KNX Database

MOT-Ix.02S KNX Motivity Ceiling, Secure MOT-Ix.02S

Tense · Order number MOT-Ix.02S · Motion Detectors › Motivity

Download .knxprod Motivity, Secure 1.0 · 189 KB

Product

ManufacturerTense
Product nameMOT-Ix.02S KNX Motivity Ceiling, Secure
Order numberMOT-Ix.02S
HardwareMotivity
MediumTwisted Pair
Bus current (mA)5
Rail mountedNo
RegistrationRegistered · 2025-10-03
Languagesde-DE, en-US, es-ES, fr-FR, it-IT
Catalog entryM-011F_H-648-1-O0083_HP-0694-10-F07A-O0083_CI-MOT.2DIx.2E02S-1
FingerprintF07A
SHA-256f78df939632132c36cb9027c71b90d5c10c866646ccdecac682eca3c7af84d70
First seen2026-11-25
Markets67 markets

Application program: Motivity, Secure 1.0

Application number$0694
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureYes
Minimum ETS version5.0
Parameters334
Group objects84
Group objects (84)
NoNameFunctionSizeDPTFlags
1In operationOutput1 Bit1.11 stateCRT
2Day/NightDay = 1 / Night = 01 Bit1.2 booleanCWTUI
2Day/NightNight = 1 / Day = 01 Bit1.2 booleanCWTUI
3SceneInput1 Byte17.1 scene numberCW
4Light channel 1 - Output 1Switch1 Bit1.1 switchCRT
4Light channel 1 - Output 1 (day)Switch1 Bit1.1 switchCRT
4Light channel 1 - Output 1Dimming absolute1 Byte5.1 percentage (0..100%)CRT
4Light channel 1 - Output 1Scene1 Byte17.1 scene numberCRT
5Light channel 1 - Output (Night)Switch1 Bit1.1 switchCRT
6Light channel 1 - Output 2 (additional)Switch1 Bit1.1 switchCRT
7Light channel 1 - InputExternal button short1 Bit1.1 switchCW
8Light channel 1 - InputExternal button long1 Bit1.1 switchCW
9Light channel 1 - InputExternal motion (Slave)1 Bit1.1 switchCW
10Light channel 1 - InputStatus of actuator channel1 Bit1.1 switchCW
11Light channel 1 - InputLock motion detection1 Bit1.3 enableCW
12Light channel 1 - InputForced guidance2 Bit2.1 switch controlCW
12Light channel 1 - InputLock object1 Bit1.3 enableCW
13Light channel 1 - InputLock object On1 Bit1.3 enableCW
14Light channel 1 - StatusAutomatic mode1 Bit1.11 stateCRT
14Light channel 1 - StatusLock/Manual mode1 Bit1.11 stateCRT
15Light channel 1 - InputSwitch dark1 Bit1.1 switchCW
16Light channel 1 - InputTeach-in dimming value for ON1 Byte5.1 percentage (0..100%)CWTUI
17Light channel 1 - InputFollow-up time 10 - 65000 s2 Bytes7.5 time (s)CWTUI
19HVAC - Output 1Switch1 Bit1.1 switchCRT
19Output - climate (HCV)Dimming absolute1 Byte5.1 percentage (0..100%)CRT
19Output - climate (HCV)Scene1 Byte17.1 scene numberCRT
22HVAC- InputExternal button short1 Bit1.1 switchCW
23HVAC - InputExternal button long1 Bit1.1 switchCW
24HVAC - InputExternal motion1 Bit1.1 switchCW
25HVAC - InputStatus of actuator channel1 Bit1.1 switchCW
26HVAC - InputLock motion detection1 Bit1.3 enableCW
27HVAC - InputForced guidance2 Bit2.1 switch controlCW
27HVAC - InputLock object1 Bit1.3 enableCW
28HVAC - InputLock object On1 Bit1.3 enableCW
29HVAC - StatusAutomatic mode1 Bit1.11 stateCRT
29HVAC - StatusLock/Manual mode1 Bit1.11 stateCRT
30HVAC - InputSwitch dark1 Bit1.1 switchCW
31HVAC - InputTeach-in dimming value for ON1 Byte5.1 percentage (0..100%)CWTUI
32HVAC - InputFollow-up time 10 - 65000 s2 Bytes7.5 time (s)CWTUI
34Alarm - OutputSwitch1 Bit1.1 switchCRT
34Alarm - Output (Day)Switch1 Bit1.1 switchCRT
35Alarm - Output (Night)Switch1 Bit1.1 switchCRT
42Alarm - InputLock1 Bit1.3 enableCW
42Alarm - InputRelease1 Bit1.3 enableCW
49TemperatureMeasured value2 Bytes9.1 temperature (°C)CRT
50BrightnessThreshold switch1 Bit1.1 switchCRT
51BrightnessMeasured value2 Bytes9.4 lux (Lux)CRT
52BrightnessSet switch-on threshold for light channels2 Bytes9.4 lux (Lux)CW
53Logic 1 {{0}}Input C1 Bit1.2 booleanCWTU
54Logic 1 {{0}}Input D1 Bit1.2 booleanCWTU
55Logic 1 {{0}}Input E1 Bit1.2 booleanCWTU
56Logic 1 {{0}}Input F1 Bit1.2 booleanCWTU
57Logic 1 {{0}}Output 11 Bit1.2 booleanCRT
57Logic 1 {{0}}Output 11 Byte17.1 scene numberCRT
57Logic 1 {{0}}Output 11 Byte5.5 ratio (0..255)CRT
57Logic 1 {{0}}Output 11 Byte5.1 percentage (0..100%)CRT
57Logic 1 {{0}}Output 12 Bit2.1 switch controlCRT
58Logic 2 {{0}}Input C1 Bit1.2 booleanCWTU
59Logic 2 {{0}}Input D1 Bit1.2 booleanCWTU
60Logic 2 {{0}}Input E1 Bit1.2 booleanCWTU
61Logic 2 {{0}}Input F1 Bit1.2 booleanCWTU
62Logic 2 {{0}}Output 21 Bit1.2 booleanCRT
62Logic 2 {{0}}Output 21 Byte17.1 scene numberCRT
62Logic 2 {{0}}Output 21 Byte5.5 ratio (0..255)CRT
62Logic 2 {{0}}Output 21 Byte5.1 percentage (0..100%)CRT
62Logic 2 {{0}}Output 22 Bit2.1 switch controlCRT
63Logic 3 {{0}}Input C1 Bit1.2 booleanCWTU
64Logic 3 {{0}}Input D1 Bit1.2 booleanCWTU
65Logic 3 {{0}}Input E1 Bit1.2 booleanCWTU
66Logic 3 {{0}}Input F1 Bit1.2 booleanCWTU
67Logic 3 {{0}}Output 31 Bit1.2 booleanCRT
67Logic 3 {{0}}Output 31 Byte17.1 scene numberCRT
67Logic 3 {{0}}Output 31 Byte5.5 ratio (0..255)CRT
67Logic 3 {{0}}Output 31 Byte5.1 percentage (0..100%)CRT
67Logic 3 {{0}}Output 32 Bit2.1 switch controlCRT
68Logic 4 {{0}}Input C1 Bit1.2 booleanCWTU
69Logic 4 {{0}}Input D1 Bit1.2 booleanCWTU
70Logic 4 {{0}}Input E1 Bit1.2 booleanCWTU
71Logic 4 {{0}}Input F1 Bit1.2 booleanCWTU
72Logic 4 {{0}}Output 41 Bit1.2 booleanCRT
72Logic 4 {{0}}Output 41 Byte17.1 scene numberCRT
72Logic 4 {{0}}Output 41 Byte5.5 ratio (0..255)CRT
72Logic 4 {{0}}Output 41 Byte5.1 percentage (0..100%)CRT
72Logic 4 {{0}}Output 42 Bit2.1 switch controlCRT
Parameters (167)
ParameterTypeDefault
Send "In operation" cyclicallylistnot active
Day/Night objectlistrequest after reset
Value for Day/NightlistDay = 1 / Night = 0
Toggle Day/Nightlistat next presence
Switch-on thresholdunsignedInt 5…1000400
Switch-on threshold "Day"unsignedInt 5…1000400
Switch-on threshold "Night"unsignedInt 5…1000400
Switch-off if exceedancelistnot active
Switch-off when exceeding …unsignedInt 75…1000800
Fallback of forced guidance/locklistnot active
Follow-up time for forced guidance/locklist3 min
Follow-up time for forced guidance/lock "Day"list3 min
Follow-up time for forced guidance/lock "Night"list3 min
Fallback time for forced guidance/locklist3 min
Fallback time for forced guidance/lock "Day"list3 min
Fallback time for forced guidance/lock "Night"list3 min
Fallback for external button long (Manual => Auto)listafter presence and follow-up time
Manual mode, follow-up time for ONlist3 min
Manual mode, follow-up time for OFFlist3 min
Manual mode, follow-up time for ON "Day"list3 min
Manual mode, follow-up time for OFF "Day"list3 min
Manual mode, follow-up time for ON "Night"list3 min
Manual mode, follow-up time for OFF "Night"list3 min
Manual mode, fallback time for ONlist3 min
Manual mode, fallback time for OFFlist3 min
Manual mode, fallback time for ON "Day"list3 min
Manual mode, fallback time for OFF "Day"list3 min
Manual mode, fallback time for ON "Night"list3 min
Manual mode, fallback time for OFF "Night"list3 min
Scene A numberlistnot active
Light channel 1listactive
Scene A Light channel 1listnot active
Scene B numberlistnot active
Scene B Light channel 1listnot active
Scene C numberlistnot active
Scene C Light channel 1listnot active
Scene D numberlistnot active
Scene D Light channel 1listnot active
Scene E numberlistnot active
Scene E Light channel 1listnot active
Scene F numberlistnot active
Scene F Light channel 1listnot active
Scene G numberlistnot active
Scene G Light channel 1listnot active
Scene H numberlistnot active
Scene H Light channel 1listnot active
Light channels influence the brightness measurementlistyes (several lights in the room)
Send brightness on change oflist10 %
Send measured value cyclicallylistnot active
Correction valuelist0 %
Room reflection factorlist0.4 medium
Threshold switchlistnot active
Threshold switch switches atunsignedInt 5…1000300
Hysteresis of threshold switchunsignedInt 5…20030
Object value when exceededlistON
Object value at "Day" and exceedancelistON
Object value at "Night" and exceedancelistON
Object value at lower deviationlistOFF
SendlistON and OFF
Send at "Day"listON and OFF
Send at "Night"listON and OFF
Lux value for Teach-inunsignedInt 200…1000450
Teach-in value at loading of applicationlistuse default value
Temperature measurementlistnot active
Send measured value on change oflist0.2 K
Correction value for sensorsignedInt -80…500
HVAClistnot active
Alarm/Message channellistnot active
Brightnesslistbasic setting or object "Switch dark" is active
Channel modelistfully automatic
Motion filter in standbylistnot active, no filtering
Reduction of follow-up timelistnot active
Maximum duration for short time presencelist20 s
Follow-up time for short time presencelist30 s
Follow-up timelist3 min
Follow-up time "Day"list3 min
Follow-up time "Night"list30 s
Forced guidance or lock objectlistforced guidance object (2 Bit)
Action on lockinglistlock motion (lock current state)
Action on unlockinglistnot active
Fallback of forced guidance/lock (General setting)listactive
Object type for output - LightlistSwitch
Output objects for Day/Nightlistone common object
Dimming value for ONlist100 %
Dimming value for OFFlist0 %
Dimming value for "Day" when ONlist100 %
Dimming value for “Day” when OFFlist0 %
Dimming value for “Night” when ONlist30 %
Dimming value for “Night” when OFFlist0 %
Orientation light for leavinglistswitch-off immediately
Switch-off delaylist30 s
Switch-off dimming valuelist30 %
Switch-off delay for "Day"list30 s
Switch-off dimming value for "Day"list30 %
Switch-off delay for "Night"list30 s
Switch-off dimming value for "Night"list20 %
Scene number for ONlist1
Scene number for OFFlist2
Scene number for "Day" when ONlist1
Scene number for "Day" when OFFlist2
Scene number for "Night" when ONlist3
Scene number for "Night" when OFFlist4
Output object 1 sendslistON and OFF
Output object 1 sends ON cyclicallylistnot active
Output object 1 sendslistdimming value for ON and OFF
Output object 1 sends value for ON cyclicallylistnot active
Output object 1 sendslistscene number for ON and OFF
Output object 1 sends scene for ON cyclicallylistnot active
Output 2 (Additional switch object)listnot active
External button short reacts tolistON and OFF
Idle time after external button short is offunsignedInt 1…305
External button long reacts tolistON and OFF
Idle time after switch offunsignedInt 0…601
If Night light is activelistswitch to Day light
If output "Day" is already ONlistswitch to manual mode
If output is already ONlistswitch to manual mode
Status informationlistnot active
Number of monitoring time slotslist3
Length of monitoring time slotunsignedInt 0…3000030
Object type for output - climate (HVAC)listSwitch
Object value for ONlistvalue "1"
Object value for OFFlistvalue "0"
Object value for “Day” when ONlistvalue "1"
Object value for “Day” when OFFlistvalue "0"
Object value for “Night” when ONlistvalue "1"
Object value for “Night” when OFFlistvalue "0"
Scene number for “Night” when ONlist3
Scene number for “Night” when OFFlist4
Output object 1 sends cyclicallylistnot active
Output object 1 sends value cyclicallylistnot active
Output object 1 sends scene cyclicallylistnot active
Idle time after external button short is OFFunsignedInt 1…305
Interference / motion filterlistnot active, no filtering
Length of monitoring time slotlist2 s
Number of monitoring time slotlist3
Lock or release objectlistlock object
Fallback of forced guidance/lock (General setting)listnot active
Output object sends atlistON and OFF
Output object sends cycliclistnot active
Logic function 1listnot active
Description of functiontext
Additional texttext
FunctionlistAND
Output objectlistSwitch
Sending conditionliston change of output
Outputlistnormal
Scene number for output value "False"list1
Scene number for output value "True"list1
Value typelist1 Byte DPT 5.005 Decimal factor (0...255)
Value for output value "False"unsignedInt 0…2550
Value for output value "True"unsignedInt 0…2550
Percent value for output value "False"list0 %
Percent value for output value "True"list0 %
Forced guidance for output value "False"list00 - no priority, Off
Forced guidance for output value "True"list00 - no priority, Off
Internal input Alistnot active
Object numberunsignedInt 0…1290
Internal input Blistnot active
External input Clistnot active
Preset logic input after reset withlistvalue "0"
External input Dlistnot active
External input Elistnot active
External input Flistnot active
Logic function 2listnot active
Logic function 3listnot active
Logic function 4listnot active
Request inputs after bus power returnlistnot active

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Motivity, Secure 1.0 latest$0694F07A2026-11-25189 KBDownload

About this file

This is the official ETS product database for the Tense MOT-Ix.02S KNX Motivity Ceiling, Secure (MOT-Ix.02S), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Tense

All Tense products