VIMAR 01546 01546 KNX Weather Station

01546 KNX Weather Station 01546

VIMAR · Order number 01546 · Sensors › Weather stations

Download .knxprod KNX Weather Station 1.3 · 174 KB

Product

ManufacturerVIMAR
Product name01546 KNX Weather Station
Order number01546
Hardware01546 KNX Wetterstation
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified
Languagesde-DE, en-US, it-IT, es-ES
Catalog entryM-002C_H-3095-1-O00C9_HP-060A-13-CC93-O00C9_CI-01546-1
FingerprintCC93
SHA-25638fe97022d7d743c9540817eecbabc18b12537a449e1e11861191fe91c932de7
First seen2026-11-25
Markets69 markets

Application program: KNX Weather Station 1.3

Application number$060A
Version1.3
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Parameters436
Group objects109
Group objects (109)
NoNameFunctionSizeDPTFlags
0Switching output nightOutput1 Bit1.1 switchCRT
1Switching output rainOutput1 Bit1.1 switchCRT
2Logic input 11 Bit1.1 switchCRW
3Logic input 21 Bit1.1 switchCRW
4Logic input 31 Bit1.1 switchCRW
5Logic input 41 Bit1.1 switchCRW
6Logic input 51 Bit1.1 switchCRW
7Logic input 61 Bit1.1 switchCRW
8Logic input 71 Bit1.1 switchCRW
9Logic input 81 Bit1.1 switchCRW
10Temperature sensor malfunctionOutput1 Bit1.1 switchCRT
11Wind sensor malfunctionOutput1 Bit1.1 switchCRT
12Temperature measured value2 Bytes9.1 temperature (°C)CRT
13Request min./max. temperatureRequest1 Bit1.1 switchCRW
14lowest measured value for temperaturesends min. temperature2 Bytes9.1 temperature (°C)CRT
15maximum measured value for temperaturesends max. temperature2 Bytes9.1 temperature (°C)CRT
16min./max. temperature resetReset temperatures1 Bit1.1 switchCRW
17Temperature threshold value 1Target value2 Bytes9.1 temperature (°C)CRW
18Temperature threshold value 1Actual value2 Bytes9.1 temperature (°C)CRT
19Temperature threshold value 2Target value2 Bytes9.1 temperature (°C)CRW
20Temperature threshold value 2Actual value2 Bytes9.1 temperature (°C)CRT
21Temperature threshold value 3Target value2 Bytes9.1 temperature (°C)CRW
22Temperature threshold value 3Actual value2 Bytes9.1 temperature (°C)CRT
23Temperature threshold value 4Target value2 Bytes9.1 temperature (°C)CRW
24Temperature threshold value 4Actual value2 Bytes9.1 temperature (°C)CRT
25Switching output temperature threshold value 11 Bit1.1 switchCRT
26Switching output temperature threshold value 21 Bit1.1 switchCRT
27Switching output temperature threshold value 31 Bit1.1 switchCRT
28Switching output temperature threshold value 41 Bit1.1 switchCRT
29Wind force measured value2 Bytes9.5 speed (m/s)CRT
30Request max. wind forceRequest1 Bit1.1 switchCRW
31maximum measured value for wind loadsends max. temperature2 Bytes9.5 speed (m/s)CRT
32max wind force resetReset wind force1 Bit1.1 switchCRW
33Wind force threshold value 1Target value2 Bytes9.5 speed (m/s)CRW
34Wind force threshold value 1Actual value2 Bytes9.5 speed (m/s)CRT
35Wind force threshold value 2Target value2 Bytes9.5 speed (m/s)CRW
36Wind force threshold value 2Actual value2 Bytes9.5 speed (m/s)CRT
37Wind force threshold value 3Target value2 Bytes9.5 speed (m/s)CRW
38Wind force threshold value 3Actual value2 Bytes9.5 speed (m/s)CRT
39Switching output wind force threshold value 11 Bit1.1 switchCRT
40Switching output wind force threshold value 21 Bit1.1 switchCRT
41Switching output wind force threshold value 31 Bit1.1 switchCRT
42Brightness measured value2 Bytes9.4 lux (Lux)CRT
43Brightness threshold value 1Target value2 Bytes9.4 lux (Lux)CRW
44Brightness threshold value 1Actual value2 Bytes9.4 lux (Lux)CRT
45Brightness threshold value 2Target value2 Bytes9.4 lux (Lux)CRW
46Brightness threshold value 2Actual value2 Bytes9.4 lux (Lux)CRT
47Brightness threshold value 3Target value2 Bytes9.4 lux (Lux)CRW
48Brightness threshold value 3Actual value2 Bytes9.4 lux (Lux)CRT
49Switching output brightness threshold value 11 Bit1.1 switchCRT
50Switching output brightness threshold value 21 Bit1.1 switchCRT
51Switching output brightness threshold value 31 Bit1.1 switchCRT
52Dawn threshold value 1Target value2 Bytes9.4 lux (Lux)CRW
53Dawn threshold value 1Actual value2 Bytes9.4 lux (Lux)CRT
54Dawn threshold value 2Target value2 Bytes9.4 lux (Lux)CRW
55Dawn threshold value 2Actual value2 Bytes9.4 lux (Lux)CRT
56Dawn threshold value 3Target value2 Bytes9.4 lux (Lux)CRW
57Dawn threshold value 3Actual value2 Bytes9.4 lux (Lux)CRT
58Switching output dawn threshold value 11 Bit1.1 switchCRT
59Switching output dawn threshold value 21 Bit1.1 switchCRT
60Switching output dawn threshold value 31 Bit1.1 switchCRT
61AND logic 1Switching output1 Bit1.1 switchCRT
62AND logic 18 bit Output A1 Byte5.10 counter pulses (0..255)CRT
63AND logic 18 bit Output B1 Byte5.10 counter pulses (0..255)CRT
64AND logic 2Switching output1 Bit1.1 switchCRT
65AND logic 28 bit Output A1 Byte5.10 counter pulses (0..255)CRT
66AND logic 28 bit Output B1 Byte5.10 counter pulses (0..255)CRT
67AND logic 3Switching output1 Bit1.1 switchCRT
68AND logic 38 bit Output A1 Byte5.10 counter pulses (0..255)CRT
69AND logic 38 bit Output B1 Byte5.10 counter pulses (0..255)CRT
70AND logic 4Switching output1 Bit1.1 switchCRT
71AND logic 48 bit Output A1 Byte5.10 counter pulses (0..255)CRT
72AND logic 48 bit Output B1 Byte5.10 counter pulses (0..255)CRT
73AND logic 5Switching output1 Bit1.1 switchCRT
74AND logic 58 bit Output A1 Byte5.10 counter pulses (0..255)CRT
75AND logic 58 bit Output B1 Byte5.10 counter pulses (0..255)CRT
76AND logic 6Switching output1 Bit1.1 switchCRT
77AND logic 68 bit Output A1 Byte5.10 counter pulses (0..255)CRT
78AND logic 68 bit Output B1 Byte5.10 counter pulses (0..255)CRT
79AND logic 7Switching output1 Bit1.1 switchCRT
80AND logic 78 bit Output A1 Byte5.10 counter pulses (0..255)CRT
81AND logic 78 bit Output B1 Byte5.10 counter pulses (0..255)CRT
82AND logic 8Switching output1 Bit1.1 switchCRT
83AND logic 88 bit Output A1 Byte5.10 counter pulses (0..255)CRT
84AND logic 88 bit Output B1 Byte5.10 counter pulses (0..255)CRT
85OR logic 1Switching output1 Bit1.1 switchCRT
86OR logic 18 bit Output A1 Byte5.10 counter pulses (0..255)CRT
87OR logic 18 bit Output B1 Byte5.10 counter pulses (0..255)CRT
88OR logic 2Switching output1 Bit1.1 switchCRT
89OR logic 28 bit Output A1 Byte5.10 counter pulses (0..255)CRT
90OR logic 28 bit Output B1 Byte5.10 counter pulses (0..255)CRT
91OR logic 3Switching output1 Bit1.1 switchCRT
92OR logic 38 bit Output A1 Byte5.10 counter pulses (0..255)CRT
93OR logic 38 bit Output B1 Byte5.10 counter pulses (0..255)CRT
94OR logic 4Switching output1 Bit1.1 switchCRT
95OR logic 48 bit Output A1 Byte5.10 counter pulses (0..255)CRT
96OR logic 48 bit Output B1 Byte5.10 counter pulses (0..255)CRT
97OR logic 5Switching output1 Bit1.1 switchCRT
98OR logic 58 bit Output A1 Byte5.10 counter pulses (0..255)CRT
99OR logic 58 bit Output B1 Byte5.10 counter pulses (0..255)CRT
100OR logic 6Switching output1 Bit1.1 switchCRT
101OR logic 68 bit Output A1 Byte5.10 counter pulses (0..255)CRT
102OR logic 68 bit Output B1 Byte5.10 counter pulses (0..255)CRT
103OR logic 7Switching output1 Bit1.1 switchCRT
104OR logic 78 bit Output A1 Byte5.10 counter pulses (0..255)CRT
105OR logic 78 bit Output B1 Byte5.10 counter pulses (0..255)CRT
106OR logic 8Switching output1 Bit1.1 switchCRT
107OR logic 88 bit Output A1 Byte5.10 counter pulses (0..255)CRT
108OR logic 88 bit Output B1 Byte5.10 counter pulses (0..255)CRT
Parameters (102)
ParameterTypeDefault
Send measured values cyclically everylist 5 sec
Send switching outputs cyclically everylist 5 sec
Logic outputs cyclical send alllist 5 sec
Communication objects logic inputslistdo not release
Communication object switching output nightlistsend in case of change
Communication object switching output rainlistsend in case of change
Transmission delay of the switching outputs after power up and programminglist10 sec
Maximum telegram quotalist 5 Telegrams per second
Measured valuelistcyclically send
from temperature change oflist0,5 °C
Temperature offset in 0.1°CsignedInt -50…500
Send and reset of the min. and max. temperature value on requestlistdo not release
Use malfunction objectlistNo
Threshold value 1listnot active
Threshold value 2listnot active
Threshold value 3listnot active
Threshold value 4listnot active
Threshold value is set bylistParameter
Threshold value in 0,1°CsignedInt -300…800200
Start threshold value in 0.1°C valid until 1.communicationsignedInt -300…800200
ATTENTION:listDo not use for first commissioning
Hysteresis of the threshold value in 0.1 °CunsignedInt 0…10030
start-up delaylistnone
Switch-off delaylistnone
Output switches atlistTV above = ON | TV - Hyst. below = OFF
Communication object switching output temperature threshold value 1listnot send
Communication object switching output temperature threshold value 2listnot send
Communication object switching output temperature threshold value 3listnot send
Communication object switching output temperature threshold value 4listnot send
from wind force change oflist1 m/sec
Send and reset of the maximum wind load value on requestlistdo not release
Threshold value in 0,1° m/secunsignedInt 0…35040
Start threshold value in 0.1 m/s valid until 1.communicationunsignedInt 0…35040
Hysteresis of the threshold value in 0.1 m/sunsignedInt 0…25020
Communication object switching output wind load threshold value 1listnot send
Communication object switching output wind force threshold value 2listnot send
Communication object switching output wind force threshold value 3listnot send
from change in %unsignedInt 1…5010
Threshold value in kluxunsignedInt 1…995
Start threshold value in kLux valid until 1.communicationunsignedInt 1…995
Hysteresis of the threshold value in kluxunsignedInt 0…992
Communication object switching output brightness threshold value 1listnot send
Communication object Schaltausgang Helligkeit Grenzwert 2listnot send
Communication object Schaltausgang Helligkeit Grenzwert 3listnot send
Threshold value in luxunsignedInt 1…1000200
Start threshold value in lux valid until 1.communicationunsignedInt 1…1000200
Hysteresis of the threshold value in kluxunsignedInt 0…100050
Communication object switching output dawn threshold value 1listnot send
Communication object switching output dawn threshold value 2listnot send
Communication object switching output dawn threshold value 3listnot send
Logic 1listnot active
Logic 2listnot active
Logic 3listnot active
Logic 4listnot active
Logic 5listnot active
Logic 6listnot active
Logic 7listnot active
Logic 8listnot active
1. Inputlistdo not use
2. Inputlistdo not use
3. Inputlistdo not use
4. Inputlistdo not use
Logic output sendslistnot
if logic = 1 ==> object A valueunsignedInt 0…255127
if logic = 0 ==> object A valueunsignedInt 0…2550
if logic = 1 ==> object B valueunsignedInt 0…255127
if logic = 0 ==> object B valueunsignedInt 0…2550
if logic = 1 ==> object valuelist1
if logic = 0 ==> object valuelist0
Communication objects AND logic 1 A and B sendlistin case of the change of the logic
Communication object AND logic 1 sendslistin case of the change of the logic
Communication objects AND logic 2 A and B sendlistin case of the change of the logic
Communication object AND logic 2 sendslistin case of the change of the logic
Communication objects AND logic 3 A and B sendlistin case of the change of the logic
Communication object AND logic 3 sendslistin case of the change of the logic
Communication objects AND logic 4 A and B sendlistin case of the change of the logic
Communication object AND logic 4 sendslistin case of the change of the logic
Communication objects AND logic 5 A and B sendlistin case of the change of the logic
Communication object AND logic 5 sendslistin case of the change of the logic
Communication objects AND logic 6 A and B sendlistin case of the change of the logic
Communication object AND logic 6 sendslistin case of the change of the logic
Communication objects AND logic 7 A and B sendlistin case of the change of the logic
Communication object AND logic 7 sendslistin case of the change of the logic
Communication objects AND logic 8 A and B sendlistin case of the change of the logic
Communication object AND logic 8 sendslistin case of the change of the logic
Logic output sendslistone 1 bit object
Communication objects OR logic 1 A and B sendlistin case of the change of the logic
Communication object OR logic 1 sendslistin case of the change of the logic
Communication object OR logic 2 sendslistin case of the change of the logic
Communication objects OR logic 2 A and B sendlistin case of the change of the logic
Communication object OR logic 3 sendslistin case of the change of the logic
Communication objects OR logic 3 A and B sendlistin case of the change of the logic
Communication object OR logic 4 sendslistin case of the change of the logic
Communication objects OR logic 4 A and B sendlistin case of the change of the logic
Communication object OR logic 5 sendslistin case of the change of the logic
Communication objects OR logic 5 A and B sendlistin case of the change of the logic
Communication object OR logic 6 sendslistin case of the change of the logic
Communication objects OR logic 6 A and B sendlistin case of the change of the logic
Communication object OR logic 7 sendslistin case of the change of the logic
Communication objects OR logic 7 A and B sendlistin case of the change of the logic
Communication object OR logic 8 sendslistin case of the change of the logic
Communication objects OR logic 8 A and B sendlistin case of the change of the logic

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX Weather Station 1.3 latest$060ACC932026-11-25174 KBDownload

About this file

This is the official ETS product database for the VIMAR 01546 KNX Weather Station (01546), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.