01535 6-out solenoid valve actuator 01535
VIMAR · Order number 01535 · Heating, air-con., ventilation › 01535 6-out solenoid valve actuator
6-out solenoid valve actuator KNX
Download .knxprod 6-out solenoid valve actuator KNX 1.1 · 448 KB
Product
| Manufacturer | VIMAR |
|---|---|
| Product name | 01535 6-out solenoid valve actuator |
| Order number | 01535 |
| Hardware | 01535 6-out solenoid valve actuator |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | Yes |
| Width (mm) | 72 |
| Registration | Certified |
| Languages | de-DE, en-US, it-IT |
| Catalog entry | M-002C_H-01535-1-O0002_HP-A07B-11-DAC6-O0002_CI-01535-1 |
| Fingerprint | DAC6 |
| SHA-256 | 0e7d9e3cae7664a0554e517904c96b73974c38ee36866fba7c31d3d7da1d2f30 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: 6-out solenoid valve actuator KNX 1.1
| Application number | $A07B |
|---|---|
| Version | 1.1 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Parameters | 354 |
| Group objects | 82 |
Group objects (82)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | General | In operation | 1 Bit | 1.2 boolean | CRT |
| 1 | General | Request status values | 1 Bit | DPT.1 | CWT |
| 2 | General | Status manual operation | 1 Bit | DPT.1 | CRT |
| 3 | General | Disable/enable man. operation | 1 Bit | 1.3 enable | CRW |
| 4 | Output A-X | Reset overload/short circuit | 1 Bit | DPT.1 | CWT |
| 5 | Object 5 | Dummy | 1 Bit | DPT.1 | |
| 6 | Object 6 | Dummy | 1 Bit | DPT.1 | |
| 7 | Object 7 | Dummy | 1 Bit | DPT.1 | |
| 8 | Object 8 | Dummy | 1 Bit | DPT.1 | |
| 9 | Object 9 | Dummy | 1 Bit | DPT.1 | |
| 10 | Output A | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 10 | Output A | Control value, switch | 1 Bit | 1.1 switch | CW |
| 11 | Output A | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 12 | Output A | Reset error message | 1 Bit | DPT.1 | CWT |
| 13 | Output A | Fault control value | 1 Bit | DPT.1 | CRT |
| 14 | Output A | Block | 1 Bit | 1.3 enable | CW |
| 15 | Output A | Forced operation | 1 Bit | 1.3 enable | CW |
| 16 | Output A | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 17 | Output A | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 18 | Output A | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 18 | Output A | Status control value | 1 Bit | DPT.1 | CRT |
| 19 | Output A | Status byte | 1 Byte | CRT | |
| 20 | Output B | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 20 | Output B | Control value, switch | 1 Bit | 1.1 switch | CW |
| 21 | Output B | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 22 | Output B | Reset error message | 1 Bit | DPT.1 | CWT |
| 23 | Output B | Fault control value | 1 Bit | DPT.1 | CRT |
| 24 | Output B | Block | 1 Bit | 1.3 enable | CW |
| 25 | Output B | Forced operation | 1 Bit | 1.3 enable | CW |
| 26 | Output B | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 27 | Output B | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 28 | Output B | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 28 | Output B | Status control value | 1 Bit | DPT.1 | CRT |
| 29 | Output B | Status byte | 1 Byte | CRT | |
| 30 | Output C | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 30 | Output C | Control value, switch | 1 Bit | 1.1 switch | CW |
| 31 | Output C | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 32 | Output C | Reset error message | 1 Bit | DPT.1 | CWT |
| 33 | Output C | Fault control value | 1 Bit | DPT.1 | CRT |
| 34 | Output C | Block | 1 Bit | 1.3 enable | CW |
| 35 | Output C | Forced operation | 1 Bit | 1.3 enable | CW |
| 36 | Output C | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 37 | Output C | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 38 | Output C | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 38 | Output C | Status control value | 1 Bit | DPT.1 | CRT |
| 39 | Output C | Status byte | 1 Byte | CRT | |
| 40 | Output D | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 40 | Output D | Control value, switch | 1 Bit | 1.1 switch | CW |
| 41 | Output D | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 42 | Output D | Reset error message | 1 Bit | DPT.1 | CWT |
| 43 | Output D | Fault control value | 1 Bit | DPT.1 | CRT |
| 44 | Output D | Block | 1 Bit | 1.3 enable | CW |
| 45 | Output D | Forced operation | 1 Bit | 1.3 enable | CW |
| 46 | Output D | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 47 | Output D | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 48 | Output D | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 48 | Output D | Status control value | 1 Bit | DPT.1 | CRT |
| 49 | Output D | Status byte | 1 Byte | CRT | |
| 50 | Output E | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 50 | Output E | Control value, switch | 1 Bit | 1.1 switch | CW |
| 51 | Output E | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 52 | Output E | Reset error message | 1 Bit | DPT.1 | CWT |
| 53 | Output E | Fault control value | 1 Bit | DPT.1 | CRT |
| 54 | Output E | Block | 1 Bit | 1.3 enable | CW |
| 55 | Output E | Forced operation | 1 Bit | 1.3 enable | CW |
| 56 | Output E | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 57 | Output E | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 58 | Output E | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 58 | Output E | Status control value | 1 Bit | DPT.1 | CRT |
| 59 | Output E | Status byte | 1 Byte | CRT | |
| 60 | Output F | Control value,continuous (PWM) | 1 Byte | 5.1 percentage (0..100%) | CW |
| 60 | Output F | Control value, switch | 1 Bit | 1.1 switch | CW |
| 61 | Output F | Overload/short circuit | 1 Bit | DPT.1 | CRT |
| 62 | Output F | Reset error message | 1 Bit | DPT.1 | CWT |
| 63 | Output F | Fault control value | 1 Bit | DPT.1 | CRT |
| 64 | Output F | Block | 1 Bit | 1.3 enable | CW |
| 65 | Output F | Forced operation | 1 Bit | 1.3 enable | CW |
| 66 | Output F | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 67 | Output F | Status valve purge | 1 Bit | 1.3 enable | CRT |
| 68 | Output F | Status control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 68 | Output F | Status control value | 1 Bit | DPT.1 | CRT |
| 69 | Output F | Status byte | 1 Byte | CRT |
Parameters (55)
| Parameter | Type | Default |
|---|---|---|
| Send communication object "In operation" | list | no |
| Sending cycle time in s [1...65,535] | unsignedInt 0…65535 | 0 |
| Sending cycle time in s [1...65,535] | unsignedInt 1…65535 | 60 |
| Sending and switching delay after bus voltage recovery in s (2...255) | unsignedInt 2…255 | 2 |
| Limit number of telegrams | list | no |
| Max. number of sent telegrams | unsignedInt 0…255 | 10 |
| Max. number of sent telegrams [1...255] | unsignedInt 1…255 | 20 |
| in period | unsignedInt 0…65535 | 56 |
| in period | list | 100 ms |
| Enable communication object "Request status values" 1 bit | list | no |
| Request with object value | list | 0 |
| Manual operation | list | enabled |
| Reset manual operation to KNX operation | list | after 1 Minute |
| Enable communication object "Status man. operation" 1 bit | list | no |
| Send object value | list | after a change |
| Enable power saving mode (LEDs in KNX mode off) | list | no |
| Type of valve drive | list | de-energised closed |
| Reaction after bus voltage recovery | list | unchanged |
| Control value after bus voltage recovery in % [0...100] | unsignedInt 1…255 | 255 |
| Control value in % [0...100] | unsignedInt 0…100 | 0 |
| Control value is received as | list | 1 bit |
| Convert control value to | list | PWM (pulse width modulation) |
| OPEN at control value greater or equal in % [1...100] | unsignedInt 1…100 | 1 |
| Cycle time of PWM in s [10...6,000] | unsignedInt 10…6000 | 180 |
| Opening time of valve drive in s [10...6,000] | unsignedInt 10…6000 | 180 |
| Closing time of valve drive in s [10...6,000] | unsignedInt 10…6000 | 180 |
| Set cycle time PWM, open./closing time for contr. value in % on bus voltage | list | <--- NOTE |
| Monitoring control values e.g. thermostat | list | no |
| Monitoring time in s [30...65,535] | unsignedInt 30…65535 | 120 |
| Send object value (Object "Fault control value" 1 bit) | list | after a change |
| Control value after controller fault in % [0...100] | unsignedInt 0…100 | 30 |
| Enable communication object "Block" 1 bit | list | no |
| Block on object value | list | 1 |
| Enable communication object "Forced operation" 1 bit | list | no |
| Forced operation on object value | list | 1 |
| Control value on forced operation in % [0...100] | unsignedInt 0…100 | 30 |
| Enable communication object "Status control value" 1 byte/1 bit | list | no |
| Object value at control value > 0 | list | 1 |
| Enable valve purge | list | no |
| Enable communication object "Status valve purge" 1 bit | list | no |
| Duration of valve purge in min. [1...255] | unsignedInt 1…255 | 10 |
| Automatic valve purge | list | no |
| Purge cycle in weeks [1...12] | unsignedInt 1…12 | 6 |
| Reset purge cycle from control value in % [1...99] | unsignedInt 1…99 | 99 |
| Reset purge cycle from control value in % [1...99] | unsignedInt 1…255 | 111 |
| Enable characteristic curve | list | no |
| Value pair 1 Control value in % [0...100] | unsignedInt 0…100 | 0 |
| Valve position in % [0...100] | unsignedInt 0…100 | 0 |
| Value pair 2 Control value in % [0...100] | unsignedInt 0…100 | 100 |
| Valve position in % [0...100] | unsignedInt 0…100 | 100 |
| Enable value pair 3 | list | no |
| Value pair 3 Control value in % [0...100] | unsignedInt 0…100 | 50 |
| Valve position in % [0...100] | unsignedInt 0…100 | 50 |
| Enable value pair 4 | list | no |
| Value pair 4 Control value in % [0...100] | unsignedInt 0…100 | 50 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| 6-out solenoid valve actuator KNX 1.1 latest | $A07B | DAC6 | 2026-11-25 | 448 KB | Download |
About this file
This is the official ETS product database for the VIMAR 01535 6-out solenoid valve actuator (01535), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from VIMAR
- 01500.1 Power supply,320mA,MDRC 01500.1
- 01500.2 Power supply unit 320mA KNX 01500.2
- 01501.1 Power supply,640mA,MDRC 01501.1
- 01501.2 Power supply unit 640mA KNX 01501.2
- 01504.1 Line-/Area Coupler, MDRC 01504.1
- 01504.2 Line coupler 01504.2
- 01506 By-me Plus KNX Secure TP router 01506
- 01507 By-me Plus KNX Secure IP router 01507
- 01510 4 Fold Input 01510
- 01514 2Inputs/Outputs Interface 01514
- 01515.1 Universal Interfaces, 4-fold 01515.1
- 01521 Switch actuator 12-fold 10A 01521