PlanoSpot 360 KNX 203 9 10*
Theben HTS AG · Order number 203 9 10* · Physikalische Sensoren › Präsenzmelder
3xlight, 2xHVAC, monitoring, brightness, Presence detectors with constant light
Download .knxprod V1.03 / 3xlight, 2xHVAC, monitoring, brightness 1.2 · 210 KB
Product
| Manufacturer | Theben HTS AG |
|---|---|
| Product name | PlanoSpot 360 KNX |
| Order number | 203 9 10* |
| Hardware | PlanoSpot 360 KNX |
| Medium | Twisted Pair |
| Bus current (mA) | 9 |
| Rail mounted | No |
| Registration | Certified · 2015-04-03 |
| Languages | de-DE, en-US, es-ES, fr-FR, it-IT, nl-NL |
| Catalog entry | M-00E8_H-50000120-0_HP-0011-12-2C56_CI-203.209.2010.2A-0 |
| Fingerprint | 2C56 |
| SHA-256 | e3859694450ca32f922f7fab29c324f1119fd8cbd379970b346df8fe5acb5820 |
| First seen | 2026-11-25 |
| Markets | 36 markets |
Application program: V1.03 / 3xlight, 2xHVAC, monitoring, brightness 1.2
| Application number | $0011 |
|---|---|
| Version | 1.2 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 3.0d |
| Parameters | 388 |
| Group objects | 97 |
Group objects (97)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Channel C1 Light | Switch | 1 Bit | CWT | |
| 1 | Channel C1 Light | Brighter/darker | 4 Bit | CWT | |
| 2 | Channel C1 Light | Send value | 1 Byte | CWT | |
| 3 | Channel C1 Light | Feedback value | 1 Byte | CWTU | |
| 4 | Channel C1 brightness switching value | Receive value | 2 Bytes | CWT | |
| 4 | Channel C1 Brightness set point value | Receive value | 2 Bytes | CWT | |
| 5 | Channel C1 brightness switching value (teach-in) | $01 = call up, $81 = save | 1 Byte | CW | |
| 5 | Channel C1 Brightness set point value (teach-in) | $01 = call up, $81 = save | 1 Byte | CW | |
| 6 | Channel C1 Alternative brightness switching value | Receive value | 2 Bytes | CWT | |
| 6 | Channel C1 Alternative brightness set point value | Receive value | 2 Bytes | CWT | |
| 7 | Measurement value on lux meter | Receive value | 2 Bytes | CW | |
| 7 | Channel C1 Measurement value on lux meter | Receive value | 2 Bytes | CW | |
| 8 | Room correction factor | Call up value | 2 Bytes | CRT | |
| 8 | Channel C1 Room correction factor | Call up value | 2 Bytes | CRT | |
| 9 | Brightness value | Send lux value | 2 Bytes | CRT | |
| 9 | Channel C1 Brightness value | Send lux value | 2 Bytes | CRT | |
| 10 | Channel C1 External brightness value | Receive lux value | 2 Bytes | CW | |
| 11 | Channel C2 Light | Switch | 1 Bit | CWT | |
| 12 | Channel C2 Light | Brighter/darker | 4 Bit | CWT | |
| 13 | Channel C2 Light | Send value | 1 Byte | CWT | |
| 14 | Channel C2 Light | Feedback value | 1 Byte | CWTU | |
| 15 | Channel C2 brightness switching value | Receive value | 2 Bytes | CWT | |
| 15 | Channel C2 Brightness set point value | Receive value | 2 Bytes | CWT | |
| 16 | Channel C2 brightness switching value (teach-in) | $01 = call up, $81 = save | 1 Byte | CW | |
| 16 | Channel C2 Brightness set point value (teach-in) | $01 = call up, $81 = save | 1 Byte | CW | |
| 17 | Channel C2 Alternative brightness switching value | Receive value | 2 Bytes | CWT | |
| 17 | Channel C2 Alternative brightness set point value | Receive value | 2 Bytes | CWT | |
| 18 | Channel C2 measured value on lux meter | Receive value | 2 Bytes | CW | |
| 19 | Channel C2 room correction factor | Call up value | 2 Bytes | CRT | |
| 20 | Channel C2 brightness value | Send lux value | 2 Bytes | CRT | |
| 21 | Channel C2 External brightness value | Receive lux value | 2 Bytes | CW | |
| 22 | Channel C1 Light | Sel. bright. switching value | 1 Bit | CW | |
| 22 | Channel C1 Light | Sel.bright.level set pt value | 1 Bit | CW | |
| 22 | Channel C1/C2 Light | Sel. bright. switching value | 1 Bit | CW | |
| 22 | Channel C1/C2 Light | Sel.bright.level set pt value | 1 Bit | CW | |
| 23 | Channel C2 Light | Sel. bright. switching value | 1 Bit | CW | |
| 23 | Channel C2 Light | Sel.bright.level set pt value | 1 Bit | CW | |
| 24 | Channel C1/C2 Light | Sel. of constant light control | 1 Bit | CW | |
| 24 | Channel C1 Light | Sel. of constant light control | 1 Bit | CW | |
| 24 | Channel C1 Light constant lighting control | Activate/deactivate | 1 Bit | CW | |
| 24 | Channel C1/C2 Light constant lighting control | Activate/deactivate | 1 Bit | CW | |
| 25 | Channel C1 Light | Standby function | 1 Bit | CW | |
| 25 | Channel C1/C2 Light | Standby function | 1 Bit | CW | |
| 26 | Channel C3 Light | Switch | 1 Bit | CWT | |
| 27 | Channel C1/C2 Lighting time delay | Receive value | 2 Bytes | CWT | |
| 27 | Channel C1 Lighting time delay | Receive value | 2 Bytes | CWT | |
| 27 | Channel C1/C2/C3 Lighting time delay | Receive value | 2 Bytes | CWT | |
| 27 | Channel C1/C3 Lighting time delay | Receive value | 2 Bytes | CWT | |
| 28 | Channel C1/C2 Light | Block/unblock | 1 Bit | CW | |
| 28 | Channel C1/C2/C3 Light | Block/unblock | 1 Bit | CW | |
| 28 | Channel C1 Light | Block/unblock | 1 Bit | CW | |
| 28 | Channel C1/C3 Light | Block/unblock | 1 Bit | CW | |
| 29 | Central command | Receive | 1 Bit | CW | |
| 30 | External scene | Receive | 1 Byte | CW | |
| 31 | Channel C4.1 Presence | Switch | 1 Bit | CRT | |
| 31 | Channel C4.1 Presence | Send value | 1 Byte | CRT | |
| 31 | Channel C4.1 Presence | Send percentage value | 1 Byte | CRT | |
| 31 | Channel C4.1 Presence | HVAC operating mode | 1 Byte | CRT | |
| 31 | Channel C4.1 Presence | Send scene | 1 Byte | CRT | |
| 32 | Channel C4.2 Presence | Switch | 1 Bit | CRT | |
| 32 | Channel C4.2 Presence | Send value | 1 Byte | CRT | |
| 32 | Channel C4.2 Presence | Send percentage value | 1 Byte | CRT | |
| 32 | Channel C4.2 Presence | HVAC operating mode | 1 Byte | CRT | |
| 32 | Channel C4.2 Presence | Send scene | 1 Byte | CRT | |
| 33 | Channel C4 Presence | Block/unblock | 1 Bit | CW | |
| 34 | Channel C5.1 Presence | Switch | 1 Bit | CRT | |
| 34 | Channel C5.1 Presence | Send value | 1 Byte | CRT | |
| 34 | Channel C5.1 Presence | Send percentage value | 1 Byte | CRT | |
| 34 | Channel C5.1 Presence | HVAC operating mode | 1 Byte | CRT | |
| 34 | Channel C5.1 Presence | Send scene | 1 Byte | CRT | |
| 35 | Channel C5.2 Presence | Switch | 1 Bit | CRT | |
| 35 | Channel C5.2 Presence | Send value | 1 Byte | CRT | |
| 35 | Channel C5.2 Presence | Send percentage value | 1 Byte | CRT | |
| 35 | Channel C5.2 Presence | HVAC operating mode | 1 Byte | CRT | |
| 35 | Channel C5.2 Presence | Send scene | 1 Byte | CRT | |
| 36 | Channel C5 Presence | Block/unblock | 1 Bit | CW | |
| 37 | Channel C6 Room monitoring | Message | 1 Bit | CT | |
| 38 | Channel C6 Room monitoring | Confirmation | 1 Bit | CW | |
| 39 | Channel C6 Room monitoring | Sabotage cyclically | 1 Bit | CT | |
| 40 | Channel C6 Room monitoring | Release | 1 Bit | CW | |
| 41 | Parallel switching | Trigger input/output | 1 Bit | CWT | |
| 42 | Scene input | Scenes 1/2 | 1 Bit | CW | |
| 42 | Scene output | Scene number | 1 Byte | CT | |
| 43 | IR external 1 switching/dimming | Switch | 1 Bit | CT | |
| 44 | IR external 1 switching/dimming | Brighter/darker | 4 Bit | CT | |
| 45 | IR external 2 switching/dimming | Switch | 1 Bit | CT | |
| 46 | IR external 2 switching/dimming | Brighter/darker | 4 Bit | CT | |
| 47 | IR external blinds 1 | Blinds Up / Down | 1 Bit | CT | |
| 48 | IR external blinds 1 | Opening/closing slats | 1 Bit | CT | |
| 49 | IR external blinds 2 | Blinds Up / Down | 1 Bit | CT | |
| 50 | IR external blinds 2 | Opening/closing slats | 1 Bit | CT | |
| 51 | Test mode presence | On/Off | 1 Bit | CW | |
| 52 | Test mode brightness | On/Off | 1 Bit | CW | |
| 53 | Software Version | Send | 2 Bytes | CRT | |
| 54 | dummy 2 | 1 Bit | CW | ||
| 55 | dummy 3 | 1 Bit | CW | ||
| 56 | dummy 4 | 1 Bit | CW |
Parameters (150)
| Parameter | Type | Default |
|---|---|---|
| Debug | list | yes |
| Version | text | 190 |
| 17.10.2013 | text | 17.10.2013 |
| ### | unsignedInt 0…255 | 0 |
| en_MasterArt | list | master in parallel switching |
| Betriebsart | list | master in individual switching |
| Operating mode | list | master |
| Master operating mode | list | individual switching |
| Parallel switching cycle time | list | 30 s |
| Channel C1 function - Light | list | switch light |
| Channel C2 function - Light | list | inactive |
| Channel C3 function - Light | list | inactive |
| Channel C4 function - Presence | list | inactive |
| Channel C5 function - Presence | list | inactive |
| Channel C6 function - Room monitoring | list | inactive |
| Activation of test mode | list | via object or remote control, max. 30 min. |
| Detection zone | list | standard |
| Detection sensitivity | list | 3 standard |
| Reduction of detection sensitivity for room monitoring | list | 2 standard |
| Parameter settings at download* | list | overwrite via download |
| Movement indicated by the LED | list | no |
| Source for brightness measurement | list | internal |
| Light measurement selection | list | use light measurement in middle |
| Light measurement selection channel C1 | list | use light measurement in middle |
| Room correction factor | list | 0.3 |
| Room correction factor on side towards window | list | 0.3 |
| Room correction factor opposite to window | list | 0.3 |
| Light measurement selection channel C2 | list | use light measurement opposite to window |
| Set brightness measurement value via bus | list | no |
| Send brightness value on bus | list | no |
| Transmit brightness value cyclically | list | every 1 min. |
| Transmit brightness value upon change | list | from > 30% |
| Configuration type | list | fully automatic |
| Brightness switching value | list | 500 lx |
| Brightness set point value | list | 500 lx |
| Set brightness switching value via bus | list | no |
| Set brightness set point value via bus | list | no |
| Lighting time delay | list | 10 min. |
| Set lighting time delay via bus | list | no |
| Select brightness level set point value | list | inactive |
| Energy saving mode | list | ECO |
| Alternative brightness set point value | list | 400 lx |
| Short presence | list | active |
| Set alternative brightness set point value via bus | list | no |
| Select brightness switching value | list | inactive |
| Alternative brightness switching value | list | 400 lx |
| Set alternative brightness switching value via bus | list | no |
| Lighting dimmable when in switching operation | list | no |
| Start of control with | list | value telegram |
| Start behaviour of control | list | with 4 bit stop telegram (standard) |
| Switch-on dimming value | list | 70% |
| Switch-on dimming value | list | ON telegram |
| Control speed | list | standard |
| Duration of manual override | list | until lighting time delay has ended |
| Control range | list | standard (10..100%) |
| Lower control limit | list | 10% |
| Upper control limit | list | 100% |
| Switching off when there is enough brightness | list | after 10 min |
| Response with manual dimming | list | school |
| Light standby time | list | inactive |
| Duration of light standby time | list | 30 min. |
| Standby dimming value | list | 10% |
| Transmit channel C1 output value cyclically | list | no |
| Activate block function | list | no |
| Lock telegram | list | block with ON telegram |
| Response at start of block | list | do not send telegram |
| Channel C3 - light response | list | See KNX-handbook PlanoSpot 360 KNX |
| Configuration type | list | as C1 |
| Helligkeitsdifferenz zu Kanal C1 | list | 0% synchronised |
| Lighting time delay | list | as C1 |
| Lighting dimmable when in switching operation | list | as C1 |
| Start of control with | list | as C1 |
| Start behaviour of control | list | as C1 |
| Control speed | list | as C1 |
| Light standby time | list | as C1 |
| Control range | list | as C1 |
| Switching off when there is enough brightness | list | as C1 |
| Response with manual dimming | list | as C1 |
| Send channel C2 output value cyclically | list | as C1 |
| Activate block function | list | as C1 |
| Send channel C3 output value cyclically | list | as C1 |
| Switch-on delay time presence | list | inactive |
| Switch-off delay time presence | list | 15 min. |
| Telegram type C4.1 | list | switching command |
| When presence recognised | list | send following telegram once |
| Telegram | list | on |
| At the end of the time delay | list | send following telegram once |
| Telegram | list | off |
| Telegram | unsignedInt 0…255 | 255 |
| Telegram | unsignedInt 0…255 | 0 |
| Telegram (%) | list | 100% |
| Telegram (%) | list | 0% |
| Telegram | list | standby |
| Telegram | list | temperature reduction at night |
| Telegram | list | scene 1 |
| Telegram | list | scene 2 |
| Should a second telegram be sent? | list | no |
| Telegram type C4.2 | list | switching command |
| Cycle time (if used) | list | every 60 min |
| Response at start of block | list | no reaction |
| Response after unblocking | list | update status |
| Telegram type C5.1 | list | switching command |
| Telegram type C5.2 | list | switching command |
| Type of report | list | cyclic with confirmation |
| Waiting time for confirmation | list | 5 min. |
| Room monitoring time delay | list | 5 min. |
| Response at start/end of presence | list | only send ON telegram |
| Response upon return of bus voltage | list | room monitoring channel unblocked |
| Sabotage cyclically | list | active |
| Cycle time sabotage | list | 4 min. |
| SendoClic APP | list | blocked |
| Upper row of buttons theSenda S controls | list | inactive |
| Upper row of buttons theSenda S controls | list | channel C1 light |
| IR group address upper row of buttons theSenda S | list | I |
| Lower row of buttons theSenda S controls | list | channel C3 light |
| Lower row of buttons theSenda S controls | list | inactive |
| Lower row of buttons theSenda S controls | list | channel C2 light |
| IR group address lower row of buttons theSenda S | list | II |
| Scene control | list | use internal scene |
| Scene control | list | inactive |
| Scene number user remote control button scene 1 | list | inactive |
| Scene number user remote control button scene 2 | list | inactive |
| Define scenes with | list | ETS |
| Output value user remote control scene 1, channel C1 | list | 30% |
| Output value user remote control scene 1, channel C1 | list | off |
| Output value user remote control scene 2, channel C1 | list | 70% |
| Output value user remote control scene 2, channel C1 | list | on |
| Output value user remote control scene 1, channel C2 | list | 30% |
| Output value user remote control scene 1, channel C2 | list | off |
| Output value user remote control scene 1, channel C3 | list | off |
| Output value user remote control scene 2, channel C2 | list | 70% |
| Output value user remote control scene 2, channel C2 | list | on |
| Output value user remote control scene 2, channel C3 | list | on |
| Scene function 1 | list | inactive |
| Scene number | list | 1 |
| Scene function 2 | list | inactive |
| Scene number | list | 2 |
| Scene function 3 | list | inactive |
| Scene number | list | 3 |
| Scene function 4 | list | inactive |
| Scene number | list | 4 |
| Scene function 5 | list | inactive |
| Scene number | list | 5 |
| Scene function 6 | list | inactive |
| Scene number | list | 6 |
| Scene function 7 | list | inactive |
| Scene number | list | 7 |
| Scene function 8 | list | inactive |
| Scene number | list | 8 |
| Validity of block | list | until unblocked |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| V1.03 / 3xlight, 2xHVAC, monitoring, brightness 1.2 latest | $0011 | 2C56 | 2026-11-25 | 210 KB | Download |
About this file
This is the official ETS product database for the Theben HTS AG PlanoSpot 360 KNX (203 9 10*), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Theben HTS AG
- theMova S360 KNX 103 9 5**
- theMova P360 KNX 103 9 60*
- PresenceLight 360-KNX 200 9 00 *
- PresenceLight 180-KNX 200 9 05 *
- thePassa P360 KNX 201 9 30*
- PlanoSpot 360 KNX S 203 9 30*
- PlanoCentro A-KNX 2059***
- thePrema P360 KNX 207 9 00*
- thePrema S360 KNX 207 9 50*
- theRonda P360 KNX 208 9 00*
- theRonda S360 KNX 208 9 5**
- compact office EIB 201 9 200