KNXdrive4U Product KNXdrive4U
Smart Building Services GmbH · Order number KNXdrive4U · HVAC › Valve actuator
Download .knxprod Application for KNXdrive4u 0.2 · 144 KB
Product
| Manufacturer | Smart Building Services GmbH |
|---|---|
| Product name | KNXdrive4U Product |
| Order number | KNXdrive4U |
| Hardware | KNXdrive4U Hardware |
| Medium | KNX RF |
| Rail mounted | No |
| Registration | Registered · 2025-02-17 |
| Languages | de-DE, fr-FR, es-ES, it-IT |
| Catalog entry | M-029F_H-ZN.2D2050-3_HP-F023-02-47FC_CI-KNXdrive4U-1 |
| Fingerprint | 47FC |
| SHA-256 | a6c12d6e72290e57990326fbbb1973b8f83e875a8462ab28da40f3b4201eb41c |
| First seen | 2026-11-25 |
| Markets | 23 markets |
Application program: Application for KNXdrive4u 0.2
| Application number | $F023 |
|---|---|
| Version | 0.2 |
| Mask version | MV-27B0 (RF System B) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 71 |
| Group objects | 36 |
Group objects (36)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | {{0}}: Restart device | Restarts device | 1 Bit | 1.17 trigger | CWU |
| 2 | {{0}}: Battery voltage | Actual battery voltage | 2 Bytes | 9.20 voltage (mV) | CRT |
| 3 | {{0}}: Battery % | Actual battery percent | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 4 | {{0}}: Battery 0% | Battery gauge 0% dot | 1 Bit | 1.1 switch | CRT |
| 5 | {{0}}: Battery 25% | Battery gauge 25% dot | 1 Bit | 1.1 switch | CRT |
| 6 | {{0}}: Battery 50% | Battery gauge 50% dot | 1 Bit | 1.1 switch | CRT |
| 7 | {{0}}: Battery 75% | Battery gauge 75% dot | 1 Bit | 1.1 switch | CRT |
| 8 | {{0}}: Battery 100% | Battery gauge 100% dot | 1 Bit | DPT.1 | CRT |
| 9 | {{0}}: Local temperature | Temperature mesures by device | 2 Bytes | 9.1 temperature (°C) | CRT |
| 10 | {{0}}: Set temperature | Temperature set by room thermostat | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 11 | {{0}}: Room temperature | Temperature measured by room thermostat | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 12 | {{0}}: Homing | Triggers motor homing | 1 Bit | 1.17 trigger | CWU |
| 13 | {{0}}: Homing required | Indicates device needs motor homing | 1 Bit | 1.5 alarm | CRT |
| 14 | {{0}}: Target position % | Position to drive valve | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 15 | {{0}}: Target position step | Position to drive valve | 2 Bytes | 7.2 time (ms) | CWU |
| 16 | {{0}}: Actual position % | Actual valve position | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 17 | {{0}}: Actual position step | Actual valve position | 2 Bytes | 7.2 time (ms) | CRT |
| 18 | {{0}}: Energy harvester voltage | Actual voltage generated by energy harvester | 2 Bytes | 9.20 voltage (mV) | CRT |
| 19 | {{0}}: Energy harvester alarm | Alarm indicating energy harvester voltage is below threshold | 1 Bit | 1.1 switch | CRT |
| 20 | {{0}}: Request datas | Indicates device is now waiting for CO's | 1 Bit | 1.17 trigger | CRT |
| 21 | {{0}}: Send datas | Triggers device sending all datas | 1 Bit | 1.17 trigger | CWU |
| 22 | {{0}}: Keep awake | Triggers delay to keep awake | 1 Bit | 1.17 trigger | CWTU |
| 23 | {{0}}: Awake status | Actual awake status | 1 Bit | 1.2 boolean | CRT |
| 24 | {{0}}: Temperature alarm 1 | Status of temperature alarm 1 | 1 Bit | 1.1 switch | CRT |
| 25 | {{0}}: Temperature alarm 2 | Status of temperature alarm 2 | 1 Bit | 1.1 switch | CRT |
| 26 | {{0}}: Freezing alarm | Status of freezing alarm | 1 Bit | 1.1 switch | CRT |
| 27 | {{0}}: Battery alarm | Status of battery alarm | 1 Bit | 1.1 switch | CRT |
| 28 | {{0}}: Forcing | Forcing | 2 Bit | 2.6 binary value control | CWTU |
| 29 | {{0}}: Anti-Stuck | Initiates anti-stuck movement | 1 Bit | 1.17 trigger | CWU |
| 30 | {{0}}: Heating mode | Status of heating mode | 1 Bit | 1.100 cooling/heating | CWTU |
| 31 | {{0}}: Set temperature shift | Shifting of set temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 32 | {{0}}: Calculated temperature | Actual temperature computed using room thermostat and local sensor | 2 Bytes | 9.1 temperature (°C) | CRT |
| 33 | {{0}}: Resulting set temperature | Status of resulting set temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 34 | {{0}}: Actual internal regulator value | Position in % calculated by internal regulator | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 35 | {{0}}: HVAC mode from thermostat | HVAC mode set by external thermostat | 1 Byte | 20.102 HVAC mode | CWTU |
| 36 | {{0}}: RHCC status | Internal RHCC status | 2 Bytes | 22.101 RHCC status | CRT |
Parameters (61)
| Parameter | Type | Default |
|---|---|---|
| Type of valve | list | Normally opened (NO) valve |
| Local temperature sensor correction | signedInt -50…50 | 0 |
| Battery gauge | list | Display as line |
| Valve_Max_pc | unsignedInt 0…255 | 0 |
| Valve_Min_pc | unsignedInt 0…255 | 0 |
| Mechanical valve offset | list | 0 steps <-> No offset (standard) |
| Valve_Default_pc | unsignedInt 0…255 | 255 |
| Min_pc_to_move | unsignedInt 0…255 | 3 |
| High_Forcing_pc | unsignedInt 0…255 | 0 |
| OverHeating_Release_1 | unsignedInt 0…65535 | 400 |
| RF_Failure_pc | unsignedInt 0…255 | 0 |
| OverHeating_Level_1 | unsignedInt 0…65535 | 450 |
| OverHeating_Release_2 | unsignedInt 0…65535 | 500 |
| OverHeating_Level_2 | unsignedInt 0…65535 | 550 |
| Wake up delay in heating mode | list | 15 min. |
| Freezing_Release | unsignedInt 0…65535 | 80 |
| OverHeating_Level_2_Max_pc | unsignedInt 0…255 | 0 |
| Energy harvester voltage to release alarm | unsignedInt 250…1000 | 250 |
| Battery voltage to release alarm | list | 3 |
| Operating mode after programming | list | Stock mode |
| Delay to operate anti-stuck movements | list | 180 days |
| Number of anti-stuck movements to operate | unsignedInt 1…5 | 3 |
| Energy harvester voltage to enter alarm | unsignedInt 250…1000 | 250 |
| Wake up delay while not in heating mode | list | 2 h |
| Low_Forcing_pc | unsignedInt 0…255 | 0 |
| Freezing_Level_Min_pc | unsignedInt 0…255 | 0 |
| Freezing_Level | unsignedInt 0…65535 | 50 |
| Battery_Empty_pc | unsignedInt 0…255 | 77 |
| Battery voltage to enter alarm | list | 2.9 |
| Delay to extend awakeness after receiving "Keep awake" CO | list | 5 min. |
| Time to listen and process CO's after requesting data's from room controller, before entering sleep mode | list | 2 |
| OverHeating_Level_1_Max_pc | unsignedInt 0…255 | 0 |
| Min. value to start opening valve | unsignedInt 1…100 | 10 |
| Min. value for max opening valve | unsignedInt 1…100 | 85 |
| Valve position while alarm | unsignedInt 0…100 | 30 |
| Local temperature to enter alarm | unsignedInt 15…60 | 45 |
| Local temperature to release alarm | unsignedInt 14…59 | 40 |
| Local temperature to enter alarm | unsignedInt 15…60 | 55 |
| Local temperature to release alarm | unsignedInt 14…59 | 50 |
| Valve upper limit while alarm | unsignedInt 0…100 | 30 |
| Valve upper limit while alarm | unsignedInt 0…100 | 0 |
| Local temperature to enter alarm | unsignedInt 5…15 | 5 |
| Local temperature to release alarm | unsignedInt 6…16 | 8 |
| Valve lower limit while alarm | unsignedInt 0…100 | 30 |
| Valve position while forcing '0' | unsignedInt 0…100 | 30 |
| Valve position while forcing '1' | unsignedInt 0…100 | 30 |
| Valve position at device start up | unsignedInt 0…100 | 100 |
| Min. change to move valve | unsignedInt 1…25 | 1 |
| Valve position while regulator failure | unsignedInt 0…100 | 30 |
| Proportional gain | list | 4K |
| Integrator | list | 120 min. |
| Set temperature, standby mode | unsignedInt 80…300 | 190 |
| Device acts as | list | Valve actuator with integrated regulator |
| Actual room temperature computing | list | Room sensor 80% <> Internal sensor 20% |
| Set temperature, night mode | unsignedInt 80…300 | 180 |
| Set temperature, comfort mode | unsignedInt 80…300 | 210 |
| Device name | text | My KNXdrive4U |
| PI regulator settings | list | Standard: 4K, 120 min. |
| Steps for min. opening | unsignedInt 1…2000 | 1950 |
| Upper opening limit (steps) | unsignedInt 1…2000 | 50 |
| Valve adjusting | list | Standard settings |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Application for KNXdrive4u 0.2 latest | $F023 | 47FC | 2026-11-25 | 144 KB | Download |
About this file
This is the official ETS product database for the Smart Building Services GmbH KNXdrive4U Product (KNXdrive4U), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.