HMT 12 S 4900374
Theben AG · Order number 4900374 · Heizungsaktoren › HMT 12 S
12x Heizungsaktor
Download .knxprod HMT 12 S 1.0 · 192 KB
Product
| Manufacturer | Theben AG |
|---|---|
| Product name | HMT 12 S |
| Order number | 4900374 |
| Hardware | HMT 12 S |
| Medium | Twisted Pair |
| Bus current (mA) | 7.5 |
| Rail mounted | Yes |
| Width (mm) | 290 |
| Registration | Certified · 2018-04-16 |
| Languages | de-DE, en-US, es-ES, fr-FR, it-IT, nl-NL |
| Catalog entry | M-0048_H-4900374-1_HP-490B-10-52CF_CI-4900374-1 |
| Fingerprint | 52CF |
| SHA-256 | 4320bd7d068505e308b4fb8d02e6648de15be01107ea7bb0735423e4764b4f2c |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: HMT 12 S 1.0
| Application number | $490B |
|---|---|
| Version | 1.0 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 808 |
| Group objects | 249 |
Group objects (249)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | Kanal H1 | Stellgröße stetig | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 1 | Kanal H1 | Stellgröße schaltend | 1 Bit | 1.1 switch | CRWU |
| 1 | Kanal H1 | Basissollwert | 2 Bytes | 9.1 temperature (°C) | CRW |
| 2 | Kanal H1 | Manuelle Sollwertverschiebung | 2 Bytes | 9.2 temperature difference (K) | CRW |
| 3 | Kanal H1 | Istwert | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 4 | Kanal H1 | Aktuelle Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 4 | Kanal H1 | Betriebsartvorwahl | 1 Byte | 20.102 HVAC mode | CRW |
| 5 | Kanal H1 | Präsenz | 1 Bit | 1.18 occupancy | CRW |
| 6 | Kanal H1 | Fensterstellung | 1 Bit | 1.19 window/door | CRW |
| 7 | Kanal H1 | aktuelle Betriebsart | 1 Byte | 20.102 HVAC mode | CRT |
| 8 | Kanal H1 | Stellgrösse Heizen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | Kanal H1 | Stellgrösse Heizen und Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 9 | Kanal H1 | Stellgrösse Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 10 | Kanal H1 | Heizen = 0, Kühlen = 1 | 1 Bit | 1.1 switch | CRWU |
| 10 | Kanal H1 | Heizen = 1, Kühlen = 0 | 1 Bit | 1.100 heating/cooling | CRWU |
| 11 | Kanal H1 | aktueller Sollwert | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 12 | Kanal H1 | Stellgrößenausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 12 | Kanal H1 | Istwertausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 13 | Kanal H1 | Zwangsbetrieb | 1 Bit | 1.3 enable | CRWU |
| 14 | Kanal H1 | Überstrom/Kurzschluss | 1 Bit | 1.5 alarm | CRTU |
| 21 | Kanal H2 | Stellgröße stetig | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 21 | Kanal H2 | Stellgröße schaltend | 1 Bit | 1.1 switch | CRWU |
| 21 | Kanal H2 | Basissollwert | 2 Bytes | 9.1 temperature (°C) | CRW |
| 22 | Kanal H2 | Manuelle Sollwertverschiebung | 2 Bytes | 9.2 temperature difference (K) | CRW |
| 23 | Kanal H2 | Istwert | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 24 | Kanal H2 | Aktuelle Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 24 | Kanal H2 | Betriebsartvorwahl | 1 Byte | 20.102 HVAC mode | CRW |
| 25 | Kanal H2 | Präsenz | 1 Bit | 1.18 occupancy | CRW |
| 26 | Kanal H2 | Fensterstellung | 1 Bit | 1.19 window/door | CRW |
| 27 | Kanal H2 | aktuelle Betriebsart | 1 Byte | 20.102 HVAC mode | CRT |
| 28 | Kanal H2 | Stellgrösse Heizen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 28 | Kanal H2 | Stellgrösse Heizen und Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 29 | Kanal H2 | Stellgrösse Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 30 | Kanal H2 | Heizen = 0, Kühlen = 1 | 1 Bit | 1.1 switch | CRWU |
| 30 | Kanal H2 | Heizen = 1, Kühlen = 0 | 1 Bit | 1.100 heating/cooling | CRWU |
| 31 | Kanal H2 | aktueller Sollwert | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 32 | Kanal H2 | Stellgrößenausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 32 | Kanal H2 | Istwertausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 33 | Kanal H2 | Zwangsbetrieb | 1 Bit | 1.3 enable | CRWU |
| 34 | Kanal H2 | Überstrom/Kurzschluss | 1 Bit | 1.5 alarm | CRTU |
| 41 | Kanal H3 | Stellgröße stetig | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 41 | Kanal H3 | Stellgröße schaltend | 1 Bit | 1.1 switch | CRWU |
| 41 | Kanal H3 | Basissollwert | 2 Bytes | 9.1 temperature (°C) | CRW |
| 42 | Kanal H3 | Manuelle Sollwertverschiebung | 2 Bytes | 9.2 temperature difference (K) | CRW |
| 43 | Kanal H3 | Istwert | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 44 | Kanal H3 | Aktuelle Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 44 | Kanal H3 | Betriebsartvorwahl | 1 Byte | 20.102 HVAC mode | CRW |
| 45 | Kanal H3 | Präsenz | 1 Bit | 1.18 occupancy | CRW |
| 46 | Kanal H3 | Fensterstellung | 1 Bit | 1.19 window/door | CRW |
| 47 | Kanal H3 | aktuelle Betriebsart | 1 Byte | 20.102 HVAC mode | CRT |
| 48 | Kanal H3 | Stellgrösse Heizen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 48 | Kanal H3 | Stellgrösse Heizen und Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 49 | Kanal H3 | Stellgrösse Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 50 | Kanal H3 | Heizen = 0, Kühlen = 1 | 1 Bit | 1.1 switch | CRWU |
| 50 | Kanal H3 | Heizen = 1, Kühlen = 0 | 1 Bit | 1.100 heating/cooling | CRWU |
| 51 | Kanal H3 | aktueller Sollwert | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 52 | Kanal H3 | Stellgrößenausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 52 | Kanal H3 | Istwertausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 53 | Kanal H3 | Zwangsbetrieb | 1 Bit | 1.3 enable | CRWU |
| 54 | Kanal H3 | Überstrom/Kurzschluss | 1 Bit | 1.5 alarm | CRTU |
| 61 | Kanal H4 | Stellgröße stetig | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 61 | Kanal H4 | Stellgröße schaltend | 1 Bit | 1.1 switch | CRWU |
| 61 | Kanal H4 | Basissollwert | 2 Bytes | 9.1 temperature (°C) | CRW |
| 62 | Kanal H4 | Manuelle Sollwertverschiebung | 2 Bytes | 9.2 temperature difference (K) | CRW |
| 63 | Kanal H4 | Istwert | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 64 | Kanal H4 | Aktuelle Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 64 | Kanal H4 | Betriebsartvorwahl | 1 Byte | 20.102 HVAC mode | CRW |
| 65 | Kanal H4 | Präsenz | 1 Bit | 1.18 occupancy | CRW |
| 66 | Kanal H4 | Fensterstellung | 1 Bit | 1.19 window/door | CRW |
| 67 | Kanal H4 | aktuelle Betriebsart | 1 Byte | 20.102 HVAC mode | CRT |
| 68 | Kanal H4 | Stellgrösse Heizen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 68 | Kanal H4 | Stellgrösse Heizen und Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 69 | Kanal H4 | Stellgrösse Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 70 | Kanal H4 | Heizen = 0, Kühlen = 1 | 1 Bit | 1.1 switch | CRWU |
| 70 | Kanal H4 | Heizen = 1, Kühlen = 0 | 1 Bit | 1.100 heating/cooling | CRWU |
| 71 | Kanal H4 | aktueller Sollwert | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 72 | Kanal H4 | Stellgrößenausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 72 | Kanal H4 | Istwertausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 73 | Kanal H4 | Zwangsbetrieb | 1 Bit | 1.3 enable | CRWU |
| 74 | Kanal H4 | Überstrom/Kurzschluss | 1 Bit | 1.5 alarm | CRTU |
| 81 | Kanal H5 | Stellgröße stetig | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 81 | Kanal H5 | Stellgröße schaltend | 1 Bit | 1.1 switch | CRWU |
| 81 | Kanal H5 | Basissollwert | 2 Bytes | 9.1 temperature (°C) | CRW |
| 82 | Kanal H5 | Manuelle Sollwertverschiebung | 2 Bytes | 9.2 temperature difference (K) | CRW |
| 83 | Kanal H5 | Istwert | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 84 | Kanal H5 | Aktuelle Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 84 | Kanal H5 | Betriebsartvorwahl | 1 Byte | 20.102 HVAC mode | CRW |
| 85 | Kanal H5 | Präsenz | 1 Bit | 1.18 occupancy | CRW |
| 86 | Kanal H5 | Fensterstellung | 1 Bit | 1.19 window/door | CRW |
| 87 | Kanal H5 | aktuelle Betriebsart | 1 Byte | 20.102 HVAC mode | CRT |
| 88 | Kanal H5 | Stellgrösse Heizen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 88 | Kanal H5 | Stellgrösse Heizen und Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 89 | Kanal H5 | Stellgrösse Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 90 | Kanal H5 | Heizen = 0, Kühlen = 1 | 1 Bit | 1.1 switch | CRWU |
| 90 | Kanal H5 | Heizen = 1, Kühlen = 0 | 1 Bit | 1.100 heating/cooling | CRWU |
| 91 | Kanal H5 | aktueller Sollwert | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 92 | Kanal H5 | Stellgrößenausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 92 | Kanal H5 | Istwertausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 93 | Kanal H5 | Zwangsbetrieb | 1 Bit | 1.3 enable | CRWU |
| 94 | Kanal H5 | Überstrom/Kurzschluss | 1 Bit | 1.5 alarm | CRTU |
| 101 | Kanal H6 | Stellgröße stetig | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 101 | Kanal H6 | Stellgröße schaltend | 1 Bit | 1.1 switch | CRWU |
| 101 | Kanal H6 | Basissollwert | 2 Bytes | 9.1 temperature (°C) | CRW |
| 102 | Kanal H6 | Manuelle Sollwertverschiebung | 2 Bytes | 9.2 temperature difference (K) | CRW |
| 103 | Kanal H6 | Istwert | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 104 | Kanal H6 | Aktuelle Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 104 | Kanal H6 | Betriebsartvorwahl | 1 Byte | 20.102 HVAC mode | CRW |
| 105 | Kanal H6 | Präsenz | 1 Bit | 1.18 occupancy | CRW |
| 106 | Kanal H6 | Fensterstellung | 1 Bit | 1.19 window/door | CRW |
| 107 | Kanal H6 | aktuelle Betriebsart | 1 Byte | 20.102 HVAC mode | CRT |
| 108 | Kanal H6 | Stellgrösse Heizen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 108 | Kanal H6 | Stellgrösse Heizen und Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 109 | Kanal H6 | Stellgrösse Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 110 | Kanal H6 | Heizen = 0, Kühlen = 1 | 1 Bit | 1.1 switch | CRWU |
| 110 | Kanal H6 | Heizen = 1, Kühlen = 0 | 1 Bit | 1.100 heating/cooling | CRWU |
| 111 | Kanal H6 | aktueller Sollwert | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 112 | Kanal H6 | Stellgrößenausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 112 | Kanal H6 | Istwertausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 113 | Kanal H6 | Zwangsbetrieb | 1 Bit | 1.3 enable | CRWU |
| 114 | Kanal H6 | Überstrom/Kurzschluss | 1 Bit | 1.5 alarm | CRTU |
| 121 | Kanal H7 | Stellgröße stetig | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 121 | Kanal H7 | Stellgröße schaltend | 1 Bit | 1.1 switch | CRWU |
| 121 | Kanal H7 | Basissollwert | 2 Bytes | 9.1 temperature (°C) | CRW |
| 122 | Kanal H7 | Manuelle Sollwertverschiebung | 2 Bytes | 9.2 temperature difference (K) | CRW |
| 123 | Kanal H7 | Istwert | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 124 | Kanal H7 | Aktuelle Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 124 | Kanal H7 | Betriebsartvorwahl | 1 Byte | 20.102 HVAC mode | CRW |
| 125 | Kanal H7 | Präsenz | 1 Bit | 1.18 occupancy | CRW |
| 126 | Kanal H7 | Fensterstellung | 1 Bit | 1.19 window/door | CRW |
| 127 | Kanal H7 | aktuelle Betriebsart | 1 Byte | 20.102 HVAC mode | CRT |
| 128 | Kanal H7 | Stellgrösse Heizen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | Kanal H7 | Stellgrösse Heizen und Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 129 | Kanal H7 | Stellgrösse Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 130 | Kanal H7 | Heizen = 0, Kühlen = 1 | 1 Bit | 1.1 switch | CRWU |
| 130 | Kanal H7 | Heizen = 1, Kühlen = 0 | 1 Bit | 1.100 heating/cooling | CRWU |
| 131 | Kanal H7 | aktueller Sollwert | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 132 | Kanal H7 | Stellgrößenausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 132 | Kanal H7 | Istwertausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 133 | Kanal H7 | Zwangsbetrieb | 1 Bit | 1.3 enable | CRWU |
| 134 | Kanal H7 | Überstrom/Kurzschluss | 1 Bit | 1.5 alarm | CRTU |
| 141 | Kanal H8 | Stellgröße stetig | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 141 | Kanal H8 | Stellgröße schaltend | 1 Bit | 1.1 switch | CRWU |
| 141 | Kanal H8 | Basissollwert | 2 Bytes | 9.1 temperature (°C) | CRW |
| 142 | Kanal H8 | Manuelle Sollwertverschiebung | 2 Bytes | 9.2 temperature difference (K) | CRW |
| 143 | Kanal H8 | Istwert | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 144 | Kanal H8 | Aktuelle Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 144 | Kanal H8 | Betriebsartvorwahl | 1 Byte | 20.102 HVAC mode | CRW |
| 145 | Kanal H8 | Präsenz | 1 Bit | 1.18 occupancy | CRW |
| 146 | Kanal H8 | Fensterstellung | 1 Bit | 1.19 window/door | CRW |
| 147 | Kanal H8 | aktuelle Betriebsart | 1 Byte | 20.102 HVAC mode | CRT |
| 148 | Kanal H8 | Stellgrösse Heizen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 148 | Kanal H8 | Stellgrösse Heizen und Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 149 | Kanal H8 | Stellgrösse Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 150 | Kanal H8 | Heizen = 0, Kühlen = 1 | 1 Bit | 1.1 switch | CRWU |
| 150 | Kanal H8 | Heizen = 1, Kühlen = 0 | 1 Bit | 1.100 heating/cooling | CRWU |
| 151 | Kanal H8 | aktueller Sollwert | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 152 | Kanal H8 | Stellgrößenausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 152 | Kanal H8 | Istwertausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 153 | Kanal H8 | Zwangsbetrieb | 1 Bit | 1.3 enable | CRWU |
| 154 | Kanal H8 | Überstrom/Kurzschluss | 1 Bit | 1.5 alarm | CRTU |
| 161 | Kanal H9 | Stellgröße stetig | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 161 | Kanal H9 | Stellgröße schaltend | 1 Bit | 1.1 switch | CRWU |
| 161 | Kanal H9 | Basissollwert | 2 Bytes | 9.1 temperature (°C) | CRW |
| 162 | Kanal H9 | Manuelle Sollwertverschiebung | 2 Bytes | 9.2 temperature difference (K) | CRW |
| 163 | Kanal H9 | Istwert | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 164 | Kanal H9 | Aktuelle Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 164 | Kanal H9 | Betriebsartvorwahl | 1 Byte | 20.102 HVAC mode | CRW |
| 165 | Kanal H9 | Präsenz | 1 Bit | 1.18 occupancy | CRW |
| 166 | Kanal H9 | Fensterstellung | 1 Bit | 1.19 window/door | CRW |
| 167 | Kanal H9 | aktuelle Betriebsart | 1 Byte | 20.102 HVAC mode | CRT |
| 168 | Kanal H9 | Stellgrösse Heizen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 168 | Kanal H9 | Stellgrösse Heizen und Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 169 | Kanal H9 | Stellgrösse Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 170 | Kanal H9 | Heizen = 0, Kühlen = 1 | 1 Bit | 1.1 switch | CRWU |
| 170 | Kanal H9 | Heizen = 1, Kühlen = 0 | 1 Bit | 1.100 heating/cooling | CRWU |
| 171 | Kanal H9 | aktueller Sollwert | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 172 | Kanal H9 | Stellgrößenausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 172 | Kanal H9 | Istwertausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 173 | Kanal H9 | Zwangsbetrieb | 1 Bit | 1.3 enable | CRWU |
| 174 | Kanal H9 | Überstrom/Kurzschluss | 1 Bit | 1.5 alarm | CRTU |
| 181 | Kanal H10 | Stellgröße stetig | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 181 | Kanal H10 | Stellgröße schaltend | 1 Bit | 1.1 switch | CRWU |
| 181 | Kanal H10 | Basissollwert | 2 Bytes | 9.1 temperature (°C) | CRW |
| 182 | Kanal H10 | Manuelle Sollwertverschiebung | 2 Bytes | 9.2 temperature difference (K) | CRW |
| 183 | Kanal H10 | Istwert | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 184 | Kanal H10 | Aktuelle Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 184 | Kanal H10 | Betriebsartvorwahl | 1 Byte | 20.102 HVAC mode | CRW |
| 185 | Kanal H10 | Präsenz | 1 Bit | 1.18 occupancy | CRW |
| 186 | Kanal H10 | Fensterstellung | 1 Bit | 1.19 window/door | CRW |
| 187 | Kanal H10 | aktuelle Betriebsart | 1 Byte | 20.102 HVAC mode | CRT |
| 188 | Kanal H10 | Stellgrösse Heizen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 188 | Kanal H10 | Stellgrösse Heizen und Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 189 | Kanal H10 | Stellgrösse Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 190 | Kanal H10 | Heizen = 0, Kühlen = 1 | 1 Bit | 1.1 switch | CRWU |
| 190 | Kanal H10 | Heizen = 1, Kühlen = 0 | 1 Bit | 1.100 heating/cooling | CRWU |
| 191 | Kanal H10 | aktueller Sollwert | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 192 | Kanal H10 | Stellgrößenausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 192 | Kanal H10 | Istwertausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 193 | Kanal H10 | Zwangsbetrieb | 1 Bit | 1.3 enable | CRWU |
| 194 | Kanal H10 | Überstrom/Kurzschluss | 1 Bit | 1.5 alarm | CRTU |
| 201 | Kanal H11 | Stellgröße stetig | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 201 | Kanal H11 | Stellgröße schaltend | 1 Bit | 1.1 switch | CRWU |
| 201 | Kanal H11 | Basissollwert | 2 Bytes | 9.1 temperature (°C) | CRW |
| 202 | Kanal H11 | Manuelle Sollwertverschiebung | 2 Bytes | 9.2 temperature difference (K) | CRW |
| 203 | Kanal H11 | Istwert | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 204 | Kanal H11 | Aktuelle Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 204 | Kanal H11 | Betriebsartvorwahl | 1 Byte | 20.102 HVAC mode | CRW |
| 205 | Kanal H11 | Präsenz | 1 Bit | 1.18 occupancy | CRW |
| 206 | Kanal H11 | Fensterstellung | 1 Bit | 1.19 window/door | CRW |
| 207 | Kanal H11 | aktuelle Betriebsart | 1 Byte | 20.102 HVAC mode | CRT |
| 208 | Kanal H11 | Stellgrösse Heizen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 208 | Kanal H11 | Stellgrösse Heizen und Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 209 | Kanal H11 | Stellgrösse Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 210 | Kanal H11 | Heizen = 0, Kühlen = 1 | 1 Bit | 1.1 switch | CRWU |
| 210 | Kanal H11 | Heizen = 1, Kühlen = 0 | 1 Bit | 1.100 heating/cooling | CRWU |
| 211 | Kanal H11 | aktueller Sollwert | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 212 | Kanal H11 | Stellgrößenausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 212 | Kanal H11 | Istwertausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 213 | Kanal H11 | Zwangsbetrieb | 1 Bit | 1.3 enable | CRWU |
| 214 | Kanal H11 | Überstrom/Kurzschluss | 1 Bit | 1.5 alarm | CRTU |
| 221 | Kanal H12 | Stellgröße stetig | 1 Byte | 5.1 percentage (0..100%) | CRWU |
| 221 | Kanal H12 | Stellgröße schaltend | 1 Bit | 1.1 switch | CRWU |
| 221 | Kanal H12 | Basissollwert | 2 Bytes | 9.1 temperature (°C) | CRW |
| 222 | Kanal H12 | Manuelle Sollwertverschiebung | 2 Bytes | 9.2 temperature difference (K) | CRW |
| 223 | Kanal H12 | Istwert | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 224 | Kanal H12 | Aktuelle Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 224 | Kanal H12 | Betriebsartvorwahl | 1 Byte | 20.102 HVAC mode | CRW |
| 225 | Kanal H12 | Präsenz | 1 Bit | 1.18 occupancy | CRW |
| 226 | Kanal H12 | Fensterstellung | 1 Bit | 1.19 window/door | CRW |
| 227 | Kanal H12 | aktuelle Betriebsart | 1 Byte | 20.102 HVAC mode | CRT |
| 228 | Kanal H12 | Stellgrösse Heizen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 228 | Kanal H12 | Stellgrösse Heizen und Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 229 | Kanal H12 | Stellgrösse Kühlen | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 230 | Kanal H12 | Heizen = 0, Kühlen = 1 | 1 Bit | 1.1 switch | CRWU |
| 230 | Kanal H12 | Heizen = 1, Kühlen = 0 | 1 Bit | 1.100 heating/cooling | CRWU |
| 231 | Kanal H12 | aktueller Sollwert | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 232 | Kanal H12 | Stellgrößenausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 232 | Kanal H12 | Istwertausfall melden | 1 Bit | 1.5 alarm | CRTU |
| 233 | Kanal H12 | Zwangsbetrieb | 1 Bit | 1.3 enable | CRWU |
| 234 | Kanal H12 | Überstrom/Kurzschluss | 1 Bit | 1.5 alarm | CRTU |
| 241 | H1 - H12 | Sommerbetrieb EIN/AUS | 1 Bit | 1.3 enable | CRWU |
| 242 | H1 - H12 | Größte Stellgröße | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 244 | H1 - H12 | Pumpe EIN/AUS (Ausgang 2. Pumpe) | 1 Bit | 1.1 switch | CRTU |
| 245 | H1 - H12 | Pumpenrelais-Status | 1 Bit | 1.1 switch | CRTU |
| 246 | H1 - H12 | Außentemperatur | 2 Bytes | 9.1 temperature (°C) | CRWU |
| 247 | H1 - H12 | Ausfall Außentemperatur | 1 Bit | 1.5 alarm | CRTU |
| 248 | H1 - H12 | Manuell | 1 Bit | 1.1 switch | CRWTU |
| 249 | Version des Busankopplers | Senden | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRTU |
| 250 | Version Firmware | Senden | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRTU |
Parameters (91)
| Parameter | Type | Default |
|---|---|---|
| Gerätetyp | list | HMT 12 S.. |
| Überwachungszeit | list | 30 min. |
| Status der Überwachung | list | nur im Fehlerfall melden |
| Status zyklisch senden | list | nein |
| Zykluszeit | list | alle 30 min. |
| Relais nur einschalten wenn mindestens (nur für Schaltausgang) | list | eine Eingangsstellgröße > 0 % ist |
| Ausschaltverzögerung | list | 10 min |
| Relaisstatus zyklisch senden | list | nein, nur bei Änderung |
| Einschalttelegramm nur wenn mindestens (nur für Schaltausgang) | list | eine Eingangsstellgröße > 0 % ist |
| Pumpensteuerung zyklisch senden | list | nein, nur bei Änderung |
| Funktion der Taste Manuell | list | gilt bis Rücksetzen über Objekt |
| Manuelle Bedienung der Kanäle | list | freigegeben |
| Größte Stellgröße senden (falls stetige Stellgröße verwendet) | list | nur wenn eigene Stellgröße größer ist |
| - | list | HMT 6/12 S |
| Anzahl Allg. Parameter | unsignedInt 1…34 | 9 |
| Download erfolgt 101 | list | ja |
| Zeit für zykl. Senden der Rückmeldeobj. (MIX 1 Serie, Best. Nr.491...) | list | 15 min |
| - | list | Link HMT 6 S Grundmodul |
| - | list | Link 1. Erweiterung HMT 6 S |
| - | list | Link Grundmodul HMT 12 S |
| - | list | Link 1. Erweiterung HMT 12 S |
| Funktion des Kanals | list | Heizungsaktor |
| Art der Stellgröße | list | stetig.. |
| Teilnahme am Sommerbetrieb | list | nein |
| Ventilschutz aktivieren | list | ja |
| Ventilschutz Sperrtelegramm | list | 1 = Sperren (Standard) |
| Stellgröße überwachen | list | nein |
| Ventilschutz ausführen | list | immer |
| Istwert überwachen | list | nein |
| PWM Einheit | list | Minuten |
| Zwangfunktion aktivieren | list | nein |
| Art der Ventilsteuerung | list | Schaltausgang |
| Wirksinn des Stellantriebes | list | Standard: 10 V = Ventil öffnen |
| Ausgangsspannung bei 0 % | list | 0 V |
| Ausgangsspannung bei 100 % | list | 10 V |
| Ausgangsspannung bei 100 % | list | 0 V |
| Ausgangsspannung bei 0 % | list | 10 V |
| Wirksinn des Stellantriebes | list | Standard: 1 = Ventil öffnen |
| Zeit für einen Stellzyklus (PWM-Periode) | list | 10 min |
| Umschalten zw. Heizen und Kühlen | list | automatisch |
| Kanal verarbeitet Stellgröße für | list | Heizen |
| Ausgabe der Stellgröße Kühlen | list | auf separates Objekt |
| Minimale Stellgröße | list | 0 % |
| - | list | 90 % |
| - | list | bei Änderung um 5 % |
| - | list | ja |
| Aktuelle Stellgröße zyklisch senden | list | nicht zyklisch, nur bei Änderung |
| Maximale Stellgröße | list | 90 % |
| Stellgröße bei Unter-/Überschreiten der minimalen/maximalen Stellgröße | list | 0 = 0 % sonst eingestellte Stellgrößen verwenden |
| Aktuelle Stellgröße senden | list | bei Änderung um 5 % |
| Kanal bei größter Stellgröße berücksichtigen | list | ja |
| Pumpe ansteuern | list | über Relais |
| Regelung | list | Standard |
| Verwendete Regelfunktionen | list | Nur Heizungregelung |
| Betriebsart nach Reset | list | Standby |
| Art des Präsenzsensors | list | Präsenzmelder |
| Komfortverlängerung durch Präsenztaster im Nachtbetrieb | list | 2 Stunden |
| Zykl. Senden der aktuellen Betriebsart | list | nicht zyklisch, nur bei Änderung |
| Anlagentyp | list | Radiatorenheizung |
| Senden der Stellgröße Heizen | list | bei Änderung um 5 % |
| Zykl Senden der Stellgröße Heizen | list | nicht zyklisch, nur bei Änderung |
| Einstellung der Regelparameter | list | über Anlagentyp |
| Proportionalband des Heizungsreglers | list | 2 K |
| Integrierzeit des Heizungsreglers | list | 10 h |
| Basissollwert nach Laden der Applikation | list | 21 °C |
| Minimal gültiger Basissollwert | list | 10 °C |
| Maximal gültiger Basissollwert | list | 32 °C |
| Absenkung in Standbybetrieb (bei Heizen) | list | 1,5 K |
| Absenkung im Nachtbetrieb (bei Heizen) | list | 5 K |
| Sollwert für Frostschutzbetrieb (bei Heizen) | list | 5 °C |
| Maximal gültige Sollwertverschiebung | list | +/- 5 K |
| Sollwertverschiebung gilt | list | bei Komfort, Standby und Nachtbetrieb |
| Aktueller Sollwert im Komfortbetrieb | list | Tatsächlichen Wert senden (Heizen <> Kühlen) |
| Zykl Senden des aktuellen Sollwertes | list | nicht zyklisch, nur bei Änderung |
| Proportionalband des Kühlenreglers | list | 4 K |
| Integrierzeit des Kühlenreglers | list | 180 min. |
| Anlagentyp | list | Kühldecke |
| Senden der Stellgröße Kühlen | list | bei Änderung um 5 % |
| Zykl Senden der Stellgröße Kühlen | list | nicht zyklisch, nur bei Änderung |
| Format Objekt Heizen/Kühlen | list | DPT1.100 (Heizen=1 / Kühlen=0) |
| Totzone zw. Heizen und Kühlen | list | 2 K |
| Anhebung im Standbybetrieb (bei Kühlen) | list | 1,5 K |
| Anhebung im Nachtbetrieb (bei Kühlen) | list | 5 K |
| Sollwert für Hitzeschutzbetrieb (bei Kühlen) | list | 42 °C d.h. quasi kein Hitzeschutz |
| Stellgröße für Notprogramm ist | list | fest |
| Notprogramm aktiv wenn Außentemperatur unter | list | 10 °C |
| Maximale Stellgröße im Notprogramm | list | 40 % |
| Festes Notprogramm bei Ausfall der Außentemperatur | list | 20 % |
| Festes Notprogramm im Winterbetrieb | list | 20 % |
| Stellgröße im Zwangsbetrieb | list | 0 % |
| Zwangstelegramm | list | 1 = Zwang (Standard) |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| HMT 12 S 1.0 latest | $490B | 52CF | 2026-11-25 | 192 KB | Download |
About this file
This is the official ETS product database for the Theben AG HMT 12 S (4900374), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.