KNX Database
Theben AG 4940280 DM 4-2 T

DM 4-2 T 4940280

Theben AG · Order number 4940280 · Dimmer › DM 4-2 T

4x FIX2 dimming actuator

Download .knxprod FIX2 DM 8-2 T 1.0 · 312 KB

Product

ManufacturerTheben AG
Product nameDM 4-2 T
Order number4940280
Product textDM 4-2 T (4 x dimming actuator, 200 W)
HardwareFIX2 Series DM 4-2 T
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)72
RegistrationCertified
Languagesde-DE, en-US, es-ES, fr-FR, it-IT, nl-NL
Catalog entryM-0048_H-4940280-2_HP-4948-10-2C43_CI-4940280-1
Fingerprint2C43
SHA-256c993dcf20fd2a1cfe0644e2fe4e65932eb066b3d8e29a96dc9159bfcec763b62
First seen2026-11-25
Markets59 markets

Application program: FIX2 DM 8-2 T 1.0

Application number$4948
Version1.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Parameters1088
Group objects209
Group objects (209)
NoNameFunctionSizeDPTFlags
0Channel C1Switching ON/OFF1 Bit1.1 switchCRWU
1Channel C1Brighter/darker4 Bit3.7 dimming controlCRWU
2Channel C1Dimming value1 Byte5.1 percentage (0..100%)CWU
3Channel C1Soft switching1 Bit1.1 switchCRWU
4Channel C1Lock1 Bit1.1 switchCRWU
5Channel C1Call up/save scenes1 ByteCRWU
6Channel C1Lock scenes = 11 Bit1.1 switchCRW
6Channel C1Enable scenes = 11 Bit1.1 switchCRW
7Channel C1Force = 11 Bit1.1 switchCRWU
7Channel C1Force = 01 Bit1.1 switchCRWU
7Channel C1Dimming value with forced op1 Byte5.1 percentage (0..100%)CRWU
7Channel C1 Forced mode2 Bit2.1 switch controlCRWU
8Channel C1Dimming value limit1 Byte5.1 percentage (0..100%)CRWU
9Channel C1Feedback On/Off1 Bit1.1 switchCRTU
10Channel C1Feedback in %1 Byte5.1 percentage (0..100%)CRTU
11Channel C1Time to next service2 BytesDPT.7CRWTU
11Channel C1Operating hours feedback2 BytesDPT.7CRWT
12Channel C1Service required1 Bit1.1 switchCRTU
13Channel C1Reset service1 Bit1.1 switchCRW
13Channel C1Reset operating hours1 Bit1.1 switchCRW
14Channel C1General error message1 Bit1.1 switchCRTU
15Channel C1Short circuit message1 Bit1.1 switchCRTU
16Channel C1Excess temperature message1 Bit1.1 switchCRTU
17Channel C1Mains power failure1 Bit1.1 switchCRTU
18Channel C1Load type message (R, C/L)1 Bit1.1 switchCRTU
20Channel C2Switching ON/OFF1 Bit1.1 switchCRWU
21Channel C2Brighter/darker4 Bit3.7 dimming controlCRWU
22Channel C2Dimming value1 Byte5.1 percentage (0..100%)CWU
23Channel C2Soft switching1 Bit1.1 switchCRWU
24Channel C2Lock1 Bit1.1 switchCRWU
25Channel C2Call up/save scenes1 ByteCRWU
26Channel C2Enable scenes = 11 Bit1.1 switchCRW
26Channel C2Lock scenes = 11 Bit1.1 switchCRW
27Channel C2Force = 01 Bit1.1 switchCRWU
27Channel C2Force = 11 Bit1.1 switchCRWU
27Channel C2Dimming value with forced op1 Byte5.1 percentage (0..100%)CRWU
27Channel C2 Forced mode2 Bit2.1 switch controlCRWU
28Channel C2Dimming value limit1 Byte5.1 percentage (0..100%)CRWU
29Channel C2Feedback On/Off1 Bit1.1 switchCRTU
30Channel C2Feedback in %1 Byte5.1 percentage (0..100%)CRTU
31Channel C2Time to next service2 BytesDPT.7CRWTU
31Channel C2Operating hours feedback2 BytesDPT.7CRWT
32Channel C2Service required1 Bit1.1 switchCRTU
33Channel C2Reset service1 Bit1.1 switchCRW
33Channel C2Reset operating hours1 Bit1.1 switchCRW
34Channel C2General error message1 Bit1.1 switchCRTU
35Channel C2Short circuit message1 Bit1.1 switchCRTU
36Channel C2Excess temperature message1 Bit1.1 switchCRTU
37Channel C2Mains power failure1 Bit1.1 switchCRTU
38Channel C2Load type message (R, C/L)1 Bit1.1 switchCRTU
40Channel C3Switching ON/OFF1 Bit1.1 switchCRWU
41Channel C3Brighter/darker4 Bit3.7 dimming controlCRWU
42Channel C3Dimming value1 Byte5.1 percentage (0..100%)CWU
43Channel C3Soft switching1 Bit1.1 switchCRWU
44Channel C3Lock1 Bit1.1 switchCRWU
45Channel C3Call up/save scenes1 ByteCRWU
46Channel C3Lock scenes = 11 Bit1.1 switchCRW
46Channel C3Enable scenes = 11 Bit1.1 switchCRW
47Channel C3Force = 11 Bit1.1 switchCRWU
47Channel C3Force = 01 Bit1.1 switchCRWU
47Channel C3Dimming value with forced op1 Byte5.1 percentage (0..100%)CRWU
47Channel C3 Forced mode2 Bit2.1 switch controlCRWU
48Channel C3Dimming value limit1 Byte5.1 percentage (0..100%)CRWU
49Channel C3Feedback On/Off1 Bit1.1 switchCRTU
50Channel C3Feedback in %1 Byte5.1 percentage (0..100%)CRTU
51Channel C3Time to next service2 BytesDPT.7CRWTU
51Channel C3Operating hours feedback2 BytesDPT.7CRWT
52Channel C3Service required1 Bit1.1 switchCRTU
53Channel C3Reset service1 Bit1.1 switchCRW
53Channel C3Reset operating hours1 Bit1.1 switchCRW
54Channel C3General error message1 Bit1.1 switchCRTU
55Channel C3Short circuit message1 Bit1.1 switchCRTU
56Channel C3Excess temperature message1 Bit1.1 switchCRTU
57Channel C3Mains power failure1 Bit1.1 switchCRTU
58Channel C3Load type message (R, C/L)1 Bit1.1 switchCRTU
60Channel C4Switching ON/OFF1 Bit1.1 switchCRWU
61Channel C4Brighter/darker4 Bit3.7 dimming controlCRWU
62Channel C4Dimming value1 Byte5.1 percentage (0..100%)CWU
63Channel C4Soft switching1 Bit1.1 switchCRWU
64Channel C4Lock1 Bit1.1 switchCRWU
65Channel C4Call up/save scenes1 ByteCRWU
66Channel C4Enable scenes = 11 Bit1.1 switchCRW
66Channel C4Lock scenes = 11 Bit1.1 switchCRW
67Channel C4Force = 01 Bit1.1 switchCRWU
67Channel C4Force = 11 Bit1.1 switchCRWU
67Channel C4Dimming value with forced op1 Byte5.1 percentage (0..100%)CRWU
67Channel C4 Forced mode2 Bit2.1 switch controlCRWU
68Channel C4Dimming value limit1 Byte5.1 percentage (0..100%)CRWU
69Channel C4Feedback On/Off1 Bit1.1 switchCRTU
70Channel C4Feedback in %1 Byte5.1 percentage (0..100%)CRTU
71Channel C4Time to next service2 BytesDPT.7CRWTU
71Channel C4Operating hours feedback2 BytesDPT.7CRWT
72Channel C4Service required1 Bit1.1 switchCRTU
73Channel C4Reset service1 Bit1.1 switchCRW
73Channel C4Reset operating hours1 Bit1.1 switchCRW
74Channel C4General error message1 Bit1.1 switchCRTU
75Channel C4Short circuit message1 Bit1.1 switchCRTU
76Channel C4Excess temperature message1 Bit1.1 switchCRTU
77Channel C4Mains power failure1 Bit1.1 switchCRTU
78Channel C1-C4Load type message (R, C/L)1 Bit1.1 switchCRTU
79Channel C1-C4Manual1 Bit1.1 switchCRWTU
80Channel C5Switching ON/OFF1 Bit1.1 switchCRWU
81Channel C5Brighter/darker4 Bit3.7 dimming controlCRWU
82Channel C5Dimming value1 Byte5.1 percentage (0..100%)CWU
83Channel C5Soft switching1 Bit1.1 switchCRWU
84Channel C5Lock1 Bit1.1 switchCRWU
85Channel C5Call up/save scenes1 ByteCRWU
86Channel C5Lock scenes = 11 Bit1.1 switchCRW
86Channel C5Enable scenes = 11 Bit1.1 switchCRW
87Channel C5Force = 11 Bit1.1 switchCRWU
87Channel C5Force = 01 Bit1.1 switchCRWU
87Channel C5Dimming value with forced op1 Byte5.1 percentage (0..100%)CRWU
87Channel C5 Forced mode2 Bit2.1 switch controlCRWU
88Channel C5Dimming value limit1 Byte5.1 percentage (0..100%)CRWU
89Channel C5Feedback On/Off1 Bit1.1 switchCRTU
90Channel C5Feedback in %1 Byte5.1 percentage (0..100%)CRTU
91Channel C5Time to next service2 BytesDPT.7CRWTU
91Channel C5Operating hours feedback2 BytesDPT.7CRWT
92Channel C5Service required1 Bit1.1 switchCRTU
93Channel C5Reset service1 Bit1.1 switchCRW
93Channel C5Reset operating hours1 Bit1.1 switchCRW
94Channel C5General error message1 Bit1.1 switchCRTU
95Channel C5Short circuit message1 Bit1.1 switchCRTU
96Channel C5Excess temperature message1 Bit1.1 switchCRTU
97Channel C5Mains power failure1 Bit1.1 switchCRTU
98Channel C5Load type message (R, C/L)1 Bit1.1 switchCRTU
100Channel C6Switching ON/OFF1 Bit1.1 switchCRWU
101Channel C6Brighter/darker4 Bit3.7 dimming controlCRWU
102Channel C6Dimming value1 Byte5.1 percentage (0..100%)CWU
103Channel C6Soft switching1 Bit1.1 switchCRWU
104Channel C6Lock1 Bit1.1 switchCRWU
105Channel C6Call up/save scenes1 ByteCRWU
106Channel C6Enable scenes = 11 Bit1.1 switchCRW
106Channel C6Lock scenes = 11 Bit1.1 switchCRW
107Channel C6Force = 01 Bit1.1 switchCRWU
107Channel C6Force = 11 Bit1.1 switchCRWU
107Channel C6Dimming value with forced op1 Byte5.1 percentage (0..100%)CRWU
107Channel C6 Forced mode2 Bit2.1 switch controlCRWU
108Channel C6Dimming value limit1 Byte5.1 percentage (0..100%)CRWU
109Channel C6Feedback On/Off1 Bit1.1 switchCRTU
110Channel C6Feedback in %1 Byte5.1 percentage (0..100%)CRTU
111Channel C6Time to next service2 BytesDPT.7CRWTU
111Channel C6Operating hours feedback2 BytesDPT.7CRWT
112Channel C6Service required1 Bit1.1 switchCRTU
113Channel C6Reset service1 Bit1.1 switchCRW
113Channel C6Reset operating hours1 Bit1.1 switchCRW
114Channel C6General error message1 Bit1.1 switchCRTU
115Channel C6Short circuit message1 Bit1.1 switchCRTU
116Channel C6Excess temperature message1 Bit1.1 switchCRTU
117Channel C6Mains power failure1 Bit1.1 switchCRTU
118Channel C1-C4Load type message (R, C/L)1 Bit1.1 switchCRTU
120Channel C7Switching ON/OFF1 Bit1.1 switchCRWU
121Channel C7Brighter/darker4 Bit3.7 dimming controlCRWU
122Channel C7Dimming value1 Byte5.1 percentage (0..100%)CWU
123Channel C7Soft switching1 Bit1.1 switchCRWU
124Channel C7Lock1 Bit1.1 switchCRWU
125Channel C7Call up/save scenes1 ByteCRWU
126Channel C7Lock scenes = 11 Bit1.1 switchCRW
126Channel C7Enable scenes = 11 Bit1.1 switchCRW
127Channel C7Force = 11 Bit1.1 switchCRWU
127Channel C7Force = 01 Bit1.1 switchCRWU
127Channel C7Dimming value with forced op1 Byte5.1 percentage (0..100%)CRWU
127Channel C7 Forced mode2 Bit2.1 switch controlCRWU
128Channel C7Dimming value limit1 Byte5.1 percentage (0..100%)CRWU
129Channel C7Feedback On/Off1 Bit1.1 switchCRTU
130Channel C7Feedback in %1 Byte5.1 percentage (0..100%)CRTU
131Channel C7Time to next service2 BytesDPT.7CRWTU
131Channel C7Operating hours feedback2 BytesDPT.7CRWT
132Channel C7Service required1 Bit1.1 switchCRTU
133Channel C7Reset service1 Bit1.1 switchCRW
133Channel C7Reset operating hours1 Bit1.1 switchCRW
134Channel C7General error message1 Bit1.1 switchCRTU
135Channel C7Short circuit message1 Bit1.1 switchCRTU
136Channel C7Excess temperature message1 Bit1.1 switchCRTU
137Channel C7Mains power failure1 Bit1.1 switchCRTU
138Channel C7Load type message (R, C/L)1 Bit1.1 switchCRTU
140Channel C8Switching ON/OFF1 Bit1.1 switchCRWU
141Channel C8Brighter/darker4 Bit3.7 dimming controlCRWU
142Channel C8Dimming value1 Byte5.1 percentage (0..100%)CWU
143Channel C8Soft switching1 Bit1.1 switchCRWU
144Channel C8Lock1 Bit1.1 switchCRWU
145Channel C8Call up/save scenes1 ByteCRWU
146Channel C8Enable scenes = 11 Bit1.1 switchCRW
146Channel C8Lock scenes = 11 Bit1.1 switchCRW
147Channel C8Force = 01 Bit1.1 switchCRWU
147Channel C8Force = 11 Bit1.1 switchCRWU
147Channel C8Dimming value with forced op1 Byte5.1 percentage (0..100%)CRWU
147Channel C8 Forced mode2 Bit2.1 switch controlCRWU
148Channel C8Dimming value limit1 Byte5.1 percentage (0..100%)CRWU
149Channel C8Feedback On/Off1 Bit1.1 switchCRTU
150Channel C8Feedback in %1 Byte5.1 percentage (0..100%)CRTU
151Channel C8Time to next service2 BytesDPT.7CRWTU
151Channel C8Operating hours feedback2 BytesDPT.7CRWT
152Channel C8Service required1 Bit1.1 switchCRTU
153Channel C8Reset service1 Bit1.1 switchCRW
153Channel C8Reset operating hours1 Bit1.1 switchCRW
154Channel C8General error message1 Bit1.1 switchCRTU
155Channel C8Short circuit message1 Bit1.1 switchCRTU
156Channel C8Excess temperature message1 Bit1.1 switchCRTU
157Channel C8Mains power failure1 Bit1.1 switchCRTU
158Channel C8Load type message (R, C/L)1 Bit1.1 switchCRTU
159Channel C5-C8Manual1 Bit1.1 switchCRWTU
231Central permanent ONON/OFF1 Bit1.1 switchCRWTU
232Central permanent OFFON/OFF1 Bit1.1 switchCRWTU
233Central switchingON/OFF1 Bit1.1 switchCRWTU
234Central scenesCall up/save1 ByteCRWTU
250BCU versionTransmit14 Bytes16.1 Character String (ISO 8859-1)CRTU
251Version C1-C4Transmit14 Bytes16.1 Character String (ISO 8859-1)CRTU
252Version C5-C8Transmit14 Bytes16.1 Character String (ISO 8859-1)CRTU
Parameters (113)
ParameterTypeDefault
TypelistDM 4-2 T
Manual operation of channelslistenabled
Function of manual push buttonlistvalid until reset via object
Art der 1 Erweiterung = keinelistDM 8-2 T
Art der 1 Erweiterung = DM 8-2 TlistDM 8-2 T
A_Objektlink Erweiterungsgerätlistleer
Adjust dimming value limitslistno
Adjust soft switchinglistno
Adjust lock functionlistno
Activate forced modelistno
Activate sceneslistno
Participation in central objectslistno
Adjust feedbacklistno
Activate hour meterlistno
Activate diagnostic messageslistno
Perform limitation when writing objectlistno
Limit applies to soft switchinglistno
Limit applies to absolute dimming (8-bit)listno
Limit applies to relative dimming (4-bit)listno
Limit applies to switching command (1-bit)listno
Time for Soft ONlist1 min
Dimming value after Soft ONlist100 %
Time between Soft ON and Soft OFFlist5 min
Time for Soft OFFlist1 min
Lock telegramlistlock with ON telegram
Response when setting the locklist10 %
Response when cancelling the locklistupdate
Format of 1-bit feedbacklistnot inverted
Send 1-bit feedback cyclicallylistno
Send 8-bit feedbacklistonly after ending dimming process
Send 8-bit feedback cyclicallylistno
Time for cyclical transmission of feedback (if available)list60 min
Load selectionlistautomatic
*** 10 % point in 100 µs (Standard=24)unsignedInt 15…9324
*** 20 % point in 100 µs (Standard=31)unsignedInt 15…9331
*** 30 % point in 100 µs (Standard=36)unsignedInt 15…9336
*** 40 % point in 100 µs (Standard=41)unsignedInt 15…9341
*** 50 % point in 100 µs (Standard=46)unsignedInt 15…9346
*** 60 % point in 100 µs (Standard=51)unsignedInt 15…9351
*** 70 % point in 100 µs (Standard=56)unsignedInt 15…9356
*** 80 % point in 100 µs (Standard=63)unsignedInt 15…9363
90 % point in 100 µs (Standard=75)unsignedInt 15…9375
*** Start-up valuelist50 %
*** Type of loadlistRC
Start-up timelist10 s
*** Start-up time (unit)list20 ms
*** Start-up time (factor)unsignedInt 0…12750
*** 90 % point in 100 µs (Standard=75)unsignedInt 15…9375
*** 100 % point in 100 µs (Standard=100)list100 % = limited to the 90 % setting
ATTENTION: USE ONLY AFTER DISCUSSING WITH HOTLINE!list RC mode SET PERMANENTLY!
Minimum dimming valuelist10 %
Dimming time 1 from 0% to 100%list4 s
Dimming time 2 from 0% to 100%list8 s
Dimming time 3 from 0% to 100%list12 s
When receiving a switching order (1 bit)listsoft on with dimming time 1
When receiving a dimming order (4 bit)listsoft on with dimming time 1
When receiving an absolute value (8 bit)listsoft on with dimming time 1
Switch-on valuelistbrightness value before previous switch-OFF
Switching ON/OFF with a 4-bit dim telegramlistyes
Format of forced objectlist1 Bit
Activate forced mode withlist1
Behaviour at start of forced mode operationlistno change
Behaviour at end of forced modelistvalue before forced mode
Reaction on forced ONlistno change
Reaction on forced OFFlistOFF
Lock telegram for sceneslistlock with ON telegram
All scene statuses of channellistoverwrite when downloading
Participation in object Central scenelistno
Channel reacts tolistscene number 1
Allocated dimming valuelist10 %
Response when receiving scene numberslistsoft on with dimming time 1
Permit teach-inlistyes
Channel reacts tolistscene number 2
Allocated dimming valuelist20 %
Channel reacts tolistscene number 3
Allocated dimming valuelist30 %
Channel reacts tolistscene number 4
Allocated dimming valuelist40 %
Channel reacts tolistscene number 5
Allocated dimming valuelist50 %
Channel reacts tolistscene number 6
Allocated dimming valuelist60 %
Channel reacts tolistscene number 7
Allocated dimming valuelist70 %
Channel reacts tolistscene number 8
Allocated dimming valuelist80 %
Type of hour meterlistoperating hours counter
Service interval (0..2000, x 10 h)unsignedInt 0…2000100
Report time to service when changed (0..100 h, 0 = no report)unsignedInt 0…10010
Transmit time to service cyclicallylistno
Report service cyclicallylistno
Time for cyclical transmissionlist60 min
Time for cyclical transmission (time to service)list60 min
Report operating hours at change (0..100 h, 0 = no report)unsignedInt 0…10010
Transmit operating hours cyclicallylistno
Status at download and bus failurelistsame as before failure
Status at restoration of bus powerlistsame as before failure
Send general error cyclicallylistno
Send short circuit cyclicallylistno
Send excess temperature cyclicallylistno
Send mains failure cyclicallylistno
Send load type cyclicallylistno
Cycle time for all diagnostic messages (if used)list60 min
Copy main parameters from channel C1listno
*** Start-up valuelist100 %
*** Type of loadlistL
Copy main parameters from channel C3listno
Copy main parameters from channel C5listno
Copy main parameters from channel C7listno
Modul Startadresselist
Anzahl Allg. ParameterunsignedInt 1…33
Download erfolgt 101listyes
A_Objektlink Grundgerätlistleer

Version history

ApplicationApp noFingerprintFirst seenSizeFile
FIX2 DM 8-2 T 1.0 latest$49482C432026-11-25312 KBDownload

About this file

This is the official ETS product database for the Theben AG DM 4-2 T (4940280), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.