT2] [D] Special Mode Status1-byte HVAC Mode1 Byte20.102 HVAC modeCRT
112[HT2] [D] Comfort Mode Status0 = Off; 1 = On1 Bit1.1 switchCRT
113[HT2] [D] Window Status 1 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
113[HT2] [D] Window Status 1 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
114[HT2] [D] Window Status 2 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
114[HT2] [D] Window Status 2 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
115[HT2] [D] Window Status 3 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
115[HT2] [D] Window Status 3 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
116[HT2] [D] Window Status 4 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
116[HT2] [D] Window Status 4 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
117[HT2] [D] Enable Window Status0 = Disabled; 1 = Enabled1 Bit1.3 enableCRW
118[HT2] [D] Thermostat Lock0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
118[HT2] [D] Thermostat Lock0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
119[HT2] [D] Comfort Lower Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
120[HT2] [D] Comfort Upper Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
121[HT2] [D] Hidden Offset On/Off0 = Off; 1 = On1 Bit1.1 switchCRW
122[HT2] [D] Hidden Offset Value[-20°C, 100°C]2 Bytes9.2 temperature difference (K)CRWTU
123[HT2] [D] Eco Mode Notification0 = Out of eco range; 1 = Setpoint in Eco Range1 Bit1.2 booleanCRT
124[HT2] [D] Eco Mode RatioPercentage of Time Working in Eco Range1 Byte5.1 percentage (0..100%)CRT
125[HT2] [D] Eco Mode: Lower Limit (Cooling)Lower Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
126[HT2] [D] Eco Mode: Upper Limit (Heating)Upper Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
127[HT2] [D] Setpoint to Split[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
128[HT2] [F] Current HumidityHumidity Sensor Value2 Bytes9.7 humidity (%)CW
129[HT2] [F] High Humidity Alarm ThresholdValue of High Humidity Alarm Threshold2 Bytes9.7 humidity (%)CRWTU
130[HT2] [F] Dehumidification Control0 = Disabled; 1 = Enabled1 Bit1.3 enableCRWTU
131[HT2] [F] Dehumidification Status0 = No Dehumidifying; 1 = Dehumidifying1 Bit1.2 booleanCRT
132[HT2] [F] High Humidity0 = No Alarm; 1 = Alarm1 Bit1.5 alarmCRT
133[HT2] [F] Enable Apparent Temperature0 = Room Temperature; 1 = Apparent Temperature1 Bit1.3 enableCRWTU
134[HT2] [Cooling] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
135[HT2] [Heating] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
136[HT2] [Cooling] Control Variable2-Point Control1 Bit1.1 switchCRT
136[HT2] [Cooling] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
137[HT2] [Heating] Control Variable2-Point Control1 Bit1.1 switchCRT
137[HT2] [Heating] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
138[HT2] [Cooling] Additional CoolTemp >= (Setpoint+Band) => "1"1 Bit1.1 switchCRT
139[HT2] [Heating] Additional HeatTemp <= (Setpoint-Band) => "1"1 Bit1.1 switchCRT
140[HT2] [Cooling] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
141[HT2] [Heating] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
142[HT3] [A] On/Off0 = Off; 1 = On1 Bit1.1 switchCW
143[HT3] [A] On/Off Status0 = Off; 1 = On1 Bit1.1 switchCRT
144[HT3] [A] Scene InputScene Value1 Byte18.1 scene controlCW
145[HT3] [A] Temperature Source 1External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
146[HT3] [A] Temperature Source 2External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
147[HT3] [A] Room TemperatureCurrent Temperature2 Bytes9.1 temperature (°C)CRT
148[HT3] [A] System Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
149[HT3] [A] User Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
150[HT3] [A] Force System Mode0 = User Mode / Auto Change; 1 = System Mode1 Bit1.1 switchCRW
151[HT3] [A] Mode Status0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRT
152[HT3] [A] Fan Speed0% - 100%1 Byte5.1 percentage (0..100%)CWTU
153[HT3] [A] Fan: Manual/Automatic0 = Manual; 1 = Automatic1 Bit1.3 enableCWTU
153[HT3] [A] Fan: Manual/Automatic0 = Automatic; 1 = Manual1 Bit1.3 enableCWTU
154[HT3] [A] On/Off Fancoil0 = Off; 1 = On1 Bit1.1 switchCRT
155[HT3] [B] User Comfort Setpoint Reset0 = Nothing; 1 = Reset1 Bit1.15 resetCW
156[HT3] [B] User Setpoint Control[-20°C, 100°C]2 Bytes9.1 temperature (°C)CWTU
156[HT3] [B] User Setpoint Offset[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CWTU
157[HT3] [B] Step User Setpoint0 = Decrease; 1 = Increase1 Bit1.7 stepCW
158[HT3] [B] Comfort Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
158[HT3] [B] Comfort Setpoint[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
159[HT3] [B] Standby Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
160[HT3] [B] Economy Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
161[HT3] [B] Protection Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
162[HT3] [B] Comfort Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
163[HT3] [B] Standby Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
164[HT3] [B] Economy Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
165[HT3] [B] Protection Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
166[HT3] [B] Real Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
167[HT3] [B] User Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
167[HT3] [B] User Setpoint Offset Status[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CRT
168[HT3] [C] Transition Time: Comfort to Default ModeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
168[HT3] [C] Transition Time: Comfort to Default ModeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
168[HT3] [C] Transition Time: Comfort to Default ModeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
169[HT3] [C] Transition Time: Standby to EconomySeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
169[HT3] [C] Transition Time: Standby to EconomyMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
169[HT3] [C] Transition Time: Standby to EconomyHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
170[HT3] [C] Comfort Setpoint Reset TimeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
170[HT3] [C] Comfort Setpoint Reset TimeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
170[HT3] [C] Comfort Setpoint Reset TimeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
171[HT3] [C] Presence Detector (Input)0 = Not Occupied; 1 = Occupied1 Bit1.18 occupancyCRW
172[HT3] [C] Lock Presence Detection0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
172[HT3] [C] Lock Presence Detection0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
173[HT3] [C] Sold/Unsold Room (Input)0 = Unsold; 1 = Sold1 Bit1.2 booleanCRW
174[HT3] [D] Special Mode1-byte HVAC Mode1 Byte20.102 HVAC modeCW
175[HT3] [D] Special Mode: Comfort0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
175[HT3] [D] Special Mode: Comfort0 = Off; 1 = On1 Bit1.1 switchCW
176[HT3] [D] Special Mode: Standby0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
176[HT3] [D] Special Mode: Standby0 = Off; 1 = On1 Bit1.1 switchCW
177[HT3] [D] Special Mode: Economy0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
177[HT3] [D] Special Mode: Economy0 = Off; 1 = On1 Bit1.1 switchCW
178[HT3] [D] Special Mode: Protection0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
178[HT3] [D] Special Mode: Protection0 = Off; 1 = On1 Bit1.1 switchCW
179[HT3] [D] Special Mode Status1-byte HVAC Mode1 Byte20.102 HVAC modeCRT
180[HT3] [D] Comfort Mode Status0 = Off; 1 = On1 Bit1.1 switchCRT
181[HT3] [D] Window Status 1 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
181[HT3] [D] Window Status 1 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
182[HT3] [D] Window Status 2 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
182[HT3] [D] Window Status 2 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
183[HT3] [D] Window Status 3 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
183[HT3] [D] Window Status 3 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
184[HT3] [D] Window Status 4 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
184[HT3] [D] Window Status 4 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
185[HT3] [D] Enable Window Status0 = Disabled; 1 = Enabled1 Bit1.3 enableCRW
186[HT3] [D] Thermostat Lock0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
186[HT3] [D] Thermostat Lock0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
187[HT3] [D] Comfort Lower Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
188[HT3] [D] Comfort Upper Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
189[HT3] [D] Hidden Offset On/Off0 = Off; 1 = On1 Bit1.1 switchCRW
190[HT3] [D] Hidden Offset Value[-20°C, 100°C]2 Bytes9.2 temperature difference (K)CRWTU
191[HT3] [D] Eco Mode Notification0 = Out of eco range; 1 = Setpoint in Eco Range1 Bit1.2 booleanCRT
192[HT3] [D] Eco Mode RatioPercentage of Time Working in Eco Range1 Byte5.1 percentage (0..100%)CRT
193[HT3] [D] Eco Mode: Lower Limit (Cooling)Lower Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
194[HT3] [D] Eco Mode: Upper Limit (Heating)Upper Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
195[HT3] [D] Setpoint to Split[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
196[HT3] [F] Current HumidityHumidity Sensor Value2 Bytes9.7 humidity (%)CW
197[HT3] [F] High Humidity Alarm ThresholdValue of High Humidity Alarm Threshold2 Bytes9.7 humidity (%)CRWTU
198[HT3] [F] Dehumidification Control0 = Disabled; 1 = Enabled1 Bit1.3 enableCRWTU
199[HT3] [F] Dehumidification Status0 = No Dehumidifying; 1 = Dehumidifying1 Bit1.2 booleanCRT
200[HT3] [F] High Humidity0 = No Alarm; 1 = Alarm1 Bit1.5 alarmCRT
201[HT3] [F] Enable Apparent Temperature0 = Room Temperature; 1 = Apparent Temperature1 Bit1.3 enableCRWTU
202[HT3] [Cooling] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
203[HT3] [Heating] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
204[HT3] [Cooling] Control Variable2-Point Control1 Bit1.1 switchCRT
204[HT3] [Cooling] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
205[HT3] [Heating] Control Variable2-Point Control1 Bit1.1 switchCRT
205[HT3] [Heating] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
206[HT3] [Cooling] Additional CoolTemp >= (Setpoint+Band) => "1"1 Bit1.1 switchCRT
207[HT3] [Heating] Additional HeatTemp <= (Setpoint-Band) => "1"1 Bit1.1 switchCRT
208[HT3] [Cooling] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
209[HT3] [Heating] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
210[HT4] [A] On/Off0 = Off; 1 = On1 Bit1.1 switchCW
211[HT4] [A] On/Off Status0 = Off; 1 = On1 Bit1.1 switchCRT
212[HT4] [A] Scene InputScene Value1 Byte18.1 scene controlCW
213[HT4] [A] Temperature Source 1External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
214[HT4] [A] Temperature Source 2External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
215[HT4] [A] Room TemperatureCurrent Temperature2 Bytes9.1 temperature (°C)CRT
216[HT4] [A] System Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
217[HT4] [A] User Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
218[HT4] [A] Force System Mode0 = User Mode / Auto Change; 1 = System Mode1 Bit1.1 switchCRW
219[HT4] [A] Mode Status0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRT
220[HT4] [A] Fan Speed0% - 100%1 Byte5.1 percentage (0..100%)CWTU
221[HT4] [A] Fan: Manual/Automatic0 = Manual; 1 = Automatic1 Bit1.3 enableCWTU
221[HT4] [A] Fan: Manual/Automatic0 = Automatic; 1 = Manual1 Bit1.3 enableCWTU
222[HT4] [A] On/Off Fancoil0 = Off; 1 = On1 Bit1.1 switchCRT
223[HT4] [B] User Comfort Setpoint Reset0 = Nothing; 1 = Reset1 Bit1.15 resetCW
224[HT4] [B] User Setpoint Control[-20°C, 100°C]2 Bytes9.1 temperature (°C)CWTU
224[HT4] [B] User Setpoint Offset[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CWTU
225[HT4] [B] Step User Setpoint0 = Decrease; 1 = Increase1 Bit1.7 stepCW
226[HT4] [B] Comfort Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
226[HT4] [B] Comfort Setpoint[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
227[HT4] [B] Standby Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
228[HT4] [B] Economy Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
229[HT4] [B] Protection Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
230[HT4] [B] Comfort Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
231[HT4] [B] Standby Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
232[HT4] [B] Economy Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
233[HT4] [B] Protection Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
234[HT4] [B] Real Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
235[HT4] [B] User Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
235[HT4] [B] User Setpoint Offset Status[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CRT
236[HT4] [C] Transition Time: Comfort to Default ModeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
236[HT4] [C] Transition Time: Comfort to Default ModeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
236[HT4] [C] Transition Time: Comfort to Default ModeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
237[HT4] [C] Transition Time: Standby to EconomySeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
237[HT4] [C] Transition Time: Standby to EconomyMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
237[HT4] [C] Transition Time: Standby to EconomyHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
238[HT4] [C] Comfort Setpoint Reset TimeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
238[HT4] [C] Comfort Setpoint Reset TimeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
238[HT4] [C] Comfort Setpoint Reset TimeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
239[HT4] [C] Presence Detector (Input)0 = Not Occupied; 1 = Occupied1 Bit1.18 occupancyCRW
240[HT4] [C] Lock Presence Detection0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
240[HT4] [C] Lock Presence Detection0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
241[HT4] [C] Sold/Unsold Room (Input)0 = Unsold; 1 = Sold1 Bit1.2 booleanCRW
242[HT4] [D] Special Mode1-byte HVAC Mode1 Byte20.102 HVAC modeCW
243[HT4] [D] Special Mode: Comfort0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
243[HT4] [D] Special Mode: Comfort0 = Off; 1 = On1 Bit1.1 switchCW
244[HT4] [D] Special Mode: Standby0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
244[HT4] [D] Special Mode: Standby0 = Off; 1 = On1 Bit1.1 switchCW
245[HT4] [D] Special Mode: Economy0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
245[HT4] [D] Special Mode: Economy0 = Off; 1 = On1 Bit1.1 switchCW
246[HT4] [D] Special Mode: Protection0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
246[HT4] [D] Special Mode: Protection0 = Off; 1 = On1 Bit1.1 switchCW
247[HT4] [D] Special Mode Status1-byte HVAC Mode1 Byte20.102 HVAC modeCRT
248[HT4] [D] Comfort Mode Status0 = Off; 1 = On1 Bit1.1 switchCRT
249[HT4] [D] Window Status 1 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
249[HT4] [D] Window Status 1 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
250[HT4] [D] Window Status 2 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
250[HT4] [D] Window Status 2 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
251[HT4] [D] Window Status 3 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
251[HT4] [D] Window Status 3 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
252[HT4] [D] Window Status 4 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
252[HT4] [D] Window Status 4 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
253[HT4] [D] Enable Window Status0 = Disabled; 1 = Enabled1 Bit1.3 enableCRW
254[HT4] [D] Thermostat Lock0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
254[HT4] [D] Thermostat Lock0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
255[HT4] [D] Comfort Lower Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
256[HT4] [D] Comfort Upper Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
257[HT4] [D] Hidden Offset On/Off0 = Off; 1 = On1 Bit1.1 switchCRW
258[HT4] [D] Hidden Offset Value[-20°C, 100°C]2 Bytes9.2 temperature difference (K)CRWTU
259[HT4] [D] Eco Mode Notification0 = Out of eco range; 1 = Setpoint in Eco Range1 Bit1.2 booleanCRT
260[HT4] [D] Eco Mode RatioPercentage of Time Working in Eco Range1 Byte5.1 percentage (0..100%)CRT
261[HT4] [D] Eco Mode: Lower Limit (Cooling)Lower Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
262[HT4] [D] Eco Mode: Upper Limit (Heating)Upper Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
263[HT4] [D] Setpoint to Split[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
264[HT4] [F] Current HumidityHumidity Sensor Value2 Bytes9.7 humidity (%)CW
265[HT4] [F] High Humidity Alarm ThresholdValue of High Humidity Alarm Threshold2 Bytes9.7 humidity (%)CRWTU
266[HT4] [F] Dehumidification Control0 = Disabled; 1 = Enabled1 Bit1.3 enableCRWTU
267[HT4] [F] Dehumidification Status0 = No Dehumidifying; 1 = Dehumidifying1 Bit1.2 booleanCRT
268[HT4] [F] High Humidity0 = No Alarm; 1 = Alarm1 Bit1.5 alarmCRT
269[HT4] [F] Enable Apparent Temperature0 = Room Temperature; 1 = Apparent Temperature1 Bit1.3 enableCRWTU
270[HT4] [Cooling] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
271[HT4] [Heating] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
272[HT4] [Cooling] Control Variable2-Point Control1 Bit1.1 switchCRT
272[HT4] [Cooling] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
273[HT4] [Heating] Control Variable2-Point Control1 Bit1.1 switchCRT
273[HT4] [Heating] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
274[HT4] [Cooling] Additional CoolTemp >= (Setpoint+Band) => "1"1 Bit1.1 switchCRT
275[HT4] [Heating] Additional HeatTemp <= (Setpoint-Band) => "1"1 Bit1.1 switchCRT
276[HT4] [Cooling] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
277[HT4] [Heating] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
278[HT5] [A] On/Off0 = Off; 1 = On1 Bit1.1 switchCW
279[HT5] [A] On/Off Status0 = Off; 1 = On1 Bit1.1 switchCRT
280[HT5] [A] Scene InputScene Value1 Byte18.1 scene controlCW
281[HT5] [A] Temperature Source 1External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
282[HT5] [A] Temperature Source 2External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
283[HT5] [A] Room TemperatureCurrent Temperature2 Bytes9.1 temperature (°C)CRT
284[HT5] [A] System Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
285[HT5] [A] User Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
286[HT5] [A] Force System Mode0 = User Mode / Auto Change; 1 = System Mode1 Bit1.1 switchCRW
287[HT5] [A] Mode Status0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRT
288[HT5] [A] Fan Speed0% - 100%1 Byte5.1 percentage (0..100%)CWTU
289[HT5] [A] Fan: Manual/Automatic0 = Manual; 1 = Automatic1 Bit1.3 enableCWTU
289[HT5] [A] Fan: Manual/Automatic0 = Automatic; 1 = Manual1 Bit1.3 enableCWTU
290[HT5] [A] On/Off Fancoil0 = Off; 1 = On1 Bit1.1 switchCRT
291[HT5] [B] User Comfort Setpoint Reset0 = Nothing; 1 = Reset1 Bit1.15 resetCW
292[HT5] [B] User Setpoint Control[-20°C, 100°C]2 Bytes9.1 temperature (°C)CWTU
292[HT5] [B] User Setpoint Offset[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CWTU
293[HT5] [B] Step User Setpoint0 = Decrease; 1 = Increase1 Bit1.7 stepCW
294[HT5] [B] Comfort Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
294[HT5] [B] Comfort Setpoint[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
295[HT5] [B] Standby Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
296[HT5] [B] Economy Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
297[HT5] [B] Protection Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
298[HT5] [B] Comfort Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
299[HT5] [B] Standby Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
300[HT5] [B] Economy Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
301[HT5] [B] Protection Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
302[HT5] [B] Real Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
303[HT5] [B] User Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
303[HT5] [B] User Setpoint Offset Status[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CRT
304[HT5] [C] Transition Time: Comfort to Default ModeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
304[HT5] [C] Transition Time: Comfort to Default ModeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
304[HT5] [C] Transition Time: Comfort to Default ModeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
305[HT5] [C] Transition Time: Standby to EconomySeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
305[HT5] [C] Transition Time: Standby to EconomyMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
305[HT5] [C] Transition Time: Standby to EconomyHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
306[HT5] [C] Comfort Setpoint Reset TimeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
306[HT5] [C] Comfort Setpoint Reset TimeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
306[HT5] [C] Comfort Setpoint Reset TimeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
307[HT5] [C] Presence Detector (Input)0 = Not Occupied; 1 = Occupied1 Bit1.18 occupancyCRW
308[HT5] [C] Lock Presence Detection0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
308[HT5] [C] Lock Presence Detection0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
309[HT5] [C] Sold/Unsold Room (Input)0 = Unsold; 1 = Sold1 Bit1.2 booleanCRW
310[HT5] [D] Special Mode1-byte HVAC Mode1 Byte20.102 HVAC modeCW
311[HT5] [D] Special Mode: Comfort0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
311[HT5] [D] Special Mode: Comfort0 = Off; 1 = On1 Bit1.1 switchCW
312[HT5] [D] Special Mode: Standby0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
312[HT5] [D] Special Mode: Standby0 = Off; 1 = On1 Bit1.1 switchCW
313[HT5] [D] Special Mode: Economy0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
313[HT5] [D] Special Mode: Economy0 = Off; 1 = On1 Bit1.1 switchCW
314[HT5] [D] Special Mode: Protection0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
314[HT5] [D] Special Mode: Protection0 = Off; 1 = On1 Bit1.1 switchCW
315[HT5] [D] Special Mode Status1-byte HVAC Mode1 Byte20.102 HVAC modeCRT
316[HT5] [D] Comfort Mode Status0 = Off; 1 = On1 Bit1.1 switchCRT
317[HT5] [D] Window Status 1 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
317[HT5] [D] Window Status 1 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
318[HT5] [D] Window Status 2 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
318[HT5] [D] Window Status 2 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
319[HT5] [D] Window Status 3 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
319[HT5] [D] Window Status 3 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
320[HT5] [D] Window Status 4 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
320[HT5] [D] Window Status 4 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
321[HT5] [D] Enable Window Status0 = Disabled; 1 = Enabled1 Bit1.3 enableCRW
322[HT5] [D] Thermostat Lock0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
322[HT5] [D] Thermostat Lock0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
323[HT5] [D] Comfort Lower Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
324[HT5] [D] Comfort Upper Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
325[HT5] [D] Hidden Offset On/Off0 = Off; 1 = On1 Bit1.1 switchCRW
326[HT5] [D] Hidden Offset Value[-20°C, 100°C]2 Bytes9.2 temperature difference (K)CRWTU
327[HT5] [D] Eco Mode Notification0 = Out of eco range; 1 = Setpoint in Eco Range1 Bit1.2 booleanCRT
328[HT5] [D] Eco Mode RatioPercentage of Time Working in Eco Range1 Byte5.1 percentage (0..100%)CRT
329[HT5] [D] Eco Mode: Lower Limit (Cooling)Lower Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
330[HT5] [D] Eco Mode: Upper Limit (Heating)Upper Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
331[HT5] [D] Setpoint to Split[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
332[HT5] [F] Current HumidityHumidity Sensor Value2 Bytes9.7 humidity (%)CW
333[HT5] [F] High Humidity Alarm ThresholdValue of High Humidity Alarm Threshold2 Bytes9.7 humidity (%)CRWTU
334[HT5] [F] Dehumidification Control0 = Disabled; 1 = Enabled1 Bit1.3 enableCRWTU
335[HT5] [F] Dehumidification Status0 = No Dehumidifying; 1 = Dehumidifying1 Bit1.2 booleanCRT
336[HT5] [F] High Humidity0 = No Alarm; 1 = Alarm1 Bit1.5 alarmCRT
337[HT5] [F] Enable Apparent Temperature0 = Room Temperature; 1 = Apparent Temperature1 Bit1.3 enableCRWTU
338[HT5] [Cooling] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
339[HT5] [Heating] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
340[HT5] [Cooling] Control Variable2-Point Control1 Bit1.1 switchCRT
340[HT5] [Cooling] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
341[HT5] [Heating] Control Variable2-Point Control1 Bit1.1 switchCRT
341[HT5] [Heating] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
342[HT5] [Cooling] Additional CoolTemp >= (Setpoint+Band) => "1"1 Bit1.1 switchCRT
343[HT5] [Heating] Additional HeatTemp <= (Setpoint-Band) => "1"1 Bit1.1 switchCRT
344[HT5] [Cooling] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
345[HT5] [Heating] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
346[HT6] [A] On/Off0 = Off; 1 = On1 Bit1.1 switchCW
347[HT6] [A] On/Off Status0 = Off; 1 = On1 Bit1.1 switchCRT
348[HT6] [A] Scene InputScene Value1 Byte18.1 scene controlCW
349[HT6] [A] Temperature Source 1External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
350[HT6] [A] Temperature Source 2External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
351[HT6] [A] Room TemperatureCurrent Temperature2 Bytes9.1 temperature (°C)CRT
352[HT6] [A] System Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
353[HT6] [A] User Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
354[HT6] [A] Force System Mode0 = User Mode / Auto Change; 1 = System Mode1 Bit1.1 switchCRW
355[HT6] [A] Mode Status0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRT
356[HT6] [A] Fan Speed0% - 100%1 Byte5.1 percentage (0..100%)CWTU
357[HT6] [A] Fan: Manual/Automatic0 = Manual; 1 = Automatic1 Bit1.3 enableCWTU
357[HT6] [A] Fan: Manual/Automatic0 = Automatic; 1 = Manual1 Bit1.3 enableCWTU
358[HT6] [A] On/Off Fancoil0 = Off; 1 = On1 Bit1.1 switchCRT
359[HT6] [B] User Comfort Setpoint Reset0 = Nothing; 1 = Reset1 Bit1.15 resetCW
360[HT6] [B] User Setpoint Control[-20°C, 100°C]2 Bytes9.1 temperature (°C)CWTU
360[HT6] [B] User Setpoint Offset[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CWTU
361[HT6] [B] Step User Setpoint0 = Decrease; 1 = Increase1 Bit1.7 stepCW
362[HT6] [B] Comfort Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
362[HT6] [B] Comfort Setpoint[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
363[HT6] [B] Standby Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
364[HT6] [B] Economy Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
365[HT6] [B] Protection Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
366[HT6] [B] Comfort Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
367[HT6] [B] Standby Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
368[HT6] [B] Economy Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
369[HT6] [B] Protection Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
370[HT6] [B] Real Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
371[HT6] [B] User Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
371[HT6] [B] User Setpoint Offset Status[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CRT
372[HT6] [C] Transition Time: Comfort to Default ModeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
372[HT6] [C] Transition Time: Comfort to Default ModeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
372[HT6] [C] Transition Time: Comfort to Default ModeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
373[HT6] [C] Transition Time: Standby to EconomySeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
373[HT6] [C] Transition Time: Standby to EconomyMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
373[HT6] [C] Transition Time: Standby to EconomyHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
374[HT6] [C] Comfort Setpoint Reset TimeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
374[HT6] [C] Comfort Setpoint Reset TimeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
374[HT6] [C] Comfort Setpoint Reset TimeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
375[HT6] [C] Presence Detector (Input)0 = Not Occupied; 1 = Occupied1 Bit1.18 occupancyCRW
376[HT6] [C] Lock Presence Detection0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
376[HT6] [C] Lock Presence Detection0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
377[HT6] [C] Sold/Unsold Room (Input)0 = Unsold; 1 = Sold1 Bit1.2 booleanCRW
378[HT6] [D] Special Mode1-byte HVAC Mode1 Byte20.102 HVAC modeCW
379[HT6] [D] Special Mode: Comfort0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
379[HT6] [D] Special Mode: Comfort0 = Off; 1 = On1 Bit1.1 switchCW
380[HT6] [D] Special Mode: Standby0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
380[HT6] [D] Special Mode: Standby0 = Off; 1 = On1 Bit1.1 switchCW
381[HT6] [D] Special Mode: Economy0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
381[HT6] [D] Special Mode: Economy0 = Off; 1 = On1 Bit1.1 switchCW
382[HT6] [D] Special Mode: Protection0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
382[HT6] [D] Special Mode: Protection0 = Off; 1 = On1 Bit1.1 switchCW
383[HT6] [D] Special Mode Status1-byte HVAC Mode1 Byte20.102 HVAC modeCRT
384[HT6] [D] Comfort Mode Status0 = Off; 1 = On1 Bit1.1 switchCRT
385[HT6] [D] Window Status 1 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
385[HT6] [D] Window Status 1 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
386[HT6] [D] Window Status 2 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
386[HT6] [D] Window Status 2 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
387[HT6] [D] Window Status 3 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
387[HT6] [D] Window Status 3 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
388[HT6] [D] Window Status 4 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
388[HT6] [D] Window Status 4 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
389[HT6] [D] Enable Window Status0 = Disabled; 1 = Enabled1 Bit1.3 enableCRW
390[HT6] [D] Thermostat Lock0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
390[HT6] [D] Thermostat Lock0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
391[HT6] [D] Comfort Lower Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
392[HT6] [D] Comfort Upper Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
393[HT6] [D] Hidden Offset On/Off0 = Off; 1 = On1 Bit1.1 switchCRW
394[HT6] [D] Hidden Offset Value[-20°C, 100°C]2 Bytes9.2 temperature difference (K)CRWTU
395[HT6] [D] Eco Mode Notification0 = Out of eco range; 1 = Setpoint in Eco Range1 Bit1.2 booleanCRT
396[HT6] [D] Eco Mode RatioPercentage of Time Working in Eco Range1 Byte5.1 percentage (0..100%)CRT
397[HT6] [D] Eco Mode: Lower Limit (Cooling)Lower Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
398[HT6] [D] Eco Mode: Upper Limit (Heating)Upper Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
399[HT6] [D] Setpoint to Split[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
400[HT6] [F] Current HumidityHumidity Sensor Value2 Bytes9.7 humidity (%)CW
401[HT6] [F] High Humidity Alarm ThresholdValue of High Humidity Alarm Threshold2 Bytes9.7 humidity (%)CRWTU
402[HT6] [F] Dehumidification Control0 = Disabled; 1 = Enabled1 Bit1.3 enableCRWTU
403[HT6] [F] Dehumidification Status0 = No Dehumidifying; 1 = Dehumidifying1 Bit1.2 booleanCRT
404[HT6] [F] High Humidity0 = No Alarm; 1 = Alarm1 Bit1.5 alarmCRT
405[HT6] [F] Enable Apparent Temperature0 = Room Temperature; 1 = Apparent Temperature1 Bit1.3 enableCRWTU
406[HT6] [Cooling] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
407[HT6] [Heating] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
408[HT6] [Cooling] Control Variable2-Point Control1 Bit1.1 switchCRT
408[HT6] [Cooling] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
409[HT6] [Heating] Control Variable2-Point Control1 Bit1.1 switchCRT
409[HT6] [Heating] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
410[HT6] [Cooling] Additional CoolTemp >= (Setpoint+Band) => "1"1 Bit1.1 switchCRT
411[HT6] [Heating] Additional HeatTemp <= (Setpoint-Band) => "1"1 Bit1.1 switchCRT
412[HT6] [Cooling] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
413[HT6] [Heating] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
414[HT7] [A] On/Off0 = Off; 1 = On1 Bit1.1 switchCW
415[HT7] [A] On/Off Status0 = Off; 1 = On1 Bit1.1 switchCRT
416[HT7] [A] Scene InputScene Value1 Byte18.1 scene controlCW
417[HT7] [A] Temperature Source 1External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
418[HT7] [A] Temperature Source 2External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
419[HT7] [A] Room TemperatureCurrent Temperature2 Bytes9.1 temperature (°C)CRT
420[HT7] [A] System Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
421[HT7] [A] User Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
422[HT7] [A] Force System Mode0 = User Mode / Auto Change; 1 = System Mode1 Bit1.1 switchCRW
423[HT7] [A] Mode Status0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRT
424[HT7] [A] Fan Speed0% - 100%1 Byte5.1 percentage (0..100%)CWTU
425[HT7] [A] Fan: Manual/Automatic0 = Manual; 1 = Automatic1 Bit1.3 enableCWTU
425[HT7] [A] Fan: Manual/Automatic0 = Automatic; 1 = Manual1 Bit1.3 enableCWTU
426[HT7] [A] On/Off Fancoil0 = Off; 1 = On1 Bit1.1 switchCRT
427[HT7] [B] User Comfort Setpoint Reset0 = Nothing; 1 = Reset1 Bit1.15 resetCW
428[HT7] [B] User Setpoint Control[-20°C, 100°C]2 Bytes9.1 temperature (°C)CWTU
428[HT7] [B] User Setpoint Offset[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CWTU
429[HT7] [B] Step User Setpoint0 = Decrease; 1 = Increase1 Bit1.7 stepCW
430[HT7] [B] Comfort Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
430[HT7] [B] Comfort Setpoint[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
431[HT7] [B] Standby Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
432[HT7] [B] Economy Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
433[HT7] [B] Protection Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
434[HT7] [B] Comfort Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
435[HT7] [B] Standby Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
436[HT7] [B] Economy Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
437[HT7] [B] Protection Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
438[HT7] [B] Real Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
439[HT7] [B] User Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
439[HT7] [B] User Setpoint Offset Status[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CRT
440[HT7] [C] Transition Time: Comfort to Default ModeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
440[HT7] [C] Transition Time: Comfort to Default ModeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
440[HT7] [C] Transition Time: Comfort to Default ModeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
441[HT7] [C] Transition Time: Standby to EconomySeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
441[HT7] [C] Transition Time: Standby to EconomyMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
441[HT7] [C] Transition Time: Standby to EconomyHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
442[HT7] [C] Comfort Setpoint Reset TimeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
442[HT7] [C] Comfort Setpoint Reset TimeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
442[HT7] [C] Comfort Setpoint Reset TimeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
443[HT7] [C] Presence Detector (Input)0 = Not Occupied; 1 = Occupied1 Bit1.18 occupancyCRW
444[HT7] [C] Lock Presence Detection0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
444[HT7] [C] Lock Presence Detection0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
445[HT7] [C] Sold/Unsold Room (Input)0 = Unsold; 1 = Sold1 Bit1.2 booleanCRW
446[HT7] [D] Special Mode1-byte HVAC Mode1 Byte20.102 HVAC modeCW
447[HT7] [D] Special Mode: Comfort0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
447[HT7] [D] Special Mode: Comfort0 = Off; 1 = On1 Bit1.1 switchCW
448[HT7] [D] Special Mode: Standby0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
448[HT7] [D] Special Mode: Standby0 = Off; 1 = On1 Bit1.1 switchCW
449[HT7] [D] Special Mode: Economy0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
449[HT7] [D] Special Mode: Economy0 = Off; 1 = On1 Bit1.1 switchCW
450[HT7] [D] Special Mode: Protection0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
450[HT7] [D] Special Mode: Protection0 = Off; 1 = On1 Bit1.1 switchCW
451[HT7] [D] Special Mode Status1-byte HVAC Mode1 Byte20.102 HVAC modeCRT
452[HT7] [D] Comfort Mode Status0 = Off; 1 = On1 Bit1.1 switchCRT
453[HT7] [D] Window Status 1 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
453[HT7] [D] Window Status 1 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
454[HT7] [D] Window Status 2 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
454[HT7] [D] Window Status 2 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
455[HT7] [D] Window Status 3 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
455[HT7] [D] Window Status 3 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
456[HT7] [D] Window Status 4 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
456[HT7] [D] Window Status 4 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
457[HT7] [D] Enable Window Status0 = Disabled; 1 = Enabled1 Bit1.3 enableCRW
458[HT7] [D] Thermostat Lock0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
458[HT7] [D] Thermostat Lock0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
459[HT7] [D] Comfort Lower Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
460[HT7] [D] Comfort Upper Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
461[HT7] [D] Hidden Offset On/Off0 = Off; 1 = On1 Bit1.1 switchCRW
462[HT7] [D] Hidden Offset Value[-20°C, 100°C]2 Bytes9.2 temperature difference (K)CRWTU
463[HT7] [D] Eco Mode Notification0 = Out of eco range; 1 = Setpoint in Eco Range1 Bit1.2 booleanCRT
464[HT7] [D] Eco Mode RatioPercentage of Time Working in Eco Range1 Byte5.1 percentage (0..100%)CRT
465[HT7] [D] Eco Mode: Lower Limit (Cooling)Lower Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
466[HT7] [D] Eco Mode: Upper Limit (Heating)Upper Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
467[HT7] [D] Setpoint to Split[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
468[HT7] [F] Current HumidityHumidity Sensor Value2 Bytes9.7 humidity (%)CW
469[HT7] [F] High Humidity Alarm ThresholdValue of High Humidity Alarm Threshold2 Bytes9.7 humidity (%)CRWTU
470[HT7] [F] Dehumidification Control0 = Disabled; 1 = Enabled1 Bit1.3 enableCRWTU
471[HT7] [F] Dehumidification Status0 = No Dehumidifying; 1 = Dehumidifying1 Bit1.2 booleanCRT
472[HT7] [F] High Humidity0 = No Alarm; 1 = Alarm1 Bit1.5 alarmCRT
473[HT7] [F] Enable Apparent Temperature0 = Room Temperature; 1 = Apparent Temperature1 Bit1.3 enableCRWTU
474[HT7] [Cooling] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
475[HT7] [Heating] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
476[HT7] [Cooling] Control Variable2-Point Control1 Bit1.1 switchCRT
476[HT7] [Cooling] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
477[HT7] [Heating] Control Variable2-Point Control1 Bit1.1 switchCRT
477[HT7] [Heating] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
478[HT7] [Cooling] Additional CoolTemp >= (Setpoint+Band) => "1"1 Bit1.1 switchCRT
479[HT7] [Heating] Additional HeatTemp <= (Setpoint-Band) => "1"1 Bit1.1 switchCRT
480[HT7] [Cooling] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
481[HT7] [Heating] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
482[HT8] [A] On/Off0 = Off; 1 = On1 Bit1.1 switchCW
483[HT8] [A] On/Off Status0 = Off; 1 = On1 Bit1.1 switchCRT
484[HT8] [A] Scene InputScene Value1 Byte18.1 scene controlCW
485[HT8] [A] Temperature Source 1External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
486[HT8] [A] Temperature Source 2External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
487[HT8] [A] Room TemperatureCurrent Temperature2 Bytes9.1 temperature (°C)CRT
488[HT8] [A] System Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
489[HT8] [A] User Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
490[HT8] [A] Force System Mode0 = User Mode / Auto Change; 1 = System Mode1 Bit1.1 switchCRW
491[HT8] [A] Mode Status0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRT
492[HT8] [A] Fan Speed0% - 100%1 Byte5.1 percentage (0..100%)CWTU
493[HT8] [A] Fan: Manual/Automatic0 = Manual; 1 = Automatic1 Bit1.3 enableCWTU
493[HT8] [A] Fan: Manual/Automatic0 = Automatic; 1 = Manual1 Bit1.3 enableCWTU
494[HT8] [A] On/Off Fancoil0 = Off; 1 = On1 Bit1.1 switchCRT
495[HT8] [B] User Comfort Setpoint Reset0 = Nothing; 1 = Reset1 Bit1.15 resetCW
496[HT8] [B] User Setpoint Control[-20°C, 100°C]2 Bytes9.1 temperature (°C)CWTU
496[HT8] [B] User Setpoint Offset[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CWTU
497[HT8] [B] Step User Setpoint0 = Decrease; 1 = Increase1 Bit1.7 stepCW
498[HT8] [B] Comfort Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
498[HT8] [B] Comfort Setpoint[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
499[HT8] [B] Standby Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
500[HT8] [B] Economy Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
501[HT8] [B] Protection Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
502[HT8] [B] Comfort Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
503[HT8] [B] Standby Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
504[HT8] [B] Economy Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
505[HT8] [B] Protection Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
506[HT8] [B] Real Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
507[HT8] [B] User Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
507[HT8] [B] User Setpoint Offset Status[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CRT
508[HT8] [C] Transition Time: Comfort to Default ModeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
508[HT8] [C] Transition Time: Comfort to Default ModeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
508[HT8] [C] Transition Time: Comfort to Default ModeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
509[HT8] [C] Transition Time: Standby to EconomySeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
509[HT8] [C] Transition Time: Standby to EconomyMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
509[HT8] [C] Transition Time: Standby to EconomyHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
510[HT8] [C] Comfort Setpoint Reset TimeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
510[HT8] [C] Comfort Setpoint Reset TimeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
510[HT8] [C] Comfort Setpoint Reset TimeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
511[HT8] [C] Presence Detector (Input)0 = Not Occupied; 1 = Occupied1 Bit1.18 occupancyCRW
512[HT8] [C] Lock Presence Detection0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
512[HT8] [C] Lock Presence Detection0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
513[HT8] [C] Sold/Unsold Room (Input)0 = Unsold; 1 = Sold1 Bit1.2 booleanCRW
514[HT8] [D] Special Mode1-byte HVAC Mode1 Byte20.102 HVAC modeCW
515[HT8] [D] Special Mode: Comfort0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
515[HT8] [D] Special Mode: Comfort0 = Off; 1 = On1 Bit1.1 switchCW
516[HT8] [D] Special Mode: Standby0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
516[HT8] [D] Special Mode: Standby0 = Off; 1 = On1 Bit1.1 switchCW
517[HT8] [D] Special Mode: Economy0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
517[HT8] [D] Special Mode: Economy0 = Off; 1 = On1 Bit1.1 switchCW
518[HT8] [D] Special Mode: Protection0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
518[HT8] [D] Special Mode: Protection0 = Off; 1 = On1 Bit1.1 switchCW
519[HT8] [D] Special Mode Status1-byte HVAC Mode1 Byte20.102 HVAC modeCRT
520[HT8] [D] Comfort Mode Status0 = Off; 1 = On1 Bit1.1 switchCRT
521[HT8] [D] Window Status 1 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
521[HT8] [D] Window Status 1 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
522[HT8] [D] Window Status 2 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
522[HT8] [D] Window Status 2 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
523[HT8] [D] Window Status 3 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
523[HT8] [D] Window Status 3 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
524[HT8] [D] Window Status 4 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
524[HT8] [D] Window Status 4 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
525[HT8] [D] Enable Window Status0 = Disabled; 1 = Enabled1 Bit1.3 enableCRW
526[HT8] [D] Thermostat Lock0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
526[HT8] [D] Thermostat Lock0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
527[HT8] [D] Comfort Lower Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
528[HT8] [D] Comfort Upper Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
529[HT8] [D] Hidden Offset On/Off0 = Off; 1 = On1 Bit1.1 switchCRW
530[HT8] [D] Hidden Offset Value[-20°C, 100°C]2 Bytes9.2 temperature difference (K)CRWTU
531[HT8] [D] Eco Mode Notification0 = Out of eco range; 1 = Setpoint in Eco Range1 Bit1.2 booleanCRT
532[HT8] [D] Eco Mode RatioPercentage of Time Working in Eco Range1 Byte5.1 percentage (0..100%)CRT
533[HT8] [D] Eco Mode: Lower Limit (Cooling)Lower Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
534[HT8] [D] Eco Mode: Upper Limit (Heating)Upper Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
535[HT8] [D] Setpoint to Split[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
536[HT8] [F] Current HumidityHumidity Sensor Value2 Bytes9.7 humidity (%)CW
537[HT8] [F] High Humidity Alarm ThresholdValue of High Humidity Alarm Threshold2 Bytes9.7 humidity (%)CRWTU
538[HT8] [F] Dehumidification Control0 = Disabled; 1 = Enabled1 Bit1.3 enableCRWTU
539[HT8] [F] Dehumidification Status0 = No Dehumidifying; 1 = Dehumidifying1 Bit1.2 booleanCRT
540[HT8] [F] High Humidity0 = No Alarm; 1 = Alarm1 Bit1.5 alarmCRT
541[HT8] [F] Enable Apparent Temperature0 = Room Temperature; 1 = Apparent Temperature1 Bit1.3 enableCRWTU
542[HT8] [Cooling] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
543[HT8] [Heating] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
544[HT8] [Cooling] Control Variable2-Point Control1 Bit1.1 switchCRT
544[HT8] [Cooling] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
545[HT8] [Heating] Control Variable2-Point Control1 Bit1.1 switchCRT
545[HT8] [Heating] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
546[HT8] [Cooling] Additional CoolTemp >= (Setpoint+Band) => "1"1 Bit1.1 switchCRT
547[HT8] [Heating] Additional HeatTemp <= (Setpoint-Band) => "1"1 Bit1.1 switchCRT
548[HT8] [Cooling] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
549[HT8] [Heating] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
550[HT9] [A] On/Off0 = Off; 1 = On1 Bit1.1 switchCW
551[HT9] [A] On/Off Status0 = Off; 1 = On1 Bit1.1 switchCRT
552[HT9] [A] Scene InputScene Value1 Byte18.1 scene controlCW
553[HT9] [A] Temperature Source 1External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
554[HT9] [A] Temperature Source 2External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
555[HT9] [A] Room TemperatureCurrent Temperature2 Bytes9.1 temperature (°C)CRT
556[HT9] [A] System Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
557[HT9] [A] User Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
558[HT9] [A] Force System Mode0 = User Mode / Auto Change; 1 = System Mode1 Bit1.1 switchCRW
559[HT9] [A] Mode Status0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRT
560[HT9] [A] Fan Speed0% - 100%1 Byte5.1 percentage (0..100%)CWTU
561[HT9] [A] Fan: Manual/Automatic0 = Manual; 1 = Automatic1 Bit1.3 enableCWTU
561[HT9] [A] Fan: Manual/Automatic0 = Automatic; 1 = Manual1 Bit1.3 enableCWTU
562[HT9] [A] On/Off Fancoil0 = Off; 1 = On1 Bit1.1 switchCRT
563[HT9] [B] User Comfort Setpoint Reset0 = Nothing; 1 = Reset1 Bit1.15 resetCW
564[HT9] [B] User Setpoint Control[-20°C, 100°C]2 Bytes9.1 temperature (°C)CWTU
564[HT9] [B] User Setpoint Offset[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CWTU
565[HT9] [B] Step User Setpoint0 = Decrease; 1 = Increase1 Bit1.7 stepCW
566[HT9] [B] Comfort Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
566[HT9] [B] Comfort Setpoint[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
567[HT9] [B] Standby Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
568[HT9] [B] Economy Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
569[HT9] [B] Protection Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
570[HT9] [B] Comfort Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
571[HT9] [B] Standby Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
572[HT9] [B] Economy Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
573[HT9] [B] Protection Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
574[HT9] [B] Real Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
575[HT9] [B] User Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
575[HT9] [B] User Setpoint Offset Status[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CRT
576[HT9] [C] Transition Time: Comfort to Default ModeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
576[HT9] [C] Transition Time: Comfort to Default ModeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
576[HT9] [C] Transition Time: Comfort to Default ModeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
577[HT9] [C] Transition Time: Standby to EconomySeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
577[HT9] [C] Transition Time: Standby to EconomyMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
577[HT9] [C] Transition Time: Standby to EconomyHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
578[HT9] [C] Comfort Setpoint Reset TimeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
578[HT9] [C] Comfort Setpoint Reset TimeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
578[HT9] [C] Comfort Setpoint Reset TimeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
579[HT9] [C] Presence Detector (Input)0 = Not Occupied; 1 = Occupied1 Bit1.18 occupancyCRW
580[HT9] [C] Lock Presence Detection0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
580[HT9] [C] Lock Presence Detection0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
581[HT9] [C] Sold/Unsold Room (Input)0 = Unsold; 1 = Sold1 Bit1.2 booleanCRW
582[HT9] [D] Special Mode1-byte HVAC Mode1 Byte20.102 HVAC modeCW
583[HT9] [D] Special Mode: Comfort0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
583[HT9] [D] Special Mode: Comfort0 = Off; 1 = On1 Bit1.1 switchCW
584[HT9] [D] Special Mode: Standby0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
584[HT9] [D] Special Mode: Standby0 = Off; 1 = On1 Bit1.1 switchCW
585[HT9] [D] Special Mode: Economy0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
585[HT9] [D] Special Mode: Economy0 = Off; 1 = On1 Bit1.1 switchCW
586[HT9] [D] Special Mode: Protection0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
586[HT9] [D] Special Mode: Protection0 = Off; 1 = On1 Bit1.1 switchCW
587[HT9] [D] Special Mode Status1-byte HVAC Mode1 Byte20.102 HVAC modeCRT
588[HT9] [D] Comfort Mode Status0 = Off; 1 = On1 Bit1.1 switchCRT
589[HT9] [D] Window Status 1 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
589[HT9] [D] Window Status 1 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
590[HT9] [D] Window Status 2 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
590[HT9] [D] Window Status 2 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
591[HT9] [D] Window Status 3 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
591[HT9] [D] Window Status 3 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
592[HT9] [D] Window Status 4 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
592[HT9] [D] Window Status 4 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
593[HT9] [D] Enable Window Status0 = Disabled; 1 = Enabled1 Bit1.3 enableCRW
594[HT9] [D] Thermostat Lock0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
594[HT9] [D] Thermostat Lock0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
595[HT9] [D] Comfort Lower Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
596[HT9] [D] Comfort Upper Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
597[HT9] [D] Hidden Offset On/Off0 = Off; 1 = On1 Bit1.1 switchCRW
598[HT9] [D] Hidden Offset Value[-20°C, 100°C]2 Bytes9.2 temperature difference (K)CRWTU
599[HT9] [D] Eco Mode Notification0 = Out of eco range; 1 = Setpoint in Eco Range1 Bit1.2 booleanCRT
600[HT9] [D] Eco Mode RatioPercentage of Time Working in Eco Range1 Byte5.1 percentage (0..100%)CRT
601[HT9] [D] Eco Mode: Lower Limit (Cooling)Lower Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
602[HT9] [D] Eco Mode: Upper Limit (Heating)Upper Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
603[HT9] [D] Setpoint to Split[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
604[HT9] [F] Current HumidityHumidity Sensor Value2 Bytes9.7 humidity (%)CW
605[HT9] [F] High Humidity Alarm ThresholdValue of High Humidity Alarm Threshold2 Bytes9.7 humidity (%)CRWTU
606[HT9] [F] Dehumidification Control0 = Disabled; 1 = Enabled1 Bit1.3 enableCRWTU
607[HT9] [F] Dehumidification Status0 = No Dehumidifying; 1 = Dehumidifying1 Bit1.2 booleanCRT
608[HT9] [F] High Humidity0 = No Alarm; 1 = Alarm1 Bit1.5 alarmCRT
609[HT9] [F] Enable Apparent Temperature0 = Room Temperature; 1 = Apparent Temperature1 Bit1.3 enableCRWTU
610[HT9] [Cooling] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
611[HT9] [Heating] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
612[HT9] [Cooling] Control Variable2-Point Control1 Bit1.1 switchCRT
612[HT9] [Cooling] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
613[HT9] [Heating] Control Variable2-Point Control1 Bit1.1 switchCRT
613[HT9] [Heating] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
614[HT9] [Cooling] Additional CoolTemp >= (Setpoint+Band) => "1"1 Bit1.1 switchCRT
615[HT9] [Heating] Additional HeatTemp <= (Setpoint-Band) => "1"1 Bit1.1 switchCRT
616[HT9] [Cooling] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
617[HT9] [Heating] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
618[HT10] [A] On/Off0 = Off; 1 = On1 Bit1.1 switchCW
619[HT10] [A] On/Off Status0 = Off; 1 = On1 Bit1.1 switchCRT
620[HT10] [A] Scene InputScene Value1 Byte18.1 scene controlCW
621[HT10] [A] Temperature Source 1External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
622[HT10] [A] Temperature Source 2External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
623[HT10] [A] Room TemperatureCurrent Temperature2 Bytes9.1 temperature (°C)CRT
624[HT10] [A] System Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
625[HT10] [A] User Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
626[HT10] [A] Force System Mode0 = User Mode / Auto Change; 1 = System Mode1 Bit1.1 switchCRW
627[HT10] [A] Mode Status0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRT
628[HT10] [A] Fan Speed0% - 100%1 Byte5.1 percentage (0..100%)CWTU
629[HT10] [A] Fan: Manual/Automatic0 = Manual; 1 = Automatic1 Bit1.3 enableCWTU
629[HT10] [A] Fan: Manual/Automatic0 = Automatic; 1 = Manual1 Bit1.3 enableCWTU
630[HT10] [A] On/Off Fancoil0 = Off; 1 = On1 Bit1.1 switchCRT
631[HT10] [B] User Comfort Setpoint Reset0 = Nothing; 1 = Reset1 Bit1.15 resetCW
632[HT10] [B] User Setpoint Control[-20°C, 100°C]2 Bytes9.1 temperature (°C)CWTU
632[HT10] [B] User Setpoint Offset[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CWTU
633[HT10] [B] Step User Setpoint0 = Decrease; 1 = Increase1 Bit1.7 stepCW
634[HT10] [B] Comfort Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
634[HT10] [B] Comfort Setpoint[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
635[HT10] [B] Standby Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
636[HT10] [B] Economy Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
637[HT10] [B] Protection Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
638[HT10] [B] Comfort Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
639[HT10] [B] Standby Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
640[HT10] [B] Economy Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
641[HT10] [B] Protection Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
642[HT10] [B] Real Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
643[HT10] [B] User Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
643[HT10] [B] User Setpoint Offset Status[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CRT
644[HT10] [C] Transition Time: Comfort to Default ModeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
644[HT10] [C] Transition Time: Comfort to Default ModeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
644[HT10] [C] Transition Time: Comfort to Default ModeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
645[HT10] [C] Transition Time: Standby to EconomySeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
645[HT10] [C] Transition Time: Standby to EconomyMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
645[HT10] [C] Transition Time: Standby to EconomyHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
646[HT10] [C] Comfort Setpoint Reset TimeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
646[HT10] [C] Comfort Setpoint Reset TimeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
646[HT10] [C] Comfort Setpoint Reset TimeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
647[HT10] [C] Presence Detector (Input)0 = Not Occupied; 1 = Occupied1 Bit1.18 occupancyCRW
648[HT10] [C] Lock Presence Detection0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
648[HT10] [C] Lock Presence Detection0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
649[HT10] [C] Sold/Unsold Room (Input)0 = Unsold; 1 = Sold1 Bit1.2 booleanCRW
650[HT10] [D] Special Mode1-byte HVAC Mode1 Byte20.102 HVAC modeCW
651[HT10] [D] Special Mode: Comfort0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
651[HT10] [D] Special Mode: Comfort0 = Off; 1 = On1 Bit1.1 switchCW
652[HT10] [D] Special Mode: Standby0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
652[HT10] [D] Special Mode: Standby0 = Off; 1 = On1 Bit1.1 switchCW
653[HT10] [D] Special Mode: Economy0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
653[HT10] [D] Special Mode: Economy0 = Off; 1 = On1 Bit1.1 switchCW
654[HT10] [D] Special Mode: Protection0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
654[HT10] [D] Special Mode: Protection0 = Off; 1 = On1 Bit1.1 switchCW
655[HT10] [D] Special Mode Status1-byte HVAC Mode1 Byte20.102 HVAC modeCRT
656[HT10] [D] Comfort Mode Status0 = Off; 1 = On1 Bit1.1 switchCRT
657[HT10] [D] Window Status 1 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
657[HT10] [D] Window Status 1 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
658[HT10] [D] Window Status 2 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
658[HT10] [D] Window Status 2 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
659[HT10] [D] Window Status 3 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
659[HT10] [D] Window Status 3 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
660[HT10] [D] Window Status 4 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
660[HT10] [D] Window Status 4 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
661[HT10] [D] Enable Window Status0 = Disabled; 1 = Enabled1 Bit1.3 enableCRW
662[HT10] [D] Thermostat Lock0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
662[HT10] [D] Thermostat Lock0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
663[HT10] [D] Comfort Lower Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
664[HT10] [D] Comfort Upper Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
665[HT10] [D] Hidden Offset On/Off0 = Off; 1 = On1 Bit1.1 switchCRW
666[HT10] [D] Hidden Offset Value[-20°C, 100°C]2 Bytes9.2 temperature difference (K)CRWTU
667[HT10] [D] Eco Mode Notification0 = Out of eco range; 1 = Setpoint in Eco Range1 Bit1.2 booleanCRT
668[HT10] [D] Eco Mode RatioPercentage of Time Working in Eco Range1 Byte5.1 percentage (0..100%)CRT
669[HT10] [D] Eco Mode: Lower Limit (Cooling)Lower Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
670[HT10] [D] Eco Mode: Upper Limit (Heating)Upper Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
671[HT10] [D] Setpoint to Split[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
672[HT10] [F] Current HumidityHumidity Sensor Value2 Bytes9.7 humidity (%)CW
673[HT10] [F] High Humidity Alarm ThresholdValue of High Humidity Alarm Threshold2 Bytes9.7 humidity (%)CRWTU
674[HT10] [F] Dehumidification Control0 = Disabled; 1 = Enabled1 Bit1.3 enableCRWTU
675[HT10] [F] Dehumidification Status0 = No Dehumidifying; 1 = Dehumidifying1 Bit1.2 booleanCRT
676[HT10] [F] High Humidity0 = No Alarm; 1 = Alarm1 Bit1.5 alarmCRT
677[HT10] [F] Enable Apparent Temperature0 = Room Temperature; 1 = Apparent Temperature1 Bit1.3 enableCRWTU
678[HT10] [Cooling] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
679[HT10] [Heating] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
680[HT10] [Cooling] Control Variable2-Point Control1 Bit1.1 switchCRT
680[HT10] [Cooling] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
681[HT10] [Heating] Control Variable2-Point Control1 Bit1.1 switchCRT
681[HT10] [Heating] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
682[HT10] [Cooling] Additional CoolTemp >= (Setpoint+Band) => "1"1 Bit1.1 switchCRT
683[HT10] [Heating] Additional HeatTemp <= (Setpoint-Band) => "1"1 Bit1.1 switchCRT
684[HT10] [Cooling] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
685[HT10] [Heating] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
686[HT11] [A] On/Off0 = Off; 1 = On1 Bit1.1 switchCW
687[HT11] [A] On/Off Status0 = Off; 1 = On1 Bit1.1 switchCRT
688[HT11] [A] Scene InputScene Value1 Byte18.1 scene controlCW
689[HT11] [A] Temperature Source 1External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
690[HT11] [A] Temperature Source 2External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
691[HT11] [A] Room TemperatureCurrent Temperature2 Bytes9.1 temperature (°C)CRT
692[HT11] [A] System Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
693[HT11] [A] User Mode0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRW
694[HT11] [A] Force System Mode0 = User Mode / Auto Change; 1 = System Mode1 Bit1.1 switchCRW
695[HT11] [A] Mode Status0 = Cooling; 1 = Heating1 Bit1.100 cooling/heatingCRT
696[HT11] [A] Fan Speed0% - 100%1 Byte5.1 percentage (0..100%)CWTU
697[HT11] [A] Fan: Manual/Automatic0 = Manual; 1 = Automatic1 Bit1.3 enableCWTU
697[HT11] [A] Fan: Manual/Automatic0 = Automatic; 1 = Manual1 Bit1.3 enableCWTU
698[HT11] [A] On/Off Fancoil0 = Off; 1 = On1 Bit1.1 switchCRT
699[HT11] [B] User Comfort Setpoint Reset0 = Nothing; 1 = Reset1 Bit1.15 resetCW
700[HT11] [B] User Setpoint Control[-20°C, 100°C]2 Bytes9.1 temperature (°C)CWTU
700[HT11] [B] User Setpoint Offset[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CWTU
701[HT11] [B] Step User Setpoint0 = Decrease; 1 = Increase1 Bit1.7 stepCW
702[HT11] [B] Comfort Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
702[HT11] [B] Comfort Setpoint[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
703[HT11] [B] Standby Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
704[HT11] [B] Economy Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
705[HT11] [B] Protection Setpoint (Cooling)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
706[HT11] [B] Comfort Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
707[HT11] [B] Standby Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
708[HT11] [B] Economy Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
709[HT11] [B] Protection Setpoint (Heating)[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
710[HT11] [B] Real Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
711[HT11] [B] User Setpoint Status[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
711[HT11] [B] User Setpoint Offset Status[-15°C, 15°C]2 Bytes9.2 temperature difference (K)CRT
712[HT11] [C] Transition Time: Comfort to Default ModeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
712[HT11] [C] Transition Time: Comfort to Default ModeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
712[HT11] [C] Transition Time: Comfort to Default ModeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
713[HT11] [C] Transition Time: Standby to EconomySeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
713[HT11] [C] Transition Time: Standby to EconomyMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
713[HT11] [C] Transition Time: Standby to EconomyHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
714[HT11] [C] Comfort Setpoint Reset TimeSeconds (0 = Disabled)2 Bytes7.5 time (s)CRWTU
714[HT11] [C] Comfort Setpoint Reset TimeMinutes (0 = Disabled)2 Bytes7.6 time (min)CRWTU
714[HT11] [C] Comfort Setpoint Reset TimeHours (0 = Disabled)2 Bytes7.7 time (h)CRWTU
715[HT11] [C] Presence Detector (Input)0 = Not Occupied; 1 = Occupied1 Bit1.18 occupancyCRW
716[HT11] [C] Lock Presence Detection0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
716[HT11] [C] Lock Presence Detection0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
717[HT11] [C] Sold/Unsold Room (Input)0 = Unsold; 1 = Sold1 Bit1.2 booleanCRW
718[HT11] [D] Special Mode1-byte HVAC Mode1 Byte20.102 HVAC modeCW
719[HT11] [D] Special Mode: Comfort0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
719[HT11] [D] Special Mode: Comfort0 = Off; 1 = On1 Bit1.1 switchCW
720[HT11] [D] Special Mode: Standby0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
720[HT11] [D] Special Mode: Standby0 = Off; 1 = On1 Bit1.1 switchCW
721[HT11] [D] Special Mode: Economy0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
721[HT11] [D] Special Mode: Economy0 = Off; 1 = On1 Bit1.1 switchCW
722[HT11] [D] Special Mode: Protection0 = Nothing; 1 = Trigger1 Bit1.16 acknowledgeCW
722[HT11] [D] Special Mode: Protection0 = Off; 1 = On1 Bit1.1 switchCW
723[HT11] [D] Special Mode Status1-byte HVAC Mode1 Byte20.102 HVAC modeCRT
724[HT11] [D] Comfort Mode Status0 = Off; 1 = On1 Bit1.1 switchCRT
725[HT11] [D] Window Status 1 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
725[HT11] [D] Window Status 1 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
726[HT11] [D] Window Status 2 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
726[HT11] [D] Window Status 2 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
727[HT11] [D] Window Status 3 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
727[HT11] [D] Window Status 3 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
728[HT11] [D] Window Status 4 (Input)0 = Closed; 1 = Open1 Bit1.19 window/doorCW
728[HT11] [D] Window Status 4 (Input)0 = Open; 1 = Closed1 Bit1.19 window/doorCW
729[HT11] [D] Enable Window Status0 = Disabled; 1 = Enabled1 Bit1.3 enableCRW
730[HT11] [D] Thermostat Lock0 = Locked; 1 = Unlocked1 Bit1.3 enableCRW
730[HT11] [D] Thermostat Lock0 = Unlocked; 1 = Locked1 Bit1.3 enableCRW
731[HT11] [D] Comfort Lower Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
732[HT11] [D] Comfort Upper Limit[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRWTU
733[HT11] [D] Hidden Offset On/Off0 = Off; 1 = On1 Bit1.1 switchCRW
734[HT11] [D] Hidden Offset Value[-20°C, 100°C]2 Bytes9.2 temperature difference (K)CRWTU
735[HT11] [D] Eco Mode Notification0 = Out of eco range; 1 = Setpoint in Eco Range1 Bit1.2 booleanCRT
736[HT11] [D] Eco Mode RatioPercentage of Time Working in Eco Range1 Byte5.1 percentage (0..100%)CRT
737[HT11] [D] Eco Mode: Lower Limit (Cooling)Lower Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
738[HT11] [D] Eco Mode: Upper Limit (Heating)Upper Value for the Ecological Range2 Bytes9.1 temperature (°C)CRWTU
739[HT11] [D] Setpoint to Split[-20°C, 100°C]2 Bytes9.1 temperature (°C)CRT
740[HT11] [F] Current HumidityHumidity Sensor Value2 Bytes9.7 humidity (%)CW
741[HT11] [F] High Humidity Alarm ThresholdValue of High Humidity Alarm Threshold2 Bytes9.7 humidity (%)CRWTU
742[HT11] [F] Dehumidification Control0 = Disabled; 1 = Enabled1 Bit1.3 enableCRWTU
743[HT11] [F] Dehumidification Status0 = No Dehumidifying; 1 = Dehumidifying1 Bit1.2 booleanCRT
744[HT11] [F] High Humidity0 = No Alarm; 1 = Alarm1 Bit1.5 alarmCRT
745[HT11] [F] Enable Apparent Temperature0 = Room Temperature; 1 = Apparent Temperature1 Bit1.3 enableCRWTU
746[HT11] [Cooling] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
747[HT11] [Heating] Control VariablePI Control (Continuous)1 Byte5.1 percentage (0..100%)CRT
748[HT11] [Cooling] Control Variable2-Point Control1 Bit1.1 switchCRT
748[HT11] [Cooling] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
749[HT11] [Heating] Control Variable2-Point Control1 Bit1.1 switchCRT
749[HT11] [Heating] Control VariablePI Control (PWM)1 Bit1.1 switchCRT
750[HT11] [Cooling] Additional CoolTemp >= (Setpoint+Band) => "1"1 Bit1.1 switchCRT
751[HT11] [Heating] Additional HeatTemp <= (Setpoint-Band) => "1"1 Bit1.1 switchCRT
752[HT11] [Cooling] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
753[HT11] [Heating] PI State0 = PI Signal 0%; 1 = PI Signal Greater than 0%1 Bit1.1 switchCRT
754[HT12] [A] On/Off0 = Off; 1 = On1 Bit1.1 switchCW
755[HT12] [A] On/Off Status0 = Off; 1 = On1 Bit1.1 switchCRT
756[HT12] [A] Scene InputScene Value1 Byte18.1 scene controlCW
757[HT12] [A] Temperature Source 1External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU
758[HT12] [A] Temperature Source 2External Sensor Temperature2 Bytes9.1 temperature (°C)CWTU

First 1000 of 1807 group objects shown. Download the .knxprod for the full list.

Parameters (156)
ParameterTypeDefault
Heartbeat (Periodic Alive Notification)unsignedInt 0…2550
PeriodunsignedInt 1…655351
Synchronize Clock Master via NTPunsignedInt 0…10
IP Address of DNS Server 1ipAddress192.168.1.1
IP Address of DNS Server 2ipAddress192.168.1.2
Domain/IP of NTP Server 1text0.pool.ntp.org
Domain/IP of NTP Server 2text1.pool.ntp.org
Time Zonelist(UTC+00:00) Dublin, Edinburgh, Lisbon, London, Reykjavik
OffsetsignedInt -720…8400
Daylight Saving Time (DST)unsignedInt 0…10
DaylistLast
MonthlistMarch
Local Hourlist02:00
MonthlistOctober
Summer Time ChangeoverlistEurope
Send Date/Time after initial connectionunsignedInt 0…10
DelayunsignedInt 0…2550
Date and Time Periodical SendingunsignedInt 0…11
ValueunsignedInt 0…25510
ValueunsignedInt 0…241
Fixed Time SendingunsignedInt 0…10
Timetime0
Send Date/Time after a net reconnectionunsignedInt 0…10
Enable Debug ObjectsunsignedInt 0…10
Send Time with ChangeoverunsignedInt 0…10
Temperature SourcelistTemperature Source 1
1-Bit Objects Working Mode (See User Manual)listSwitch
Default ModelistEconomy
Economy Setpointfloat -20…10030
Economy Setpointfloat -20…10016
Thermostat FunctionlistHeating and Cooling
H/C Automatic ChangeoverlistDisabled
H/C Mode after ProgramminglistHeating
Additional Cooling BandsignedInt 5…10025
Additional Heating BandsignedInt -100…-5-25
Control Methodlist2-Point Control
Upper HysteresisunsignedInt 1…20010
Lower HysteresisunsignedInt 1…20010
Control TypelistContinuous (1 Byte)
Control ParameterslistCooling Ceiling (5K/240min)
Control ParameterslistWarm Water (5K/150min)
Proportional BandunsignedInt 1…154
Integral TimeunsignedInt 5…255150
Restart Accumulated Error on Saturation?listYes
Thermostat Always On?listYes
Startup Setting (on Bus Voltage Recovery)listLast (before Bus Failure)
Sending Statuses on Bus Voltage RecoverylistNo
Sending DelayunsignedInt 0…2550
Standby Setpointfloat -20…10019
Comfort Setpointfloat -20…10022
Comfort Setpointfloat -20…10024
Standby Setpointfloat -20…10027
Additional CoolinglistNo
Additional HeatinglistNo
Window StatusunsignedInt 0…10
Resending Period (0 = Disabled)unsignedInt 0…2550
Control VariableslistIndependent Objects for Heating and Cooling
Send both H/C Control Signals Periodically?listNo
PI CycleunsignedInt 0…25515
PWM Minimum TimeunsignedInt 1…25510
If the Switching Time Is Lower than the MinimumlistSwitch the Control Signal Using the Minimum Time
ScenesunsignedInt 0…10
Scene 1unsignedInt 0…10
Scene NumberunsignedInt 1…641
On/OfflistDo Not Change
H/C ModelistDo Not Change
Special ModelistDo Not Change
Scene 2unsignedInt 0…10
Scene 3unsignedInt 0…10
Scene 4unsignedInt 0…10
Scene 5unsignedInt 0…10
Initial Mode (after Programming)listEconomy
Comfort to Default Mode Time (0 = Disabled)unsignedInt 0…2550
Standby to Economy Time (0 = Disabled)unsignedInt 0…2550
Time to Reset the User Comfort Setpoint (0 = Disabled)unsignedInt 0…2550
Setpoint after Returning to Comfort ModelistSystem Comfort (Delayed)
User Comfort Setpoint ConstraintsunsignedInt 0…10
Lower Limitfloat -20…10015
Upper Limitfloat -20…10030
Offset Valuefloat -20…1002
Cooling Lower Limitfloat -20…10023
Heating Upper Limitfloat -20…10023
Eco Mode NotificationunsignedInt 0…10
Hidden OffsetunsignedInt 0…10
Comfort Lower BandunsignedInt 0…25530
Comfort Upper BandunsignedInt 0…25530
Allow Scene RecordingunsignedInt 0…11
1-Bit Occupancy ObjectunsignedInt 0…10
Mode to Activate after Switching to OccupiedlistLast Mode
Overheating Protection Setpointfloat -20…10035
Freezing Protection Setpointfloat -20…1007
Number of ObjectsunsignedInt 1…41
1-Byte Special Mode ControlunsignedInt 0…10
ScenesunsignedInt 0…11
Day Occupation (0 = Disabled)unsignedInt 0…640
Not Occupied (0 = Disabled)unsignedInt 0…640
False Non-Occupied Detection (0 = Disabled)unsignedInt 0…640
Restrict the State Object to the Setpoint LimitunsignedInt 0…10
Sold/Unsold Room ObjectunsignedInt 0…11
Mode after Exiting ComfortlistStay in the Same H/C Mode
Default ModelistStandby
Mode to Activate when the Room Is not SoldlistEconomy
Configurationlist0 = Closed; 1 = Open
Configurationlist0 = Unlocked; 1 = Locked
Thermostat Locking ObjectunsignedInt 0…10
Fan Mode Object Valuelist0 = Automatic; 1 = Manual
Initial Fan SpeedunsignedInt 0…100100
Initial Fan Mode for ComfortlistManual
Night Occupation (0 = Disabled)unsignedInt 0…640
Setpoint to SplitunsignedInt 0…10
Offset Value when System Mode is HeatingsignedInt -50…5020
Offset Value when System Mode is CoolingsignedInt -50…50-20
Value to Lock Occupancy Objectlist0 = Unlocked; 1 = Locked
DehumidificationunsignedInt 0…10
Reference TemperaturelistRoom Temperature
High HumidityunsignedInt 0…10065
HysteresisunsignedInt 1…255
Fan SpeedunsignedInt 0…10010
ComfortunsignedInt 0…2000
StandbyunsignedInt 0…20010
EconomyunsignedInt 0…20010
Dehumidification in Occupied RoomunsignedInt 0…10
Return HysteresisunsignedInt 0…2005
ProtectionunsignedInt 0…20020
Setpoint TypelistAbsolute
th[0].hcAuto_relativeunsignedInt 0…10
Out of Comfort Lower BandunsignedInt 0…2550
Out of Comfort Upper BandunsignedInt 0…2550
Step User Setpoint ObjectunsignedInt 0…10
Temperature Incrementfloat 1…1005
PWM Minimum TimeunsignedInt 1…301
Restart Accumulated Error after Setpoint Change?listYes
Maximum Sending ObjectsunsignedInt 0…2555
Minimum Time between Object SendingsunsignedInt 0…2552
Hospitality Thermostat 1unsignedInt 0…10
Hospitality Thermostat 2unsignedInt 0…10
Hospitality Thermostat 3unsignedInt 0…10
Hospitality Thermostat 5unsignedInt 0…10
Hospitality Thermostat 6unsignedInt 0…10
Hospitality Thermostat 7unsignedInt 0…10
Hospitality Thermostat 8unsignedInt 0…10
Hospitality Thermostat 9unsignedInt 0…10
Hospitality Thermostat 10unsignedInt 0…10
Hospitality Thermostat 11unsignedInt 0…10
Hospitality Thermostat 12unsignedInt 0…10
Hospitality Thermostat 13unsignedInt 0…10
Hospitality Thermostat 14unsignedInt 0…10
Hospitality Thermostat 15unsignedInt 0…10
Hospitality Thermostat 16unsignedInt 0…10
Hospitality Thermostat 17unsignedInt 0…10
Hospitality Thermostat 18unsignedInt 0…10
Hospitality Thermostat 19unsignedInt 0…10
Hospitality Thermostat 20unsignedInt 0…10
Hospitality Thermostat 4unsignedInt 0…10
checkHWlist
DEVICE_TYPE (virtual)listKIPI SC

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KIPI SC 1.1 1.1 latest$6391346B2026-11-25669 KBDownload

About this file

This is the official ETS product database for the Zennio KIPI SC (ZSYKIPISC), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Zennio

All Zennio products