KNX Database

STEINEL Wall switch KNX 4007841032xxx

STEINEL professional · Order number 4007841032xxx · Presence detector › presence Control PRO

Download .knxprod Wall switch KNX V1.00 1.0 · 94 KB

Product

ManufacturerSTEINEL professional
Product nameSTEINEL Wall switch KNX
Order number4007841032xxx
HardwareWandschalter KNX
MediumTwisted Pair
Bus current (mA)12
Rail mountedNo
RegistrationRegistered · 2016-08-08
Languagesde-DE, en-US
Catalog entryM-008E_H-4007841032xxx-1_HP-6799-10-EB29_CI-4007841032xxx-1
FingerprintEB29
SHA-2569c73d5892cf501febca2de4ba526074be1b06c72518e1ff0cac3fec5b4500772
First seen2026-11-25
Markets69 markets

Application program: Wall switch KNX V1.00 1.0

Application number$6799
Version1.0
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version3.0f
Parameters140
Group objects57
Group objects (57)
NoNameFunctionSizeDPTFlags
0Test mode statusON/OFF1 Bit1.1 switchCRT
1Presence outputON/OFF1 Bit1.1 switchCRT
2Disable presence outputON/OFF1 Bit1.1 switchCWT
3Presence output disabling statusON/OFF1 Bit1.1 switchCRT
4Presence slaveON1 Bit1.1 switchCWT
8Interference source switching statusON/OFF1 Bit1.1 switchCWT
9Time factor for presence switch-'ON' delay0..51 ByteDPT.5CRWT
10Time factor for presence stay-'ON' time1...2551 ByteDPT.5CRWT
11Light level measured(10...1500 lux)2 Bytes9.4 lux (Lux)CRT
12Light-level setting(10...1000 lux)2 Bytes9.4 lux (Lux)CRWT
13Time factor for lighting stay-'ON' time0...2551 ByteDPT.5CRWT
14Switch light 1 outputON/OFF1 Bit1.1 switchCRT
15Switch light 2 outputON/OFF1 Bit1.1 switchCRT
16Switch light 3 outputON/OFF1 Bit1.1 switchCRT
17Switch light 4 outputON/OFF1 Bit1.1 switchCRT
18Light 1 output dimming level0...100%1 Byte5.1 percentage (0..100%)CRT
19Light 2 output dimming level0...100%1 Byte5.1 percentage (0..100%)CRT
20Light 3 output dimming level0...100%1 Byte5.1 percentage (0..100%)CRT
21Light 4 output dimming level0...100%1 Byte5.1 percentage (0..100%)CRT
22Disable light-level controlON/OFF1 Bit1.1 switchCWT
23Light-level control disabling statusON/OFF1 Bit1.1 switchCRT
24Switch light 1 inputON/OFF1 Bit1.1 switchCWT
25Dim light 1 inputbrighter / darker4 Bit3.7 dimming controlCWT
26Light 1 input dimming level0...100%1 Byte5.1 percentage (0..100%)CWT
27Switch light 2 inputON/OFF1 Bit1.1 switchCWT
28Dim light 2 inputbrighter / darker4 Bit3.7 dimming controlCWT
29Light 2 input dimming level0...100%1 Byte5.1 percentage (0..100%)CWT
30Switch light 3 inputON/OFF1 Bit1.1 switchCWT
31Dim light 3 inputbrighter / darker4 Bit3.7 dimming controlCWT
32Light 3 input dimming level0...100%1 Byte5.1 percentage (0..100%)CWT
33Switch light 4 inputON/OFF1 Bit1.1 switchCWT
34Dim light 4 inputbrighter / darker4 Bit3.7 dimming controlCWT
35Light 4 input dimming level0...100%1 Byte5.1 percentage (0..100%)CWT
36HVAC outputON/OFF1 Bit1.1 switchCRT
37Disable HVAC outputON/OFF1 Bit1.1 switchCWT
38HVAC output disabling statusON/OFF1 Bit1.1 switchCRT
39Time factor for HVAC switch-'ON' delay0...2551 ByteDPT.5CRWT
40Time factor for HVAC stay-'ON' time1...2551 ByteDPT.5CRWT
418-bit scene outputselect / save1 ByteCRT
42Switch basic illumination outputON/OFF1 Bit1.1 switchCRT
43Twilight sensor input(0...1000 lux)2 Bytes9.4 lux (Lux)CWT
44Basic light-level threshold(10...1000 lux)2 Bytes9.4 lux (Lux)CRWT
45Time factor for basic illumination 'ON' period1...2551 ByteDPT.5CRWT
46Boost factor1...41 ByteDPT.5CRWT
47Sensitivity1=high/0=low1 Bit1.1 switchCRWT
48Twilight sensor inputLux2 Bytes9.4 lux (Lux)CWT
49SabotageON/OFF1 Bit1.1 switchCRT
50Temperature measured(0...40°C)2 Bytes9.1 temperature (°C)CRT
51Humidity measured(0...100%)2 BytesDPT.9CRT
52Light-switching buttonON/OFF1 Bit1.1 switchCRT
53Light-dimming buttonbrighter/darker4 Bit3.7 dimming controlCRT
54Discontinuous roller-shutter operating buttonup/down1 Bit1.8 up/downCRT
55Continuous roller-shutter operating buttonup/down1 Bit1.8 up/downCRT
561-byte encoderunsigned Byte1 ByteDPT.5CRT
572-byte encoderunsigned 2 Byte2 BytesDPT.7CRT
58Brightness encoder0...1500Lux2 Bytes9.4 lux (Lux)CRT
59Temperature encoder0...40°C2 Bytes9.1 temperature (°C)CT
Parameters (89)
ParameterTypeDefault
InitFlagunsignedInt 0…6553565535
Detector ModelistSingle detector
Presence outputlistinactive
HVAC outputlistinactive
Light-level measuredlistinactive
Temperature measuredlistinactive
Humidity measuredlistinactive
Remote Controllistinactive
Normal / test modelistNormal mode
Sabotagelistinactive
Button functionlistinactiv
Boost factorlistmax
SensitivitylistN
Can be read / changed by buslistYes
Presence switch-'ON' delay (in seconds)unsignedInt 0…51
Min. number of movements detected during switch-'ON' delayunsignedInt 1…202
Time factor seconds or minuteslistSeconds
Presence stay-'ON' timeunsignedInt 1…25510
Break in presence detectionunsignedInt 0…2550
Switch-'ON' delay and stay-'ON' time can be read / changed by buslistYes
Send presence cyclicallylistinactive
Disable presence outputlistNo
Behaviour on disabling presence outputlistno action
Behaviour on enabling presence outputlistSet presence to current status
Presence output disabling status objectlistNo
Type of light-level controllistconstant-lighting control
Daytime operationlistNo
Light-level setting (in lux)unsignedInt 10…1000500
Light-level setting can be read / changed by buslistYes
Start dim levelunsignedInt 1…100100
Max. variation from the settinglist30 lux
Max. dimming steplist2%
Send new dimming level afterlist2 s
Lighting with sufficient daylightlistswitching OFF
Minimum dimming levellist0,50%
Lighting group 2 offset to dimming level for lighting-group 1signedInt -100…1000
Lighting group 3 offset to dimming level for lighting-group 1signedInt -100…1000
Lighting group 4 offset to dimming level for lighting-group 1signedInt -100…1000
Light-level control for dim light x inputlistdisable and dim
External brightnesslistNo
Number of lighting groupslist1
Operation lightinglistautomatically 'ON' and 'OFF' (fully automatic)
Stay-'ON' time Lighting (in minutes)unsignedInt 0…2550
Stay-'On' time can be read / changed by buslistYes
Disabling light-level controllistNo
Behaviour on disabling light-level controllistno action
Behaviour on enabling light-level controllistContinuing control
Light-level control disabling status objectlistNo
Basic illuminationlistinactive
Interference source switching status objectlistNo
Basic illumination bylistdimming level to light 1 output
Basic illumination ONlistfor a limit time
Basic light-level threshold (in lux)unsignedInt 10…100050
Basic illumination 'ON' period (in minutes)unsignedInt 1…25515
Basic illumination dimming levelunsignedInt 1…10010
Threshold and stay-'ON' time can be read / changed by buslistYes
HVAC switch-'ON' delay (in minutes, 0 = room surveillance)unsignedInt 0…2550
HVAC stay-'ON' time (in minutes)unsignedInt 1…25515
Disable HVAC outputlistNo
Behaviour on disabling HVAC outputlistno action
Behaviour on enabling HVAC outputlistSet HVAC output to current status
HVAC output disabling status objectlistNo
Min. light-level changelist30 lux
Send measured level cyclicallylistinactive
Min. temperaturel change x0.1°CunsignedInt 1…2551
Min. change in humidity x0.1%unsignedInt 1…2551
Send humidity cyclicallylistinactive
Scene number for button, scene 1 (0=no assignment)unsignedInt 0…630
Scene number for button, scene 2 (0=no assignment)unsignedInt 0…630
Scene number for button, scene 3 (0=no assignment)unsignedInt 0…630
Scene number for button, scene 4 (0=no assignment)unsignedInt 0…630
Min. cycle time for send presencelist30 s
Send sabotage cyclicallylist1 Min
TelegramlistON
1 byte modelist0...255
Starting valueunsignedInt 0…2550
Starting valueunsignedInt 0…1000
Value adjustment via long button presslistinactive
incrementunsignedInt 1…201
time between two telegramslist1s
Value adjustment starting valuelistStarting value
OverrunlistNo
2 byte modelist0...65k
Starting valueunsignedInt 0…655350
incrementunsignedInt 0…655350
Starting valueunsignedInt 0…400
Starting valuelist0
Scene number [1 to 64] for button (0 = no assignment)unsignedInt 0…630
Lighting-group(chose only an activ group)list1

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Wall switch KNX V1.00 1.0 latest$6799EB292026-11-2594 KBDownload

About this file

This is the official ETS product database for the STEINEL professional STEINEL Wall switch KNX (4007841032xxx), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.