Switch-/Dimming Actuator JB 526C23, 2x 20A, 5WG1 526-4CB23
Siemens · Order number 5WG1 526-4CB23 · Room controller › Lighting › Switch-/Dimming Actuator, 2-fold
Switch-/Dimming Actuator 2x 20A, AC 277V or AC 347V, Dimming Ctrl 0/1...10V
Download .knxprod 07 B0 A2 Dimmer 983C01 0.1 · 95 KB
Product
| Manufacturer | Siemens |
|---|---|
| Product name | Switch-/Dimming Actuator JB 526C23, 2x 20A, |
| Order number | 5WG1 526-4CB23 |
| Hardware | #SDA_2fach |
| Medium | Twisted Pair |
| Bus current (mA) | 15 |
| Rail mounted | No |
| Registration | Registered · 2016-12-07 |
| Languages | en-US, de-DE |
| Catalog entry | M-0001_H-hp.5F00306-1_HP-983C-01-D7C4_CI-5WG1.20526.2D4CB23-1 |
| Fingerprint | D7C4 |
| SHA-256 | 679605411ed26651f4d366fc7e3da51739d07554a60b918e87d38ea4ae3d8c59 |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: 07 B0 A2 Dimmer 983C01 0.1
| Application number | $983C |
|---|---|
| Version | 0.1 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 453 |
| Group objects | 30 |
Group objects (30)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | A, 8-bit scene | recall / save | 1 Byte | 18.1 scene control | CW |
| 2 | A, Locking | On / Off | 1 Bit | 1.3 enable | CW |
| 3 | A, Night mode | On / Off | 1 Bit | 1.3 enable | CW |
| 4 | A, Switching | On / Off | 1 Bit | 1.1 switch | CW |
| 5 | A, Dimming | brighter / darker | 4 Bit | 3.7 dimming control | CW |
| 6 | A, Dimming value | 8-bit value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 8 | A, Status switching | On / Off | 1 Bit | 1.1 switch | CRT |
| 9 | A, Status dimming value | 8-bit value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 10 | A, Switching cycle, counter value | 4-byte value | 4 Bytes | 12.1 counter pulses (unsigned) | CR |
| 11 | A, Switching cycle, threshold | 4-byte value | 4 Bytes | 12.1 counter pulses (unsigned) | CRW |
| 12 | A, Switching cycle, threshold overrun | 1 = yes / 0 = no | 1 Bit | 1.2 boolean | CRT |
| 13 | A, Operating hours, counter value | 4-byte value | 4 Bytes | 12.1 counter pulses (unsigned) | CR |
| 14 | A, Operating hours, threshold | 4-byte value | 4 Bytes | 12.1 counter pulses (unsigned) | CRW |
| 15 | A, Operating hours, threshold overrun | 1 = yes / 0 = no | 1 Bit | 1.2 boolean | CRT |
| 16 | A, Operating time, seconds | 4-byte value | 4 Bytes | 13.100 time lag (s) | CR |
| 23 | B, 8-bit scene | recall / save | 1 Byte | 18.1 scene control | CW |
| 24 | B, Locking | On / Off | 1 Bit | 1.3 enable | CW |
| 25 | B, Night mode | On / Off | 1 Bit | 1.3 enable | CW |
| 26 | B, Switching | On / Off | 1 Bit | 1.1 switch | CW |
| 27 | B, Dimming | brighter / darker | 4 Bit | 3.7 dimming control | CW |
| 28 | B, Dimming value | 8-bit value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 30 | B, Status switching | On / Off | 1 Bit | 1.1 switch | CRT |
| 31 | B, Status dimming value | 8-bit value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 32 | B, Switching cycle, counter value | 4-byte value | 4 Bytes | 12.1 counter pulses (unsigned) | CR |
| 33 | B, Switching cycle, threshold | 4-byte value | 4 Bytes | 12.1 counter pulses (unsigned) | CRW |
| 34 | B, Switching cycle, threshold overrun | 1 = yes / 0 = no | 1 Bit | 1.2 boolean | CRT |
| 35 | B, Operating hours, counter value | 4-byte value | 4 Bytes | 12.1 counter pulses (unsigned) | CR |
| 36 | B, Operating hours, threshold | 4-byte value | 4 Bytes | 12.1 counter pulses (unsigned) | CRW |
| 37 | B, Operating hours, threshold overrun | 1 = yes / 0 = no | 1 Bit | 1.2 boolean | CRT |
| 38 | B, Operating time, seconds | 4-byte value | 4 Bytes | 13.100 time lag (s) | CR |
Parameters (88)
| Parameter | Type | Default |
|---|---|---|
| Transmission blocking period for status objects after supply/bus voltage recovery [1...60 seconds] | unsignedInt 1…60 | 15 |
| Delay status objects [0…10 in 1/10 sec] | unsignedInt 0…10 | 2 |
| 8-bit scenes configurable by user | list | Yes |
| Assignment 1 to scene [1...64] (0=not used) | list | 0 |
| Assignment 2 to scene [1...64] (0=not used) | list | 0 |
| Assignment 3 to scene [1...64] (0=not used) | list | 0 |
| Assignment 4 to scene [1...64] (0=not used) | list | 0 |
| Assignment 5 to scene [1...64] (0=not used) | list | 0 |
| Assignment 6 to scene [1...64] (0=not used) | list | 0 |
| Assignment 7 to scene [1...64] (0=not used) | list | 0 |
| Assignment 8 to scene [1...64] (0=not used) | list | 0 |
| Predefine | list | No |
| Dimming value [0...100%] | unsignedInt 0…255 | 255 |
| Dimming value [0...100%] | unsignedInt 0…100 | 100 |
| Min | unsignedInt 0…255 | 0 |
| Max | unsignedInt 0…255 | 100 |
| Dimming time [0...255 seconds]) | unsignedInt 0…65535 | 20 |
| Dimming time [0...255 seconds]) | unsignedInt 0…255 | 2 |
| Factor | unsignedInt 0…65535 | 10 |
| Min | unsignedInt 0…65535 | 0 |
| Max | unsignedInt 0…65535 | 2550 |
| Delete saved scene value | list | No |
| LDAB mode | list | No |
| 8-bit scene control | list | No |
| Status object switching | list | No |
| transmit object | list | send on read request only |
| Heartbeat time | unsignedInt 0…1440 | 0 |
| Idle Period [in seconds] | unsignedInt 1…60 | 1 |
| Status object dimming | list | No |
| Idle Period [in seconds] | unsignedInt 0…65535 | 30 |
| Idle Period [in seconds] | unsignedInt 1…60 | 3 |
| Min | unsignedInt 0…65535 | 10 |
| Max | unsignedInt 0…65535 | 600 |
| Status object actuator | list | send on read request only |
| Status object error information | list | send on read request only |
| Status object loadtype | list | send on read request only |
| Blocking object | list | No |
| Night mode | list | No |
| ON period during night mode [1...255 minutes] | unsignedInt 0…65535 | 1800 |
| ON period during night mode [1...255 minutes] | unsignedInt 1…255 | 30 |
| Min | unsignedInt 0…65535 | 60 |
| Max | unsignedInt 0…65535 | 15300 |
| Factor | unsignedInt 0…65535 | 60 |
| Warning before switching Off [0...255 seconds] | unsignedInt 0…255 | 30 |
| Counting of switching cycles | list | No |
| Counting of power-on hours | list | No |
| Behaviour on KNX power voltage failure | list | no change of relay contact |
| Behaviour on KNX power voltage recovery | list | as before voltage failure |
| Value on power voltage recovery [0...100%] | unsignedInt 0…255 | 255 |
| Max | unsignedInt 0…255 | 255 |
| Value on power voltage recovery [0...100%] | unsignedInt 0…100 | 100 |
| Operating mode | list | Normal Mode |
| Load adaptation: Dimmer operation according to | list | Automatic detection of load type |
| Compensation ripple control | list | Yes |
| Minimum dimming value [1...50%] | unsignedInt 0…255 | 3 |
| Min | unsignedInt 0…255 | 3 |
| Max | unsignedInt 0…255 | 128 |
| Minimum dimming value [1...50%] | unsignedInt 1…50 | 1 |
| Maximum dimming value [10...100%] | unsignedInt 0…255 | 255 |
| Min | unsignedInt 0…255 | 26 |
| Maximum dimming value [10...100%] | unsignedInt 10…100 | 100 |
| Dimming time for switching On/Off [0...255 seconds] | unsignedInt 0…65535 | 0 |
| Dimming time for switching On/Off [0...255 seconds] | unsignedInt 0…255 | 0 |
| Dimming time for dimming darker / brighter from 0% to 100% [1...255 seconds] | unsignedInt 0…65535 | 50 |
| Dimming time for dimming darker / brighter from 0% to 100% [1...255 seconds] | unsignedInt 1…255 | 5 |
| Dimming time for setting dimming value from 0% to 100% [0...255 seconds] | unsignedInt 0…65535 | 0 |
| Dimming time for setting dimming value from 0% to 100% [0...255 seconds] | unsignedInt 0…255 | 0 |
| Starting value | list | switch On value according to parameter |
| Switch On value [1...100%] | unsignedInt 0…255 | 255 |
| Switch On value [1...100%] | unsignedInt 1…100 | 100 |
| Switching off via dimming darker | list | Yes |
| Switching on via dimming brighter | list | Yes |
| Switching via dimming value | list | On if dimming value >= min. dimming value |
| ON delay [0…600 seconds] | unsignedInt 0…65535 | 0 |
| ON delay [0…600 seconds] | unsignedInt 0…600 | 0 |
| Max | unsignedInt 0…65535 | 60000 |
| Factor | unsignedInt 0…65535 | 100 |
| OFF-delay [0…600 seconds] | unsignedInt 0…65535 | 0 |
| OFF-delay [0…600 seconds] | unsignedInt 0…600 | 0 |
| ON period 1 [1...255 minutes] | unsignedInt 1…255 | 15 |
| ON period 2 [1...255 minutes] | unsignedInt 1…255 | 15 |
| Dimming value during ON period 2 [0...100%] | unsignedInt 0…255 | 128 |
| Dimming value during ON period 2 [0...100%] | unsignedInt 0…100 | 50 |
| ON period Flashing [1...255 seconds] | unsignedInt 1…255 | 1 |
| OFF period Flashing [1...255 seconds] | unsignedInt 1…255 | 1 |
| Min. output voltage [1 … 5V] | list | 1.0 |
| Max. output voltage [6 … 10V] | list | 10.0 |
| VisibilityParameter | list | Yes |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| 07 B0 A2 Dimmer 983C01 0.1 latest | $983C | D7C4 | 2026-11-25 | 95 KB | Download |
About this file
This is the official ETS product database for the Siemens Switch-/Dimming Actuator JB 526C23, 2x 20A, (5WG1 526-4CB23), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Siemens
- Control Module Box AP 118 5WG1 118-4AB01
- Binary Input RL 260/23 5WG1 260-4AB23
- Binary Input JB 260C23 5WG1 260-4CB23
- Binary Output RS 510/23 5WG1 510-2AB23
- Binary Output JB 510C23 5WG1 510-4CB23
- Switching Actuator RL 512/23 5WG1 512-4AB23
- Switching Actuator JB 512C23 5WG1 512-4CB23
- Binary Output JB 513C23 5WG1 513-4CB23
- Binary Output RL 513D23 5WG1 513-4DB23
- Solar Protection Actuator JB 521C23 5WG1 521-4CB23
- Universal Dimmer RS 525/23 5WG1 525-2AB23
- Universal Dimmer JB 525C23 5WG1 525-4CB23