KNX Database
VIMAR 01525 01525 Blind/Shutter Actuator 8-fold

01525 Blind/Shutter Actuator 8-fold 01525

VIMAR · Order number 01525 · Shutter › Switch

Blind/Shutter_Actuator_8-fold_KNX

Download .knxprod Blind/Shutter_Actuator_8-fold_KNX 1.4 · 742 KB

Product

ManufacturerVIMAR
Product name01525 Blind/Shutter Actuator 8-fold
Order number01525
HardwareJRA/S8.230.1.1 Jal./Rol.Akt.8f,230V,REG
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)144
RegistrationCertified
Languagesde-DE, en-US, it-IT
Catalog entryM-002C_H-2CDG.20110.20131.20R0011-1-O0002_HP-A079-14-17B2-O0002_CI-01525-1
Fingerprint17B2
SHA-2569895672bd7a3000202250eeeb86e58b102cf849c39f48e89b4cf95146808dd6e
First seen2026-11-25
Markets69 markets

Application program: Blind/Shutter_Actuator_8-fold_KNX 1.4

Application number$A079
Version1.4
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Parameters2360
Group objects306
Group objects (306)
NoNameFunctionSizeDPTFlags
0GeneralIn operation1 BitCRT
1GeneralRequest status values1 BitCW
2GeneralDisable/enable man. operation1 BitCW
3GeneralStatus manual operation1 BitCRT
4Output A-XWind alarm no. 11 BitCWTU
5Output A-XWind alarm no. 21 BitCWTU
6Output A-XWind alarm no. 31 BitCWTU
7Output A-XRain alarm1 BitCWTU
8Output A-XFrost alarm1 BitCWTU
9Object 91 BitCW
10Output AMove blinds/shutter up-down1 BitCW
10Output AFlaps open-closed/on-off1 BitCW
11Output ASlat adjustm./stop up-down1 BitCW
11Output AStop Up-Down1 BitCW
12Output AEnable limitation1 BitCW
12Output ABlinds/shutter up-down limited1 BitCW
13Output AMove to position height 0..2551 ByteCW
14Output AMove slats 0..2551 ByteCW
15Output AMove to position 1, 21 BitCW
16Output AMove to position 3, 41 BitCW
17Output ASet position 1, 21 BitCW
18Output ASet position 3, 41 BitCW
19Output ATrigger travel detection1 BitCW
19Output ATrigger reference movement1 BitCW
20Output A8 bit scene1 ByteCW
21Output AActivation of autom. control1 BitCWTU
22Output ASun1 BitCWTU
23Output AMove to height for sun 0..2551 ByteCWTU
24Output AAdjust slat for sun 0..2551 ByteCWTU
25Output APresence1 BitCWTU
26Output AHeating1 BitCWTU
27Output ACooling1 BitCWTU
28Output AReceive room temperature2 BytesCWTU
29Output ADisable/enable autom. control1 BitCWTU
30Output ADisable/enable direct control1 BitCWTU
31Output ABlock1 BitCWTU
32Output AForced operation 1 bit1 BitCWTU
32Output AForced operation 2 bit2 BitCWTU
32Output AForced operation 2 bit2 BitCW
33Output AStatus open-closed/on-off1 BitCRT
33Output AStatus height 0...2551 ByteCRT
34Output AStatus slat 0...2551 ByteCRT
35Output AStatus upper end position1 BitCRT
36Output AStatus lower end position1 BitCRT
37Output AStatus operability1 BitCRT
38Output AStatus automatic control1 BitCRT
39Output AStatus information2 BytesCRT
40Output BMove blinds/shutter up-down1 BitCW
40Output BFlaps open-closed/on-off1 BitCW
41Output BSlat adjustm./stop up-down1 BitCW
41Output BStop Up-Down1 BitCW
42Output BBlinds/shutter up-down limited1 BitCW
42Output BEnable limitation1 BitCW
43Output BMove to position height 0..2551 ByteCW
44Output BMove slats 0..2551 ByteCW
45Output BMove to position 1, 21 BitCW
46Output BMove to position 3, 41 BitCW
47Output BSet position 1, 21 BitCW
48Output BSet position 3, 41 BitCW
49Output BTrigger reference movement1 BitCW
49Output BTrigger travel detection1 BitCW
50Output B8 bit scene1 ByteCW
51Output BActivation of autom. control1 BitCWTU
52Output BSun1 BitCWTU
53Output BMove to height for sun 0..2551 ByteCWTU
54Output BAdjust slat for sun 0..2551 ByteCWTU
55Output BPresence1 BitCWTU
56Output BHeating1 BitCWTU
57Output BCooling1 BitCWTU
58Output BReceive room temperature2 BytesCWTU
59Output BDisable/enable autom. control1 BitCWTU
60Output BDisable/enable direct control1 BitCWTU
61Output BBlock1 BitCWTU
62Output BForced operation 1 bit1 BitCWTU
62Output BForced operation 2 bit2 BitCWTU
62Output BForced operation 2 bit2 BitCW
63Output BStatus height 0...2551 ByteCRT
63Output BStatus open-closed/on-off1 BitCRT
64Output BStatus slat 0...2551 ByteCRT
65Output BStatus upper end position1 BitCRT
66Output BStatus lower end position1 BitCRT
67Output BStatus operability1 BitCRT
68Output BStatus automatic control1 BitCRT
69Output BStatus information2 BytesCRT
70Output CMove blinds/shutter up-down1 BitCW
70Output CFlaps open-closed/on-off1 BitCW
71Output CSlat adjustm./stop up-down1 BitCW
71Output CStop Up-Down1 BitCW
72Output CBlinds/shutter up-down limited1 BitCW
72Output CEnable limitation1 BitCW
73Output CMove to position height 0..2551 ByteCW
74Output CMove slats 0..2551 ByteCW
75Output CMove to position 1, 21 BitCW
76Output CMove to position 3, 41 BitCW
77Output CSet position 1, 21 BitCW
78Output CSet position 3, 41 BitCW
79Output CTrigger reference movement1 BitCW
79Output CTrigger travel detection1 BitCW
80Output C8 bit scene1 ByteCW
81Output CActivation of autom. control1 BitCWTU
82Output CSun1 BitCWTU
83Output CMove to height for sun 0..2551 ByteCWTU
84Output CAdjust slat for sun 0..2551 ByteCWTU
85Output CPresence1 BitCWTU
86Output CHeating1 BitCWTU
87Output CCooling1 BitCWTU
88Output CReceive room temperature2 BytesCWTU
89Output CDisable/enable autom. control1 BitCWTU
90Output CDisable/enable direct control1 BitCWTU
91Output CBlock1 BitCWTU
92Output CForced operation 1 bit1 BitCWTU
92Output CForced operation 2 bit2 BitCWTU
92Output CForced operation 2 bit2 BitCW
93Output CStatus height 0...2551 ByteCRT
93Output CStatus open-closed/on-off1 BitCRT
94Output CStatus slat 0...2551 ByteCRT
95Output CStatus upper end position1 BitCRT
96Output CStatus lower end position1 BitCRT
97Output CStatus operability1 BitCRT
98Output CStatus automatic control1 BitCRT
99Output CStatus information2 BytesCRT
100Output DMove blinds/shutter up-down1 BitCW
100Output DFlaps open-closed/on-off1 BitCW
101Output DSlat adjustm./stop up-down1 BitCW
101Output DStop Up-Down1 BitCW
102Output DBlinds/shutter up-down limited1 BitCW
102Output DEnable limitation1 BitCW
103Output DMove to position height 0..2551 ByteCW
104Output DMove slats 0..2551 ByteCW
105Output DMove to position 1, 21 BitCW
106Output DMove to position 3, 41 BitCW
107Output DSet position 1, 21 BitCW
108Output DSet position 3, 41 BitCW
109Output DTrigger reference movement1 BitCW
109Output DTrigger travel detection1 BitCW
110Output D8 bit scene1 ByteCW
111Output DActivation of autom. control1 BitCWTU
112Output DSun1 BitCWTU
113Output DMove to height for sun 0..2551 ByteCWTU
114Output DAdjust slat for sun 0..2551 ByteCWTU
115Output DPresence1 BitCWTU
116Output DHeating1 BitCWTU
117Output DCooling1 BitCWTU
118Output DReceive room temperature2 BytesCWTU
119Output DDisable/enable autom. control1 BitCWTU
120Output DDisable/enable direct control1 BitCWTU
121Output DBlock1 BitCWTU
122Output DForced operation 1 bit1 BitCWTU
122Output DForced operation 2 bit2 BitCWTU
122Output DForced operation 2 bit2 BitCW
123Output DStatus height 0...2551 ByteCRT
123Output DStatus open-closed/on-off1 BitCRT
124Output DStatus slat 0...2551 ByteCRT
125Output DStatus upper end position1 BitCRT
126Output DStatus lower end position1 BitCRT
127Output DStatus operability1 BitCRT
128Output DStatus automatic control1 BitCRT
129Output DStatus information2 BytesCRT
130Output EFlaps open-closed/on-off1 BitCW
130Output EMove blinds/shutter up-down1 BitCW
131Output EStop Up-Down1 BitCW
131Output ESlat adjustm./stop up-down1 BitCW
132Output EEnable limitation1 BitCW
132Output EBlinds/shutter up-down limited1 BitCW
133Output EMove to position height 0..2551 ByteCW
134Output EMove slats 0..2551 ByteCW
135Output EMove to position 1, 21 BitCW
136Output EMove to position 3, 41 BitCW
137Output ESet position 1, 21 BitCW
138Output ESet position 3, 41 BitCW
139Output ETrigger reference movement1 BitCW
139Output ETrigger travel detection1 BitCW
140Output E8 bit scene1 ByteCW
141Output EActivation of autom. control1 BitCWTU
142Output ESun1 BitCWTU
143Output EMove to height for sun 0..2551 ByteCWTU
144Output EAdjust slat for sun 0..2551 ByteCWTU
145Output EPresence1 BitCWTU
146Output EHeating1 BitCWTU
147Output ECooling1 BitCWTU
148Output EReceive room temperature2 BytesCWTU
149Output EDisable/enable autom. control1 BitCWTU
150Output EDisable/enable direct control1 BitCWTU
151Output EBlock1 BitCWTU
152Output EForced operation 1 bit1 BitCWTU
152Output EForced operation 2 bit2 BitCW
152Output EForced operation 2 bit2 BitCWTU
153Output EStatus open-closed/on-off1 BitCRT
153Output EStatus height 0...2551 ByteCRT
154Output EStatus slat 0...2551 ByteCRT
155Output EStatus upper end position1 BitCRT
156Output EStatus lower end position1 BitCRT
157Output EStatus operability1 BitCRT
158Output EStatus automatic control1 BitCRT
159Output EStatus information2 BytesCRT
160Output FFlaps open-closed/on-off1 BitCW
160Output FMove blinds/shutter up-down1 BitCW
161Output FStop Up-Down1 BitCW
161Output FSlat adjustm./stop up-down1 BitCW
162Output FEnable limitation1 BitCW
162Output FBlinds/shutter up-down limited1 BitCW
163Output FMove to position height 0..2551 ByteCW
164Output FMove slats 0..2551 ByteCW
165Output FMove to position 1, 21 BitCW
166Output FMove to position 3, 41 BitCW
167Output FSet position 1, 21 BitCW
168Output FSet position 3, 41 BitCW
169Output FTrigger reference movement1 BitCW
169Output FTrigger travel detection1 BitCW
170Output F8 bit scene1 ByteCW
171Output FActivation of autom. control1 BitCWTU
172Output FSun1 BitCWTU
173Output FMove to height for sun 0..2551 ByteCWTU
174Output FAdjust slat for sun 0..2551 ByteCWTU
175Output FPresence1 BitCWTU
176Output FHeating1 BitCWTU
177Output FCooling1 BitCWTU
178Output FReceive room temperature2 BytesCWTU
179Output FDisable/enable autom. control1 BitCWTU
180Output FDisable/enable direct control1 BitCWTU
181Output FBlock1 BitCWTU
182Output FForced operation 1 bit1 BitCWTU
182Output FForced operation 2 bit2 BitCW
182Output FForced operation 2 bit2 BitCWTU
183Output FStatus open-closed/on-off1 BitCRT
183Output FStatus height 0...2551 ByteCRT
184Output FStatus slat 0...2551 ByteCRT
185Output FStatus upper end position1 BitCRT
186Output FStatus lower end position1 BitCRT
187Output FStatus operability1 BitCRT
188Output FStatus automatic control1 BitCRT
189Output FStatus information2 BytesCRT
190Output GFlaps open-closed/on-off1 BitCW
190Output GMove blinds/shutter up-down1 BitCW
191Output GStop Up-Down1 BitCW
191Output GSlat adjustm./stop up-down1 BitCW
192Output GEnable limitation1 BitCW
192Output GBlinds/shutter up-down limited1 BitCW
193Output GMove to position height 0..2551 ByteCW
194Output GMove slats 0..2551 ByteCW
195Output GMove to position 1, 21 BitCW
196Output GMove to position 3, 41 BitCW
197Output GSet position 1, 21 BitCW
198Output GSet position 3, 41 BitCW
199Output GTrigger reference movement1 BitCW
199Output GTrigger travel detection1 BitCW
200Output G8 bit scene1 ByteCW
201Output GActivation of autom. control1 BitCWTU
202Output GSun1 BitCWTU
203Output GMove to height for sun 0..2551 ByteCWTU
204Output GAdjust slat for sun 0..2551 ByteCWTU
205Output GPresence1 BitCWTU
206Output GHeating1 BitCWTU
207Output GCooling1 BitCWTU
208Output GReceive room temperature2 BytesCWTU
209Output GDisable/enable autom. control1 BitCWTU
210Output GDisable/enable direct control1 BitCWTU
211Output GBlock1 BitCWTU
212Output GForced operation 1 bit1 BitCWTU
212Output GForced operation 2 bit2 BitCW
212Output GForced operation 2 bit2 BitCWTU
213Output GStatus open-closed/on-off1 BitCRT
213Output GStatus height 0...2551 ByteCRT
214Output GStatus slat 0...2551 ByteCRT
215Output GStatus upper end position1 BitCRT
216Output GStatus lower end position1 BitCRT
217Output GStatus operability1 BitCRT
218Output GStatus automatic control1 BitCRT
219Output GStatus information2 BytesCRT
220Output HFlaps open-closed/on-off1 BitCW
220Output HMove blinds/shutter up-down1 BitCW
221Output HStop Up-Down1 BitCW
221Output HSlat adjustm./stop up-down1 BitCW
222Output HEnable limitation1 BitCW
222Output HBlinds/shutter up-down limited1 BitCW
223Output HMove to position height 0..2551 ByteCW
224Output HMove slats 0..2551 ByteCW
225Output HMove to position 1, 21 BitCW
226Output HMove to position 3, 41 BitCW
227Output HSet position 1, 21 BitCW
228Output HSet position 3, 41 BitCW
229Output HTrigger reference movement1 BitCW
229Output HTrigger travel detection1 BitCW
230Output H8 bit scene1 ByteCW
231Output HActivation of autom. control1 BitCWTU
232Output HSun1 BitCWTU
233Output HMove to height for sun 0..2551 ByteCWTU
234Output HAdjust slat for sun 0..2551 ByteCWTU
235Output HPresence1 BitCWTU
236Output HHeating1 BitCWTU
237Output HCooling1 BitCWTU
238Output HReceive room temperature2 BytesCWTU
239Output HDisable/enable autom. control1 BitCWTU
240Output HDisable/enable direct control1 BitCWTU
241Output HBlock1 BitCWTU
242Output HForced operation 1 bit1 BitCWTU
242Output HForced operation 2 bit2 BitCW
242Output HForced operation 2 bit2 BitCWTU
243Output HStatus open-closed/on-off1 BitCRT
243Output HStatus height 0...2551 ByteCRT
244Output HStatus slat 0...2551 ByteCRT
245Output HStatus upper end position1 BitCRT
246Output HStatus lower end position1 BitCRT
247Output HStatus operability1 BitCRT
248Output HStatus automatic control1 BitCRT
249Output HStatus information2 BytesCRT
Parameters (180)
ParameterTypeDefault
Konvertierbar ab Version 0.6unsignedInt 0…2556
Wird bei jedem Download auf 0xFF gesetzt App. setzt es dann auf 0unsignedInt 0…255255
Time-delayed switching of driveslistdeactivated
Falls Parent = inaktiv wird hier 0 runter geladenunsignedInt 0…2550
Time delay in s [1...15]unsignedInt 1…151
Sending and switching delay after bus voltage recovery in s [2...255]unsignedInt 2…2552
During sending and switching delay outputs remain unchanged.list<-- Note
Send object "in operation"listno
Sending cycle time in s [1...65,535]unsignedInt 1…6553560
Object valuelist1
Limit number of telegramslistno
Max. number of sent telegramsunsignedInt 1…2551
in periodlist1 s
Enable communication object "Request status values" 1 bitlistno
Request with object valuelist1
JA bei JRA/Sx.yyy.5.1 d.h. alle Geräte mit Handbedienunglistno
Manual operationlistenabled
Manual operation after bus voltage recovery, programming and resetlistenabled
Reset manual operation to KNX operationlistautomatically and via push button
Time for automatic reset in s [10...6,000]unsignedInt 10…6000300
Enable communication object "Status man. operation" 1 bitlistno
Send object valuelistno, update only
Safety commands such as weather alarms blocking and forced operation havelist<-- Note
Parameter settingsliststandard
Order of priority for weather alarm functionslist1.Wind alarm - 2.Rain alarm - 3.Frost alarm
Communication object no. 1 for wind alarmlistactivated
Communication object no. 2 for wind alarmlistdeactivated
Communication object no. 3 for wind alarmlistdeactivated
Monitoring period for wind alarm in s [0...1,000] (0 = monitoring deact.)unsignedInt 0…10000
Communication object for rain alarmlistdeactivated
Monitoring period for rain alarm in s [0...1,000] (0 = monitoring deact.)unsignedInt 0…10000
Communication object for frost alarmlistdeactivated
Monitoring period for frost alarm in s [0...1,000] (0 = monitoring deact.)unsignedInt 0…10000
Wind, rain, and frost alarm are active only if a position is setlist<-- Note
Read activated weather alarm objects after bus voltage recoverylistno
Read flags must be set in sending device!list<-- Note
Operation modelistcontrol with slat adjustment
To control venetian- or vertical blinds and other shading systems with slatslist<-- Note
To control roller shutters, awnings and other products without slatslist<-- Note
Reaction on bus voltage failureliststop
Reaction on bus voltage failurelistopen/on
Reaction after bus voltage recoveryliststop
Reaction after bus voltage recoverylistopen/on
Position height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…1000
Position slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…1000
Reaction after programming or after ETS resetliststop
Reaction after programming or after ETS resetlistopen/on
Invert outputlistno
Staircase lighting functionlistdeactivated
Duration/opening time for staircase lighting function in s [0...30,000]unsignedInt 0…3000060
Output reacts on communication object for wind alarm no.list1
Position on wind alarmlistactivated - up
Position on wind alarmlistdeactivated
Position height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…1000
Position slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…1000
Position on rain alarmlistdeactivated
Position for frost alarmlistdeactivated
Blocklistdeactivated
Position during blockinglistno reaction
Forced operation (1 bit/2 bit)listdeactivated
Position during forced operationlistopen/on
Position on reset of weather alarm, blocking and forced operationlistno reaction
Position on reset of weather alarm, blocking and forced operationlistopen/on
Position will only be carried out with inactive autom. sun protectionlist<-- Note
Order of priority for safety alarm functionslist1.Weather alarm - 2.Block - 3.Forced operation
Disable automatic sun protection on reset of safety functionlistno
Wind, rain, and frost alarm are active if objects on page "Weather alarms"list<-- Note
Detect travel times (Up/Down)listno - set travel times
Enable travel detectionlistautomatically
Position after travel detectionlistno reaction, remain in upper end position
Travel time UP in s [0...6,000]unsignedInt 0…600060
Travel time DOWN in s [0...6,000]unsignedInt 0…600060
Disconnect output from power afterlisttotal travel time + 10% Overflow
Enable communication object "Trigger reference movement" 1 bitlistno
Position after reference movementlistno reaction, remain in upper end position
Delete saved travel times after Downloadlistno
Pause on change in direction in ms (see technical data of drive!) 50...10,000unsignedInt 50…10000500
Delay times for driveliststandard
Difference between coasting delay and start-up delay in ms [-128..127]signedInt -128…1270
Minimum run time for drive in ms [10...255]unsignedInt 10…25550
Jalousie/Raffstore mit Arbeitsstellunglistno
Lamellenstellung bei Ab-Fahrt in % (0% = offen;100% = geschlossenunsignedInt 0…2550
Determine times for slatlistvia duration of slat adjustment (step)
Duration to turn slat from 0% - 100% in ms [50...60,000]unsignedInt 50…600001500
Duration of slat adjustment (step) in ms [50...1,000]unsignedInt 50…1000200
Number of slat adjustments (from 0% = open to 100% = closed)unsignedInt 1…607
Quotient duration to turn slat and number of slat adjustments >= 50 mslist<-- Note
Limit step commands to number of slat adjustmentslistyes
Total turning of slats after move DOWNlistno
Position of slat after arriving on lower end position (100% = disabled)unsignedInt 0…100100
Limit travelling rangelistno
Upper limit in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…1000
Upper limit valid for automatic commandslistno
Upper limit valid for direct commandslistno
Lower limit in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…100100
Lower limit valid for automatic commandslistno
Lower limit valid for direct commandslistno
Set dead timesliststandard
Dead time blinds/shutter from bottom until moving up in ms [0...5,000]unsignedInt 0…50000
Dead time of slat from 100% closed until slat turn in ms [0...5,000]unsignedInt 0…50000
Slippage of blinds/shutter on change of direction in ms [0...5,000]unsignedInt 0…50000
Slippage of slat on change of direction in ms [0...5,000]unsignedInt 0…50000
Tensioning blinds/shutter or slot positioninglistno
Time for tensioning/slot positioning in ms [0...5,000]unsignedInt 0…50000
Enable positions/presetslistno
Enable automatic sun protectionlistno
Enable 8 bit scenelistno
Enable communication object "Move to pos. height 0..255"listno
Enable communication objects "Move to pos. height/Move slat 0..255"listno
Enable communication objects "Move to/set position 1-4" 1 bitlistno
Overwrite position values (presets) during downloadlistyes
Enable communication object "Status open-closed/on-off" 1 bitlistno
Position 1: Height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…10020
Position 1: Slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…10020
Position 2: Height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…10040
Enable communication object "Status operability" 1 bitlistno
Position 2: Slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…10040
Position 3: Height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…10060
Enable communication object "Status information" 16 bitlistno
Position 3: Slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…10060
Position 4: Height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…10080
Position 4: Slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…10080
Move to positionlistdirectly
Deactivation of automatic controllistvia object "Activation" and move command
Automatic reactivation of automatic controllistdeactivated
Time to reactivate automatic control automatically in min. [10...6,000]unsignedInt 10…6000300
Toggling to automatic controllistenabled
Toggling to direct controllistenabled
Position for sun = 1 (sun)listdown
Position for sun = 0 (no sun)listup
Delay for sun = 1 in s [0...6,000]unsignedInt 0…60000
Delay for sun = 0 in s [0...6,000]unsignedInt 0…60000
Read activated automatic objects after bus voltage recoverylistno
Read flags must be set at sending devicelist<-- Note
Enable heating/cooling automaticlistno
Delay for presence = 1 in s [0...6,000]unsignedInt 0…60000
Delay for presence = 0 in s [0...6,000]unsignedInt 0…60000
Position for heating = 1 and sun = 1listup
Use overheat controllistno
Upper threshold value room temperature in °C [21...50]unsignedInt 21…5024
Position at upper threshold value and sun = 1listdown
Position height in % [0...100] (0% = top; 100% = bottom)unsignedInt 0…1000
Position slat in % [0...100] (0% = open; 100% = closed)unsignedInt 0…1000
Position for heating = 1 and sun = 0listno reaction
Position for cooling = 1 and sun = 1listdown
Position for cooling = 1 and sun = 0listno reaction
On heating = 1 and cooling = 1 or on heating = 0 and cooling = 0list<-- Note
A: Scenelistdeactivated
Overwrite scenes on downloadlistno
Use 1st assignmentlistno
Assignment to scene number 1...64listscene no. 1
Use 2nd assignmentlistno
Use 3rd assignmentlistno
Use 4th assignmentlistno
Use 5th assignmentlistno
Use 6th assignmentlistno
Use 7th assignmentlistno
Use 8th assignmentlistno
Use 9th assignmentlistno
Use 10th assignmentlistno
Use 11th assignmentlistno
Use 12th assignmentlistno
Use 13th assignmentlistno
Use 14th assignmentlistno
Use 15th assignmentlistno
Use 16th assignmentlistno
Use 17th assignmentlistno
Use 18th assignmentlistno
Enable communication object "Status height/slat 0...255" 1 bytelistno
Enable communication object "Status height 0...255" 1 bytelistno
Enable communication object "Status upper/lower end pos." 1 bitlistno
Enable communication object "Status automatic" 1 bitlistno
B: Scenelistdeactivated
C: Scenelistdeactivated
D: Scenelistdeactivated
Output reacts on communication object for wind alarm no.listoutput does not react on wind alarm
E: Scenelistdeactivated
F: Scenelistdeactivated
G: Scenelistdeactivated
H: Scenelistdeactivated

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Blind/Shutter_Actuator_8-fold_KNX 1.4 latest$A07917B22026-11-25742 KBDownload

About this file

This is the official ETS product database for the VIMAR 01525 Blind/Shutter Actuator 8-fold (01525), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from VIMAR

All VIMAR products