KNX Database
Siemens 5WG1 510-2AB13 Binary Output UP 510/13

Binary Output UP 510/13 5WG1 510-2AB13

Siemens · Order number 5WG1 510-2AB13 · Output › Binary output, 2-fold › UP Wall Mounted Devices › UP 510/13

Binary Output , 2 x 10A, AC 230V (Relay)

Download .knxprod 07 B0 A2 Switch actuator 982E02 0.2 · 607 KB

Product

ManufacturerSiemens
Product nameBinary Output UP 510/13
Order number5WG1 510-2AB13
Hardware#Binausgabegerät 2fach UP 510/_3
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2012-04-10
Languagesen-US, de-DE
Catalog entryM-0001_H-hp.5F00276-1_HP-982E-02-A241_CI-5WG1.20510.2D2AB13-1
FingerprintA241
SHA-256d7f074c94342b7c9632b76cf5e63ab1dd99f07944dcfbb3ae48243bd19bf458b
First seen2026-11-25
Markets59 markets

Application program: 07 B0 A2 Switch actuator 982E02 0.2

Application number$982E
Version0.2
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version3.0f
Parameters53
Group objects52
Group objects (52)
NoNameFunctionSizeDPTFlags
1A 8-bit Scenerecall / store1 ByteCW
2A Night modeOn / Off1 Bit1.3 enableCRW
3A Manual overrideOn / Off1 Bit1.1 switchCRW
4A Forced controlOn / Off2 Bit2.1 switch controlCRW
5A SwitchingOn / Off1 Bit1.1 switchCRWT
6A Logic operationOn / Off1 Bit1.1 switchCRW
7A Status SwitchingOn / Off1 Bit1.1 switchCRWT
8A Threshold for switching cyclesValue4 Bytes12.1 counter pulses (unsigned)CRW
9A Number of switching cyclesValue4 Bytes12.1 counter pulses (unsigned)CRW
10A Exceedance of threshold for switching cyclesOn / Off1 Bit1.1 switchCRWT
11A Threshold for operating hoursValue4 Bytes12.1 counter pulses (unsigned)CRW
12A Operating hoursValue4 Bytes12.1 counter pulses (unsigned)CRW
13A Exceedance of threshold for operating hoursOn / Off1 BitCRWT
14B 8-bit Scenerecall / store1 ByteCW
15B Night modeOn / Off1 Bit1.3 enableCRW
16B Manual overrideOn / Off1 Bit1.1 switchCRW
17B Forced controlOn / Off2 Bit2.1 switch controlCRW
18B SwitchingOn / Off1 Bit1.1 switchCRWT
19B Logic operationOn / Off1 Bit1.1 switchCRW
20B Status SwitchingOn / Off1 Bit1.1 switchCRWT
21B Threshold for switching cyclesValue4 Bytes12.1 counter pulses (unsigned)CRW
22B Number of switching cyclesValue4 Bytes12.1 counter pulses (unsigned)CRW
23B Exceedance of threshold for switching cyclesOn / Off1 Bit1.1 switchCRWT
24B Threshold for operating hoursValue4 Bytes12.1 counter pulses (unsigned)CRW
25B Operating hoursValue4 Bytes12.1 counter pulses (unsigned)CRW
26B Exceedance of threshold for operating hoursOn / Off1 BitCRWT
27C 8-bit Scenerecall / store1 ByteCW
28C Night modeOn / Off1 Bit1.3 enableCRW
29C Manual overrideOn / Off1 Bit1.1 switchCRW
30C Forced controlOn / Off2 Bit2.1 switch controlCRW
31C SwitchingOn / Off1 Bit1.1 switchCRWT
32C Logic operationOn / Off1 Bit1.1 switchCRW
33C Status SwitchingOn / Off1 Bit1.1 switchCRWT
34C Threshold for switching cyclesValue4 Bytes12.1 counter pulses (unsigned)CRW
35C Number of switching cyclesValue4 Bytes12.1 counter pulses (unsigned)CRW
36C Exceedance of threshold for switching cyclesOn / Off1 Bit1.1 switchCRWT
37C Threshold for operating hoursValue4 Bytes12.1 counter pulses (unsigned)CRW
38C Operating hoursValue4 Bytes12.1 counter pulses (unsigned)CRW
39C Exceedance of threshold for operating hoursOn / Off1 BitCRWT
40D 8-bit Scenerecall / store1 ByteCW
41D Night modeOn / Off1 Bit1.3 enableCRW
42D Manual overrideOn / Off1 Bit1.1 switchCRW
43D Forced controlOn / Off2 Bit2.1 switch controlCRW
44D SwitchingOn / Off1 Bit1.1 switchCRWT
45D Logic operationOn / Off1 Bit1.1 switchCRW
46D Status SwitchingOn / Off1 Bit1.1 switchCRWT
47D Threshold for switching cyclesValue4 Bytes12.1 counter pulses (unsigned)CRW
48D Number of switching cyclesValue4 Bytes12.1 counter pulses (unsigned)CRW
49D Exceedance of threshold for switching cyclesOn / Off1 Bit1.1 switchCRWT
50D Threshold for operating hoursValue4 Bytes12.1 counter pulses (unsigned)CRW
51D Operating hoursValue4 Bytes12.1 counter pulses (unsigned)CRW
52D Exceedance of threshold for operating hoursOn / Off1 BitCRWT
Parameters (2)
ParameterTypeDefault
CO switching parameterunsignedInt 0…2550
CO switching parameterunsignedInt 0…2555

Version history

ApplicationApp noFingerprintFirst seenSizeFile
07 B0 A2 Switch actuator 982E02 0.2 latest$982EA2412026-11-25607 KBDownload

About this file

This is the official ETS product database for the Siemens Binary Output UP 510/13 (5WG1 510-2AB13), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Siemens